Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹98,853.48Admitted-Finance 001 HPS MARKET KANPUR GANDHI CHAURAHA RAEBARELI UTTAR PRADESH 229206 UDYAM UP 62 0025959 | RAE BARELI | UTTAR PRADESH | 229206 | -1.00% | ₹98,853.48 | L1 | Admitted-Finance |
Tender Value
₹99,852
EMD Value
₹1,997
Closing Date
29 Jun 2026, 12:00 pmClosed
Assistant Engineer (Elect)
Engg Dte FHQ BSF 3rd Floor E Block Pushpa Bhawan Madangir New Delhi 110062
Providing and installation of energy efficient 5 Star ACs in Room No. 805 DIG (0Prov office at Block No 10 of CGO Complex under FHQ BSF New Delhi
2026_BSF_913874_1
08/NIT/ENGG/ELECT/2026-27
Open Tender
Electrical Works
Percentage
15 days
HQ DG BSF Block No. 10 CGO Complex New Delhi
As per NIT
9 documents required · 9 mandatory
₹0
₹1,997
6 Jul 2026
19 Jun 2026
30 Jun 2026
19 Jun 2026
29 Jun 2026
19 Jun 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 0.0 | Supplying, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for VRV/VRF system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of 19 mm thick insulation as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
(1.1) 6.4 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 9 | Mtr | 256 | ₹2,304 |
| 1.2 | 12.7 mm dia (OD) (Soft drawn) with tube thickness 1.2 mm | 9 | Mtr | 487 | ₹4,383 |
| 0.0 | HI - WALL SPLIT SYSTEMS
Supplying, Installation, Testing and Commissioning of Air Cooled Hi Wall split type Air conditioners complete with Indoor unit (IDU), Out door unit (ODU), surface/ concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 3 Mtr (IDU to ODU), copper power cable upto 3.5 Mtr (IDU to ODU) i/c drain pipe R-32/R-410/ R-407 Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz , 1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll/ rotary compressor. The system shall be able to deliver 100% of the rated capacity upto 42 0C. Min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). Must comply : Electrical cable IS 694 or IS 9968 temperature sensing control IS/ International Electrotechnical Commission (IEC) 60730, hermetic compressor IS 10617, heat exchanger IS 11329, capacitor IS 2993 and motor IS 12615. Complete as per CPWD specification and IS : 1391 Part II 2023. The system shall be able to operate up to 50 0C (out door ambient temperature). Inverter Type - Cooling only Make : Daikin/ Voltas/ Blue star/ Hitachi
(2.1) 1.5 TR with 5 Star BEE Rating | 2 | Each | 43,539 | ₹87,078 |
| 0.0 | Supplying and fixing 4 core x 2.5 sq. mm. size PVC insulated and sheathed, round copper flexible conductor cable on the existing surface or in recessed steel/ PVC conduit/ cable tray as required. Make National or it's equivalent to Anchor/Finolex/Panasonic/HPL | 15 | Mtr | 192 | ₹2,880 |
| 0.0 | Providing and fixing of 15 mm PVC drain pipe with cotton sheathed by PVC clips on wall surface/ recess for indoor unit of air conditioner including testing, connections etc. complete as required. | 7 | Mtr | 75 | ₹525 |
| 0.0 | Providing and fixing 3 pin, 16 Amp, 240 volt plug top on exising power socket including connection etc. complete as required. Anchor make or it's equivalent to Havells/Goldmedal/Standard | 2 | Each | 156 | ₹312 |
| 0.0 | Supplying and fixing of powder coated M.S. stand floor/ wall mounted suitable for outdoor unit of 1.5/2.0 Ton cassette/ split air conditioner complete with nut, bolts and washers etc. as required. | 2 | Each | 1,185 | ₹2,370 |
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.77 MB
BOQ_960400.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .