Asst. Gen. Manager (Engg-E)
Hubballi Airport, Hubballi
Replacement of 11KV DP structure and 11 KV HT Metering Cubicle panel at MSSR Station Bellary and AAI Residential Colony, Mangalore Airport.
2023_AAI_140396_1
AAI/HUB/ENGGE/NIT/HTMC/2022-23
Open Tender
Electrical Works
Item Rate
30 days
Bellary and Mangalore
Please refer Tender documents.
11 documents required · 11 mandatory
₹1,180
₹18,154
4 Jul 2025
9 Jan 2023
16 Feb 2023
10 Jan 2023
14 Feb 2023
10 Jan 2023
10 Jan 2023 - 20 Jan 2023
Amount
SH-1 11KV HT Work at MSSR Bellary
Supply, Installation Testing and Commissioning of 11 KV DP structure to terminate the HT cable/ACSR conductor, with all associated accessories such as 2 no's of RCC Poles of 9 -10 Mtr height (supply & erection), 6 no's of 11 KV Disc Insulators, 3 no's of 11 KV pin insulators,1 set of 11KV 200Amp Single break GOS switch, 3sets of 10kV 5 KA Lightning Arrestor, 3sets of 11KV 200Amps DOLO cutouts/HG Fuse unit, DP structure holding MS clamps,structure Brackets, Arms, clamps, bolts, nuts and washers complete painting with primer and finish paint complete as required with 2 set of pipe Earthing and required qty of 11 KV ACSR conductor for terminations etc as per GESCOM standards including dismantling of Existing 11KV DP structure and handing over to store as per EIC instructions complete as required as per site requirements at MSSR Station Bellary.
Supplying , Erecting , testing & Commissioning of 11 KV HT Metering cubicle as per GESCOM Specification with 3 Nos CT with ratio : 30 / 5 A ( Single Core Single Ratio) - 0.2S Class , 10 VA Burden, 3 Nos. PT with Ratio : 11KV / 110V , 0.2 Class 50 VA Burden, (2 No's of ABT METER shall be provided by AAI), the metering panel shall be installed on existing platform. The cost includes interconnections with existing HT cables, De-commissioning and dismantling of existing metering cubicle and handing over to store as per EIC instructions, Calibration of ABT Meters, liasoning work for getting Approvals from GESCOM, 02 Sets of Earthing for HTMC as per GESCOM and all other related work for Commissioning complete as required as per site requirement and as per special conditions of contract(SCC). (Note- ABT meter shall be taken over from AAI Before ordering Metering cubicle for confirmation of CT ,PT ratio)
SH-2 11KV HT Work AAI Residential Colony, Mangalore
Supply, Installation Testing and Commissioning of 11 KV DP structure to terminate the HT cable/ACSR conductor, with all associated accessories such as 2 no's of RCC Poles of 9 -10 Mtr height (supply & erection), 6 no's of 11 KV Disc Insulators, 3 no's of 11 KV pin insulators,1 set of 11KV 200Amp Single break GOS switch, 3sets of 10kV 5 KA Lightning Arrestor, 3sets of 11KV 200Amps DOLO cutouts/HG Fuse unit, DP structure holding MS clamps,structure Brackets, Arms, clamps, bolts, nuts and washers complete painting with primer and finish paint complete as required with 2 set of pipe Earthing and required qty of 11 KV ACSR conductor for terminations etc as per MESCOM standards including dismantling of Existing 11KV DP structure and handing over to store as per EIC instructions complete as required as per site requirements at AAI, Residential colony Mangalore Airport, Mangalore.
Supplying , Erecting , testing & Commissioning of 11 KV ABT Metering cubicle with Load break switch as per MESCOM Specifications with 2 no's of ABT meters, 3 Nos. CT ( Single Core Single Ratio) - 1 Class , 3.75 VA Burden, 3 Nos. PT with Ratio : 11KV / 110V , 1 Class 50 VA Burden, Construction of (1.5m x 1.5m x 1.2m) platform for metering cubicle. The cost includes interconnections with existing HT cables, De-commissioning and dismantling of existing metering cubicle and handing over to store as per EIC instructions, Calibration of ABT Meter, liasoning work for getting Approvals from MESCOM, 02 Sets of Earthing for HTMC as per MESCOM and all other related work for Commissioning complete as required as per site requirement and as per special condition of the contract.
Classic Electricals
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .