Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.3 LAccepted-AOC | L1 | Accepted-AOC Being lowest bidder and reasonable | |
| 2 | L2₹39.9 L+₹6.7 L (20.3%)Rejected-AOC | L2 | Rejected-AOC Not being lowest bidder | |
| 3 | L3₹42.4 L+₹9.3 L (28.0%)Rejected-AOC | L3 | Rejected-AOC Not being lowest bidder | |
| 4 | L4₹45.8 L+₹12.7 L (38.3%)Rejected-AOC | L4 | Rejected-AOC Not being lowest bidder | |
| 5 | Rejected-Technical | - | Rejected-Technical Not enlisted in category c(vi) |
Tender Value
Refer Docs
EMD Value
₹94,000
Closing Date
29 Mar 2021, 6:00 pmClosed
GE I R nd D West Bengaluru
GARRISON ENGINEER I R nd D WEST BANGALORE DRDO COMPLEX CV RAMAN NAGAR BANGALORE
PERIODICAL MAINT, REPAIRS TO RADAR OTP, MISC REPAIRS TO FIRE ALARM SYSTEM AND REPLACE OF LT PANELS AT LRDE TECH AREA AND NEW CAIR BENGALURU
2021_MES_416074_1
GE(I) R ND D (WEST)/BAN/66 OF 2020-21 8864E8
Open Tender
Civil Works
Item Rate
180 days
Bengaluru
Class and category as per NIT
8 documents required · 8 mandatory
₹500
GE I R nd D West Bengaluru
₹94,000
Yes
9 Jun 2021
9 Feb 2021
5 Apr 2021
10 Feb 2021
29 Mar 2021
2 Mar 2021
10 Feb 2021 - 1 Mar 2021
Amount
Rectification of defective fire alarm system, Panel and wiring of Make: GST at MLCP by checking cable continuity, checking and repairing of fault in the system, activation of MCP settings including making serviceable entire system complete all as specified and as directed in Engineer -in-Charge.
Rectification of defective fire alarm system, Panel and wiring of Make: Apollo at RADL by checking cable continuity, checking and repairing of fault in the system, activation of MCP settings including making serviceable entire system complete all as specified and as directed in Engineer -in-Charge.
Rectification of defective fire alarm system, Panel and wiring of Make: Ravel at EMP building by checking cable continuity, checking and repairing of fault in the system, activation of MCP settings including making serviceable entire system complete all as specified and as directed in Engineer -in-Charge.
Rectification of defective fire alarm system, Panel and wiring of Make: Siemens at A3MTDC by checking cable continuity, checking and repairing of fault in the system, activation of MCP settings including making serviceable entire system complete all as specified and as directed in Engineer -in-Charge.
Rectification of defective fire alarm system, Panel and wiring of Make: Notifier at Networking Block at CAIR by checking cable continuity, checking and repairing of fault in the system, activation of MCP settings including making serviceable entire system complete all as specified and as directed in Engineer -in-Charge.
Rectification of defective fire alarm system, Panel and wiring of Make: Notifier at Administrator Block at CAIR by checking cable continuity, checking and repairing of fault in the system, activation of MCP settings including making serviceable entire system complete all as specified and as directed in Engineer -in-Charge.
Rectification of existing defective main control board including component on fire alarym systems of Make Notifier at CAIR Technical Area (Administration Block, Networking Block, System Block), getting the board servicing at OEM Servicing or visiting OEM authorized servicing centre technician to site Centre and repair the board and re-fixing the same in respective locations complete all as specified and as directed by Engineer-in-Charge Note for Sl Item Nos 1 to 7 : - i) The tenderer shall visit site before quoting their rates ii) The tenderer shall be solely responsible for making the fire alarm system functional and his quoted rates shall deemed to include for manpower and spares other than that mentioned here-in-after as "Supply only". MES will not pay nothing extra in this regards. .
Rectification of defective main control board including component on fire alarm of Make : Notifier at CAIR technical area 03 Nos (system complete all as specified and as directed in Engineer -in-Charge.
Supply and install Photoelectric Smoke Detector with Junction boxes and accessorier. Make : System Sensor / Ravel or technocommercially approved manufacturer, complete all as specified and as directed.
Supply and install Photoelectric Heat Detector with Junction boxes and accessorier. Make : System Sensor / Ravel or technocommercially approved manufacturer, complete all as specified and as directed.
Supply and installing single loop card that can support around 159 detector and 159 devices all as per Cat No . SLC of Notifier make or it's techno commercially equivalent model in other makes complete all as specified and as directed.
Supply and fix, manual call point with junction boxes, accessories as directed.
Supply and fix, conventional manual call point consisting of break glass unit, Alarm status indicator with red colour LED lights, operating on 24 Volts DC supply ,as directed. Make : Ravel / GST / Systems Sensor
Supply and fix conventional hooter, wall mountable type of capacity 80db at 1.00 metre distance, operating on 24 Volts, DC supply, Piezo electric type, operating current 40 mA complete all as specified and as directed. Make : System Sensor / Ravel / Dixi
Supply and fix, SMF Lead Acid, 12 V, 7 Ah battery complete all as specified and as directed. MAKE : Exide or it's techno commercially equivalent make.
Supply and fix, Rubber reinforced line (RRL) hose of 15 metres long, 63 mm dia conforming to IS-636 with one set of gun metal female and male instantaneous coupling complete all as specified and as directed
Supply and fix, Gun metal branch pipes of 63 mm dia, 250 mm length with detachable gun metal nozzles all as per IS 903 with ISI mark embossed on it complete all as specified and as directed.
Supply and fix, Rubber braided hose 19 mm dia, 30 metre long with PVC shut off nozzle complete all as specified and as directed.
Supply, fixing and connecting PVC hose of 19 mm dia suitable for drum of 1.5 metre length complete all as specified and as directed.
Supply, fixing and connecting Swing type hose reel drum including 19 mm dia 30 m long rubber hose including nozzles, etc, (ISI marked) complete all as specified and as directed. Make : GETECH / NEWAGE / QUEEN / SAFEX
Servicing of existing un serviceable booster pump of 12.5 HP capacity by dismantling the pump set from site, greasing and lubricating of pump spare parts and coupling, checking and correcting the alignment of pump with motor, coupling and shaft, checking of cable terminals, foundation bolts tightening replacement of unserviceable spares including transportation of pump set to work shop and bringing back site complete all as specified and as directed.
Servicing of electrically operated motor of 13.4 HP capacity, 3 phase, 415 Volts, AC, after unscrewing of nuts, bolt and bearing and reassembling the same after applying varnish, greasing, oiling and alignment of all the loosen parts complete all as specified and as directed.
Servicing of electrically operated motor of 1 HP capacity, 3 phase, 415 Volts, AC, after unscrewing of nuts, bolt and bearing and reassembling the same after applying varnish, greasing, oiling and alignment of all the loosen parts complete all as specified and as directed
Servicing of electrically operated centrifugal pump of 5 HP capacity, 3 Phase, 415 Volts, AC after unscrewing of nuts, bolt, bearing and rotor and reassembling the same after applying varnish, greasing , oiling and alignment of all the loosen parts complete all as specified and as directed
Material and labour for Greasing winch spindles, guide rollers, platform locking pins and gear box arrangement after rubbing and scrapping old grease and cleaning with cotton waste and applying fresh grease of approved quality complete all as specified and as directed. NOTE:- i) Net weight of fresh grease applied will be measured against this item. ii) The quoted rate shall deemed to include for necessary tools and plant, etc., as required at site for carrying out work in vertical height of 28 m. iii) Tenderers are advised to visit site of work and quote their rates. Nothing extra over and above his quoted rate will be admissible
Overhauling of electrically operated motor of 13.4 HP capacity, 3 phase, 415 Volts AC, measuring no load current, IR value and winding resistance using micro ohm meter before overhauling, dismantling of motor, measuring stator and rotor ID, carry out dynamic balancing of rotor if required, applying grease and varnish, assembling of motor, carry out no load current and KW study and alignment of all the loosen parts including transportation from LRDE to workshop in Bangalore and back including re-fixing, connecting, commissioning and testing complete all as specified and as directed. NOTE: - Rate quoted includes for all minor spares only and major spare parts will be measured and paid separately as "Supply only" under relevant items of this BOQ, but labour element for replacing same shall deemed to be inlcuded in this item.
Dismantling motor, 3 phase, 415 Volts, AC of 0.5 HP to 1 HP capacity, opening up, remove the burn out winding, rewinding with same gauge copper conductor, insulating, varnishing, greasing, reassemble parts, re-fixing to the position, testing and commissioning complete all as specified and as directed.
All as per Sl Item No. 27.00 here-in-before but motor of 13.4 HP capacity.
Supply only Black Cadmium compound applied as directed on hoisting mechanism wire rope after fully cleaning by removing old dry compound using wire brushes and thinner complete all as directed. NOTE:- i) The quoted rate shall deemed to include for necessary tools and plant, etc., as required at site for carrying out work in vertical height of 28 m and No of ropes are 16 Nos ii) Tenderers are advised to visit site of work and quote their rates. Nothing extra over and above his quoted rate will be admissible
Supply only Gear Oil, 90 grade for winch gear box after draining out the old oil, cleaning and filling the new oil complete all as specified directed.
Supply only Hydraulic oil suitable for winch thruster break, cleaning and filling the new oil after draining out the old oil complete all as specified and as directed.
Supply and fix, PVC insulated, PVC sheathed cable with copper bunched conductor of size 1.5 sq. mm, 2 core fixed on vertical or horizontal surfaces with and including 19 mm dia PVC rigid medium conduit alongwith accessories, i.e., bends, elbows, flexible conduits, etc., and taking down existing wiring, complete all as specified and as directed. Note : one run of cable and one run of Conduit will be measured as unit per RM
Supply and fix in repairs, Power contactor, 3 pole, 32 Amps, 415 Volts, 50 Hz all as per Cat No. 3 TF 32 of Siemens or equivalent model in other makes specified complete all as specified and as directed.
Supply and fix in repairs, Control HRC fuse, DIN type, 6 to 32 Amps complete all as specified and as directed
Supply and fix, Over load protection relay directly operated range 13 to 21 Amps all as per Cat No SS 91859OOCO of L&T or equivalent of model in other makes specified including taking down old one complete all as directed.
Supply and fix, Over load protection relay directly mounting 6 to 10 Amps all as per Cat No SS 91858OOVO of L&T or equivalent of model in other makes specified including taking down old one complete all specified and as directed.
Supply and fix, Over load protection relay directly mounting 2.5 to 4 Amps all as per Cat No SS 91858OOBO of L&T or equivalent of model in other makes specified including taking down old one complete all as specified and as directed.
Supply and fix, Over load protection relays directly operated, range 0.6 to 1 Amps all as per Cat No ST94074OOKO of L&T or equivalent of model in other makes specified including taking down old one complete all as specified and as directed.
Supply and fix, Actuator unit 6 Amps, 415 Volts, black colour 2 position suitable to match as required to site all as per Cat No. SS91516 of L&T or equivalent model in other makes specified including taking down old one complete all as complete all as directed.
Supply and fix, Paper role Bearing of No. 3207 suitable for rope Pulley complete all as specified and as directed
Supply and fix, Ball Bearing of No. 6303/6304 including taking out old bearing complete all as specified and as directed.
Supply and fix, Bearing of No. 30204A URB/6006ZZ VBF/6207VBF including taking out old bearing complete all as specified and as directed.
Supply and fix, Bearing of No. 6008ZZ VBF/6010ZZ VBF including taking out old bearing complete all as specified and as directed.
Supply and fix in repairs, Brake shoe assembly with liner complete all as specified and as directed.
Supply and fix in repairs, Coupling suitable for 1 HP motor complete all as specified and as directed.
Supply and fix in repairs, Break drum Coupling 200 mm dia suitable for winch complete all as specified and as directed.
Supply and fix in repairs, Rotary limit switch type RLS -48, 415 Volts, 40 Amps complete all as specified and as directed.
Supply and fix in repairs, Lever type Limit Switch type - KCLS, 415 Volts, 40 Amps complete all as specified and as directed
Supply and fix, thruster for break, type KTM, 415 Volts, three phase, 50 Hz including taking down old one complete all as specified and as directed.
Supply and fix, synthetic insulation mat of size 2 m x 1 m x 19 mm including taking down old one complete all as specified and as directed.
Supply and Installation of intelligent Addressable Networkable 2 Loop Fire Alarm Control Panel is able to connect 250 devices (Detector or Module) per loop in any combination and have suitable number of loop in the panel with 20% spare address for detectors in each & every loop. Should have Min 854 Char LCD multi-line QVGA LCD display complete with inbuilt additional Seven customized programmable function switch for direct activation of any device or control along with three programmable LED's indication. Inbuilt min three Notification applicable circuit (NAC) for hooters. (UL, ULC listed & CSFM, MEA, FM approved). Make: Notifier, NFS 640 complete all as specified and as directed.
Supply and Installation of Female Coupling - Gun Metal of 63mm dia complete all as specified and as directed.
Supply and Installation of Glass for Hydrant Box with rubber beading complete all as specified and as directed.
Servicing of Existing of Main Electrical Pump of capacity 25 to 50 HP Greasing and Oil of Pump Spares and Coupling, Check the alignment of pump with motor, coupling and shaft, checking of cable terminals, Foundation Bolt tightening and suitable size of glad rope as required complete all as specified and as directed.
Servicing of Existing of booster pump. Greasing and Oil of Pump Spares and coupling, Check the alignment of pump with motor, Coupling and shaft., Checking of cable terminals and Foundation Bolt tightening and suitable size of gland rope as suitable sixe of gland rope as required complete all as specified and as directed.
Supply and installation of Pressure Gauge 0 to 16 kg/cm2 complete all as specified and as directed.
Supply and installation of key of hydrant box complete all as specified and as directed.
Supply and installation of hammer for hydrant box complete all as specified and as directed.
Supply and installation of Glass -4mm thickness for key in hydrant box complete all as specified and as directed.
Supply and installation of Hydrant Lug for hydrant valve complete all as specified and as directed.
Supply and installation of Spindle Washer for Hydrant Valve complete all as specified and as directed.
Supply and installation of Rubber Blank Cap for Hydrant Valve outlet of size 63mm dia. complete all as specified and as directed.
Supply and installation of Shut off Nozzle, PVC type to be picked at the end of rubber hose in the hose reel drum. complete all as specified and as directed.
Supply and installation of lip washer complete all as specified and as directed.
Notes for Sl Item Nos 65 & 66 :-The Contractor shall submit Valid CPRI Certificate alongwith panel drawings duly signed by manufacturer and Contractor for Approval of Accepting Officer before placing Order on the manufacturer.
Supply and fix, 8 mm / 10 mm gland rope suitable for Pumps complete all as specified and as directed.
Supply, install, testing of microprocessor controlled based conventional 4 zone Fire Alarm Panel (Make : Ravel / Notifier or Techno commercial equivalents mentioned here-in-after, complete all as specified and as directed.
Supply, install, test and commissioning of 4 Channel weight controller system of RADAR Open Test Platform, complete all as specified and directed
Preparation of old painted steel surfaces of any description not other wise described over 10 cm width or girth applying one coat of synthetic enamel paint complete all as specified and as directed. Note: i) Painting shall be carried out to RADAR Test Platform Unit, comprising of stair case, columns, Lift upto 30 m height, Fixed Platform at 28 m height and Moving Platform. ii) Contractor's quoted rate shall deemed to include for necessary scaffolding required for carrying out painting with all safety precautions (including insurance) for persons engaged, iii) Tenderers are advised to visit site of work and quote their rates. Nothing extra over and above his quoted rate will be admissible.
Preparation of new steel surfaces of any description not other wise described over 10 cm width or girth applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer, complete all as specified and as directed.
Excavation in trenches not exceeding 1.5 m deep and not exceeding 1.5 m wide and getting out in hard / dense soil all as directed.
Returning and filling in, soils, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick all as directed.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all as directed.
Taking down existing unserviceable, 1100 Volts grade cable, Supply and lay new 1100 V grade, XLPE insulated, screened, bedded galvanised steel strip/wire armoured heavy duty with aluminium conductor of cross sectional area 95 Sqmm 3.5 core with cable protection works (as aplicable) laid in trenches/ ducts/ fixed on pole/ wall /laid under road /path/ culvert/ drains/ encased in pipe, including necessary lugs,joiniting and tesing complete all as specified and as directed.
Taking down existing unserviceable, 1100 Volts grade cable, Supply and lay new 1100 V grade, XLPE insulated, screened, bedded galvanised steel strip/wire armoured heavy duty with aluminium conductor of cross sectional area 70 Sqmm 3.5 core with cable protection works (as aplicable) laid in trenches/ ducts/ fixed on pole/ wall /laid under road /path/ culvert/ drains/ encased in pipe, including necessary lugs,joiniting and tesing complete all as specified and as directed. Note for Serial Item Nos 75.00 & 76.00 : Necessary excavation, earthwork and cable protection works will be measured and paid for separately under respective items.
Material and labour for, sand cushioning (using M-Sand) in layers for cables in trenches / ducts for cable including consolidation complete all as specified and directed. NOTE: Punned thickness will be measured for payment purpose.
Material and labour for, Bricks, sub class 'B' of old size 230 mm x 115 mm x 75 mm laid in trenches for cable protection all as specified and directed.
Laying only, Bricks, sub class 'B' of old size 230 mm x 115 mm x 75 mm in trenches for cable protection all as specified and directed. Note: Serviceable bricks obtained while excavation shall be used under this item.
Material and labour, Galvanized Iron tubing, light grade, 80 mm bore for protection of cable laid at road crossing / on pole including removal of old unserviceable pipes complete all as specified and directed.
Taking out old unserviceable/burnt joints including Supplying, jointing & testing end termination heat shrink type cable jointing kit suitable for 1100 V, LT UG XLPE cable of size 3.5 Core, 70 to 150 sqmm complete all as specified and as directed
Demolishing of existing earth pits, and providing Material and labour for, earthing complete with Copper earth plate electrode 600 mm x 600 mm x 3.15 mm buried directly in ground vertically in pit of depth not less than 2.25 metre below normal ground level with top edge of the earth plate at a depth not less than 1.5 metre below normal ground level surrounded from all sides with mixture of charcoal and common salt in alternate layers and electrode connected to Copper earth strip of 20 mm x 3 mm by means of bolts, nuts, check nuts and washers, earth strip protected by galvanized steel pipe 40 mm bore (light grade) connected to machinery/ equipment all as shown in electrical plate No. 3 of SSR-2009 Part I and including necessary excavation and earth work in any type of soil, 20 mm bore medium grade GI pipe for watering funnel wire mesh, PCC chamber in CC (1:3:6), type C1 , manhole cover with RCC (1:2:4), type B1, reinforced with 6 mm dia MS round bars @ 15 cm c/c both ways for cover and MS frame etc., complete all as specified and as directed NOTES :- (i) Earth pit shall be constructed at least 0.5 metre away from each earth chamber.
Pacific Enterprises
Satya Dharam Vikas Fire Safety & Security Services
Archana Enterprises
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .