Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.3 LAccepted-AOC WARD NO 40 REGRON KA MOHALLA NEAR RAVI DASS JI MANDIR SHIV BARI BIKANER RAJSTHAN 334001 | BIKANER | RAJASTHAN | 334001 | L1 | Accepted-AOC OK | |
| 2 | L2₹24.5 L+₹2.2 L (9.89%)Rejected-Finance EAST DIGHI TANK OLD LIC COMPOUND GAYA BIHAR 823001 | GAYA | BIHAR | 823001 | L2 | Rejected-Finance Not Lowest | |
| 3 | L3₹27.2 L+₹4.9 L (22.0%)Rejected-Finance MAGADH COLONY ROAD NO 6 SHERGHATI ROAD GAYA BIHAR 823001 | GAYA | GAYA | BIHAR | 823001 | L3 | Rejected-Finance Not Lowest | |
| 4 | Rejected-Technical | - | Rejected-Technical Not Qualified | |
| 5 | Rejected-Technical | - | Rejected-Technical Not Qualified |
Tender Value
₹28.8 L
EMD Value
₹57,640
Closing Date
18 Aug 2022, 6:00 pmClosed
Y K GOUR
HQ CWE RANCHI Millitary Engineer Services Dipatoli Cantt Ranchi-834009
REPAIR MAINT OF 33 KV HT SWITCH YARD AND 11 KV HT DISTRIBUTION SYSTEM AND ALLIED WORKS UNDER GE DANAPUR
2022_MES_538650_1
80599/1415/E8
Open Tender
Electrical and Maintenance Works
Works
180 days
Danapur
As per NIT
6 documents required · 6 mandatory
₹500
GE Danapur
₹57,640
Yes
HQ CWE RANCHI
15 Nov 2022
19 Jul 2022
25 Aug 2022
19 Jul 2022
18 Aug 2022
3 Aug 2022
19 Jul 2022 - 25 Jul 2022
25 Jul 2022
Amount
Excavating in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth for laying of cables & foundation of poles ,stay assembly and getting out in soft/ loose soil complete all as directed.
All as per item No 1 above but in hard/ dense soil.
Excavating in trenches not exceeding 1.5 m wide exceeding 1.5 m but not exc 3 m in depth for laying of cables & foundation of poles , stay assembly and getting out in soft/loose of soil complete all as directed .
All as per item No 2 above by hard/ dense soil.
Returning, filling in excavated approved soil, including spreading, leveling, watering and well ramming in layers not exceeding 25cm each complete all as directed.
Removing excavated soil not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as directed.
Sand cushioning to under ground cables ( 8 cm deep before laying of cable and 15 cm deep over the cable ) & punning gently complete all as directed .
Bricks , klin burnt , well burnt , whole , old size of compressive strength not less than 50 kg per sq cm laid in trenches as cable cover / protection complete all as directed .
PCC (1:2:4) type B-1 using 20mm graded stone aggregate in foundation and mass concrete/filling, complete all as directed.
Cement concrete 1:3:6 type C-2 using 40mm graded stone aggregate in foundations, filling and mass concrete complete all as directed .
Steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-55 ( 11 meter long) complete, Including disconnecting and taking out old damage any type pole all as directed . Make National Tubing co / Indian tube co ltd / Bharat Conduit & steel works kanpur. (Note - Earth work and PCC shall be measured and paid separately as these respectively).
Aluminium conductor steel reinforced (ACSR) of any type including binding with and including suitable size of binding wire complete Including dismantling and taking out worn out ACSR conductor from overhead electric line comlete . All as directed (Make - Indian Aluminium Co. / ICC / Ujala /ALIND / BHARAT CONDUCTORS).
All as per item No. 10 but GI wire 4 mm dia complete.
GI stay wire of 7/4 SWG upto required length including taking out old u/s one complete all as directed.
Mild steel galvanised stay assembly set complete comprising of 14mm dia, 400mm long stay bow, 2150mm long stay rod 20mm dia, 300mm x 300mm x 6mm stay plate, thimble, loop insulator large size all as shown in electrical plate No.1 of MES Schedule part-I 2010 including dismantling and taking out old damaged stay complete all as directed. (Note :- PCC , earth work and Insulators etc shall be measured and paid separately).
Gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level Vertical type for rating upto 400 Amps, 11000 volts complete with GI operating pipe of heavy duty including taking down U/S one. Complete all as directed. (Make - BHEL / JAIPURIA / RASHTRIYA / MEI) .
Drop out fuse assembly complete set with Insulator-02 Nos and connected accessories for 11000 Volts grade of 400 Amps capacity including taking down U/S DO fuse assmbly. Complete all as directed. (Make - BHEL / JAIPURIA / RASHTRIYA / MEI) .
Gang operated air break switches, triple pole, manually operated, mounted on insulators and steel frame, with operating mechanism worked from ground level horizontal type /Vertical type in double stack type for rating upto 400 Amps, 33000 volts complete with GI operating pipe of heavy duty including taking down unserviceable one complete all as directed.
Taking down and repairing/overhauling of air break gang operated switch with DO fuse unit 11 KV/ 33 KV rating 200 Amp/400 Amp capacity triple pole mechanically operated mounted on insulators and steel frame installed vertically / horizontally , replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothing and polishing of electric contacts with providing conducting jelly of contacts refixed the same after repair including proper allignment complete all as directed. (Note:- Worn out component/ insulators / ASCR shall be measured and paid separately under respective items of this schedule.)
Supply only Female contact or fixed contact heavy duty and high conductive metal capacity 200A/400 Amp, 11 KV rated. Complete all as directed. (Make - BHEL / Jaipuria/ Rashtriya/ MEI).
Supply only Male contact or Moving contact heavy duty and high conductive metal capacity 200A/400Amp 11 KV. Complete all as directed. (Make - BHEL / Jaipuria/ Rashtriya/ MEI).
Supply only Tinned copper flexible jumper of capacity 200A/400A suitable for 11KV rated GOD. Complete all as directed. (Make - BHEL / Jaipuria/ Rashtriya/ MEI).
Supply only Fixed top contact & Fixed bottom contact 11 KV 400 Amp for DO fuse unit. Complete all as directed. (Make - BHEL / Jaipuria/ Rashtriya/ MEI).
Supply only Fiber glass tube with metalic fittings both ends suitable for DO fuse 11KV. Complete all as directed. (Make - BHEL / Jaipuria/ Rashtriya/ MEI).
Supply only mild steel jumper carrier suitable for 11 KV GOD (as per sample. Kept in GE office). Complete all as directed.
Supply only back connector plate suitable for 11 KV GOD (as per sample. Kept in GE office). Complete all as directed.
Supply only post insulator suitable for 11 KV GOD (as per sample. Kept in GE office). Complete all as directed.
Supply only Female contact or fixed contact heavy duty and high conductive metal capacity 400 Amp suitbale for 33 KV rated horizontal GOD. Complete all as directed. (Make - BHEL / Jaipuria/ Rashtriya/ MEI).
Supply only Male contact or Moving contact heavy duty and high conductive metal capacity 400 Amp suitbale for 33 KV rated horizontal GOD. Complete all as directed. (Make - BHEL / Jaipuria/ Rashtriya/ MEI).
Supply only post insulator suitable for 33 KV GOD (as per sample. Kept in GE office). Complete all as directed.
Supply only Tinned copper flexible jumper of capacity 200A/400A suitable for 33 KV complete all as directed.
Supply only Fixed top contact & Fixed bottom contact 33 KV 400 Amp for DO fuse unit. Complete all as directed. (Make Rastriya/Jaipuria/BHEL/MEI)
Supply only Fiber glass tube with metalic fittings both ends suitable for DO fuse 33 KV.Complete all as directed. (Make Rastriya/Jaipuria/ BHEL/MEI)
Supply only mild steel jumper carrier. Complete all as directed. (Make Rastriya/Jaipuria/BHEL/MEI).
Supply only back connector plate (as per sample. Kept in GE office). Complete all as directed.
Lightening arrestor linear resistance type distribution class 9 KV RMS suitable for 11 KV system pole mounting type conforming to IS - 3070 Part-I including taking down existing unserviceable one complete all as directed.
Cross arms, bracing, supports, clamps and back plate, fabricated from structural steel section including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of synthetic enamel paint over a coat of red oxide primer, including dismantling and taking out damage/rusted cross arms, bracings, supports, clamps and back plates from existing poles / dismantled poles / pole structures complete all as directed.
Danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white with letter figures and conventional skull and bones in signal red colour and fix with MS clamp for HT, size 25 X 20 Cm and taking out of us one complete all as directed.
Pin type, porcelain, vitreous, white, brown or green insulator, 150 mm height, 150 mm dia for 11000 volts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut and taking out unsv one complete all as directed. (Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL).
Disc type insulator, porcelain, vitreous, white, brown or green insulator ( Single disc assembly ) of size 145 mm height, 255 mm dia ball socket type for working pressure 11 kv volts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut and taking out U/S one complete all as directed. (Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL).
Loop type, porcelain, vitreous, white, brown or green insulator large type 140 mm , clearence of hole 25.5 mm for 11000 volts grade including out U/S one complete all as directed. (Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL).
Restraining of HT /LT over head line single ACSR conductor comprising of any size of conductor aluminium/copper/GI after opening binding wire from insulators and replace binding wire and achieved permissible sag limit of over head line conductor complete all as directed.
Sealed lead acid battery for constant voltage charge of capacity 12V , 7Ah including taking out the unserviceable battery complete all as directed. Make:- Exide/Amron/Luminous/AMCO
Lithium battery for RMU ER 14250 ,3.6V ,1/2AA ,1200mAh including taking out unserviceable battery complete. Make :- Exide/Hero Moto Corp/Greaves cotton/Everest/Amron/AMCO.
Repair / Servicing / maintenance of transformer 11 / .433 KV indoor / outdoor type , plinth / pole mounted type including the following work services :- (a) Disconnecting transformer from electric system and providing electric power to user from alternative arrangement including taking out from existing position . (b) Decanning of transformer oil , opening top cover , disconnecting of all internal connections , lifting and taking out of core assemble , LT / HT bushes, Tap changer etc ,cleaning and inspection of core and winding , segrigetion of serviceable and unserviceable items , removing of sludge and cleaning tank and cooling pipes / fins /tanks with pressure water and drying the tank complete. (c) Replacinig unserviceable LT / HT bushing by replacing rubber / cork oil seals and damage terminal rod & replacement of Transformer cover gasket of rubber cork sheet. (d) Re installation of TFR including reassembling of core / winding assebly complete including replacement of unsv parts , repair the defective parts and tighting of all loose / sparks wire / nut bolts etc and refixing the to the existing position , connecting with HT/LT cables and earthing strip and testing complete including necessary Transportation ( If required ) to the work shop and back and including Dehyderation and refilling of existing or new transformer oil of required quantity . (NOTE FOR ITEM NO 42 :- (i) Dehydration of oil and new Transformer oil shall be measured seperately . (ii) Transportation of TFR measured and paid seperately . (iii) HT & LT Busing , Tap Changer will be measured & Paid separataly. (iv) In case HV / LV Winding found damages then Contactor shall be made serviceable with new winding and the same will be measured and paid seperately. (v) The rate of cork sheet & Packing Material for following cap of TFR are included in coated rate of transformer capacity 100 to 160 KVA
As Per Item No 43 above But capacity 200 to 300 KVA .
As Per Item No 43 above But capacity 400 to 500 KVA .
Supply only for incorporated to the repair of transformer HT bushing porcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable for outdoor type Transformer of capacity 100 to 160 KVA .
As Per Item No 46 above But capacity 200 to 300 KVA .
As Per Item No 46 above But capacity 400 to 500 KVA .
Supply only for incorporated to the repair of transformer LT bushing porcelain with copper stud, nuts, bolts, washers, gasket, oil seal suitable for indoor/outdoor type Transformer of capacity 100 to 160 KVA . Complete all as directed.
As Per Item No 49 above But capacity 200 to 300 KVA .
As Per Item No 49 above But capacity 400 to 500 KVA .
Supply only for incorporated to the repair of transformer Off load Tap changer switch of existing model / type of Transformer of capacity 100 to 160 KVA . Complete all as directed.
Supply only for incorporated to the repair of transformer Off load Tap changer switch of existing model / type of Transformer of capacity 200 to 300 KVA .Complete all as directed.
Supply only for incorporated to the repair of transformer Off load changer switch of existing model / type of Transformer of capacity 400 to 500 KVA . Complete all as directed.
Dehydration of transformers oil minimum three cycles to achieve dielectric strength up to 50 KV in 2.5 mm gap electrode including toping up of Transformer oil if required at site . Note: (i) Dehydration of transformer oil shall be carried out at site and contractor shall be taken the testing result before and after dehydration of oil and shown to the EIC at site and maintain necessary documents for record . (ii) Dehydration Machine with all T&P & Transformer oil testing machine for dehydration of Transformer oil and necessary transportation for the machines shall be arranged by contractor . (iii) Oil required for topping up the transformer will be measured & paid separatly.
Supply and topup of transformer oil EHV as per IS 335 of 1993 Part II with dielectric strength up to 50 KV in 2.5 mm gap electrode complete all as directed.
Removing of existing damage insulating material from LV Winding , Cleaning the winding and reinsulating the LV Winding with approved grade and make of insulating paper and heating the coil in the heat chamber to obtained desired result of insulating resistence complete and re-installation complete all as directed.
Rewinding of transformer HV coil with super enamelled / paper coated copper wire of existing gauge including all associated insulating material such as separator etc complete varnishing, heating including dismantling of top cover, decanting transformer oil, storing the same in suitable container,disconnection live part, dismantling of bushing, lifting of core Assey, checking the windings, cleaning of cooling tube, conservator and all internal connection after all necessary repair work and rewinding, assemble the complete transformer and refilling after necessary filtration including all internal connection etc of any type / capacity transformer. Complete all as directed. (Note : Filtration of oil, insulator, spindle and gasket etc shall be measured and paid separately).
Rewinding of transformer LV coil with super enamelled / paper coated copper wire of existing gauge including all associated insulating material such as separator etc complete varnishing, heating including dismantling of top cover, decanting transformer oil, storing the same in suitable container,disconnection live part, dismantling of bushing, lifting of core Assey, checking the windings, cleaning of cooling tube, conservator and all internal connection after all necessary repair work and rewinding, assemble the complete transformer and refilling after necessary filtration including all internal connection etc of any type / capacity transformer. Complete all as directed. (Note : Filtration of oil, insulator, spindle and gasket etc shall be measured and paid separately).
Supply and replacement of silica gel cristal complete all as directed.
Supply and fixing in repalcement of heavy duty breather assembly with Silica jel cristal complete for Transformer upto 300 KVA complete all as directed.
S & F in replacement Winding tempreture gauge for Transformer 0 - 150 C complete all as directed.
Painting of steel pole with cross arms, clamp of any length and shape for HT overhead line with single coat of aluminium paint including preparation of the existing surface including marking pole numbers in a 20 cm dia RED circle with yellow colour numbering with synthetic enamelled paint and strip marking of THREE RED AND THREE YELLOW alternatively of width 15 cm by fluorescent paint, from bottom of pole to 90 CM height and providng three nos of Red ,Yellow & Blue of reflecting strip of 25 mm width adhesive PVC tape around the pole at suitable height complete all as directed.
Description same all as per item No 63 but HT 2-Pole structure complete all as directed. Note : - Complete 2 pole structure shall be measured as one unit.
Cleaning and scraping out old rubbed paint / rust & Painting of transformer complete of capacity up to 63 to 250 KVA 11/.433 KV outdoor / Indoor type with one coat of spray painting with synthetic enamelled gray paint (first grade) by sprey painting machine on transformer & Making SM NO on surface of transformer complete all as directed.
Description same all as per item No 65 but capacity 300 to 500 KVA 11/0.433 V complete all as directed.
Supply only Lead acid battery 2 volt 200 AH TOBULAR (TBS). Complete all as directed. (Make :- Exide/ Express/Amco/Amron).
Earthing to OH/Sub stn with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead GI wire 4 mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule pt-I 2009, GI earth lead wire protected by GI pipe 15mm dia light grade and connected to earth test point including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete in repair all as directed. (Note : Main earth lead beyond 7.5 meter shall measured and paid saperatly).
Description all as per above item no 68 but main earth lead 32 x 6 mm galvanised iron strip complete all as directed.
Earth continuity conductor or main earthing lead of 4 mm dia galvanized iron or steel wire, buried in ground or fixed to wall in repair complete all as directed.
Earth continuity conductor or main earthing lead of 32 x 6 mm galvanized iron strip, buried in ground or fixed to wall in repair complete all as directed.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including testing complete all as directed. (Make - Denson /Raychem / 3M).
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm including testing complete all as directed. (Make - Denson /Raychem / 3M)
Cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm including testing complete all as directed. (Make - Denson /Raychem / 3M).
Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm including testing complete all as directed. (Make - Denson /Raychem / 3M)
Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm including testing complete all as directed. (Make - Denson /Raychem / 3M).
Cable jointing kit for 11 KV grade cable for straight through outdoor heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 50 to 95 sqmm including testing complete all as directed. (Make - Denson /Raychem / 3M).
Cable jointing kit for 11 KV grade cable for straight through outdoor heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured Al conductor cable of size 120 to 185 sqmm including testing complete all as directed. (Make - Denson /Raychem / 3M).
Supplying, laying, jointing, testing and commissioning HT XLPE insulated, screened , PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) with aluminium conductor screening with extruded semi conditioning layers insulation screening with copper tape cover laid upto with PVC (ST-2) extruded, inner sheathing galvanized steel strip armoured PVC (ST-2) outer sheathed cable confirming to IS-7098 (Pt-II) 11/6.35 KV grade suitable for earthed system cross sectional area 95 sqmm 3 core H.T.U.G cable laid in trenches/through GI pipe/fixed along with pole complete all as directed including taking out of old unserviceable cable. (Make: Havells/Plaza/Polycab/KEI).
GI tubing, light grade, 100 mm bore with all fitting laid in trenches / pole / wall for protection of cables in repairs complete all as directed. (Make - TATA / ZINDAL / Bansal).
HT Cable rout indicator made out of PCC Post of 1:2:4 of size not less than 20 x 15 cm and one meter height with making embossing the letters "HT CABLE" of size 100 mm in the PCC Post including necessary excavation and embedding in PCC (1:2:4) type B-I using 20 mm graded stone aggregate (30 X 30 x 30 CM) embedded in the ground. Complete all as directed.
Synthetic insulating rubber mat suitable for 33 KV HT installation of size 2 m x 1m x 25 mm complete all as directed.
Digital over current protection relay ( 3 OC + 1 EF & INST. Protection ) with micro processor based complete all as directed . (Make - Cat No - CGI 14 N/C of CG OR equivalent of L & T / Siemence / C & S). NOTE : - Relay shall be suitable as per existing type / Make for 11 / 33 KV VCB'S / Control Panel .
Repair / Servicing / maintenance of Current/ Potential transformer (CT and PT) 33 / 11 KV outdoor type, steel structure mounted type of any capacity including disconnecting of CT/PT from electric system including taking out from existing position, decanning of transformer oil, opening of cover complete checking of all connection and including replacing of old transformer oil and all gaskets, complete new painting as per existing and providing greasing/lubrication to other jointing/rusting components, reconditioning electric connections, replacinig unserviceable HT bushing, rubber / cork oil seals and damage spindle as required complete all as ditected.
Servicing / Calibration to 33 KV HT VCB panel and PCOB for Vaccum interruptor complete including the following : switching off electric supply, Checking of mechanical system for proper functioning, replacing closing buffer, triping buffer (VMX type), V I connection gap check, motor coil resistance check, closing coil resistance check, spring charging cut off switch check, aux switch check, NO-NC states check, trip coil resistance check, testing details, timing test, oil value test, breaker timing test, connector resistance test, IR value test, HV test, mechanical and electrical mechanism check, counter reading check, shock observer check, pre close/ post close circuit check, test and service position limit switch check, breaker drive screw operation check, trip coil assemble operation check, mechanical latch . Cleaning & servicing the fixed/ moving contact & blowing out dust and applying the proper lubrication/ greasing and reassembling the VCB including connection to HT panel complete to be replaced where reqd all as directed by EIC. Note:- (1) Maitenance of all HT VCB will be carried out as per maintenance schedule (2) Testing of above job to be carried out by engineers of authorised dealer/service centre. (3) Replacing new items shall be measured and paid separately as supply only
Servicing / Calibration to 11KV HT VCB/RMU panel complete including the following (a) Taking out 11KV HT VCB of 630 Amps rating trolley from HT Panel after switching off electric supply.Checking of mechanical system for proper functioning of upward/downward movement of HT VCB trolley including replacing closing buffer, triping buffer (VMX type), VI connection gap check, motor coil resistance check, closing coil resistance check, spring charging cut off switch check, aux switch check, NO-NC states check, trip coil resistance check, testing details, timing test, oil value test, breaker timing test, connector resistance test, IR value test, HV test, mechanical and electrical mechanism check, counter reading check, shock observer check, pre close/ post close circuit check, test and service position limit switch check, breaker drive screw operation check, trip coil assemble operation check, mechanical latch . Cleaning & servicing the fixed/ moving contact & blowing out dust and applying the proper lubrication/ greasing and reassembling the VCB including connection to HT panel complete to be replaced where reqd all as directed by EIC. Note:- (1) Maitenance of all HT VCB will be carried out as per maintenance schedule (2) Testing of above job to be carried out by engineers of authorised dealer/service centre. (3) Replacing new items shall be measured and paid separately under relevant item.
Supply only shunt closing/tripping coil operated on 110 /30 volt system suitable for working of relay of HT SF6 / VCB complete all as directed.
Supply and fixing in repairs spring charging motor suitable for fixing with 33/11 KV indoor type VCB panels complete all as directed. (Make - MICO/ABB/C&S/L&T).
Digital earth fault and over current relay in , in existing 11/33 KV panel complete all as directed. (Make:- L&T nX series MC61A cat MC61ANX2200 or equvilant of cromption /ABB).
Vacuum interputer suitable for 11 KV VCB trolly complete in repair all as directed.
Moving contacts of VCB made of copper and suitable for 11 KV VCB Trolley compete in repair all as directed.
Supply only meter devices 3 phase digital type Amp meter 0- 120 Amp class 0.5 of size 96 mmx96 mm to match the ratio of existing CTs. Complete all as directed. (Make: Conzerve Cat No DM 3258 or equivalent model of IMP/AE Bombay/Meco).
Supply only meter devices 3 phase digital type Volt Meter 0- 12 KV class 0.5 of size 96mm x 96 mm to match the ratio of existing CTs. Complete all as directed. (Make conzerve Cat No DM 3256 or equivalent model of IMP/AE Bombay/Meco).
Lightening arrestor linear resistance type complete with all fitting,distribution class suitable for 33 KV system pole mounting type conforming to IS - 3070 Part-I including taking down existing unserviceable one complete all as directed.
Post insulator porcelain viterous brown suitable for 33 KV complete all as directed
Pin type insulator, porcelain, vitreous, white, brown or green insulator, suitable for 33000 volts grade including taking out of unsv one complete all as directed. (Make -PACTIL / MADRAS PORCELAIN / NGEF / JAIPURIA / BHEL).
spreading and leveling evenly (any thickness) 40 mm graded stone aggregated complete all as directed.
Cutting removing the vegetation growth and surface dressing all around the installation yard including two pole structure areas, around power house, substation (external only) to keep installation clean and tidy all as directed.
Painting to the Transformer yard fencing made out of GI wire mesh with two coats of synthetic enamel paint complete all as directed.
Cement concrete (1:2:4) type B-1 using 20 mm graded stone aggregate in coping to poles & the like, etc including weathering, slightly rounded or chamfered angles and throating as directed including necessary form work complete all as directed.
M/s Vinay Kumar
M/S AJAY KUMAR SINGH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .