Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 LAccepted-AOC | L1 | Accepted-AOC BEING A LOWEST BIDDER | |
| 2 | L2₹7.7 L+₹12,352 (1.63%)Rejected-AOC | L2 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 3 | L3₹8.0 L+₹48,185 (6.38%)Rejected-AOC | L3 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 4 | L4₹8.1 L+₹51,280 (6.79%)Rejected-AOC | L4 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 5 | L5₹8.8 L+₹1.3 L (16.8%)Rejected-AOC | L5 | Rejected-AOC OTHER THAN LOWEST BIDDER |
Tender Value
Refer Docs
EMD Value
₹19,800
Closing Date
27 Mar 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
HQ CWE Nagrota
HQ CWE NAGROTA C/O 56 APO
PROVN OF TRANSFORMER OF 200 KVA CAPACITY FOR HQ 16 CORPS CAMP AT NAGROTA UNDER GE NAGROTA
2021_MES_426134_1
CWE/NGT-61/2020-21
Open Tender
Civil Works
Item Rate
180 days
NAGROTA
pls refer tender document
9 documents required · 9 mandatory
₹500
GE NAGROTA
₹19,800
Yes
23 Apr 2021
27 Feb 2021
29 Mar 2021
27 Feb 2021
27 Mar 2021
13 Mar 2021
27 Feb 2021 - 5 Mar 2021
60 days
Amount
Supply, installation, testing and comissioning of step down transformer 11 KV/433 Volts, 3 phase 50 Hz 200 KVA outdoor type, with off load tap changing arrangement on HT side to vary secondary voltage upto 7.5% in step (+ or -) 2.5% including suitable cable entry boxes both on HT to receive 95 Sqmm 3 core XLPE cable and on low voltage side to accomodate XLPE cable of suitable size complete in all respect with standard accessories and fitment confirming to IS:2026 Part-I of 1977. Primary side Delta and secondary side Star. The sailent feature of transformer shall be as follows:-
(a) Transformer shall be oil immerse, naturally self cooled copper wound,winding core type MS radiator cooled tank complete with first fill of transformer oil plus 5% spare oil as per IS:335 of 1980 with cooling system.The temperature of oil shall not rise more than 50 degree centigrade to amient temp and 55 degree centigrade of winding.Transformer shall be painted with two coat of epoxy paint as per IS-632. (b) Transformer shall be provided with the followings:- (i) Rating and diagram plate. (ii) Earthing terminals 2 Nos. (iii) Lifting lugs. (iv) Thermometer pocket. (v) Air release hole with plug. (vi) Tap changer with locking provision. (vii) Oil temperature indicator.
M&L for construction of transformer plateform with overall outer dimension 1.5 m x 1.5 m x 1.5 m with necessary excavation in ground at the bottom with 150 mm thick 1:2:4 cement concrete raft at the bottom and top and 225 mm thick wall constructed in brick masanory built in cement mortar 1:6 and remaining hallow portion shall be filled in by 1:5:10 cement concrete duly plastered 20 mm thick outsides including two coats of white wash on new plastered surface complete. including XPM jalli fabricated with angle iron, brick work etc all as specified and directed by Engineer in charge and as per Drg No. CE/TD/1033/90 , sheet no (1/1)
Supply, laying, jointing and testing XLPE insulated PVC sheathed armoured under ground cable heavy duty with aluminium conductor LT 1100 V grade cross sectional area 185 Sqmm 3.5 core, complete all as specified and directed by Engineer-in-Charge.
S&F out door, triple pole, gang operated switch single bank, tilting type suitable to vertical/horizontal mounting consisting of hot dipped electro plated galvanised channel iron base with drop out fuse having 9 Nos insulators 11 KV, copper/copper alloy tinned contacts, copper or chromium plated MS arcing chains capable of making and breakign the magnetising current complete with horizonatal bar, GI pipe as down level coupling and operating handle with locking arrangements and drop out fuzes working voltage 11000 volts 200 Amps including testing complete all as specified.
S&F Lighting Arrestor expulsion type for out door use complete with all fittings transmission class discharge capacity 65 KA suitable for 11000 V including bracket, clamps, nuts and washers and connecting to earth wire complete all as specified.
Supply installation and commissioning and testing of LT pannel cubical type suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system floor mounted, out dor type factory fabricated duly powder coated inside and out side suitable for 415 volts 3 phase 4 wire 50 Hz AC supply system floor mounted outdoor type , factory fabricated outer shall ade out of 3.15mm thick CRCA sheet and internal shell and partion made out of 2mm thick CRCA sheet with angle iron 50x50x6mm covered from all side with front and back and openable weather proof including suitable rating aluminium bus bar for 3 phase 4 wire system and wiring with suitable size copper cable and embeded in PCC in PCC 1:2:4 type B-1 foundation for fixing panel of required size in ground with nuts bolts and washer etc complete with comprising of following:
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground (Earth pit not less than 2.25 m below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected and including GI strip 32 mmx6mm (upto the body of equipment) by means of brazing, GI bolts, nuts, check nuts and washers, earth plates surrounded by packed layers of coal dust and common salt 15 cm thick all around top and bottom and watering pipe 20 mm bore of GI pipe, light grade all as shown in Electrical plate No 5 of SSR Part I, testing on completion including PCC 1:2:4 tye B1 using 20mm graded stone aggregate as in pit cover and PCC chamber in PCC 1:3:6 type C-1 using 20mm graded stone aggregate including excavation and earth work, disposal of surplus spoil to a distance n exc 50 m complete all as specified and directed by Engineer-in-Charge
Earthing complete with copper earth plate electrode 60cm x 60cm x 3.15 mm thick buried directly in ground ( Earth pit not less than 2.25 m below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected and including copper strip 20 mm x 3mm (upto the body of equipment) by means of Brazing, GI bolts , nuts, check nuts and washers earth plates surrounded by packed layers of coal dust earth plate surrounded by packed layers of coal dust and common salt 15 cm thick all around top and bottom and watering pipe 20 mm bore of GI pipe ,light grade all as shown in Electrical plate No 5 of SSR part –I testing on completion including PCC (1:2: 4) pit cover and PCC chamber in PCC 1:3 :6 type C-1 using 20mm graded crushed stone aggregate including excavation and earth work, disposal of surplus spoil to a distance n exc 50 m complete all as specified.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of underground cable and getting out soft/loose of soil complete all as specified
Excavation in trenches not -exceeding 1.5 meters wide and exceeding 1.5 meters and not exceeding 3.0 meters deep for errection of pole and getting out soft/ loose of soil complete all as specified.
Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cms. thick in soft / loose soil complete all as specified.
Removal of surplus soil not exceeding 50 Mtr and depositing where directs at a level not exceeding 1.5 Mtr above the starting point complete all as specified.
M&L for sand cushioning in trenches spreading and consolidation 8cm thick before laying the cable & 15 cm of sand after laying the cable complete all as specified.
Supply and laying Un-reinforced precast concrete cable cover 'factory made' of class HVP, Type 1 with peak, of size 300 mm x 180 mm x 40 mm complete all as specified.
Supply & laying brick over cable laid in trenches as profection to cables with width equal to the length of bricks with well burnt sub class 'B' bricks complete all as specified.
M&L galvanized iron tube light grade for protection of cable at road crossing of size 80 mm dia. complete all as specified.
Supply, Laying, jointing, jointing and testing of under ground cables XLPE insulated screened PVC bedded galvanized steel strips armoured electric power cable (heavy duty) with aluminium conductor HT 11000 volts grade and cross sectional area 95 sqmm 3 core conforming to latest IS and ISI marked complete all as specified and directed by Engrr-in-Charge.
Cable and termination heat shrinkable jointing kit outdoor type suitable for HT cable XLPE insulated aluminium conductor of size 95 Sqmm 3 Core complete all as specified and directed by Engineer-in-Charge.
Pin type precelain, vitreous brown or green insulators including one galvanised mild steel spindle two galvansed iron washer with one galvanised iron nuts 150 mm height 150 mm dia for 11000 Volt grade complete all as specified.
Disc type insulators, protection vitreous 145 mm high and 255 dia ball & socket type white brown or green two-in- series assembly for tension with clamps for conductor working pressure 11000 Volt complete all as specified.
Supply and errection steel tublar swaged pole. 410-SP-55 of 11 meters long completet with cast iron base plate 400X 400X 5 mm thicks, finial taper bolts nuts and screws complete including painting with two coasts of aluminnimum paints over a coat of red oxide primer including painting up to 1.50m high from ground level in black & white strips & duly marking/ numbering, complette all as specified and directed.
M & L cross arms of M.S channel or angle section etc complete of different sizes brancings, supports,clamps and back plates febricated from structural steel sections incluiding nuts, bolts, washers, wellding, bending cold or hot drilling for bolts in any size or shape as indicated or directed and inclusive of one primer coat , on under coat and one finishing coat of paint complete all as specified and directed by Engr-in-charge.
PCC 1:4:8 type D-2 using 40 mm graded crushed stone aggregate in foundation of electric poles including necessary from work and exposed surfaces finished fair without using extra cement complete all as specified.
PCC 1:2:4 type B-1 (using 20mm graded crushed stone aggregates) as in coping/above ground level around the pole etc complete all as specified.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, for HT , 25 X 20 cm size complete all as specified.
S&F of Chain link MS Galvanised fencing size 75 X 75 X 3.5mm complete all as specified.
S&F chain link fencing including line wires, any mesh size and type to any type standards . Rails, straining bolts etc including provision of binding wire
M & L PCC 1:3:6 type C-1 using 20 mm graded stone aggregate with 100 mm thick including use and waste of form work around transformer, GOD, LT Panel
Jiwan Singh
ASHOKA ENGINEERS AND BUILDERS
SHREE KRISHANA ENTERPRISES
M/S MANJIT SINGH AND SONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .