Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.1 CrAdmitted-Finance 9TH FLOOR 920 WAVE SILVER TOWER SECTOR 18 NOIDA GAUTAM BUDDHA NAGAR UTTAR PRADESH 201301 | GAUTAM BUDDHA NAGAR | UTTAR PRADESH | 201301 | ₹5.1 Cr | L1 | Admitted-Finance |
| 2 | L2₹6.4 Cr+₹1.2 Cr (24.3%)Admitted-Finance B 2 46 SECTOR 18 ROHINI DELHI 110089 | NORTH WEST | DELHI | 110089 | ₹6.4 Cr+₹1.2 Cr (24.3%) | L2 | Admitted-Finance |
| 3 | L3₹6.6 Cr+₹1.4 Cr (27.6%)Admitted-Finance | ₹6.6 Cr+₹1.4 Cr (27.6%) | L3 | Admitted-Finance |
| 4 | L4₹6.6 Cr+₹1.4 Cr (27.8%)Admitted-Finance | ₹6.6 Cr+₹1.4 Cr (27.8%) | L4 | Admitted-Finance |
| Sl No | Description | Qty | Unit | CGMP Projects Pvt. Ltd L1 | INTEGRATED CLEANROOM TECHNOLOGIES LTD L4 | Aircon Technique Pvt Ltd L2 | ASEPTIC PROJECTSS L3 |
|---|---|---|---|---|---|---|---|
| 1.00Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in charge. | |||||||
| 1.01 | All kinds of soil | 33 | Cum | 833 ₹27,489 | 900 ₹29,700 | 242 ₹7,986 Lowest | 750 ₹24,750 |
| 2.00Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level : | |||||||
| 2.01 | 1:3:6 (1 Cement: 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources) | 5.63 | Cum | 8,700 ₹48,981 | 9,400 ₹52,922 | 8,063 ₹45,394.69 Lowest | 12,500 ₹70,375 |
| 3.00Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level : | |||||||
| 3.01 | 1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size de rived from natural sources) | 15 | Cum | 11,063 ₹1,65,945 | 11,948 ₹1,79,220 | 9,870 ₹1,48,050 Lowest | 21,000 ₹3,15,000 |
| 4.00Centering and shuttering including strutting, propping etc. and removal of form for | |||||||
| 4.01 | Foundations, footings, bases for columns | 42 | Sqm. | 873 ₹36,666 | 943 ₹39,606 | 363 ₹15,246 | 0.01 ₹0.42 Lowest |
| 4.02 | Lintels, beams, plinth beams, girders, bressumers and cantilevers | 9 | Sqm. | 920 ₹8,280 | 994 ₹8,946 | 718 ₹6,462 | 0.01 ₹0.09 Lowest |
| 5.00Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. | |||||||
Tender Value
₹5.7 Cr
EMD Value
₹11.4 L
Closing Date
11 Dec 2023, 3:00 pmClosed
Executive Engineer
Office of the Executive Engineer (ED-I), Main Building, IIT Delhi, Hauz Khas, New Delhi-110016
Setting up sterilization facility and clean room (Class 1000 and Class 10000) for mPRAGATI at ISTE building at IIT Delhi
2023_IIT_783399_1
IITD/WORKS (SP-4435)/2023
Open Tender
Miscellaneous Works
Works
240 days
Indian Institute of Technology Delhi
As per tender documents
15 documents required · 15 mandatory
₹0
₹11.4 L
15 Feb 2024
1 Dec 2023
12 Dec 2023
1 Dec 2023
11 Dec 2023
1 Dec 2023
Amount
Earth work in excavation by mechanical means (Hydraulic excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in charge.
All kinds of soil
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :
1:3:6 (1 Cement: 3 coarse sand (zone-III) derived from natural sources : 6 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement - All work up to plinth level :
1:1.5:3 (1 cement : 1.5 coarse sand (zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size de rived from natural sources)
Centering and shuttering including strutting, propping etc. and removal of form for
Foundations, footings, bases for columns
Lintels, beams, plinth beams, girders, bressumers and cantilevers
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level.
Thermo-Mechanically Treated bars of grade Fe-500D or more.
Half brick masonry with common burnt clay F.P.S. (non-modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level.
Cement mortar 1:4 (1 cement :4 coarse sand)
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete.
Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing in position, and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.
Electric resistance or induction butt welded tubes
Providing and laying rectified Glazed Ceramic floor tiles of size 300x300 mm or more (thickness to be specified by the manufacturer), of 1st quality conforming to IS : 15622, of approved make, in all colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3 kg/ sqm including pointing the joints with white cement and matching pigments etc., complete.
Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns minimum to avoid scratches during transportation and should be supplied in single length upto 12 metre or as desired by Engineerin-charge. The sheet shall be fixed using self drilling /self tapping screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape wherever required.
Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+0.05 %) total coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self tapping screws complete :
Ridges plain (500 - 600mm)
Gutter (600 mm over all girth)
Demolishing cement concrete manually/ by mechanical means including disposal of material within 50 metres lead as per direction of Engineer - in - charge
Nominal concrete 1:3:6 or richer mix (i/c equivalent design mix)
Demolishing R.C.C. work manually/ by mechanical means including stacking of steel bars and disposal of unserviceable material within 50 metres lead as per direction of Engineer - in- charge.
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge.
In cement mortar
Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead.
Of area 3 sq. metres and below
Of area beyond 3 sq. metres
Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.
For thickness of tiles above 25 mm and up to 40 mm
Dismantling wooden boardings in lining of walls and partitions, excluding supporting members but including stacking within 50 metres lead :
Thickness above 25 mm up to 40 mm
Dismantling cement asbestos or other hard board ceiling or partition walls including stacking of serviceable materials and disposal of unserviceable materials within 50 metres lead.
Dismantling G.I. pipes (external work) including excavation and refilling trenches after taking out the pipes, manually/ by mechanical means including stacking of pipes within 50 metres lead as per direction of Engineer-in-charge:
15 mm to 40 mm nominal bore
Dismantling C.I. pipes including excavation and refilling trenches after taking out the pipes, manually/ by mechanical means breaking lead caulked joints, melting of lead and making into blocks including stacking of pipes & lead at site within 50 metre lead as per direction of Engineer-in-charge:
Up to 150 mm diameter
Dismantling of flushing cistern of all types (C.I./PVC/Vitreous China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead.
Disposal of building rubbish / malba / similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved.
Supplying at site
Welded steel wire fabric of required width having rectangular mesh painted with two or more coats of enamel paint of approved shade over a coat of primer (Priming & Painting to be paid for separately)
Welded steel wire fabric fencing with posts of specified material and of standard design placed and embedded in cement concrete blocks 45x45x 60 cm of mix 1:5:10 (1 cement:5 fine sand : 10 graded stone aggregate 40 mm nominal size), every 15th post, last but one end post and corner post shall be strutted on both sides and end post on one side only and struts embedded in cement concrete blocks 70x45x50 cm of the same mix, provided with welded steel wire fabric fixed between the posts fitted and fixed with G.I. staples on wooden plugs or tied to 6 mm bar nibs with G.I. binding wire (cost of posts, welded steel wire fabric, painting, earth work in excavation and concrete to be paid for separately).
Non Schedule Providing and laying ready to use non shrink. Cementitious free flow micro concrete of Compressive strength ≥ 50 MPa (28 days) according to ASTM C 109 of approved make and manufacture complete as per direction of Engineer-in-charge for replacing the carbonated part of concrete and repairing the damaged surface of concrete after fix the form work across the profile of damaged structural element. Pour the free flow non shrink. Cementitious free flow micro concrete mix in the form work. Payment shall be made on the basis of consumed dry material of micro concrete mix. (Product :- Renderock RG of Fosroc/ SikaRep® Microcrete -4 of Sika / MasterEmaco S-346 of BASF or equivalent of Pidilite)
a) Without addition of aggregate
Supply and installation of clean room wall panel ; 50mm thick double skin (PPGI) on both sides with 40±2 kg/m3 density PUF filing, 0.6 mm sheets on both sides. This will include all accessories, sealent and complete in all respect.
Supply and installation of clean room wall panel ; 100mm thick double skin (PPGI) on both sides with 40±2 kg/m3 density PUF filing/ RA riser duct, 0.6 mm sheets on both sides. This will include all accessories, sealent and complete in all respect.
Supply and installation of clean room ceiling system : Walkable double skin false ceiling of 50 mm thick with skin (PPGI) on both sides with 40±2 kg/m3 density PUF filing with 0.6 mm thick sheets on both sides. This will include all accessories, sealent and complete in all respect. All cutouts shall be factory fabricated. Ceiling supporting system included under this head.
Providing and fixing Aluminium powder coated internal Covings with Aluminium Backing-R-50
Providing and fixing Aluminium powder coated external Covings with Aluminium Backing-R-50
Providing and fixing 2D/ 3D Aluminium powder coated corner coving
Providing and fixing Two Way External Corner For 50mm Wall Panel
Two Way External Corner For 100mm Wall Panel
Supply & Installation of clean room campatible 50mm single /Double leaf door made up of 0.6mm thick GI pre coated sheet with door frame, with all SS acessoriess such as door closure, D-Handle, Hinges, push and pull plates etc., including view pannel, to be fitted on 50 mm / 100 mm thick clean rooms walls panel. All door shall have automatic bottom seal / drop seal.
Providing and fixing Single Door 1000mmx2100mm
Providing and fixing Double Door 1200mmx2100mm
Providing and fixing Emergency Door 900mmx2100mm with panic baar
Providing and fixing Double Door 2400mmx2100mm
Providing and fixing Clean room compatible double glazed windows to be fitted on clean room wall. View Panel size 1000 x 1000
Providing and fixing Cutouts In ceiling Panel
Providing and fixing Cutouts In Wall Panel for Electrical Socket, switches
Providing and fixing Conduit PVC 1" disembodied inside PUF panel
Providing and fixing C Channel powder coated
Providing and fixing Cleanroom Return air Riser duct 900 x 80 mm made of GI internal for return of air
Providing and fixing Riser Grill SS with capsule perforations, SS dome bolts and slot for filter
Providing and fixing Riser Prefilter
Providing and fixing Riser Damper to be operated from within the riser from cleanroom
EPOXY FLOORING (a) Surface Preparation: It is essential that Nitoflor SL2000 of Fosroc / SIka Floor 261hs of Sika or equivelant of BASF is applied to sound, clean and dry surfaces in order that maximum bond strength is achieved between the substrate and the flooring system. All dust and debris should be removed prior to application of the product or its primer. New concrete floors: New concrete, or cementitious substrates, should be at least 28 days old and have a moisture content not exceeding 5%. Laitance deposits on new concrete are best removed by light grit blasting, mechanical scrabbling or grinding. Old concrete floors: Existing concrete floors which require refurbishment must be prepared to ensure a strong adhesive bond between the flooring system and the existing floor. Mechanical cleaning methods are strongly recommended particularly where heavy contamination by oil and grease has occurred or existing coatings are present. To ensure adhesion, all contamination should be removed. Alternatively, blasting techniques can be used to provide the required substrate.
(b) Priming: All surfaces treated with Nitoflor SL2000 of Fosroc / SIka Floor 261hs of SIka or equivelant of BASF should be primed with Nitoprime 25 of Fosroc/ Sika Floor 290 of Sika / equivelant of BASF, a solvent based epoxy resin primer designed for maximum absorption and adhesion to concrete substrates. Add the entire contents of the hardener tin to the base tin and mix the two primer components thoroughly for at least 2 minutes - under no circumstances should part mixing be considered. Once mixed, the primer should be applied immediately to the prepared substrate using stiff brushes or rollers. The primer should be well ‘scrubbed’ into the substrate to ensure full coverage, but care should be taken to avoid over application or ‘ponding’. Allow the primer to dry (see table below) before proceeding to the next stage, do not proceed whilst the primer is ‘tacky’ as this will lead to unsightly marks in the finished surface. Porous substrates may require a second primer coat - when the first coat is directly absorbed into the substrate - but minimum overcoating times must still be observed (see table below). The minimum overcoating times will vary slightly according to the porosity of the substrate. However, they should be in accordance with the following ambient application temperatures.
(c) Epoxy Underlay: Providing mixing and laying to the designated area the epoxy underlay, Nitoflor EU5 of Fosroc/ Sika Floor 291 of Sika or equievelant of BASF consists of special resins and graded aggregates formulated to withstand chemical attack and impact shock. Shall be supplied as a 3 component system comprising resin base, resin hardener and fillers. When correctly laid Nitoflor EU5 of Fosroc/ Sika Floor 291 of Sika or equivelant of BASF will provide a surface ready to receive applications of Fosroc/ Sika or equivelant of BASF flooring systems. Epoxy Underlay shall achieve a minimum compressive strength of 60 N/mm^2, Flexural strength of 20 N/mm^2 and Tensile strength of 10N/mm^2 @ 7 days. The underlay shall have nil water absorption when tested as per BS1881 Part 122-1983. The adhesion strength of the epoxy underlay shall be greater than the tensile strength of concrete. Cost Inclusive of Supply, apply, equipment. Exclusive of Taxes as applicable,. Client shall provide Storage, Power, water,etc. Flooring work shall be executed by Fosroc/ Sika/ BASF Authorised Applicator.
(d) Epoxy Topping: Providing mixing and laying to the designated floor areas shall be surfaced with Nitoflor SL2000 of Fosroc/ Sika Floor 261 hs of Sika or equvelant of BASF, a 2 mm thick flow-applied epoxy resin floor topping. Nitoflor SL2000 of Fosroc / Sika Floor 261 hs of Sika or Equivelant of BASF consists of graded aggregates bound in a pigmented epoxy resin binder. It is supplied as a four component system, pre-weighed for on-site mixing. When laid, it provides a smooth, light-reflective surface. It is available in a range of standard colours. The topping shall achieve a minimum compressive strength of 40 N/mm2 and a flexural strength of 25 N/mm2 at 7 days when tested to BS6319. Slip resistance : 91.3 & 135.6 (As per TRRL skid test in accordance with BS 6677 : Part 1:1986, Shore D Hardness as per (ASTM D 2240) : 80 .Abrasion resistance : 0.1mg/ cycle-loss of weight (ASTM D 4060) (with CS 17 wheel of 1000g weight) . Adhesion Strength @ 7 days (ASTM D412) :> 1.0N/mm2. it shall be capable of accepting foot traffic at 24 hours and vehicular traffic at 48 hours. Cost Inclusive of Supply, apply, equipment’s. Exclusive of Taxes as applicable,. Client shall provide storage, power, water, etc. Flooring work shall be executed by Fosroc/ Sika or equivelant of BASF Authorised Applicator.
Epoxy underlay 3.0mm + Epoxy Self Levelling Topping at 2.0 mm
Providing and fixing75mm X 75mm Providing, laying and fixing epoxy coving at all required junction i.e wall/floor, wall/ceiling, Wall/wall which shall be constructed with solvents very high abrasion resistant aggregates. Coving shall be impermeable with water & flush with wall/floor/ceiling & with proper levelling at all floor, all levels, all heigh
CLEANROOM LAB FURNITURE AS DETAILED BELOW Providing and fixing SS 304 show rack cum cross over bench made of 18 swg SS. Dimensions: 1000mm (L) x 300mm (W) x 650mm (H) matt finish
Providing and fixing MS painted Emergency shower and Eye wash station with hand operated shower and foot / elbow operated eye wash. The unit shall have a common water inlet and drain point.
Providing and fixing Static Pass Box mde of SS 316 working size approx 600 x 600 x 600 mm with door interlock, UV light, UV counter all complete
Providing and fixing Dynamic Pass Box made of SS 316 working size approx 600 x 600 x 600 mm with HEPA filtered air supply, blower motor assembly, door interlock, UV light, UV counter all complete
Providing and fixing Single entry air shower fabricated with SS-304, 20G sheet for movement of single person with all complete with H13 HEPA Filter, Pre-filter, blowers, ss adjustable nozzles, SS grated floor, two doors with inter-locking arrangement timer with fully adjustable, fully automatic with electronic logic control. Air shower shall confirm to clean room class 100 at nozzle outlet
Providing and fixing Self levelling compound for preparation of floor 3 mm thick
Providing and fixing Aluminium powder coated Supply and Return air module (perforated sheet) with air adjustable damper.
Providing and fixing 36W LED cleanroom light fixture 2' x 2', Bottom openable, with electronic ballast
UTILITIES SITC of Compressed Dry Air system consisting of skid mounted 3 HP air compressor Piston type, with electric motor, Air receiver of 200 Ltr, Maximum working pressure 12 kg /cm2 and flow 12 CFM. Air dryer 20 CFM. System shall have line filter 0.01 PPM (0.01 micron) for removal of solid particles, liquid water and oil aerosol. Line filter 0.003 ppm (Activated carbon filter) for removal of oil vapour and hydrocarbon odours. Life of 1000 Hrs.
Providing and fixing SITC of Industrial RO Plant 100Ltr/ hour capacity consisting of high pressure Pump, panel interconnecting piping, 1000 ltr PVC tanks all complete.
(Providing and fixing SS 304 Pendent for Utility Piping inside lab
Fabrication and installation of SS 304 pendent hanging from ceiling 3" dia with buffed external surface. Each pendent shall have provision to accommodate 3 pipes each of 1/4" or 1/2" diameter of various utilities. Bottom of pendent shall be at 1.8 mtr above floor level. Internal spacer for pipes shall be provided at top and bottom face of pendent and shall be welded with ss plate. The pendent shall be supported from ceiling. Price of internal pipes shall be paid separately under different heads.
Providing and fixing Fabrication and installation of SS 304 pendent hanging from ceiling 2" dia with buffed external surface. Each pendent shall have provision to accommodate 2 pipes each of 1/4" or 1/2" diameter of various utilities. Bottom of pendent shall be at 1.8 mtr above floor level. Internal spacer for pipes shall be provided at top and bottom face of pendent and shall be welded with ss plate. The pendent shall be supported from ceiling. Price of internal pipes shall be paid separately under different heads.
UTILITY PIPING SYSTEM: Installation of utility piping, Orbital Welding, TIG welding etc as required for various system Gas bank Accessories Providing and fixing Frame 1+1 Cyl. Manifold, GI
Providing and fixing Cylinder Bracket with chain SS 202
Providing and fixing Nut Bullnose 1/4" SS 316, 150 Bar
Providing and fixing Check Valve 1/4" SS 316, 150 Bar
Providing and fixing Hose ,1 Mtr Long, 1/4" SS 316, 150 Bar
Providing and fixing Isolation Valve, 1/4" SS 316, 150 Bar
Providing and fixing Double Stage Regulator With PRV 1/4" NPTF (Flow: 200 LPM) SS316, 150 Bar in and 0.1-10 bar outlet pressure.
Providing and fixing Connector 1/4" x 1/2" SS 316, 150 Bar
Providing and fixing Manifold Block T type, SS316
Providing and fixing Ball Valve, 1/2" SS316, 150 Bar
Providing and fixing Flash BacK Arrestor with Connector 1/2", Brass, 10 Bar
Providing and fixing Flash BacK Arrestor with Connector 1/4", Brass, 10 Bar
Providing and fixing CO2 Heater With Inlet & Outlet Connector, Brass
Providing and fixing Seamless Tube 1/4" SS 316, 150 Bar
Lab Piping & Accessories as below. Providing and fixing Source Connector 1", SS316, 10 Bar
Providing and fixing Source Connector 1/2", SS316, 10 Bar
Providing and fixing Ball Valve 1", SS316, 10 Bar
Providing and fixing Ball Valve 1/2", SS316, 10 Bar
Providing and fixing Ball Valve 1/4", SS316, 10 Bar
Providing and fixing Y-Strainer With Connector 1", 3 Bar, Brass
Providing and fixing Y-Strainer With Connector 1/2", 3 Bar, Brass
Providing and fixing Pressure Reducing Valve 1", 3 Bar, Brass
Providing and fixing Pressure Reducing Valve 1/2", 3 Bar, Brass
Providing and fixing Zero Dead Leg Valve including TC Liner and Clamp With Connector 1/2", 3 Bar, SS316
Providing and fixing Pressure Gauge 4"Dial 1/2"BSPM Ball Valve 1/2"BSPF Connector 1/2"BSPM x 1/2"OD Unequal Tee 1"OD x 1/2"OD
Providing and fixing Pressure Gauge 4"Dial 1/2"BSPM Ball Valve 1/2"BSPF Connector 1/2"BSPM x 1/2"OD Equal Tee 1/2"OD
Providing and fixing Point Of Use Control Panel 1/4"
Providing and fixing Line Regulator (Flow 150 LPM) along with Pressure Gauges & Mounting Plate
Providing and fixing Connector 1/4" x 1/2" SS 316, 0 - 10 Bar
Providing and fixing Equal Tee 1" X 1" SS 316
Providing and fixing Equal Tee 1/2" X 1/2" SS 316
Providing and fixing Unequal Tee 1" X 1/2" SS 316
Providing and fixing Unequal Tee 1" X 1/4" SS 316
Providing and fixing Reducer 1" X 1/2" SS 316
Providing and fixing Reducer 1/2" X 1/4" SS 316
Providing and fixing OD to PU Connector
Providing and fixing Shower Connector
Providing and fixing End Connector 1" SS 316
Providing and fixing End Connector 1/2" SS 316
Providing and fixing Elbow 1" SS 316
Providing and fixing Seamless Tube 1" SS 316, 150 Bar
Providing and fixing Seamless Tube 1/2" SS 316, 150 Bar
Providing and fixing Seamless Tube 1/4" SS 316, 150 Bar
Providing and fixing Flexible PU Pipe 1/4"
Providing and fixing SpeciaL supports comprising of SS Clamp, Unistrut Channel, PP Clamp With Rail Nut(For all size of tubes as per BOQ), Aluminium Profile , PP End Caps, M10 GI Threaded Rod, M10 GI Plane Washer & nut, M10 GI Anchor Bolt For Threaded all above mentioned items ,Tagging & accessories.
Providing and fixing RO System : CPVC Piping 1/2" diameter for distributon of RO water from source to point of use, including proper support, joints/ sockets, tee, elbow all as required as directed by the engineer.
INSTALLATION OF PROCESS EQUIPMENT AS BELOW: Installation of Bio safety cabinets including exhaust arrangement for BSL lab. IIT shall provide the Bio safety cabinet at site and contactor has to make cutout in ceiling, provide exhaust duct, direct drive exhaust fan and cowl with bird screen.
Installation of Double door autoclave for BSL lab. IIT shall provide the Autoclave at site and contactor has to make cutout in wall to suit installation of the Autoclave. Equipment manufacturer will install and commission the Autoclave.
Less Credit for Dismantled Materials Firewood from damaged cupboards etc.
Old Flush door shutter of various thickness and size with fitting etc.
Old M.S. section / steel bars scrap / G.I. pipes etc.
Old/ Broken Aluminium section + beading etc.
Schedule B - E & M Works Supplying and laying of one number PVC insulated and PVC sheathed / XLPE armouredaluminium power cable of 1.1 KV grade ISI marked of size 3.5 Core x 300 sqmmas per following. (Acceptable make: Havells / Polycab / NICCO / RR Kabel / Skytone / Gloster / KEI / Universal)
Direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
On wall surface as required.
On cable tray as required.
Supplying and laying of 1 Core x 185 sqmm PVC insulated ISI marked flexible copper cable including end termination with copper lugs etc. as required. (for connection from busbar to main MCCB) (Acceptable make: Havells / Polycab / NICCO / RR Kabel / Skytone / Gloster / KEI / Universal)
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel / PVC conduit as required. (Acceptable make: Havells / Polycab / NICCO / RR Kabel / Skytone / Gloster / KEI / Universal / Finolex)
3 x 4 sqmm
3 x 1.5 sqmm
supplying and fixing of following sizes of ISI marked steel conduit alongwith accessories in surface / recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed
Providing and fixing 630 A, 50 KA, FPMCCB with thermomagnetic release and terminal spreaders with sheet steel cubicle panel board on wall duly painted with powder coat of size not less than 600 mm x 600 mm x 400 mm (depth) including drilling holes in cubicle panel, hinged door openable form front side, with operating handle, making connections, etc. as required. (Acceptable make of MCCB: L&T / Havells / Siemens / GE / C&S / Crompton / Legrands)
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mmdia G.I. pipe from earth electrode including connection `with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm diaG.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required
Providing and fixing4.00 mm dia bare copper wire on surface or in recess for loop earthing as required.
Providing and fixing earth bus of 50 mm X 5 mm copper strip on surface for connections etc. including drilling different holes as required.
Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray (Galvanization thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. (Acceptable make: Technofab / Indiana cable tray / Legrand)
100 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "bends" (galvanization not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. [same make as cable tray]
100 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and installing following size of perforated Hot Dipped Galvanized Iron cable tray "Tee" (galvanization not less than 50 microns) with perforation not more than 7.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required. [same make as cabe tray]
100 mm width X 50 mm depth X 1.6 mm thickness
225 mm width X 50 mm depth X 1.6 mm thickness
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as required . [Acceptable make: Havells / Siemens / Standard / Crompton / L&T / Legrand / GM]
12 way (4 + 36), Double door
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface / recess, complete with tinned copper busbar, neutral busbar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (but without MCB / isolator) [Acceptable make: Havells / Siemens / Standard / Crompton / L&T / Legrand / GM]
8 Way, Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. [Acceptable make: Havells / Siemens / Standard / Crompton / L&T / Legrand / GM]
Single pole
Double pole
Triple pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. [Acceptable make: Havells / Siemens / Standard / Crompton / L&T / Legrand / GM]
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet, with 4 pole and earth, metal enclosed plug top along with 30 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required [Acceptable make: Havells / Siemens / Standard / Crompton / L&T / Legrand / GM]
Supplying and fixing Cable End Box (Loose Wire Box) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 Volts, on surface/ recess, complete with testing and commissioning etc.as required.
For 12-way, Double door TPN MCBDB
Supplying and fixing Cable End Box (Loose Wire Box) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 Volts, on surface/ recess, complete with testing and commissioning etc.as required.
For 8-way, Double door SPN MCBDB
Supplying and fixing of rcessed type clean room compatible LED luminaire of size 595 mm x 595 mm (approx) with provision of bottom openable, IP 65 protection, body made of CRCA powder coated with white colour, high transmittance diffuser completes with connections etc. as required. CCT not less than 5700 K, Wattage 36 - 50 Watt [Acceptable make: Philips / Panasonic / Bajaj / Polycab / Wipro / Crompton / Osram / Havells /
Supplying and fixing following size / modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. [Acceptable make: Legrand / Havells / L&T / MDS / Wipro / GM / Polycab / Schneider]
2 module
3 Module
6 Module
8 Module
12 Module
Supplying and fixing following modular base & cover plate on existing modular metal boxes etc. as required. [Acceptable make: Legrand / Havells / L&T / MDS / Wipro / GM / Polycab / Schneider]
2 module
3 Module
6 Module
8 Module
12 Module
Supplying and fixing following modular switch / socket on the existing modular plate and switch box including connections but excluding modular plate as required. [Acceptable make: Legrand / Havells / L&T / MDS / Wipro / GM / Polycab / Schneider]
5/6 A switch (light loads)
Telephone socket outlet
15/16 A switch (power loads)
6 pin 15/16 A socket outlet
Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. [Acceptable make: Havells / MDS / GM / L&T]
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. (Acceptable make: Havells / Finolex / Polycab / KEI)
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. (Acceptable make: D Link / Legrand / Finolex)
1 run of cable
2 run of cable
Supplying and fixing following type and module data sockets on the existing modular plate and switch box including connections as required. [Acceptable make: L&T / MDS / Wipro / Havells / GM]
RJ11 socket with shutter 1 M
Twin RJ11 socket with shutter 1 M
RJ45 CAT6 socket with shutter
Supplying and fixing of 250 mm sweep fresh air (exhaust fan) fan of not more than 45 watt rating, 1100 - 1350 rpm, complete with motor blade assembly, non-metallic frame (body), louvre shutter with two year warranty on product, colour white or off white. [Acceptable make: Havells / Usha / Bajaj / Orient) Ref similar product: Havells Ventilair DX 250]
SITC of surface mounted LED downlighter with metallic body (either round or square shaped, with inbuilt driver, CRI not less than 80) luminaire of 12 watt rating cool day light with colour temperature 6000-6500 K, lumen output not less than 1000 lumen suitable for use on 230-volt, 50 Hz ac supply as required. [Acceptable make: Philips / Panasonic / Bajaj / Wipro / Crompton / Osram / Havells]
Supplying and laying of flame-retardant rubber mat of 11 KV di-electric strength grade (ISI marked) of thickness not less than 2.0 mm, finished with anti-slip ribbed srface compliant to IEC 61111:2009 for laying infront of electrical panel and utilities etc. complete as required. (Acceptable make: Mrvel / Shock Pru / Duratuf / Dozz / Insulatica)
Fabrication, supply, Installation testing & commissioning of Electrical control panel of cubicle construction, floor mounted type, fabricated out of 2mm thick CRCA sheet, compartmentalized with hinged lockable doors, dust and vermin proof, powder coated of approved shade after 7 tank treatment process, cable alley, inter-connection with suitable size copper conductor cable/solid copper strip, having switchgears and accessories, mountings and internal wiring, earth terminals, numbering etc. complete in all respect, suitable for MAIN MV DISTRIBUTION PANEL complete as per CPWD specification for Electrical Works with following Incoming and Outgoing, suitable for operation on 415 V, 3 phase, 50 Hz ac Supply with enclosure protection class IP 42 as required. VFD with fan cooler unit should be incorporated in the compartment for AHU with connections (cost of VFD excluded in Panel): Size 2300 mm (L) x 2000 mm (H) x 450 mm (Depth) (acceptable make: Adlec / Trocolite / Rittal / Jakson / Milestone / Advance / Neptune / Anand / EAP / Intracool)
INCOMING: 400 A, 50 kA, 4 Pole MCCB, with microprocessor release conforming to IS/IEC 60947-2, Ics = 100% Icu, adjustable overload setting from 0.4 to 1.0 x Ir, inbuilt instantaneous protection with front handle for operation, spreader terminal for cable / busbar connection (Acceptable make: L&T / Legrand / Siemens / Havells / GE)
LED type RYB Phase indicating lamps, ON, OFF indicating lamps
Set of copper busbar 600 A with proper insulated mountings
OUTGOINGS: 125 A, 30 kA, 4 Pole MCCB, conforming to IS/IEC 60947-2, Ics = 100% Icu, adjustable overload setting, with front handle for operation, spreader terminal / phase barrier for cable / busbar connection : 2 nos. (Acceptable make: L&T / Legrand / Siemens / Havells / GE)
63 A, 10 kA, 4 Pole MCCB, conforming to IS/IEC 60947-2, Ics = 100% Icu, adjustable overload setting, with front handle for operation, spreader terminal / phase barrier for cable / busbar connection : 12 nos. (Acceptable make: L&T / Legrand / Siemens / Havells / GE)
32 A, 10 kA, 4 Pole MCCB, conforming to IS/IEC 60947-2, Ics = 100% Icu, adjustable overload setting, with front handle for operation, spreader terminal / phase barrier for cable / busbar connection : 04 nos. (Acceptable make: L&T / Legrand / Siemens / Havells / GE)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.
3.5 Core x 300 sqmm
Supplying, Installation, Testing and Commissioning of 10 KVA online 3 phase UPS system with 30-minute backup including batteries, interconnecting cables, battery racks etc. complete as required. (Acceptable make of UPS: Emerson / APC / Mitsubishi / Siemens / DB Power Electronics / GE / Microtech& Acceptable make of battery: Exide / Amararaja / Luminous / stamford / AMCO / NICCO / Prestolite / Pacesetter / Furukawa)
Supplying and fixing of 30-Watt LED street light for compound lighting made of pressure die cast housing with toughened glass with high power LEDs with IP66 protection fitted on wall with GI pipe of appropriate size with clamps, nuts, bolts, etc. as directed by the Engineer-in-charge. (Acceptable make: Philips / Wipro / Panasonic / Havells / Crompton)
(HVAC WORK) Supplying, Installing, Testing and Commissioning of screw / scroll type water chilling machine each having capacity of 1,45,150 Kcal / hour [56 TR] at chilled water inlet / outlet temperature of 11-12 deg C / 5.5 - 6.5 deg C with chilled water circulation rate of 150 (min) to 516 (max) LPM [nominal] and air cooled condenser made of copper coil, suitable for operation on 400±10% Volt, 50 Hz ac supply & refrigerant R 407c / R410 (environment friendly) for screw / scroll type machine each comprising of the following complete as per specifications and as required. (Acceptable make: Bluestar / Daikin / Trane / Carrier / Voltas)
Multiple compresors (not less than 2) - Scroll / screw type compressor fully hermetic complete with automatic capacity control, safety switches, speed increasing gears, forced feed lubrication system etc. as per specifications.
Close transition type automatic soft / star-delta starter suitable for compressor motor complete with ammeter with CTs, overload protection, under voltage protection, protection against phase reversal & independent single phase preventors etc. complete as required.
Necessary drive arrangement
Lubrication device consisting of automatic electric pump, oil cooler, head tank, oil strainer, automatic pressure regulating valve, oil heater, oil heater thermal switch etc. as per specifications.
Matching air-cooled condenser of copper tubes and integrally finned
Matching shell & tube flooded type / DX chiller for scroll / screw type units of MS shell and copper tubes.
Refrigerant piping fittings, valves and accessories to interconnect compressor, condenser, chiller and expansion valve.
Microprocessor based control panel complete with accessories as per specifications.
Refrigerant line accessories comprising of safety valves, angle valve, liquid line indications, liquid level control etc.
Water flow switches at inlet and outlet of chiller, water drain & air purge valves wherever required.
Suction line and chiller insulation with minimum 19 mm thick polyvinyl nitrile rubber insulation finished with 0.63 mm thick G.S.S. cladding complete as required.
Frame work for mounting the above condenser, chiller compressor and motor with base plate complete with antivibration pads / springs.
Initial / first charge of refrigerant gas and compressor oil
Proper foundation on existing RCC / MS foundation for the chilling unit
Supplying, erection, testing and commissioning mono block / split casing chilled water pump set capable of delivering 516 LPM (matching with the chiller unit) of water against a head of 30 metre. Each pump shall comprise of following as required as per specifications. (Acceptable make: Beacon / Batliboi / Mther& Platt / KSB / BE / WASP / Grandfos / Jyoti / Crompton / Kirloskar)
1 no. - Mono block / split casing type pump
1 no. - suitable HP, SPDP sqirrel cage induction motor with class - B insulation, matching with chilled water circulation, operating on 415 +/- 10% volts, 3 pphase, 50 Hz a.c. supply.
1 Lot - expanded polystrene [T.F. quality] insulation of not less than 50 mm thick duly cladded between aluminium sheets of 0.5 mm thickness and properly clamped to pump in two semicircular sections as per specifications.
2 nos. - 150 mm dia dial type pressure gauges
1 Lot - Mounting frame with ant vibration pads
Foundation for the pump unit on existing RCC / MS structure
Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. asper specifications and as required complete in all respect. Note:-The Pipes shall be M.S. 'C' class as per IS : 1239 , minimum 6.35mm thick M.S. Sheet (Acceptable make: Bansal / TATA / ITC / ATC / JST / Jindal / Zenith / Nezone)
80 mm dia (32 mm thick insulation)
65 mm dia (32 mm thick insulation)
50 mm dia (32 mm thick insulation)
40 mm dia (32 mm thick insulation)
32 mm dia (19 mm thick insulation)
25 mm dia (19 mm thick insulation)
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. (Acceptable make: BDK / Crane / Intervalve / KSB Ltd / Indian Valve International / Kirloskar)
65 mm dia
50 mm dia
40 mm dia
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. BALANCING VALVE WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. (Acceptable make: BDK / Crane / Intervalve / KSB Ltd / Indian Valve International / Kirloskar)
80 mm dia
Supplying, fixing, testing and commissioning of following valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications. Y-STRAINER of Ductile CI Body flanged ends with stainless steel strainer for chilled water circulation including insulation as specified. (Acceptable make: BDK / Crane / Intervalve / KSB Ltd / Indian Valve International / Kirloskar / Leader / Sant / Trishul / Fountain Annapurna / L&T / Amco)
80 mm dia
65 mm dia
50 mm dia
40 mm dia
32 mm dia
Supply, Installation, Testing and Commissioning of following sizes electronic, self-balancing, pressure independent type dynamic balancing valve with integrated 3 way modulating control valve in a single body. The actuator shall be capable of accepting upto 10V DC and upto 20mA electric signal and shall provide similar transduced feedback output to control system. The maximum close off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for 65 mm & above. Valves should have a pressure rating of 25 Bar minimum. (Acceptable make: Honeywell / JCI / Siemens / Danfoss / Staefa)
50 mm dia
40 mm dia
32 mm dia
25 mm dia
Supplying, installation, testing and commissioning of return air exhaust air temperature sensor as required. (Aceeptable make: Siemens / ABB / /Honeywell / L&T / Schneider)
Supplying, installation, testing and commissioning of electric strip heaters of following capacities for monsoon reheat and winter heating arranged in banks complete with cooling / heating thermostats [TH], humidistats [HU], safety stats [SF] etc. as per details given below for AHUs complete with interwiring [but excluding cable & connection from AHU switch board] and connections etc. complete as required and as per specifications. (Acceptable make: KEPL / Intracool / Rapid Control)
RECIRCULATION & AIR HANDLING UNIT: Supply, Installation, Testing and commissioning of factory built floor mounted cDouble skin air handling units with 2 mm thick thermal break aluminium profile, 43+-2 thick Puf panel having a density not less than 38 kg/m.Panel shall have 0.6mm precoated G.I sheet as outer skin and 0.6mm thick plane GI inner skin. The Unit shall be suitable for clean room applications with coving inside. The AHU shall consists of return air mixing chamber, EU4 filter, chilled water cooling minimum 6 row deep with bypass damper if required, fan section with DIDW centrifugal backward curved fan with TEFC squrirral cage induction motor, filter section with EU7 filters. AHU shall be complete with fresh air, return air and supply air dampers. Fan section & filter sections shall have service door of not less than 500 mm width. The AHUs will have fresh air module with 10 micron filter &Aluminium low leakage damper of required capacities. The unit shall be suitable for 415 V ±10% volts, 50 Hz, ac supply suitably designed for variable frequency drive application, drain connections, stainless steel drain pan with PUF insulation, pressure gauge, thermometers (inlet & outlet of coil), auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as required. (Acceptable make: Edgetech / Zeco / System Air / Climcone) [Test certificate of showing capacity of the unit needs to be submitted]
4000 CFM @125 mm WC SP (not less than 7.5 TR) with HEPA filter
5000 CFM @125 mm WC SP (not less than 4.5 TR) with HEPA filter
6000 CFM @125 mm WC SP (not less than 5.2 TR) with HEPA filter
5000 CFM @ 125mm WC SP (Not Less Than 5.2 TR)
Supply,installation, balancing and commissioning of fabricated at site GSS sheet metal rectangular / round ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vane hangers, supports etc. as per approved drawings and specifications of following sheet thickness complete as required. [For outdoor application] (Acceptable make of sheet: TATA / Jindal / SAIL / HSL / Nippon / National)
Thickness 0.63 mm sheet
Thickness 0.80 mm sheet
Providing and fixing duct insulation XLPE Rubber insulation on supply & return air GI ducts and dampers with adhesive and tape -
19 MM thick
19 mm thick & 5 mil glass cloth with UV protection.
20 mm thick Pre Insulated Ducting sheets of appropriate size having a PUF density of 45 Kg/CuM with 80 Micron Aluminum facing on both the sides with stucco type finish, duly Class ‘O’ certified as per BS along with the standard installation accessories. All longitudinal and transverse joints sealed with silicon sealant. (Inddor application; measurement of outer duct size) (Acceptable make: RR Engineers / Asawa / Paul)
Supply, installation, testing and commissioning of GI volume control duct damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications. (Acceptable make: System Air / Carrier)
Supply, installation, testing and commissioning of Motorized (ON-OFF Type) duct mounted GI volume control damper with enthalpy sensor and necessary control wire (minimum 1.5 sqmm) for integration within AHU room. (Acceptable make: System Air / Carrier / Airflow / Siemens / Staefa)
Damper
Actuator
Supplying, installation, testing and commissioning of following items in appropriate position of damper as required. (Make: Same as fire damper)
Fusible link type MS / GI fire damper at AHU
Fusible Link
Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti-smudge ring & removable core. (Acceptable make: System Air / Carrier / Airflow / Siemens / Staefa)
Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core. (Acceptable make: System Air / Carrier / Airflow / Siemens / Staefa)
Supplying, Fixing, testing and commissioning of fire dampers in supply air duct/main branch and return air path as and where required of required sizes i/c control wiring, the damper shall be motorized and spring return so as to close the damper in the event of power failure automatically and open the same in case of power being restored. The spring return action shall be inbuilt mechanism and not externally mounted. The damper shall also be closed in the event of fire signal complete as required and as per specifications. (Acceptable make: System Air / Carrier / Airflow / Siemens / Staefa)
Fire damper
Actuator
HEPA Terminal Supplying, installation, testing and commissioning of terminal hepa filter (H13) with terminal, damper & SS perforated sheet and HEPA H13 (for ISO-6, 7 areas). Terminal shall be complete with HEPA filter, SS perforated sheet and volume control damper. Terminals shall be suitable for following size of HEPA filters. (Acceptable make of HEPA filters: AAF / Camfil / Frudenburg)
HEPA filters. Size : 610 x 610 mm. of 750 CFM rating
HEPA filters. Size : 305 x 305 mm. of 300 CFM rating
Supplying, fixing, testing and commissioning of GI water pipes on wall of following size alongwith necessary clamps, fittings such as bends, tees etc. adequately supported as per specifications and as required. (Acceptable make: TATA / Jindal / Nezone / Bansal / ITC / ATC / Zenith)
25 mm dia GI pipe medium class [for drainage of water from FCUs]
Building Management System Supply, installation, testing and commissioning of main operator station comprising: Centralized automation along with controllers, sensors and control valves, man machine interface unit, cabling interconnecting the units and integrator units for the building management system to operate remotely for the entire Clean room labs. (Acceptable make: Siemens / Bosch / Honeywell)
Windows based graphical user software, web based with GUI, Alarming, reporting software as per specifications (With Including Web Client Facility. In Which, after providing IP address, BMS Software can be monitored thorugh web. Where as with LCD monitoring there is distance limitation of VGA Cable around 10 to 15 Mtr depending upon cable quality, but with web client we can monitor BMS parameter from anywhere irrespective of distance).
Operator Workstation with latest Intel micriprocessor, Core I 5, 16 GB RAM, 1 TB HDD, 2.8 Ghz, Keyboard, Mouse, Microsoft Windows Operating System with MS Office, Licenced Anti-Virus Software LED Monitor - 32 inch
DDC Ethernet controllers, I/P based, with supply , relays, wiring trays, wiring in an enclosure of required points as per design. (Including Controller Panel Box)
UL listed, BTL certified, Soft point integrator, Open Protocol Software Integration. These integrators shall be of same make as DDCs and shall contain min total 1250 data points with all necessary ports & points capacity for software integration with equipment.
Modulating type motorized actuator of 5 Nm torque with operating voltage of 24 Volt AC/DC and modulating voltage of 0-10 V DC supply
Duct mounting type temperature and RH sensor with output of 4 to 20 mA or 0-10V DC supply and input of 24V DC/AC
Differential pressure switch for Filter & Fan Status with potential free contact.
CO2 Sensors
Room Differential Pressure (DP) sensor cum transmitter
Supplying and laying of one number PVC insulated and PVC sheathed / XLPE armoured copper cable of 1.1 KV grade ISI marked of following size on surface or recess as required. (Acceptable make: Havells / Polycab / NICCO / RR Kabel / Skytone / Gloster / KEI / Universal)
4 core x 16 sqmm (main panel to chiller unit)
3 core x 10 sqmm (for AHUs, pumps)
4 core x 6 sqmm (for heaters)
4 core x 1.5 sqmm (BMS)
2 core x 1.5 sqmm (BMS)
Supplying and fixing 125mm height U trap made from HEAVY DUTY PVC 25 mm dia for AHU drain to avoid back flow of air
Variable frequency drives indepedently with bypass starter panel and also differential pressure gear with cabling from the sensor located on the duct to the the VFD for air handling units of following capacity motors including necessary fittings in enclosure and fixing accessories etc. complete as required. (Acceptable make: ABB / Mitsubishi / Siemens)
For AHU : 5.5 KW
For AHU : 2.2 KW
Velocity sensor for Ducting
SITC of Magnhelic gauges with GI box with SS cover plate and sensors with necessary tubing for HEPA filters at AHU as required. (Acceptable make: Dwyer / Sensocon)
Steel structure works consisting of C channel, M.S. angles, full threaded rods for AHU supporting structure above false ceiling, supports for condensing units, ducting, piping supports etc.
(SECURITY CONTROL, FIRE & MISC) ACCESS CONTROL SYSTEM Supplying, installation, testing and commissioning of Access control system for building security comprising of controller, E&M Locks, Reader, cabling, recording, display system, hardware and software support as required. There will be separate reader at two locations on 3 levels (Acceptable make Smart card reader / Access control software / Controller: Bosch / Honeywell / Nextwatch / GE-Casi / Lenel)
Providing, Installation, Testing and Commissioning of Access Control System having biometric finger print, key pad, LED screen, USB port for communication and data back up. Stand alone type
Door interlock system with electromgnetic locks, control panel, push butttons all complete for 2 doors
CCTV SYSTEM Providing, Installation, Testing and Commissioning of CCTV DVR 8 CHANNEL metal body, 4 Audio, AV output, 16 channel. Price shall inlcude voltage converter, Plug points for each camera (Acceptable make CCTV Camera / DVR / Matrix Switcher / Monitor: Honeywell / Pelco / Bosch / Sony / Vicon)
Dome camera 2 MP rating HD quality
Video Cable RG-11 for CCTV camera including
Display Monitor 32''
Hard disk,1TB
FIRE DETECTION & FIGHTING SYSTEM INTELLIGENT FIRE ALARM SYSTEM: Supplying, installation, testing and commissioning of micro processor based intelligent addressable main fire alarm panel, central processing unit with the following loop modules and capable of supporting not less than 240 devices (including detectors) and minimum 120 detectors per loop and loop length up to 2 km, network communication card, minimum 320 character graphics/ LCD display with touch screen or other keypad and minimum 4000 events history log in the non volatile memory (EPROM), power supply unit (230 ± 5% V, 50 hz), 48 hrs back-up with 24 volt sealed maintenance free batteries with automatic charger. The panel shall have facility to connect printer to printout log and facility to have seamless integration with analog/digital voice evacuation system and shall be complete with all accessories . The panel shall be compatible for IBMS system with open protocol BACnet/ Modbus over IP complete as per specifications. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Two Loop Panel.
Supplying, installation, testing & commissioning of response indicator on surface/recessed MS Box having two LED, metallic cover complete with all connections etc as required. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Supplying, installation, testing & commissioning of intelligent addressable programmable sounder complete as required. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Supplying, installation, testing & commissioning of fault isolator complete with base as required. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Supplying, installation, testing & commissioning of intelligent addressable photothermal detector complete with mounting base complete as required. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Supplying, installation, testing & commissioning of intelligent addressable thermal detector with rate of rise cum fixed tempreature thermistor complete with base as required. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Supplying, installation, testing & commissioning of addressable fire control module complete as required. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Supplying, installation, testing & commissioning of addressable manual call point complete as required. (Acceptable make: (Johnson Control(IFC)/ Notifier (UL)/ Bosch(UL)/ Mircom (UL)/ Fike (UL))
Supplying & laying of 2x1.5 sqmm fire alarm armoured cable, 600/1000V rated with annealed copper conductor having XLPE insulation, steel wire armouring& FRLS outer sheath complete as required. (Cable shall be red in colour) (Acceptable make: Havells / Polycab / NICCO / RR Kabel / Skytone / Gloster / KEI / Universal / Finolex)
Providing and fixing ISI marked 4.5 kg carbondi-oxide type fire extinguisher in seamless MS cylinder complete with pressure gauge, discharge hose & horn, brass valve with initial full charge and base tray for keeping on floor etc. as required. (Acceptable make: Minimax / Lifeguard / Ceasefire / Agni / Impulse / Safex / Newage / Ansul / Eversafe)
Providing and fixing ISI marked 4.0 kg clean agent type fire extinguisher in seamless MS cylinder complete with pressure gauge, discharge hose & horn, valve with initial full charge and base tray for keeping on floor etc. as required. (Acceptable make: Minimax / Lifeguard / Ceasefire / Agni / Impulse / Safex / Newage / Ansul / Eversafe)
Supplying and fixing of illuminating type exit signage black/white anodized aluminium profile with SMD based LED illumination (12V DC) available in white / green / red, yellow / amber, Input Voltage 230V, Consumption not more than 5W of appropriate size, Protection IP-20, LEDs: SMD Led, Application on Wall / Ceiling of size 12 inch x 6 inch (approx) Lithium Ion battery Back Up 4-5 Hours etc as required. (Acceptable make: Agni / Hochiki / Bosch)
SITC of Compressed Dry Air system consisting of skid mounted 3 HP air compressor Piston type, with electric motor, Air receiver of 200 Ltr, Maximum working pressure 12 kg /sqcm and flow 12 CFM, Air dryer 20 CFM. System shall have line filter 0.01 PPM (0.01 micron) for removal of solid particles, liquid water and oil aerosol. Line filter 0.003 ppm (Activated carbon filter) for removal of oil vapour and hydrocarbon odours having life of not less than 1000 working Hrs. (Suggested make: Chicago Pneumatic / Atlas Copco / Ingersolrand)
SITC of Industrial RO Plant 100 Litre/ hour capacity consisting of high pressure Pump, panel interconnecting piping, 1000 Litre PVC water storage tanks, interconnecting pipes suitable for operation on 230 V, 50 Hz, ac supply having TDS not more than 150 ppm with test certificate etc. complete as required. (Acceptable make: ION Exchaneg / Livepure / HUL / V-guard / Aqua Libra / Ozone)
VALIDATION OF CLEAN ROOMS: DQ documents, Cleanroom validation, O&M manual, test certificate for equipment including following tests for two labs viz., Microbiology Lab and Sterility Lab: 1. Light Test for ducts 2. Air Balancing and velocity profile test 3. Pressure balancing Test 4. Practicle Count Test 5. Tempreture& RH test 6. HEPA Filter Integrity test
Supplying, fixing, testing and commissioning of following valves, in the pipelines as per specifications. BALL VALVE with duel plate of C I body SS plates vulcanized NBR seal flanged end & PN 16 pressure rating for water circulation as specified. (Acceptable make: Audco / BDK / Intervalve / Kirloskar / Indian Valve International / Intervalve / Fouress Engineering Ltd)
GAS BASED TOTAL FLOODING FIRE SUPPRESSION SYSTEM [a] The quantity given are indicative and tentative. Total designing of the system to be done by OEM before execution and to be got approved from the Engineer-in-charge. (Acceptable makes are: SIEMENS / ANSUL / CEASEFIRE [b] The entire installation including the fire alarm system integrated to the Gaseous Fire Extinguishing System, to be tested as per IS 15493. SITC of 120 Ltr Seamless Fire Protection Fluid storage Tank having Clean Agent Gas stored at 42 Bar Pressure in single cylinder assembly with required Valves suitable for storage of required quantity of agent, conforming to IS 7285 & IS 15493, certified in accordance to requirements of Chief Controller of Explosives, Nagpur, securely fastened to ensure stability with low pressure switch provision & safety burst disc.
Supply and charge of Fire protection Fluid (FM 200) / HFC 227ea factory fill in kit in Kgs. The Gas calculation to be done by software. The calculation software should be VdS / LPCB approved.
Supply Installation Testing and Commissioning Master cylinder and Slave cylinder kits with accessories. The complete kit must be VdS / LPCB approved ( Single Cylinder) a) Pr. Gauge + Low Pr. Supervisory Switch b) Electromagnetic Actuator c) Pneumatic Actuator d) Flexible Discharge Hose e) Flexible Actuation Hose f) Manual Pneumatic Actuator g) Other Required Accessories
Supply, Installation, Testing and Commissioning of Gas Release Nozzles, of Size according to Software Calculation.
Supply, Installation, Testing and Commissioning Sch 40 Seamless ASTM 106 gr B, piping with 3000 psi fittings, rigid supports with angles, 2 coats of Zinc primer & 3 coats of P.O red Paint etc. as required.
80 mm dia
50 mm dia
40 mm dia
Supply, Installation, Testing and Commissioning of MS Manifold and Cylinder Strap having any ISI Mark
Single Cross Zone (2 Zone) Detection & Release Panel with following features. Cross Zoning with timer Card (0-256 secs ) or as per the UL guidelines for Maximum timer. Input for low pressure switch connection, Abort / Release inputs, Manual & Standby Modes, Solenoid output of 2.0 Amps, built in power supply, Battery backup of 24 AH.
SITC of Release Switch with Lock
SITC of Abort Switch
Supply and Installation of Warning Sign Board
CAMC (Supplementary Agreement shall be formed for CAMC) Operation and comprehensive maintenance of BSL 3 & Clean rooms complete with HVAC system, lighting system, electrical installations, fire detection & firefighting system, building management system, plumbing / drainage etc. as per terms and conditions of the contract. [a] One skilled person & one helper shall be made available for two shifts (Morning & Evening) for 6 days during the whole maintenance period who shall be vigilant and take care of all equipment for proper functioning. [b] Attendance of deputed staff shall be maintained through manual as well as biometric machine to be kept in the fire control room and to be certified by the lab authority [c] any shortfall of attendance of staff will affect the billing proportionately [d] Latest Labour regulation shall be complied strictly. EPF & ESI contribution as applicable shall be borne by the contractor and the same document shall be produced in respect of the deputed staff before claiming bill. No reimbursement shall be made by the IITD. 1 Job means for a period of 01 month N.B.:: 1st year CAMC (except operation) to be done free of cost [to be reckoned from the date of commissioning of the entire installations to the satisfaction of the Engineer-in-charge]
1st year (defect liability period) Free of cost (except operation)
2nd year
3rd year
4th year
5th year
6th year
Aircon Technique Pvt Ltd
ASEPTIC PROJECTSS
INTEGRATED CLEANROOM TECHNOLOGIES LTD
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.42 MB
BOQ_823470.xls
BOQ • 0.48 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .