Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.5 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹10.9 L+₹49,501 (4.74%)Rejected-AOC BADABAZAR BARIPADA DIST MAYURBHANJA 757001 | MAYURBHANJ | ODISHA | 757001 | L2 | Rejected-AOC Rejected | |
| 3 | Not Admitted-Fee/PreQual/Technical AT BEGAMPUR PO NARAHARIPUR PS REMUNA DIST BALASORE | BALASORE | BALASORE | ODISHA | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
₹9.5 L
EMD Value
₹9,519
Closing Date
4 Oct 2018, 5:00 pmClosed
EE MLI Division Baripada
EE MLI Division Baripada near chhou padia infront of the stadium, Bhonjpur, Baripada, Mayurbhanj Pin- 757002 Odisha
Installation and energisation of Badada II TW under Suliapada Block in Mayurbhanj District
2018_OLIC_49622_12
Bid Identification No- 3734 Date. 06.09.2018
National Competitive Bid
Civil Works - Lift Irrigation Schemes
Item Rate
90 days
Baripada
Please refer Tender documents.
2 documents required · 2 mandatory
₹4,000
E E, MLI Division, Baripada
₹9,519
Yes
24 Jan 2022
24 Sept 2018
10 Oct 2018
24 Sept 2018
4 Oct 2018
24 Sept 2018
24 Sept 2018 - 3 Oct 2018
Amount
E/Work in excavation in hard soil in fdn. Including rough dressing & levelling the bed not exceeding 0.30 m in depth as per specification :-
Filling in Fdn. & Plinth with sand watered and rammed :-
CC (1:4:8) with 4 cm size HG metal :-
1st Class well burnt Flyash Brick massonery in CM (1:6) in Foundation :-
1st Class well burnt Flyash Brick massonery in CM (1:6) in Foundation (Superstructure)
12 mm th. Cement Plaster in CM (1:6) over Brick Massonery :-
Cement Punning
Labour for M.S.reinforcement for RCC works including cost of M.S.Rod, cutting, bending,binding & tying the grills and placing in position.
Rigid & smooth Centering & shuttering for RCC works including false works & dismentalling those after casting with complete cost (Slab)
Lintel
Column
Finishing wall with water proffing cement of any colour 2 coats including cost of materials
White washing 2 coats with shell lime
2.5 cm AS flooring in cement concrete (1:2:4) using 12mm h.g. chips
Cost of Iron shutter & MS grill window
Labour for fitting & fixing of MS door including cost of all material complete
Painting two coats with any approved paint over Iron shutter
Cost of paint & Primer for pump chamber
Filling with excavated materials :-
Pump chamber wiring with PVC conduit pipe with fitting of necessary beds , drilling hole on the wall, fittng of bulb , clamping as per requirement complete.
Laying & fitting of 160 mm dia UPVC pipes (Cl-I ) in under ground including excavation of trench of size (0.75 M x 1.00 M) in proper alignment & filling the trench after fitting of the pipes including cutting of heaps and making the base of the trench uniformely sloping & laying for of the pipes in uniform gradient including supply of jointing materials like solvent cement etc.and also fixing the PVC "Tee", PVC Reducers , PVC Bends , N.R.Valves of different sizes at required places along the pipe line including transportation of materials to the work site etc.complete as per the direction of the Site Engineer in Charge.
Fabrication of display board including writing and painting board in black colour paint over yellow back ground in odia language as per the direction of the Engineer-in charge
Spreading of 50 mm size metal inside sub-stattion boundary
Cost of MS Gate for sub-station
Installation of 6 HP Submerssible Pumpsets lowering with 100mm dia G.I.Pipe of required length jointed with Bend, socket and Delivery G.I & PVC pipe fitting with clamp over RCC pillar support & fitted Flange with Sluice valve including transportation complete as per the direction of the Site Engineer in Charge.
Making earthing with required earthing materials like Charcoal , Common salt , Conduit pipe, Soft solder , Alcape , Nuts & Bolts, Cable sockets etc including excavation of earth pits of size (1.20 M x 1.20 M x 1.5 M) for fixing of earthing pipes of size 37.5 mm dia x 1.5 M length with required slottings in Pipe and fitting with 37.5 mm dia G.I.Flange including excavation of earthing trench for laying of earthing G.I.Wire and filling the trench & pit after fixing of pipes on completion of earthing works including supply of all the materals, including transportation etc.complete as per the direction of the Site Engineer in Charge.
Installation of Starter, Capacitor, fitting of 63 AMP Kit Kat, jointed with Troppodar cable to main supply line & substation cable with making cable trench including transportation all complete as per the direction of the site Engineer in charge..
Cutting , threading of 100 mm dia G.I.Pipes to proper size with required length making leak proof for flow of water and fitting it in proper position including transportation of Materials to Work site etc. complete as per the direction of the Site Engineer in Charge.
6 HP / 4.5 K.W Submerssible Star rated Pumpset coupled with totally enclosed Water cooled squirrel cage induction motor confirming to 8034/2002 & motor IS 9283/1979 with delivery discharge 600 LPM at 30 M head with cable , cable clip with 80mm delivery & suction , support clamp & Bronze Impeller etc suitable for operation at 415 + 6% - 15 % , 3 phase , 50 Hz, A.C power supply outlet dia 80mm and CED coated.
Auto Star Delta Starter of sheet Steel enclosure suitable for operation of squirrel cage Induction Motor up to 10 HP with 16 MP ( AC-3) duly contactor at 415 Volt + 6% - 15% , 3 phase 50 Hz , A.C supply with Over Load Relay range 8.9 to 13.5 Amp and No volt coil suitable for operation at voltage range of 350-440 Volt and to provide dependable protection during over load and single phasing.(BCH Make)
2.5mm² Submerssible Flat Cable
3 Core x 10mm² Insulated ( HD ) armoured Electric Cable with Alluminium conductor for use in 3 phase power system of working voltage up to and including 1100 Volts at 50 Hz confirming to IS 1554 (Pt - 5 ) / 1988.
3 KVAR Capacitor
63 Amp 415 Volt T.P.Main Switch confirming to IS 4064 (Pt-I & Pt-II) with utilization category Ac-22.
4 mm² PVC Insulated Copper wire with ISI mark
Rigid UPVC pipe of 160 mm dia Ivory grey in colour having specific gravity of 1.4 to 1.46 Gm / CC of straight length of 6 M for portable water supplies confirming to IS 4985 / 2000 of BIS - Amendment - 2 Read with Table - I , of IS specification bearing ISI mark for working pressure of 2.5 Kgf / Cm² as per latest ammendment of IS 4985 including cost of coupler for plain ended pipes or one end plain and other bell ended. The pipe should be tested by CIPET and each pipe should be clearly & indelible marked ink or Stenciled confirming to ISI 4985 / 2000.
100mm dia Nominal Bore G.I.Pipe having wall thickness 4.5 mm, Electrical resistence welded , Medium Class confirming to IS 1239 ( Pt) - 1 / 2004) with latest ammendment screwed at both ends as per IS 554 with socketed at one end and other end protected with plastic thread protector. The socket confirming to IS - 1239 (Pt)-II / 1992 ) with latest ammendment with random length of 4 to 7 M & should bear ISI certification and manufacturer Trade marks.
100mm dia G.I.Bend confirming to IS No. 1239 (Pt-II/1992)
100 mm dia Screw Boss Flange confirming to IS No. 6392 /19 71
100 mm dia C.I.Sluice Valve confirming to IS - 14846 - 2000 (Pt-I) with ISI mark , hand wheel, GM fitting, Brass Spindle , S/S 410 Spindle Kirloskar Make.
100mm dia G.I.Socket confirming to IS No. 1239 (Pt-II/1992)
100 mm dia M.S.Clamp
200 mm dia M.S.TW cap with 100 mm dia hole.
Cost of RCC Protection cover stand for Motor clamp
160 x 160 x 160 mm dia PVC equal Tee (6 Kgf / Cm²) confirming to PL- R PVC- IS 2000F
150x150x100 mm dia M.S.Tee Joint Bend with two No. of 100mm dia M.S.Short Bend & 1.25 Mtr of 100mm dia M.S.Pipe with Flange joint & locking arrangement suitable for pushing of 160 mm dia PVC pipe in to the Tee joint for water distribution system.
Labour charges for Fitting of M.S.Tee
110 mm dia PVC Tail piece (6 Kgf / Cm²) confirming to PL- R PVC- IS 2000F
110 mm dia PVC Flange (6 Kgf / Cm²) confirming to PL- R PVC- IS 2000F
160 x 110 mm dia PVC Reducing Socket (6 Kgf / Cm²) confirming to PL- R PVC- IS 2000F
160 mm dia PVC End cap (6 Kgf / Cm²) confirming to PL- R PVC- IS 2000F
5/8" x 3" M.S. Full threaded Nut Bolt (Heavy Duty)
3 mm ( 1/8") thick Rubber Insertion
Construction and erection of 11/0.416 KV 25 KVA Star rated DP Sub-Station confirming to RE Rule 1956. Mounted on 2.44 mt. long structure, supported on 9 mt long PSC pole, Transformer Hard Channel & top Channel made of 2.8 mtr long 100X50X6 mm size MS Channel, transformer belting on 2.80 mtr long 50X50X5mm size M.S.Angle, (all REC SPN. Std) with all accessories like, 3-Pole 11 KV H.G. Fuse and A.B. Switches both mounted on 2.8 mtr long 75X40X6 mm size M.S.Channel & supported by 1.0 Mtr long 50x50x5mm M.S.Angle , with 3 Nos 11 KV lightening Arrestor & Distribution box for 25 KVA S/S mounted on Box (75x40x6 mm) 2.5 Mtr long 40mm pipe earthing including cost of 95 Sqmm 3.5 core L.T.Cable connecting the supply line with 55 sqmm AAA conductor , providing 18mm G.I. HT stay as required carping & padding of poles, Danger Board at each pole. Anti climbing Device & all other necessary fittings i.e. required size of Nuts & bolts brackets, cable, cable sockets etc including cost of all labours transpsortation complete with liasion for testing, inspection and commissioning & writing on the poles as per prescribed colour code . etc. Complete as per the direction of the Site Engineer in charges.
Construction of 3 phase 11 KV line as per REC standard confirming to RE Rules 1956 with 9 M long PSC Pole support in 60 M span, 55 Sqmm AAA conductor, 11 KV "V" Cross arm , with required No.of 11 KV T & C Disc.Insulators & 11 KV Pin Insulators, Carping & Padding of Poles, Danger Board at each Pole, Anti Climbing Devices, Stay Set at Bending point & Double Stay at end point with 18 mm G.I. H.T Stay , concreting of Stay with Anchor plate, guarding at Road crossings etc. Marking OLIC in every PSC pole in enamel paint including cost of all materials, labour ,transpotation,inspection & commissioning with stud stay 1 No etc.complete as per direction of Junior Engineer, Electrical in charge .
Transpower
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .