CHIEF ENGINEER RND SECUNDERABAD
CHIEF ENGINEER RND SECUNDERABAD OPP JUBILEE BUS STATION PICKET SECUNDERABAD 500003
PROVISION AND INSTALLATION OF NEW INTELLIGENT INTEGRATED FIRE DETECTION AND ALARM SYSTEM AT DRDL, HYDERABAD
2026_MES_779017_1
84052
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
KANCHANBAGH HYDERABAD
Class B category c(vi)
8 documents required · 8 mandatory
₹2,000
GARRISON ENGINEER I RND KANCHANBAGH
₹3.1 L
Yes
17 Aug 2026
16 Jul 2026
17 Aug 2026
16 Jul 2026
13 Aug 2026
6 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing, programming & commissioning of Computer System, i7 Processor, latest generation, 2.93GHz, 4MB Cache with 16 GB RAM, & 1 TB SSD, 2GB 4K Graphics Card, 10/100 Mbps Ethernet card, USB connection & internal modem, Microsoft(R) Windows(R) 10 OS Professional Enterprise or latest, Web server software, 100/1000 Mbps NIC for network connection and antivirus software as per specifications. Accessories included 50 Inch UHD 4K LED Screen, Optical Mouse & Key Pad, Windows Licensed software compatible with the above FAS System configuration complete all as specified and directed. | 2 | EACH | - | - |
| 2 | Supply, installation, testing & commissioning of scaleable & upgradeable software for Fire Alarm System with features like 3D vector dynamic graphics with AutoCAD import of plan with Zoom In & Zoom Out facility, Plant Viewer, Trend Viewer, Object Viewer, Report Viewer, Alarm router. The Web-Based Server software shall permit use of Standard Web-Browsers such as Microsoft Internet Explorer, Netscape Navigator, etc. The software shall be capable of integration third-party systems and should supports latest IP technology (IP V4/V6). The Web based software shall include Client License for remote viewing. The software shall have Online Engineering capability i.e. Zero Downtime for software graphics modification. | 1 | EACH | - | - |
| 2.01 | Software should be capable to integrate BMS, Gas Suppression & VESDA Panels Seamlessly complete all as specified and directed.
Software should comply to OPEN Protocols like:
- BACnet/IP for HVAC Automation/BMS
- SNMP for UPS & Networking Integration
- Modbus/IP for Energy Monitoring
- IEC61850 for Electrical & Power Integration
- ONVIF for CCTV Integration
- OPC for any other Integration. | - | - | - | - |
| 3 | Supplying, installation, testing and commissioning of UL 864 10th edition UL listed and FM approved Analog addressable 2 Loop Fire Alarm Control Panel having the total panel capacity of 252 devices. The panel shall be able to give pin point location of all Fire/fault and Isolation conditions of addressable units via the address codes. The panel shall have the capacity of storing upto 10000 events. Further, the panel must be able to automatically switch ON /OFF respective control module whenever any alarm is triggered. The panel should have inbuilt common Alarm, Fault and monitored sounder output. The panel shall have a 2” x 4-3/4” size VGA monochrome LCD display and having maximum 320 (8 x 40) characters in the display with optional 24 | 4 | EACH | - | - |
| 3.01 | zones LED indicators. The panel shall have a built in power supply of 170 Watts and battery charger. Battery charger shall be able to charge the system batteries of upto 33AH capacity. The Panel shall have the capacity of connecting additional 31 panels or network terminals using network card, with redundancy in the network. The panel shall have the capacity of connecting maximum 16 Remote terminals / 16 remote displays or combined by using. The panel shall be compatible for IBMS system with open protocol BACnet over IP complete all as specified and directed. | - | - | - | - |
| 4 | All as per Sl Item No. 3 above but for 1 Loop Panel. | 5 | EACH | - | - |
| 5 | Supplying, installation, testing & commissioning of UL 864 10th edition UL listed and FM approved Networkable Repeater Panel. The panel shall be able to give pin point location of all Fire / fault and Isolation conditions of addressable units via the address codes. The panel shall have the capacity of storing upto 10000 events. Further, the panel must be able to automatically switch ON/OFF respective control module whenever any alarm is triggered. The panel should have inbuilt common Alarm, Fault and monitored sounder output. The panel shall have a 2” x 4-3/4” size VGA monochrome LCD display and having maximum 320 (8 x 40) characters in the display with optional 24 zones LED indicators. The panel shall have a built in | 2 | EACH | - | - |
| 5.01 | power supply of 170 Watts and battery charger. Battery charger shall be able to charge the system batteries of upto 33AH capacity. The panel shall have the capacity of connecting additional 31 panels or network terminals using network card, with redundancy in the network. The panel shall have the capacity of connecting maximum 16 remote terminals / 16 remote displays complete all as specified and directed.
NOTE: All disturbed existing surfaces shall be made good after completion of works. Any damage caused during execution shall be repaired and restored by the contractor at no extra cost. | - | - | - | - |
| 6 | Supply, installation, testing & commissioning of UL268 6th & 7th edition compliance and FM approved Intelligent Addressable multi-criteria detector (optical and thermal sensors) complete with standard base, facility to mount in different comprehensive environment, Tri-color detector-status LED with 360° view, microprocessor circuitry with error check; detector self-diagnostics and supervision programs, Rate-of-Rise Detection: 15°F/min. (8.3°C/min.) - Fixed: 135°F (57°C), Field programmable as rate-of rise or fixed temperature, Polarity insensitive, Superior EMI and RFI immunity, RoHS compliant. Detector shall have in-built isolator for better reliability, circuit integrity and advanced fault finding. | 1,553 | EACH | - | - |
| 6.01 | Manufacturers not having in-built isolator feature in detector shall consider isolator base in place of standard base OR separate isolator before and after every detector to comply the same without any extra cost complete all as specified and directed.
Note: All fire alarm detectors shall be installed on the existing POP/false ceiling without causing any damage or disturbance to the ceiling finishes. In case any damage occurs during installation, the contractor shall be fully responsible for carrying out all necessary repair and reinstatement works to restore the ceiling to its original condition at no additional cost. | - | - | - | - |
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.18 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.44 MB
84052Tender.pdf
Tender Documents • 1.01 MB
BOQ_872548.xls
BOQ • 2.43 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .