Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹20.5 LAccepted-AOC | 1 | Accepted-AOC AOC | |
| 2 | 2₹24.0 L+₹3.5 L (17.2%)Rejected-Finance 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | 2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | 3₹25.1 L+₹4.6 L (22.6%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | 3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | 4₹25.2 L+₹4.7 L (23.1%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | 4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | 5₹25.4 L+₹4.9 L (24.0%)Rejected-Finance | 5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹33.3 L
EMD Value
₹66,520
Closing Date
4 Jan 2024, 6:00 pmClosed
GE Amritsar
GE Amritsar Pin 143001
SPECIAL REPAIR/REPLACEMENT OF OH LINE TO UG CABLE WITH LT PANEL AT VIKRAM BATRA JCO/OR MD ACCN UNDER GARRISON ENGINEER AMRITSAR CANTT
2023_MES_632759_1
GE/ASR-74/2023-24
Open Tender
Civil Works
Works
180 days
GE Amritsar
class D category b i
8 documents required · 8 mandatory
₹500
GE Amritsar
₹66,520
3 Apr 2024
14 Dec 2023
5 Jan 2024
14 Dec 2023
4 Jan 2024
29 Dec 2023
Amount
Taking down carefully from poles ACSR conductor any size ; Complete all as specified and directed by Engineer-in-charge.
Taking down carefully from poles cross arms of any size incl clamps nuts bolts etc ; Complete all as specified and directed by Engineer-in-charge.
Taking down carefully from poles LT pin/ shacle insulators ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for taking up or down LT UG cable from ground/ pole/ wall etc all as directed of sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 10 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for taking up or down LT UG cable from ground/ pole/ wall etc all as directed of sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 16 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for taking up or down LT UG cable from ground/ pole/ wall etc all as directed of sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 35 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for taking up or down LT UG cable from ground/ pole/ wall etc all as directed of sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 70 sqmm 3.5 Core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for taking up or down LT UG cable from ground/ pole/ wall etc all as directed of sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 95 sqmm 3.5 Core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for relaying of LT UG cables 1100V grade Aluminium conductor of the following sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 10 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for relaying of LT UG cables 1100V grade Aluminium conductor of the following sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 16 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for relaying of LT UG cables 1100V grade Aluminium conductor of the following sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 35 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for relaying of LT UG cables 1100V grade Aluminium conductor of the following sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 70 sqmm 3.5 Core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for relaying of LT UG cables 1100V grade Aluminium conductor of the following sizes Note -The rate for excavation will be measured and paid separately under relevant items (a) 95 sqmm 3.5 Core, ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 10 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 16 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 25 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 35 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 50 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 70 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 95 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 150 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Supply and Laying in trenches or drawn through pipe or fixed on wall / poles , LT UG cable 1100 Volts, heavy duty XLPE insulated, screened, PVC bedded, galvanised steel strip or wired armoured with stranded aluminium conductor after removing old one of following size:- (a) 185 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge. Note -The rate quoted shall be inclusive of end joints for the cables both ends where ever terminated for connections on pole/ panels etc ; Complete all as specified and directed by Engineer-in-charge.
Material and labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick, buried vertically in ground (Each pit not less than 2.25 mtrs deep below normal ground level with top edge of plate not less than 1.50 M below normal ground level) connected to GI strip 32 x 6 mm , by means of bolts, nuts, and check nuts and washers etc encased in GI protection pipe 40 mm dia light grade pipe for protection of GI earth strip both to be provided to the extet of 7.5 meters, all as shown on electrical plate No 3 of MES SSR - 2004 Part - I, GI protection pipe buried in ground, laid under floors / plinths or mixed on walls / pole etc or concealed in walls etc; with provision of mixture of charcoal dust and common salt packed upto minimum 150 mm all around the earth plate, including PCC 1:2:4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with GI 20 mm dia medium grade pipe and MS funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of soil / strata and testing on completion ; Complete all as specified and directed by Engineer-in-charge. Note:- i) Cost of GI strip 32 x 6 mm and protection pipe 40 mm dia is deemmed to be included in rate quoted ii) Excavation and returning filling of Soil any type is deemed to be included in rates.
Material and labour for earthing complete with galvanised steel earth plate electrode 600 x 600 x 6.0 mm thick, buried vertically in ground (Each pit not less than 2.25 mtrs deep below normal ground level with top edge of plate not less than 1.50 M below normal ground level) connected to GI wire 4 mm , by means of bolts, nuts, and check nuts and washers etc encased in GI protection pipe 15 mm dia light grade pipe for protection of GI earth strip both to be provided to the extet of 7.5 meters, all as shown on electrical plate No 3 of MES SSR - 2004 Part - I, GI protection pipe buried in ground, laid under floors / plinths or mixed on walls / pole etc or concealed in walls etc; with provision of mixture of charcoal dust and common salt packed upto minimum 150 mm all around the earth plate, including PCC 1:2:4 type B-1 earth pit with M.S angle iron frame, cast iron cover with locking arrangement, with GI 20 mm dia medium grade pipe and MS funnel with wire mesh for watering arrangement, including necessary excavation and earth work in any type of soil / strata and testing on completion ; Complete all as specified and directed by Engineer-in-charge. Note:- i) Cost of GI wire 4 mm and protection pipe 15 mm dia is deemed to be included in rate quoted ii) Excavation and returning filling of Soil any type is deemed to be included in rates.
Supply ,Install, test and commissioning of LT panel board, CPRI approved factory fabricated made out door, cubical type , vermin proof, dust proof, cubical type, IP-56, made out of 3.15 mm thick CRCA sheet and inner sheet of 2.0mm thick and bottom angle iron frame of size 50x50x5mm 90 cm long and size suitable to accommodate the following accessories, with insulated alluminium busbar 500 amps capacity , 3 phase , 4 wire system, both sides openable (front and back) with locking arrangement , duly powder coated internally and externally with minimum seven tank process traetment connecting with cable with lugs including internal wiring with copper cables of suitable size using lugs comprising the following accessories all as directed.( Pocket 1) (a)MCCB 300 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 36 KA-01 No (Incoming) (b) MCCB 63 Amps 415V 04 pole with thermal magnetic setting breaking cap 18KA - 08 Nos (For Out Going) (c) MCCB 100 Amps,415V, (4P) with breaking capacity 25 KA -01 Nos (For Out Going) (d) Volt Meter (digital Type (0 -500 Volts)-01 No (e ) Ammeter (digital type) with CTs 0-300Amps)-01 No (f) Phase indication lamps LED type with holder-01 Set(Set of Three)
All as per item No. 25 above but consiting of the following ( Pocket No. 2) (a)MCCB 250 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 36 KA-01 No (Incoming) (b) MCCB 63 Amps 415V 04 pole with thermal magnetic setting breaking cap 18KA - 07 Nos (For Out Going) (c) Volt Meter (digital Type (0 -500 Volts)-01 No (d ) Ammeter (digital type) with CTs 0-300Amps)-01 No (e) Phase indication lamps LED type with holder-01 Set(Set of Three) Notes:- 1. The Panel Should be CPRI approved 2.The rates Quoted shall include for earth work and excavation for angle iron frame for foundation of panel board up to 0.45 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.45 M from GL to the bottom of panel board.
All as per item No. 25 above but consiting of the following ( Pocket No. 3) (a)MCCB 300 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 36 KA-01 No (Incoming) (b) MCCB 63 Amps 415V 04 pole with thermal magnetic setting breaking cap 18KA - 11 Nos (For Out Going) (c) Volt Meter (digital Type (0 -500 Volts)-01 No (d ) Ammeter (digital type) with CTs 0-300Amps)-01 No (e) Phase indication lamps LED type with holder-01 Set(Set of Three)
All as per item No. 25 above but Bus bar 300 amps 4 nos and consiting of the following ( Pocket No. 4 & 5) (a)MCCB 160 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 36 KA-01 No (Incoming) (b) MCCB 63 Amps 415V 04 pole with thermal magnetic setting breaking cap 18KA - 7 Nos (For Out Going) (c) Volt Meter (digital Type (0 -500 Volts)-01 No (d ) Ammeter (digital type) with CTs 0-300Amps)-01 No (e) Phase indication lamps LED type with holder-01 Set(Set of Three)
All as per item No. 25 above but with Bus bar 200 amps 4 nos and consiting of the following ( Pocket No. 6) (a)MCCB 100 Amp,415 V four pole with thermal magnetic setting with Breaking Cap 25 KA-01 No (Incoming) (b) MCCB 40 Amps 415V 04 pole with thermal magnetic setting breaking cap 18KA - 6 Nos (For Out Going) (c) Volt Meter (digital Type (0 -500 Volts)-01 No (d ) Ammeter (digital type) with CTs 0-300Amps)-01 No (e) Phase indication lamps LED type with holder-01 Set(Set of Three) Notes: for item No. 25 to29 . - 1. The Panel Should be CPRI approved 2. The rates Quoted shall include for earth work and excavation for angle iron frame for foundation of panel board up to 0.45 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.45 M from GL to the bottom of panel board..
Loop in box make sintex model GSJB 3020/ equivalent with Heavy duty 4 way connector and MCB SP 6 Amps B series -01 no. incl clamps made of GI flat 25x4 mm with nut bolts washers etc ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for straight through joint for LT UG cable 1100 Volt garde 3.5/4 core of sizes (a) 10 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for straight through joint for LT UG cable 1100 Volt garde 3.5/4 core of sizes (a) 1 6 Sqmm 4 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for straight through joint for LT UG cable 1100 Volt garde 3.5/4 core of sizes (a) 35 Sqmm 3.5 core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for straight through joint for LT UG cable 1100 Volt garde 3.5/4 core of sizes (a) 70 sqmm 3.5 Core, ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for straight through joint for LT UG cable 1100 Volt garde 3.5/4 core of sizes (a) 95 sqmm 3.5 Core, ; Complete all as specified and directed by Engineer-in-charge.
Supply and laying of HDPE DWC pipe of 75 mm dia for protection to LT cables to be relaid ; Complete all as specified and directed by Engineer-in-charge.
Supply and laying of HDPE DWC pipe of 100 mm dia for protection to LT cables to be relaid ; Complete all as specified and directed by Engineer-in-charge.
Excavation in trenches not exc. 1.50 m wide and not exc. 1.50 m in depth for foundation etc. or for laying of pipes and fittings, cables, HT / LT poles, stay assembly etc including forming bottom surfaces to required level and slope and getting out in hard / dense soil ; Complete all as specified and directed by Engineer-in-charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc. 25 cm thick in each layer as in hard / dense soil ; Complete all as specified and directed by Engineer-in-charge.
Removing surplus excavated material (SOIL) to distance not exc. 50 m and depositing where directed at a level not exc. 1.50 m above the starting point ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for road cutting for laying of protection pipes ; Complete all as specified and directed by Engineer-in-charge.
Material and Labour for PCC 1:3:6 type C2 using 40 mm graded stone aggregate for redressing of road surfaces ; Complete all as specified and directed by Engineer-in-charge.
kailu construction co
R D Bansal
Raman Electric Trading Co
Bharat Builder
GULSHAN SINGH GHAI AND SON
dinesh enterprises
B S TRADERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .