EE II CKHED
P12 CIT Road 1st floor Kol 14
Replacement of 2 No s Duct able Split AC machines and allied Electrical work in Dissection Section Hall at Forensic Building under NRSMC and H Kolkata during the year 2025 26
2025_WBPWD_903438_1
WBPWD/EE-II/CKHED/ eNIT-49/25-26
Open Tender
ELECTRICAL WORKS ORG
30 days
NRS MCH
as per NIT
4 documents required · 4 mandatory
₹11,507
central kolkata health electrical division
9 Jan 2026
16 Sept 2025
10 Oct 2025
16 Sept 2025
8 Oct 2025
22 Sept 2025
19 Sept 2025
Amount
Supply and Delivery of Microprocessor based air cooled 5.5 TR ceiling suspended ductable type Split Air Conditioner having 2200 CFM air flow and nominal cooling capacity of 66000 BTU/hr. at ISI condition with scroll compressor (R-410/R-410A/R-32 ) suitable for operation on 400V - 50 Hz-3PH AC supply. (Make: Hitachi/Daikin/Voltas/Carrier)
Errection & Commissioning Charges for the above-said 5.5TR Ductable Split Air Conditioner.
Supply, Installation & commissioning of hard/soft copper refrigeration pipeline, complete with fittings, elbows, bends, supporting arrangement on walls. (Make- Ryoku/Rajco/Mandev/Totaline)
a)Liquid Line ( 1/2" OD with 0.8mm thick)
b)Suction Line (7/8" OD HD Copper Pipe with 1mm thick)
Supply & Fixing 9mm nitrile rubber tube Insulation on suction line & Liquid Line copper pipe of ductable split AC. (Make-Accoflex)
a)Liquid Line ( 1/2")
a) Suction Line (7/8")
Control Cabling from ODU to IDU (Make:- Gloster /Finolex/ KEI)
a) 4 Core 2.5sq. mm.
Supply, fabrication and installation of sheet metal duct in accordance with the approve ducting, laying,drawing, including accessories like anchor fasteners, MS angle /rod for support, dampers, turning vanes etc. ( Make-SAIL)
a) 24gauge galvanized sheet
Supply & fixing of Fusible link mechanical type fire damper.
Supply and fixing flexible canvass connection for Ductable air-conditioners.
Supply & fixing 9mm thick fire-retardant nitrile rubber thermal insulation for Duct. (Make-Accoflex)
Supply and fixing of acoustic lining with 12.5mm thick fiberglass rigid board using shalikote primer hot bitumen and mechanically fastened, covered with 30 guage Al perforated sheet on the inner side of the duct.
Supply & laying Drain Water piping work out of PVC / HDPE hard pipes of following sizes incl. fitting, accessories, bends, elbows, tees, flanges, tappings, wall sleeves, hangers, supports, anchors.
a) 25 mm dia
Charges for Dismanting of exsisting 2 nos. AC machine (IDU+ ODU) and shifting to departmental store also Scaffolding arrangement incl. lifting & Shifting for outdoor & indoor units of Ductable Split AC.
Dismentling the old damaged electrical wirings including fixtures from their original position and mending good the damages as per direction of EIC.
Distribution wiring in 1.1 KV single core stranded 'FRLS' PVC insulated & unsheathed copper wire (RR Kabel/Finolex/Polycab/KEI) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required as per direction of EIC. [ E-14,1(a) ]
a) 4 x 6 sqmm + 2 x 4 sqmm as ECC [ E-14,1(b)(v) ]
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [ F-5,9 ]
a) 4 x 6 sqmm + 2 x 4 sqmm as ECC
Supply & Fixing of single LED Tube light fitting [Make - Philips cat no. TMC 501 P 1x T-LED / Wipro, cat no.WIO921208 /complete with 18/20 Watt LED tube lamps [Make - Philips Master LED tube model no.18W 865 T8 I 2100lm / Wipro cat no.- LL13-181-65SE/Lighting technology ]with 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. and by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length.
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with suitable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length, as per G.S.
Supplying and fixing of 4 way 40A MCB SS enclosure with IP-20/30 protection, powder coated provision for four pole MCB, concealed in wall after cutting the wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment, as per direction of the EIC. [Make-Legrand/LK]
Rate should be quoted incl. of all taxes and cess.
Cold room Defect Liability period : 1 year
MODERN REFRIGERATION AND ELECTRICAL WORKS (BID ID -7044612)
WEATHER CONTROLS (BID ID -7045951)
MILLENNIUM AIRCON (BID ID -7011906)