Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.6 LAccepted-Finance A 63 ELDECO COUNTY PHASE II RAJGARH JHANSI U P 284135 | JHANSI | JHANSI | UTTAR PRADESH | 284135 | L1 | Accepted-Finance Being L1 | |
| 2 | L2₹32.7 L+₹17,880 (0.55%)Rejected-Finance C 40 BHAGAT SINGH NAGAR BHIND ROAD GWALIOR MP 474005 | NA | NA | 474005 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹40.4 L+₹7.9 L (24.2%)Rejected-Finance VILLAGE TAPARIYAN BABINA CANTT BABINA JHANSI UP 284401 | BABINA | JHANSI | UP | 284401 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹41.5 L+₹8.9 L (27.4%)Rejected-Finance | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹45.4 L+₹12.8 L (39.4%)Rejected-Finance | L5 | Rejected-Finance Other than L1 |
| Sl No | Description | Qty | Unit | m/s gupta trading L4 | ROHIT ENTERPRISES L1 | MONA GENERATOR SEVICES PVT. LTD. L6 | S.R ENGINEER WORKS L5 | M/S Kharya Associates L3 | SHRI HARI CONSTRUCTION L2 |
|---|---|---|---|---|---|---|---|---|---|
| 1.01 | Excavation in trenches in soft/loose soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed. | 405 | Cum | 30 ₹12,150 Lowest | 80 ₹32,400 | 170 ₹68,850 | 100 ₹40,500 | 120 ₹48,600 | 80 ₹32,400 |
| 2.01 | Excavation in trenches in any type of soil exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed. | 1 | Cum | 200 ₹200 | 130 ₹130 | 236 ₹236 | 150 ₹150 | 140 ₹140 | 50 ₹50 Lowest |
| 3.01 | Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed. | 395 | Cum | 10 ₹3,950 Lowest | 20 ₹7,900 | 76 ₹30,020 | 40 ₹15,800 | 38 ₹15,010 | 10 ₹3,950 Lowest |
| 4.01 | Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed. | 11 | Cum | 30 ₹330 | 50 ₹550 | 47 ₹517 | 100 ₹1,100 | 38 ₹418 | 10 ₹110 Lowest |
| 5.01 | Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 63mm, inner dia 50 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes complete all as specified and directed by Engineer-in-Charge. | 1,500 | RM | 150 ₹2,25,000 | 50 ₹75,000 Lowest | 97 ₹1,45,500 | 55 ₹82,500 | 70 ₹1,05,000 | 70 ₹1,05,000 |
| 6.01 | Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 105 mm, inner dia 95 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes complete all as specified and directed by Engineer-in-Charge. | 1,000 | RM | 200 ₹2,00,000 | 70 ₹70,000 Lowest | 159 ₹1,59,000 | 90 ₹90,000 | 90 ₹90,000 | 90 ₹90,000 |
| 7.01 | M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles all as specified and directed by Engr-in-Charge. | 2 | Cum | 1,000 ₹2,000 Lowest | 3,500 ₹7,000 | 5,953 ₹11,906 | 4,000 ₹8,000 | 3,500 ₹7,000 | 1,800 ₹3,600 |
| 8.01 | M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete for poles all as specified and directed by Engr-in-Charge. | 1 | Cum | 1,000 ₹1,000 Lowest | 2,500 ₹2,500 | 5,526 ₹5,526 | 2,200 ₹2,200 | 2,000 ₹2,000 | 1,800 ₹1,800 |
| 9.01 | M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge. | 4 | Cum | 1,000 ₹4,000 Lowest | 3,000 ₹12,000 | 5,684 ₹22,736 | 3,000 ₹12,000 | 2,200 ₹8,800 | 1,800 ₹7,200 |
| 10.01 | Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 400Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed. | 80 | RM | 1,550 ₹1,24,000 | 1,650 ₹1,32,000 | 2,153 ₹1,72,240 | 2,000 ₹1,60,000 | 1,800 ₹1,44,000 | 1,350 ₹1,08,000 Lowest |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
19 Jul 2025, 6:00 pmClosed
GE Babina
GE Babina, Babina Cantt, Jhansi (UP) PIN-284401
REPAIR/ REPLACEDMENT OF EXTERNAL ELECTRIC SUPPLY WORKS INCLUDING UNSV LT PANEL, FEEDER PILLAR BOXES AND OTHER CONNECTED WORKS AT CERTAIN UNITS AREA UNDER GE BABINA CANTT
2025_MES_713773_1
8388/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Babina
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE Babina
₹96,000
Yes
4 Sept 2025
11 Jun 2025
21 Jul 2025
11 Jun 2025
19 Jul 2025
28 Jun 2025
Amount
Excavation in trenches in soft/loose soil not exc 1.5 mtrs wide and not exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
Excavation in trenches in any type of soil exc 1.5 mtr in depth for laying of pipe/ cables/ poles etc and getting out complete all as specified and as directed.
Returning filling in any type of soil including spreading leveling watering and well ramming in layers n.exc 25 cm complete all as specified and as directed.
Removing excavated soils to a distance n.exc. 50 mtr and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified and as directed.
Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 63mm, inner dia 50 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes complete all as specified and directed by Engineer-in-Charge.
Material and labour for Double wall corrugated HDPE pipe,PN-10 ISI marked of outer dia 105 mm, inner dia 95 mm with smooth internal and profiled external surface, non-pressure type, laid in trenches/floors/duct or fixed on walls /pole including all connections, accessories like socket, couplers, bends, etc for protection of LT cable XLPE grade 1100 volts including taking down of u/s existing HDPE pipes complete all as specified and directed by Engineer-in-Charge.
M&L for PCC 1:2:4 type B-1 (using 20mm graded stone aggregates) as in coping etc including form work for poles all as specified and directed by Engr-in-Charge.
M&L for PCC 1:4:8 type D-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete for poles all as specified and directed by Engr-in-Charge.
M&L for PCC 1:3:6 type C-2 (using 40mm graded stone aggregates) as in foundation filling and mass concrete including form work for poles all as specified and directed by Engr-in-Charge.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 400Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 300Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 240Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 185Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 150Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 95Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 70Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 50Sqmm 3.5 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 25Sqmm 4 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 16Sqmm 4 core as per IS 7092 Pt -I complete all as specified and directed.
Supply, laying and testing in repair/replcement of XLPE insulated cable, screened, PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 10Sqmm 4 core as per IS 7092 Pt -I complete all as specified and directed.
Supply and fix in repair/replcement of PVC unarmoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 10 Sqmm 2 core ISI marked complete all as specified and directed.
Supply and fix in repair/replcement of PVC unarmoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 6 Sqmm 2 core ISI marked complete all as specified and directed.
Supply and fix in repair/replcement of PVC unarmoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 4 Sqmm 2 core ISI marked complete all as specified and directed.
Supply and fix in repair/replcement of PVC unarmoured electric power cable (heavy duty) 1100V grade with multistranded aluminium conductor of size 2.5 Sqmm 2 core ISI marked complete all as specified and directed.
Supply and fixing of three phase automatic street light timer switch of capacity 12 KW using integrated sensor based NATURE SWITCH for automatic switching of street light based on LUX level of natural light required illuminance for switching on is less than 30Lux and for switching off greater than 10 Lux level. The sensor (nature switch) along with suitable power contactors input (supply) MCB and output (load MCB (s), support terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP 66 degree of ingress three phase 8KW lighting load capacity including mounting bracket, cable glands, openable doors with locking arrangement complete all as specified and as directed. The contactor MCB and circuit wiring should enough to take load of 12 KW equally distributed over three phase and street light timer should be comprising of following:- (a) Input MCB rating 40 Amps 230 volst-03 Nos (b) Contactor rating 40 Amps 230 volts- 03 Nos (c) Out put MCB rating 40 Amps vots-03 Nos (d) three phase circuit wiring minimum 10 Sqmm multistranded copper wire. Make: Cat Part No SWADEEP-02EC 12 KW1P, Note :- 01 Year Guarantees+01 year warranty on remaining other item from date of purchase.
Supply , fix in repairs , commissioning and testing factory made LT feeder pillar , outdoor type floor mounted , suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated . The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 50x50x5mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement. LT Panel board should be as per IS/IEC 61439-I: 2011 & IS/IEC 61439-2 : 2011, Type Test certificates for Short Circuit Test, Temperature Rise Test, Di-Electric Property Test and Degree of Protection IP-65 at minimum 4000 Amps with Breaking capacity not less than 65KA.The panel shall be powder coated finish with RAL 7032 SIEMENS GRAY STRUCTURE after seven tank phosphating treatment, front & back opening type, and fixing 2 Nos.danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door to LT panel with voltage and danger indicated in Hindi and English, airvent gasket for natural flow of air, Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following :- Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/s universal switchgear Ltd
Note:- (i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job. (iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v) Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate.
Supply , fix in repairs , commissioning and testing factory made LT feeder pillar , outdoor type floor mounted , suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber duly insulated . The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 50x50x5mm thick angle iron base frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, both side opening type, with aprons for cable entry, with double door shutter and locking arrangement. LT Panel board should be as per IS/IEC 61439-I: 2011 & IS/IEC 61439-2 : 2011, Type Test certificates for Short Circuit Test, Temperature Rise Test, Di-Electric Property Test and Degree of Protection IP-65 at minimum 4000 Amps with Breaking capacity not less than 65KA.The panel shall be powder coated finish with RAL 7032 SIEMENS GRAY STRUCTURE after seven tank phosphating treatment, front & back opening type, and fixing 2 Nos.danger notice plate with letter, figures and conventional skull bones in signal red colour and fixed front & back door to LT panel with voltage and danger indicated in Hindi and English, airvent gasket for natural flow of air, Neoprene adhesive type gasket shall be used to make panel vermin proof and comprising of following:- Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/s universal switchgear Ltd
(a) Aluminum bus bar four strips 600 Amps ,415 volts, fixed horizontally, duly insulated with heat shrinkable sleeves in colour code - 01 Set. (b) Incoming MCCB, 04 Pole, 400 Amps with ultimate breaking capacity Icu-35 KA at 415 volts, fixed type with thermal and magnetic settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 01 No (Ics=Icu=100%) (c) Outgoing MCCB, 04 Pole, 200 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 02 No (Ics=Icu=100%) (d) Outgoing MCCB, 04 Pole, 160 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 01 Nos (Ics=Icu=100%) (d) OutgoingMCCB, 04 Pole, 100 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermal settings conforming to IEC 60947 Part-I/IS-13947 Part-I - 01 Nos (Ics=Icu=100%) (d ) Spare way for 200 Amp, MCCB 4 way-01Nos (f) Digital voltmeter 0-500 Volt -1 Set (f) Digital Ammeter 0-400 Amps -1 Set (g) Indication lamps R,Y,B LED type -1 set: h) Internal wiring with suitable size of PVC insulated stranded copper conductor cable duly crimped with copper lugs & ferruled and aluminum strips for MCCB's.
Note:- (i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job. (iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v) Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate.
M & L for earthing complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to galvanised earth lead 32X6mm by means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and salt and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 5 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronge size 75x75x25 mm complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item.
S&F in replacement kiosk box for luminaires ,weather proof made out of HDPE/FRP housing fire retardant, non fusing, shock & rust proof, single piece moulded and cover with hinged door, pole mounting type comprising of four pole copper connectors of 16 Amps capacity with 6 Amp MCB single pole , of minimum size 300x200x125mm, fixed on pole with MS, clamps 30 x 5mm with necessary nuts, washer and incl applying two coats of synthetic enamel paint over a red oxide primer on steel surface/clamps and embossing/painting of Danger sign of size not less than 10cms x 7.5cms with letter and conventional skull and bones in single red color on front face of kiosk box complete all as directed. The quoted rate also includes cost for material & repalcement of 4 sqmm multistranded twincore aluminium cable ISI marked from overhead conductor to junction box and replacement of 3 core copper cable of 1.5 Sqmm ISI marked from junction box to security light length as per required at site. Make-Syntex/Supreme/Hensal
S & F in replacement of GI brackets for fixing LED street light fitting fabricated out of GI tubing 40 mm dia, medium grade, 1.2 mtr long , bend to 120 degree shape by cutting, welding and well finishing including MS clamp of flat iron of size 32 x 4 mm -02 Nos complete for steel poles / PCC pole as per site requirement with nut, bolt & washers for fixing of GI bracket complete all as specified and directed.
S&F in replacement of new generation energy saving and enviromental friendly long life LED security/ street light fitting made up of innovative die cast aluminium housing high power LED as lighting source with IP-65 power consumption 45 W complete input voltage of 150-240 Volts (Normal rated voltage 240Volts) complete including replacement of twisted 3 core copper cable of size 1.5Sqmm dia for connecting phase, neutral and earth from junction box to LED light through copper connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 70/72 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 90 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED security/ street light fittings made up of innovative die cast aluminium housing high power LED as lighting source with IP - 65 power consumption 120 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 100 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 150 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F in replacement of new generation energy saving and environmental friendly long life LED flood light made up of innovative die cast aluminium housing high power LED as lighting source with IP - 66 power consumption 250 watt colour white complete input voltage of 150-240 Volt (nominal rated voltage 240 Volt) complete including replacement of twisted 3 core copper cable of size 1.5 Sqmm dia for connecting phase, neutral and earth from junction box to light through connectors complete as specified and as directed.
S&F for replacement & testing commissioning of outdoor type bus bar panel weather proof MS cubical panel board made of 3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 200 Amp 25 KA (Ics =Icu=100%) including one coat of redoxide and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:4:8 type D-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/s universal switchgear Ltd. Note:- (i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job. (iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v) Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate.
S&F for replacement & testing commissioning of outdoor type bus bar panel weather proof MS cubical panel board made of 3.15 mm CRCA MS sheet outdoor type of size 110 cm x 80 cm x 40 cm, 4 Nos of aluminium bus bar of 300 Amp capacity with MCCB 4 pole of Capacity 160 Amp 25 KA (Ics =Icu=100%) including one coat of red oxide and two coat of enamel paint powder coated, mounted on angular frame work of 50x50x5mm thick angle iron base frame, minimum 60 cm hight and fixed with PCC 1:3:6 type C-2 (using 40mm graded crushed stone aggregate) in foundation for fixing panels, aluminium busbar chanel insulated with colour coated heat shrinkable sleaves and mounted on DMC/Epoxy insulator all as specified & directed. Make:- M/s Mclayers Bhopal/M/s shalabh(india) Ltd/ M/s universal switchgear Ltd. Note:- (i) Panel drawing and make of MCCB and connected accessories will be submitted by the contractor for approval of Accepting officer before ordering the panel. (ii) The holes / aprons of cable exit and incoming should be close with suitable size of gland.( iii) The contractor should submit all Certificates before executing the job. (iv) CA No.,Contractor name, item of CA No. to be mentioned on the panel.(v) Suitable Cable glands for incoming cables and outgoing cable to be provided in the panel by the contractors. Cost of provisioning of cable glands deemed to be included in qouted rate.
M & L for earthing in repairs complete with galvanized steel earth plate electrode 600 x 600 x 6 mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal GL and connected to earth plate . Earth plate surrounded by 15 cm thick packed layers of charcoal dust and common salt upto 1.5 meter depth all around the earth plate and connected to earth lead of GI strip 25X4 mm by means of bolts, nuts, check nuts and washers of galvd iron or steel surronded by charcoal of coke and salt and protected by galvanized iron or steel pipe light grade 40 mm bore and water pipe 20mm bore GI medium grade with funnel and wire mesh, including all necessary excavation and earth work PCC chamber in cement concrete 1:3:6 type C-2 and RCC cover and all as shown in electrical plate No 3 of MES schedule Pt I of 2009 and also including making test point for testing of earthing made out of gun metal or phosphorous bronge size 75x75x25 mm complete . Note : 1. RCC pit cover shall be pre-cast of RCC (1:2:4) type B-I , 80mm thick reinforced with XPM weighting not less than 4 KG/sqmm in lieu of CI cover. 2. Charcoal dust and common salt upto 1.5 meter depth shall be filled in layers of 15 centimeters all around the earth plate inside earth pit . On testing after completion of earthing if desired earth resistance is not achieved , the earthing will be redone at no extra cost to obtain the desired earth values less than 2 ohms.3. The cost of GI earth lead and GI pipe of 7.50m lenth for protection of GI wire and excavationwork fpr pit shall deemed to be included in this item.
M & L for decorative LED post top gate light of capacity 20 W with IP 65 pretection resistant to impact and corrosion, glare free and better uniformity and complete fitting arrangement on gates/pillars complete all as specified and as directed.
M & L for decorative LED bollard stainless steel 9 watt weather proof light(warm white) with acrylic diffuser complete with all accessaries complete all as specified and as directed.
Supply, erecting and fixing in true vertical position, steel tubular swaged pole (410 SP-31) 9.0 mtr long, complete with cast iron base plate, pole cap / finial taper plug, bolts, nuts and washers, welded reduced section and longitudinal weld throughout entire length of pole including 2 coats of black bituminous paint externally upto planting depth and remaining exterior portion of pole shall be provided with two coats of aluminium paint over one coat of red oxide primer and incl taking down existing old unserviceable poles complete all as specified and directed. (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size as directed.) Note :- Excavation incl earth work and PCC foundation will be measured and paid separately.
Supply, erecting and fixing in replacement of true vertical position, prestressed concrete pole 9.0 mtr long 102 mm x 172 mm at top and 152 mmx 279 mm at bottom class 10 (Numbering of the poles shall be done with synthetic enameled painted letter of shape & size) including taking down of old unserviceble pole & shifting of cross arms ACR conductor , GI wire, insulator, street light brackets etc complete all as directed. Note :- Excavation incl earth work and PCC foundation will be measured and paid separately. The old unserviceable pole obtained from dismanting shall be remove by the contractor form cantt area/MOD. If the contractor has not removed the dismantled item a penality of Rs.500.00 per pole will be charged from the contractor as a penality.
S & F in replacement of MCCB, 04 Pole, capacity 40 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of MCCB, 04 Pole, capacity 63 Amps with ultimate breaking capacity 16 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of MCCB, 04 Pole, capacity 100 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of MCCB, 04 Pole, capacity 160 Amps with ultimate breaking capacity 25 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of MCCB, 04 Pole, capacity 200 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of MCCB, 04 Pole, capacity 250 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of MCCB, 04 Pole, capacity 315 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of MCCB, 04 Pole, capacity 400 Amps with ultimate breaking capacity 36 KA at 415 volts with fixed thermalsettings conforming to IEC 60947 Part-I/IS-13947 Part-I , (Ics=Icu=100%) in the existing panel with suitable connecting copper terminals at site complete all specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S&F in replacement of off load change over switch, 200 Amps, 4 pole, AC 415 volts, 50 Hz in SS enclosure side handle operated complete all as specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of off load change over switch, 100 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of off load change over switch, 63 Amps, 4 pole, AC 415 Volt, 50Hz in SS enclosure side handle operated complete all as specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of off load change over switch with SS enclosure, 400 Amps, 4 pole, AC 415 Volt, 3 phase with mounting arrangement complete all as specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of off load change over switch with SS enclosure, 630 Amps, 4 pole, AC 415 Volt, 3 phase with mounting arrangement complete all as specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
S & F in replacement of off load change over switch with SS enclosure, 1000 Amps, 4 pole, AC 415 Volt, 3 phase with mounting arrangement complete all as specified and directed. Make- Havells /L&T/Indo-Asian/Legtand/ABB
Supply & fixing GI tube 50 mm bore light grade with all fittings for laid in trenches/fixed along with poles/walls & floor of buildings etc under crossing of road for protection of cables including demolition and taking down of the old existing pipe including repair of the floor/wall and matching with the existing surface if required complete as directed by Engineer-in-Charge.
S & F and replacement of cross arms, bracing, supports clamps and back plates fabricated from structural steel sections incl nuts & bolts, washers, welding bending cold or hot, drilling holes for bolts in any shape or size and inclusive of one red oxide primer coat, one under coat and one finishing coat of synthetic enamel paint complete all as specified and directed.
M&L for painting of steel tubuler 11/9 mtr poles any type complete incl flat iron clamps, D clamps, Stay clamps, earth wire clamps, bracing, cross arm with two coat aluminium paint including prepration old painted surface initally & applying one coat of red oxide, applying two coat of aluminum paint over the red oxide, marking with alternate white and red strips 30 cm height 5 Nos strips with two coat of synthetic enamel paint (Ist quality of manufacturer )and also including numbering of poles with white paint are located on different locations complete all as specified and directed .
M & L for cutting of road up to 0.75m deep suitable for laying underground cable/MS tubes of any size/dia including GI pipe of 50mm dia and making good the disturbed area to match with the existing level with cement concrete including removing the surplus soil to a distance upto 50mtrs complete all as specified and directed.
Trimming of tree branches touching to over head lines, upto 1.5 mtr distance all around of ACSR conductors of span 30meter to 50 meter of HT/LT feeders and depositing cut branches away from site as directed and clearence of HT/LT pole and sub station premises all as directed by Engg-in-charges. Note: (i) Trimming of all branches of trees falling under one span between two pole shall be shall be considered as as one span only. (ii) Contractor have to arrange all T&P , safty equipments manpower and vehicle for trimming at different locations. Contractor or his rep has to ensure power shut down of overhead lines before carrying out trimming. Contractor shall be responsible for any lapses/ mishapning occured due to negelency of safty aspects.
Taking out under ground, HT/LT cables, any sizes, by excavation and earth work in any type of soil, removing bricks or PCC tiles of any size, re-laying in the same trenches for re-routing /after rectification of fault as required complete all as specified and directed NOTE:- (i) Joint and joiting materials, new cables, additional bricks, sand shall be measured & paid for separetely. (ii) Retrieved serviceable bricks or PCC cable cover and sand shall be re-laid on the cable & the cost for the same is deemed to be included in the unit rate. (iii) Cost for excavation, R&F, removing shall be included in quoted rate.
M &L for cable jointing kit for 1.1 KV (Earthed) grade cable for straight through Heat shrink type complete with joining material and accessory suitable for 25 sqmm to 50 Sqmm 3.5 core XLPE armored aluminum conductor cable including jointing with copper lugs and ferrules complete all as specified and directed.
M &L for cable jointing kit for 1.1 KV (Earthed) grade cable for straight through Heat shrink type complete with joining material and accessory suitable for 70 sqmm to 120 Sqmm 3.5 core XLPE armored aluminum conductor cable including jointing with copper lugs and ferrules complete all as specified and directed.
M &L for cable jointing kit for 1.1 KV (Earthed) grade cable for straight through Heat shrink type complete with joining material and accessory suitable for 150 sqmm to 240 Sqmm 3.5 core XLPE armored aluminum conductor cable including jointing with copper lugs and ferrules complete all as specified and directed.
M&L in replacement of aluminium conductor, steel reinforced ACSR of any size/description on HT/LT poles/lines incl stringing, tightening, binding to insulators with aluminium wire making and connecting jumpers, connections etc incl connecting, commissioning and testing also taking down of the existing complete all as specified & directed.
M & L for painting of steel cross arm, bracing supports of 11/9 mtr PCC poles any type incl flat iron clamps, D clamps, stay clamps, earth wire clamps, bracing, cross arm with two coat aluminium paint incl prepration old painted surface and applying cemente based paint over cemented portion of PCC poles, marking with alternator white and red strips 30 cm height 5 Nos strips with two coat of synthetic enamel paint (Ist quality of manufacturer ), numbering of poles complete all as specified and directed.
S&F in replacement Factory made sheet metal enclosure of CRCA sheet 2 mm thickness suitable for fixing of MCCB 4 with fixing arrangement including provision of MCCB 63 Amp to 125 Amps, 16KA, 4Pole ( Ics=Icu=100%) with cable connection with copper glands packing etc complete all as specified and direcetd. Make- ABB/Havells/L&T/Indo asian/Seimens
S&F in replacement Factory made sheet metal enclosure of CRCA sheet 2 mm thickness suitable for fixing of MCCB 4 with fixing arrangement including provision of MCCB 200 Amp to 250 Amps, 25KA, 4Pole ( Ics=Icu=100%) with cable connection with copper glands packing etc complete all as specified and direcetd. Make- ABB/Havells/L&T/Indo asian/Seimens
M&L for repairs to main electric panel at sub stations by tightning the all loose connections of the cable ends and replacing the damage/US/burnt aluminium lugs of required sizes, insulating/secure the weak insulated portion of cables ends inside the panel by taping with good quality of insulation tape, clean the dust by air blower complete all as specified and as directed.
Labour only for attending complaint by replacement of worn out insulators of any type and size for 1100 Volts grade complete all as specified and as directed.Note:- Insulator will be measured and paid seperatly under respective items.
Supply and fixing of single phase automatic street light timer switch of capacity 8KW using integrated sensor based NATURE SWITCH for automatic switching of street light based on LUX level of natural light required illuminance for switching on is less than 30Lux and for switching off greater than 10 Lux level. The sensor (nature switch) along with suitable power contactors input (supply) MCB and output (load MCB (s), support terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR graded SMC junction box conforming to IP 66 degree of ingress three phase 8KW lighting load capacity including mounting bracket, cable glands, openable doors with locking arrangement complete all as specified and as directed. The contactor MCB and circuit wiring should enough to take load of 8KW equally distributed over single phase and street light timer should be comprising of following:- (a) Input MCB rating 63 Amps 230 volst-01 Nos (b) Contactor rating 63 Amps 230 volts- 01 Nos (c) Out put MCB rating 63 Amps 230 vots-01 Nos (d) three phase circuit wiring minimum 16 Sqmm multistranded copper wire. Make: Cat Part No SWADEEP-02EC 8 KW1P, Note :- 01 Year Guarantees+01 year warranty on remaining other item from date of purchase.
M&L for Painting of LT Panel/LT bus bar feeder pillar box out door type with two coat aluminium paint including prepration old painted surface initally & applying one coat of red oxide, applying two coat of aluminum paint over the red oxide synthetic enamel paint by isolating ,disconnecting of input/output ,supply cable, detecting of fault ,u/s component in panel ,cleaning of serviceable parts/ component and Welding of Panel door & replacement of door lock, replacement of old wiring with 2.5 sqmm to 6 sqmm etc, if required all as specified and directed.
S&F in repairs pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut of size 100 mm height, 65 mm dia for 1100 volts grade complete all as specified and directed.
S&F in repair Shackle type 75mm height and 90mm dia insulator, porcelain, vitreous, white, brown or green including galvanised mild steel strap 31mm X 3mm, insulator bolts 12mm dia with suitable washers and nut, suitable for working pressure upto & including 1100 volts fixed on LT poles complete all as specified and directed.
SHRI HARI CONSTRUCTION (BID ID -3348387)
M/S Kharya Associates (BID ID -3347930)
m/s gupta trading (BID ID -3347437)
S.R ENGINEER WORKS (BID ID -3356816)
MONA GENERATOR SEVICES PVT. LTD. (BID ID -3364493)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .