Refurbishment of 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
CC/NT/W-HVDC/DOM/A10/26/08649
Open
Power/Energy Projects/Products
Works
Talcher and Kolar
18 Jun 2026
18 Jun 2026
3 Aug 2026
18 Jun 2026
3 Aug 2026
18 Jun 2026
3 Jul 2026
Pole 1 Pole Control System
Event No. Device Device Type Input Type Panel Event Code Event Text
Pole 1 Converter Transformer Interface 21T01+X1
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L1 OIL TEMP L1 OIL TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L1 STAR TEMP L1 STAR WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L1 DELTA TEMP L1 DELTA WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L1 LINE TEMP L1 LINE WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L2 OIL TEMP L2 OIL TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L2 STAR TEMP L2 STAR WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L2 DELTA TEMP L2 DELTA WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L2 LINE TEMP L2 LINE WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L3 OIL TEMP L3 OIL TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L3 STAR TEMP L3 STAR WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L3 DELTA TEMP L3 DELTA WINDING TEMPERATURE
- =21T01 SU200 AI Pole 1 Converter Transformer Interface =21T01/L3 LINE TEMP L1 LINE WINDING TEMPERATURE
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L1 CMD RAISE L1 TAP CHANGER RAISE
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L1 CMD LOWER L1 TAP CHANGER LOWER
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L1 CMD COOl ON L1 COOLING ON
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L1 CMD COOl OFF L1 COOLING OFF
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L2 CMD RAISE L2 TAP CHANGER RAISE
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L2 CMD LOWER L2 TAP CHANGER LOWER
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L2 CMD COOl ON L2 COOLING ON
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L2 CMD COOl OFF L2 COOLING OFF
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L3 CMD RAISE L3 TAP CHANGER RAISE
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L3 CMD LOWER L3 TAP CHANGER LOWER
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L3 CMD COOl ON L3 COOLING ON
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =21T01/L3 CMD COOl OFF L3 COOLING OFF
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =20C08-Q9 EN INTERLOCK =20C08-Q9 ISO INTERLOCK
- =21T01 SU200 BO Pole 1 Converter Transformer Interface =20C08-Q8 EN INTERLOCK =20C08-Q8 ES INTERLOCK
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.A-Q1/OFF =20C08.A-Q1 ISOLATOR OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.A-Q1/ON =20C08.A-Q1 ISOLATOR CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.A-Q0/OFF =20C08.A-Q0 CB OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.A-Q0/ON =20C08.A-Q0 CB CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.A-Q6/OFF =20C08.A-Q6 ISOLATOR OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.A-Q6/ON =20C08.A-Q6 ISOLATOR CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.B-Q61/OFF =20C08.B-Q61 ISOLATOR OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.B-Q61/ON =20C08.B-Q61 ISOLATOR CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.B-Q0/OFF =20C08.B-Q0 CB OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.B-Q0/ON =20C08.B-Q0 CB CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.B-Q62/OFF =20C08.B-Q62 ISOLATOR OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.B-Q62/ON =20C08.B-Q62 ISOLATOR CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q6/OFF =20C08.C-Q6 ISOLATOR OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q6/ON =20C08.C-Q6 ISOLATOR CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q0/OFF =20C08.C-Q0 CB OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q0/ON =20C08.C-Q0 CB CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q2/OFF =20C08.C-Q2 ISOLATOR OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q2/ON =20C08.C-Q2 ISOLATOR CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q53/OFF =20C08.C-Q53 EARTH SWITCH OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q53/ON =20C08.C-Q53 EARTH SWITCH CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q9/OFF =20C08.C-Q9 ISOLATOR OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q9/ON =20C08.C-Q9 ISOLATOR CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q8/OFF =20C08.C-Q8 EARTH SWITCH OPEN
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =20C08.C-Q8/ON =20C08.C-Q8 EARTH SWITCH CLOSED
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/X1 SU200 ALARM RESET
106 =21B01+X1 SU200 BI Pole 1 Converter Transformer Interface =21B01+X1/PWR SPLY FLT VALVE HALL INTERFACE POWER SUPPLY FAULT
113 =20T11 SU200 BI Pole 1 Converter Transformer Interface =20T01/COOL FAULT SPARE TRAFO COOLING SYST. FAULT
115 =20T11 SU200 BI Pole 1 Converter Transformer Interface =20T01/GROUP ALR SPARE TRAFO GROUP ALARM
118 =20T11 SU200 BI Pole 1 Converter Transformer Interface =20T01/PWR SPLY FLT SPARE TRAFO HEATING/POWER SUPPLY FAULT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 TAP POS BCD_1 TAP CHANGER L1 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 TAP POS BCD_2 TAP CHANGER L1 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 TAP POS BCD_4 TAP CHANGER L1 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 TAP POS BCD_8 TAP CHANGER L1 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 TAP POS BCD_10 TAP CHANGER L1 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 TAP POS BCD_20 TAP CHANGER L1 POSITION BIT
127 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OLTC RUN TAP CHANGER L1 RUNNING
128 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OLTC FLT TAP CHANGER L1 FAULT
129 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OLTC LOC CTRL TAP CHANGER L1 LOCAL CONTROL
130 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OLTC OILFILT FLT TAP CHANGER L1 OIL FILTER FAULT
131 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OLTC OFF POS TAP CHANGER L1 OFF POSITION
132 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 PWR SPLY FLT L1 AUXILIARY POWER SUPPLY FAULT
133 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 FLT AC SPLY L1 AC SUPPLY FAULT
134 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 CTRL SPLY FLT L1 CONTROL VOLTAGE FAULT
135 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 FLT INT AC L1 INTERNAL 3PHASE FAULT
136 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01+X1/SU1 ALR RES L1 ALARM-RESET
137 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 COOL ON TRAFO COOLING SYSTEM L1 ON
138 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 COOL OFF TRAFO COOLING SYSTEM L1 OFF
139 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 BUCHHOLZ TRP L1 BUCHHOLZ RELAY MAIN TANK TRIP
140 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 PRES MAIN TRP L1 PRESSURE RELIEF DEVICE MAIN TANK TRIP
141 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OIL TEMP TRP L1 OIL TEMPERATURE TRIP
142 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 WIND TEMP TRP L1 WINDING TEMPERATURE TRIP
143 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 PROT DIV TRP L1 PROT. RELAY DIVERTER SWITCH TRIP
144 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 PRES DIV TRP L1 PRESS. RELIEF DEV. DIVERTER SWITCH TRIP
145 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 COOL FLT L1 COOLER GROUP FAULT
147 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 HYDRAN GAS HI HYDRAN GAS MONITORING "GAS HI"
148 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 HYDRAN GAS HI HI HYDRAN GAS MONITORING "GAS HI-HI"
149 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 HYDRAN SYST FLT HYDRAN GAS MONITORING SYSTEM FAULT
150 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 SF6 TRP L1 STAR SF6 TRIP
151 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 SF6 ALR L1 STAR SF6 ALARM
152 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 WIND TEMP ALR L1 WINDING TEMP. ALARM
153 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 BUCHHOLZ ALR L1 BUCHHOLZ RELAY MAIN TANK ALARM
154 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OIL TEMP ALR L1 OIL TEMPERATURE MAIN TANK ALARM
156 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OIL LOW L1 LOW OIL LEVEL ALARM
157 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L1 OIL HIGH L1 HIGH OIL LEVEL ALARM
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 TAP POS BCD_1 TAP CHANGER L2 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 TAP POS BCD_2 TAP CHANGER L2 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 TAP POS BCD_4 TAP CHANGER L2 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 TAP POS BCD_8 TAP CHANGER L2 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 TAP POS BCD_10 TAP CHANGER L2 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 TAP POS BCD_20 TAP CHANGER L2 POSITION BIT
167 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OLTC RUN TAP CHANGER L2 RUNNING
168 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OLTC FLT TAP CHANGER L2 FAULT
169 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OLTC LOC CTRL TAP CHANGER L2 LOCAL CONTROL
170 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OLTC OILFILT FLT TAP CHANGER L2 OIL FILTER FLT
171 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OLTC OFF POS TAP CHANGER L2 OFF POSITION
172 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 PWR SPLY FLT L2 AUXILIARY POWER SUPPLY FAULT
173 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 FLT AC SPLY L2 AC SUPPLY FAULT
174 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 CTRL SPLY FLT L2 CONTROL VOLTAGE FAULT
175 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 FLT INT AC L2 INTERNAL 3PHASE FAULT
176 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01+X1/SU2 ALR RES L2 ALARM-RESET
177 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 COOL ON TRAFO COOLING SYSTEM L2 ON
178 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 COOL OFF TRAFO COOLING SYSTEM L2 OFF
179 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 BUCHHOLZ TRP L2 BUCHHOLZ RELAY FOR MAIN TANK TRIP
180 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 PRES MAIN TRP L2 PRESSURE RELIEF DEVICE MAIN TANK TRIP
181 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OIL TEMP TRP L2 OIL TEMPERATURE TRIP
182 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 WIND TEMP TRP L2 WINDING TEMPERATURE TRIP
183 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 PROT DIV TRP L2 PROTECTION RELAY DIVERTER SWITCH TRIP
184 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 PRES DIV TRP L2 PRESS. RELIEF DEV. DIVERTER SWITCH TR
185 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 COOL FLT L2 COOLER GROUP FAULT
187 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 HYDRAN GAS HI HYDRAN GAS MONITORING "GAS HI"
188 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 HYDRAN GAS HI HI HYDRAN GAS MONITORING "GAS HI-HI"
189 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 HYDRAN SYST FLT HYDRAN GAS MONITORING SYSTEM FAULT
190 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 SF6 TRP L2 STAR SF6 TRIP
191 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 SF6 ALR L2 STAR SF6 ALARM
192 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 WIND TEMP ALR L2 WINDING TEMP. ALARM
193 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 BUCHHOLZ ALR L2 BUCHHOLZ RELAY FOR MAIN TANK ALARM
194 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OIL TEMP ALR L2 OIL TEMPERATURE IN MAIN TANK ALARM
196 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OIL LOW L2 LOW OIL LEVEL ALARM
197 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L2 OIL HIGH L2 HIGH OIL LEVEL ALARM
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 TAP POS BCD_1 TAP CHANGER L3 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 TAP POS BCD_2 TAP CHANGER L3 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 TAP POS BCD_4 TAP CHANGER L3 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 TAP POS BCD_8 TAP CHANGER L3 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 TAP POS BCD_10 TAP CHANGER L3 POSITION BIT
- =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 TAP POS BCD_20 TAP CHANGER L3 POSITION BIT
207 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OLTC RUN TAP CHANGER L3 RUNNING
208 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OLTC FLT TAP CHANGER L3 FAULT
209 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OLTC LOC CTRL TAP CHANGER L3 LOCAL CONTROL
210 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OLTC OILFILT FLT TAP CHANGER L3 OIL FILTER FLT
211 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OLTC OFF POS TAP CHANGER L3 OFF POSITION
212 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 PWR SPLY FLT L3 AUXILIARY POWER SUPPLY FAULT
213 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 FLT AC SPLY L3 AC SUPPLY FAULT
214 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 CTRL SPLY FLT L3 CONTROL VOLTAGE FAULT
215 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 FLT INT AC L3 INTERNAL 3PHASE FAULT
216 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01+X1/SU3 ALR RES L3 ALARM-RESET
217 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 COOL ON TRAFO COOLING SYSTEM L3 ON
218 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 COOL OFF TRAFO COOLING SYSTEM L3 OFF
219 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 BUCHHOLZ TRP L3 BUCHHOLZ RELAY FOR MAIN TANK TRIP
220 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 PRES MAIN TRP L3 PRESSURE RELIEF DEVICE MAIN TANK TR.
221 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OIL TEMP TRP L3 OIL TEMPERATURE TRIP
222 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 WIND TEMP TRP L3 WINDING TEMPERATURE TRIP
223 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 PROT DIV TRP L3 PROTECTION RELAY DIVERTER SWITCH TRIP
224 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 PRES DIV TRP L3 PRESS. RELIEF DEV. DIVERTER SWITCH TR
225 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 COOL FLT L3 COOLER GROUP FAULT
227 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 HYDRAN GAS HI HYDRAN GAS MONITORING "GAS HI"
228 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 HYDRAN GAS HI HI HYDRAN GAS MONITORING "GAS HI-HI"
229 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 HYDRAN SYST FLT HYDRAN GAS MONITORING SYSTEM FAULT
230 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 SF6 TRP L3 STAR SF6 TRIP
231 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 SF6 ALR L3 STAR SF6 ALARM
232 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 WIND TEMP ALR L3 WINDING TEMP. ALARM
233 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 BUCHHOLZ ALR L3 BUCHHOLZ RELAY FOR MAIN TANK ALARM
234 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OIL TEMP ALR L3 OIL TEMPERATURE IN MAIN TANK ALARM
236 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OIL LOW L3 LOW OIL LEVEL ALARM
237 =21T01 SU200 BI Pole 1 Converter Transformer Interface =21T01/L3 OIL HIGH L3 HIGH OIL LEVEL ALARM
Pole 1 Valve cooling system control
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/VC INLET TEMP VC INLET TEMPERATURE
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/VC OUTLET TEMP VC OUTLET TEMPERATURE
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/VC MAIN COND. VC MAIN CONDUCTIVITY
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/VC ION 1 COND. VC ION EXHANGER 1 CONDUCTIVITY
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/VC ION 2 COND. VC ION EXHANGER 2 CONDUCTIVITY
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/VC EXP. TANK LEVEL VC EXPANSION TANK LEVEL
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/VH TEMPERATURE VH TEMPERATURE
- =21U61 SU200 AI Pole 1 Valve cooling system control =21U61/AMBIENT TEMPERATURE AMBIENT TEMPERATURE
- =21U61 SU200 BO Pole 1 Valve cooling system control =21U61/VALVE ENERGISED VALVE ENERGISED
- =21U61 SU200 BO Pole 1 Valve cooling system control =21U61/REMOTE OFF VH VENTLN REMOTE OFF
- =21U61 SU200 BO Pole 1 Valve cooling system control =21U61/REMOTE ON VH VENTLN REMOTE ON
241 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC OFF VALVE COOLING SYSTEM OFF
242 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC ON VALVE COOLING SYSTEM ON
243 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC SYS ALR VALVE COOLING SYSTEM ALARM
244 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC TOWER FLT COOLING TOWER FAULT
245 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC PUMP1 ON PUMP 1 ON
246 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC PUMP2 ON PUMP 2 ON
247 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC PUMP1 FLT PUMP 1 FAULT
248 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC PUMP2 FLT PUMP 2 FAULT
249 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC EXP TNK TRP EXPANSION TANK LOW TRIP
250 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC INLET TEMP ALR INLET TEMPERATURE HIGH ALARM
251 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC INLET TEMP TRP INLET TEMPERATURE VERY HIGH TRIP
252 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC MAIN COND ALR MAIN CONDUCTIVITY HIGH ALARM
253 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC MAIN COND TRP MAIN CONDUCTIVITY HIGH TRIP
254 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC ION COND ALR IONEXCHANGE CONDUCTIVITY HIGH ALARM
255 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC WATER FLOW ALR WATER FLOW ALARM
256 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC WATER FLOW TRP WATER FLOW TRIP
257 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC WATER LEAKAGE WATER LEAKAGE
258 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC STOR TNK ALR STORAGE TANK LOW ALARM
259 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC SPRAY ALR SPRAY WATER STORAGE TANK LOW ALARM
260 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC SPRAY PMP FLT SPRAY PUMP FAILURE
261 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC WATER TREAT FLT WATER TREATMENT FAILURE
262 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC AC FLT AC FAILURE
263 =21U61 SU200 BI Pole 1 Valve cooling system control =21U61/VC DC FLT DC FAILURE
265 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV OFF VALVE HALL VENTILATION OFF
266 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV ON VALVE HALL VENTILATION ON
267 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV FAN 1 ON VALVE HALL VENTILATION FAN 1 ON
268 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV FAN 2 ON VALVE HALL VENTILATION FAN 2 ON
269 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV FAN 1 FLT VALVE HALL VENTILATION FAN 1 FAILURE
270 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV FAN 2 FLT VALVE HALL VENTILATION FAN 2 FAILURE
271 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV FILTER ALR VALVE HALL VENTILATION FILTER GLOGGED
272 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV ROOM TEMP ALR VALVE HALL TEMPERATURE HIGH
273 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV DAMP NOT CLOSED VALVE HALL VENTILATION DAMPER NOT CLOSED
274 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV DAMP NOT OPENED VALVE HALL VENTILATION DAMPER NOT OPENED
275 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV HEAT FLT VALVE HALL VENTILATION HEATER FAILURE
276 =21U71 SU200 BI Pole 1 Valve cooling system control =21U71/VHV GEN ALR VALVE HALL VENTILATION GENERAL ALARM
Pole 1 Valve Hall Interface -21B01+X1
- =21B01-Q51 SU200 AI Pole 1 Valve Hall Interface =21B01/AMB_TEMP AMBIENT TEMPERATURE
- =21B01-Q51 SU200 BO Pole 1 Valve Hall Interface =21B01-Q51/CMD OFF TRANSF (STAR) EARTH SWITCH OPEN CMD
- =21B01-Q51 SU200 BO Pole 1 Valve Hall Interface =21B01-Q51/CMD ON TRANSF (STAR) EARTH SWITCH CLOSE CMD
- =21B01-Q51 SU200 BO Pole 1 Valve Hall Interface =21B01-Q51/CMD RELEASE TRANSF (STAR) EARTH SWITCH LOCAL CTRL REL
- =21B01-Q52 SU200 BO Pole 1 Valve Hall Interface =21B01-Q52/CMD OFF TRANSF (DELTA) EARTH SWITCH OPEN CMD
- =21B01-Q52 SU200 BO Pole 1 Valve Hall Interface =21B01-Q52/CMD ON TRANSF (DELTA) EARTH SWITCH CLOSE CMD
- =21B01-Q52 SU200 BO Pole 1 Valve Hall Interface =21B01-Q52/CMD RELEASE TRANSF (DELTA) EARTH SWITCH LOCAL CTRL REL
- =21B01-Q55 SU200 BO Pole 1 Valve Hall Interface =21B01-Q55/CMD OFF LV EARTH SWITCH OPEN CMD
- =21B01-Q55 SU200 BO Pole 1 Valve Hall Interface =21B01-Q55/CMD ON LV EARTH SWITCH CLOSE CMD
- =21B01-Q55 SU200 BO Pole 1 Valve Hall Interface =21B01-Q55/CMD RELEASE LV EARTH SWITCH LOCAL CTRL REL
- =21B01-L SU200 BO Pole 1 Valve Hall Interface =21B04-L/KEY RELEASE SMR KEY RELEASE +VE
- =21B01-L SU200 BO Pole 1 Valve Hall Interface =21B04-L/KEY RELEASE SMR KEY RELEASE -VE
- =21B01-Q54 SU200 BO Pole 1 Valve Hall Interface =21B01-Q54/CMD OFF HV EARTH SWITCH OPEN CMD
- =21B01-Q54 SU200 BO Pole 1 Valve Hall Interface =21B01-Q54/CMD ON HV EARTH SWITCH CLOSE CMD
- =21B01-Q54 SU200 BO Pole 1 Valve Hall Interface =21B01-Q54/CMD RELEASE HV EARTH SWITCH LOCAL CTRL REL
- =21B01 SU200 BO Pole 1 Valve Hall Interface =21B01/CMD DOOR RELEASE VH DOOR RELEASE
- =21B01 SU200 BO Pole 1 Valve Hall Interface =21B01/CMD DOOR LOCK ENABLE VH DOOR LOCK ENABLE
- =21B04 SU200 BO Pole 1 Valve Hall Interface =21B04+UT1/CMD SMR COOLING OFF SMR COOLING OFF
- =21B04 SU200 BO Pole 1 Valve Hall Interface =21B04+UT1/CMD SMR COOLING ON SMR COOLING ON
321 =21B01-Q51 SU200 BI Pole 1 Valve Hall Interface =21B01-Q51/OFF TRANSF (STAR) EARTH SWITCH OPEN
322 =21B01-Q51 SU200 BI Pole 1 Valve Hall Interface =21B01-Q51/ON TRANSF (STAR) EARTH SWITCH CLOSED
323 =21B01-Q51 SU200 BI Pole 1 Valve Hall Interface =21B01-Q51/FLT TRANSF (STAR) EARTH SWITCH FAULT
324 =21B01-Q51 SU200 BI Pole 1 Valve Hall Interface =21B01-Q51/LOC CTRL TRANSF (STAR) EARTH SWITCH LOCAL CONTROL
325 =21B01-Q52 SU200 BI Pole 1 Valve Hall Interface =21B01-Q52/OFF TRANSF (DELTA) EARTH SWITCH OPEN
326 =21B01-Q52 SU200 BI Pole 1 Valve Hall Interface =21B01-Q52/ON TRANSF (DELTA) EARTH SWITCH CLOSED
327 =21B01-Q52 SU200 BI Pole 1 Valve Hall Interface =21B01-Q52/FLT TRANSF (DELTA) EARTH SWITCH FAULT
328 =21B01-Q52 SU200 BI Pole 1 Valve Hall Interface =21B01-Q52/LOC CTRL TRANSF (DELTA) EARTH SWITCH LOCAL CTRL
329 =21B01-Q55 SU200 BI Pole 1 Valve Hall Interface =21B01-Q55/OFF LV EARTH SWITCH OPEN
330 =21B01-Q55 SU200 BI Pole 1 Valve Hall Interface =21B01-Q55/ON LV EARTH SWITCH CLOSED
331 =21B01-Q55 SU200 BI Pole 1 Valve Hall Interface =21B01-Q55/FLT LV EARTH SWITCH FAULT
332 =21B01-Q55 SU200 BI Pole 1 Valve Hall Interface =21B01-Q55/LOC CTRL LV EARTH SWITCH LOCAL CONTROL
333 =21B01-Q54 SU200 BI Pole 1 Valve Hall Interface =21B01-Q54/OFF HV EARTH SWITCH OPEN
334 =21B01-Q54 SU200 BI Pole 1 Valve Hall Interface =21B01-Q54/ON HV EARTH SWITCH CLOSED
335 =21B01-Q54 SU200 BI Pole 1 Valve Hall Interface =21B01-Q54/FLT HV EARTH SWITCH FAULT
336 =21B01-Q54 SU200 BI Pole 1 Valve Hall Interface =21B01-Q54/LOC CTRL HV EARTH SWITCH LOCAL CONTROL
337 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B01/DOOR CLOSE VH MAIN DOOR CLOSED
338 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B01/DOOR OPEN VH MAIN DOOR OPEN
339 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B01/DOOR LOCK VH MAIN DOOR LOCKED
340 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B01/DOOR LOCK REQ VH MAIN DOOR LOCK ENABLED
341 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B04+UT1/COOL OFF SMR COOLING OFF
342 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B04+UT1/COOL ON SMR COOLING ON
343 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B04+UT1/POWER SUPPLY FAULT SMR COOLING POWER SUPPLY FAULT
344 =21B01 SU200 BI Pole 1 Valve Hall Interface =21B04+UT1/COOL LOCAL CTRL SMR COOLING LOCAL CTRL
345 =21B01-Z1 SU200 BI Pole 1 Valve Hall Interface =21B01-Z1/SF6 TRP DC BUSHING SF6 TRIP
346 =21B01-Z1 SU200 BI Pole 1 Valve Hall Interface =21B01-Z1/SF6 ALR DC BUSHING SF6 ALARM
353 =21T01 SU200 BI Pole 1 Valve Hall Interface =21T01/PWR SPLY FLT TRANSF. INTERFACE POWER SUPPLY FAULT
354 =21B04-L SU200 BI Pole 1 Valve Hall Interface =21B04-L/FENCE_LOCKED SMOOTHING REACTOR AREA FENCE LOCKED
355 =21B04-L SU200 BI Pole 1 Valve Hall Interface =21B04-L/FENCE_UNLOCKED SMOOTHING REACTOR AREA FENCE UNLOCKED
Pole 1 Valve Base Electronics
361 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/TRIG PLS FLT TRIGGER PULSE FAULT
362 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/NO THYR RED NO THYRISTOR REDUNDANCY
363 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/PROT FIRE EX MAXIMUM NUMBER OF PROT. FIRING EXCEEDED
365 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/PRINTER FLT PRINTER FAULT
366 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/VALVECHECK NOK VALVE CHECK NOT O.K.
367 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/VBE1 FLT VBE 1 FAULT
368 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/VBE1 PWR FLT VBE 1 POWER SUPPLY FAULT
369 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/MIN CHKBCK NOK MIN. NO. OF CHECK BACK SIGNALS NOT AVAIL
370 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/THYR MON SUSP THYRISTOR MONITORING SUSPENDED
375 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/VBE2 FLT VBE 2 FAULT
376 =21V31 SU200 BI Pole 1 Valve Base Electronics =21V31/VBE2 PWR FLT VBE 2 POWER SUPPLY FAULT
377 =21T01+R1 SU200 BI Pole 1 Valve Base Electronics =21T01+R1/87M1 TRP BANK DIFFERENTIAL PROTECTION OPERATED
378 =21T01+R1 SU200 BI Pole 1 Valve Base Electronics =21T01+R1/87T REF TRP DIFF./REF. PROTECTION OPERATED
379 =21T01+R1 SU200 BI Pole 1 Valve Base Electronics =21T01+R1/24 TRP OVERFLUXING RELAY OPERATED
380 =21T01+R1 SU200 BI Pole 1 Valve Base Electronics =21T01+R1/86A.M1 86B.M1 TRP BANK DIFFERENTIAL PROTECTION OPERATED
381 =21T01+R1 SU200 BI Pole 1 Valve Base Electronics =21T01+R1/86A.87T 86B.87T TRP TRIP RELAY OPERATED
382 =21T01+R1 SU200 BI Pole 1 Valve Base Electronics =21T01+R1/87T REF TRP FIRE PROTECTION SYSTEM FAULT
383 =21T01+R1 SU200 BI Pole 1 Valve Base Electronics =21T01+R1/PWR SUPPLY FLT PANEL SUPPLY DISTURBANCE
Pole 1 DC Station Control Interface =21B11+X1
- =21B02-Q1 SU200 BO Pole 1 DC Station Control Interface =21B02-Q1/CMD OFF DCF1 HV - DISCONNECTOR OFF CMD
- =21B02-Q1 SU200 BO Pole 1 DC Station Control Interface =21B02-Q1/CMD ON DCF1 HV - DISCONNECTOR ON CMD
- =21B02-Q2 SU200 BO Pole 1 DC Station Control Interface =21B02-Q2/CMD OFF DCF1 LV - DISCONNECTOR OFF CMD
- =21B02-Q2 SU200 BO Pole 1 DC Station Control Interface =21B02-Q2/CMD ON DCF1 LV - DISCONNECTOR ON CMD
- =21B02-Q51 SU200 BO Pole 1 DC Station Control Interface =21B02-Q51/CMD OFF DCF1 HV - EARTH SWITCH OFF CMD
- =21B02-Q51 SU200 BO Pole 1 DC Station Control Interface =21B02-Q51/CMD ON DCF1 HV - EARTH SWITCH ON CMD
- =21B02-Q52 SU200 BO Pole 1 DC Station Control Interface =21B02-Q52/CMD OFF DCF1 LV - EARTH SWITCH OFF CMD
- =21B02-Q52 SU200 BO Pole 1 DC Station Control Interface =21B02-Q52/CMD ON DCF1 LV - EARTH SWITCH ON CMD
- =21B02-Q1 SU201 BO Pole 1 DC Station Control Interface =21B02-Q1/CMD RELEASE DCF1 HV - DISCONNECTOR CMD REL
- =21B02-Q2 SU202 BO Pole 1 DC Station Control Interface =21B02-Q2/CMD RELEASE DCF1 LV - DISCONNECTOR CMD REL
- =21B02-Q51 SU203 BO Pole 1 DC Station Control Interface =21B02-Q51/CMD RELEASE DCF1 HV - EARTH SWITCH CMD REL
- =21B02-Q52 SU204 BO Pole 1 DC Station Control Interface =21B02-Q52/CMD RELEASE DCF1 LV - EARTH SWITCH CMD REL
- =21B03-Q1 SU205 BO Pole 1 DC Station Control Interface =21B03-Q1/CMD OFF DCF2 HV - DISCONNECTOR OFF CMD
- =21B03-Q1 SU200 BO Pole 1 DC Station Control Interface =21B03-Q1/CMD ON DCF2 HV - DISCONNECTOR ON CMD
- =21B03-Q2 SU200 BO Pole 1 DC Station Control Interface =21B03-Q2/CMD OFF DCF2 LV - DISCONNECTOR OFF CMD
- =21B03-Q2 SU200 BO Pole 1 DC Station Control Interface =21B03-Q2/CMD ON DCF2 LV - DISCONNECTOR ON CMD
- =21B03-Q51 SU200 BO Pole 1 DC Station Control Interface =21B03-Q51/CMD OFF DCF2 HV - EARTH SWITCH OFF CMD
- =21B03-Q51 SU200 BO Pole 1 DC Station Control Interface =21B03-Q51/CMD ON DCF2 HV - EARTH SWITCH ON CMD
- =21B03-Q52 SU200 BO Pole 1 DC Station Control Interface =21B03-Q52/CMD OFF DCF2 LV - EARTH SWITCH OFF CMD
- =21B03-Q52 SU200 BO Pole 1 DC Station Control Interface =21B03-Q52/CMD ON DCF2 LV - EARTH SWITCH ON CMD
- =21B03-Q93 SU200 BO Pole 1 DC Station Control Interface =21B03-Q93/CMD OFF HSNBS CMD OFF
- =21B03-Q93 SU200 BO Pole 1 DC Station Control Interface =21B03-Q93/CMD ON HSNBS CMD ON
- =21B03-Q93 SU200 BO Pole 1 DC Station Control Interface =21B03-Q93/EN LOCAL CTRL HSNBS LOCAL CTRL ENABLE
- =21B04-Q51 SU200 BO Pole 1 DC Station Control Interface =21B04-Q51/EN LOCAL CTRL =21B04-Q51 LOCAL CTRL ENABLE
- =21B04-Q9 SU200 BO Pole 1 DC Station Control Interface =21B04-Q9/EN LOCAL CTRL =21B04-Q9 HSNBS LOCAL CTRL ENABLE
- =21B03-Q1 SU201 BO Pole 1 DC Station Control Interface =21B03-Q1/CMD RELEASE DCF2 HV - DISCONNECTOR CMD REL
- =21B03-Q2 SU202 BO Pole 1 DC Station Control Interface =21B03-Q2/CMD RELEASE DCF2 LV - DISCONNECTOR CMD REL
- =21B03-Q51 SU203 BO Pole 1 DC Station Control Interface =21B03-Q51/CMD RELEASE DCF2 HV - EARTH SWITCH CMD REL
- =21B03-Q52 SU204 BO Pole 1 DC Station Control Interface =21B03-Q52/CMD RELEASE DCF2 LV - EARTH SWITCH CMD REL
401 =21B02-Q1 SU200 BI Pole 1 DC Station Control Interface =21B02-Q1/OFF DC FILTER 1 HV-ISOLATOR OPEN
402 =21B02-Q1 SU200 BI Pole 1 DC Station Control Interface =21B02-Q1/ON DC FILTER 1 HV-ISOLATOR CLOSED
403 =21B02-Q1 SU200 BI Pole 1 DC Station Control Interface =21B02-Q1/FLT DC FILTER 1 HV-ISOLATOR FAULT
404 =21B02-Q1 SU200 BI Pole 1 DC Station Control Interface =21B02-Q1/LOC CTRL DC FILTER 1 HV-ISOLATOR LOCAL CTRL
405 =21B02-Q2 SU200 BI Pole 1 DC Station Control Interface =21B02-Q2/OFF DC FILTER 1 LV-ISOLATOR OPEN
406 =21B02-Q2 SU200 BI Pole 1 DC Station Control Interface =21B02-Q2/ON DC FILTER 1 LV-ISOLATOR CLOSED
407 =21B02-Q2 SU200 BI Pole 1 DC Station Control Interface =21B02-Q2/FLT DC FILTER 1 LV-ISOLATOR FAULT
408 =21B02-Q2 SU200 BI Pole 1 DC Station Control Interface =21B02-Q2/LOC CTRL DC FILTER 1 LV-ISOLATOR LOCAL CTRL
409 =21B02-Q51 SU200 BI Pole 1 DC Station Control Interface =21B02-Q51/OFF DC FILTER 1 HV-EARTH SWITCH OPEN
410 =21B02-Q51 SU200 BI Pole 1 DC Station Control Interface =21B02-Q51/ON DC FILTER 1 HV-EARTH SWITCH CLOSED
411 =21B02-Q51 SU200 BI Pole 1 DC Station Control Interface =21B02-Q51/FLT DC FILTER 1 HV-EARTH SWITCH FAULT
412 =21B02-Q51 SU200 BI Pole 1 DC Station Control Interface =21B02-Q51/LOC CTRL DC FILTER 1 HV-EARTH SWITCH LOCAL CTRL
413 =21B02-Q52 SU200 BI Pole 1 DC Station Control Interface =21B02-Q52/OFF DC FILTER 1 LV-EARTH SWITCH OPEN
414 =21B02-Q52 SU200 BI Pole 1 DC Station Control Interface =21B02-Q52/ON DC FILTER 1 LV-EARTH SWITCH CLOSED
415 =21B02-Q52 SU200 BI Pole 1 DC Station Control Interface =21B02-Q52/FLT DC FILTER 1 LV-EARTH SWITCH FAULT
416 =21B02-Q52 SU200 BI Pole 1 DC Station Control Interface =21B02-Q52/LOC CTRL DC FILTER 1 LV-EARTH SWITCH LOCAL CTRL
417 =21R04+R1 SU200 BI Pole 1 DC Station Control Interface =21R04+R1/PWR SPLY FLT DCFP SYS 1 POWER SUPPLY FAULT
418 =21R04+R1 SU200 BI Pole 1 DC Station Control Interface =21R04+R1/TESTMODE DCFP SYS 1 TEST MODE
419 =21R04+R1 SU200 BI Pole 1 DC Station Control Interface =21R04+R1-A1/SIMD HW FLT DCFP SYS 1 SIMADYN D HARDWARE FAULT
420 =21R04+R1 SU200 BI Pole 1 DC Station Control Interface =21R04+R1-A1/SIMD FAN FLT DCFP SYS 1 SIMADYN D FAN FAULT
421 =21R04+R1 SU200 BI Pole 1 DC Station Control Interface =21R04+R1-A1/SW FLT DCFP SYS 1 SOFTWARE FAULT
422 =21R04+R1 SU200 BI Pole 1 DC Station Control Interface =21R04+R1-A1/SW WRN DCFP SYS 1 SOFTWARE WARNING
423 =21R04+R2 SU200 BI Pole 1 DC Station Control Interface =21R04+R2/PWR SPLY FLT DCFP SYS 2 POWER SUPPLY FAULT
424 =21R04+R2 SU200 BI Pole 1 DC Station Control Interface =21R04+R2/TESTMODE DCFP SYS 2 TEST MODE
425 =21R04+R2 SU200 BI Pole 1 DC Station Control Interface =21R04+R2-A1/SIMD HW FLT DCFP SYS 2 SIMADYN D HARDWARE FAULT
426 =21R04+R2 SU200 BI Pole 1 DC Station Control Interface =21R04+R2-A1/SIMD FAN FLT DCFP SYS 2 SIMADYN D FAN FAULT
427 =21R04+R2 SU200 BI Pole 1 DC Station Control Interface =21R04+R2-A1/SW FLT DCFP SYS 2 SOFTWARE FAULT
428 =21R04+R2 SU200 BI Pole 1 DC Station Control Interface =21R04+R2-A1/SW WRN DCFP SYS 2 SOFTWARE WARNING
441 =21B03-Q1 SU200 BI Pole 1 DC Station Control Interface =21B03-Q1/OFF DC FILTER 2 HV-ISOLATOR OPEN
442 =21B03-Q1 SU200 BI Pole 1 DC Station Control Interface =21B03-Q1/ON DC FILTER 2 HV-ISOLATOR CLOSED
443 =21B03-Q1 SU200 BI Pole 1 DC Station Control Interface =21B03-Q1/FLT DC FILTER 2 HV-ISOLATOR FAULT
444 =21B03-Q1 SU200 BI Pole 1 DC Station Control Interface =21B03-Q1/LOC CTRL DC FILTER 2 HV-ISOLATOR LOCAL CTRL
445 =21B03-Q2 SU200 BI Pole 1 DC Station Control Interface =21B03-Q2/OFF DC FILTER 2 LV-ISOLATOR OPEN
446 =21B03-Q2 SU200 BI Pole 1 DC Station Control Interface =21B03-Q2/ON DC FILTER 2 LV-ISOLATOR CLOSED
447 =21B03-Q2 SU200 BI Pole 1 DC Station Control Interface =21B03-Q2/FLT DC FILTER 2 LV-ISOLATOR FAULT
448 =21B03-Q2 SU200 BI Pole 1 DC Station Control Interface =21B03-Q2/LOC CTRL DC FILTER 2 LV-ISOLATOR LOCAL CTRL
449 =21B03-Q51 SU200 BI Pole 1 DC Station Control Interface =21B03-Q51/OFF DC FILTER 2 HV-EARTH SWITCH OPEN
450 =21B03-Q51 SU200 BI Pole 1 DC Station Control Interface =21B03-Q51/ON DC FILTER 2 HV-EARTH SWITCH CLOSED
451 =21B03-Q51 SU200 BI Pole 1 DC Station Control Interface =21B03-Q51/FLT DC FILTER 2 HV-EARTH SWITCH FAULT
452 =21B03-Q51 SU200 BI Pole 1 DC Station Control Interface =21B03-Q51/LOC CTRL DC FILTER 2 HV-EARTH SWITCH LOCAL CTRL
453 =21B03-Q52 SU200 BI Pole 1 DC Station Control Interface =21B03-Q52/OFF DC FILTER 2 LV-EARTH SWITCH OPEN
454 =21B03-Q52 SU200 BI Pole 1 DC Station Control Interface =21B03-Q52/ON DC FILTER 2 LV-EARTH SWITCH CLOSED
455 =21B03-Q52 SU200 BI Pole 1 DC Station Control Interface =21B03-Q52/FLT DC FILTER 2 LV-EARTH SWITCH FAULT
456 =21B03-Q52 SU200 BI Pole 1 DC Station Control Interface =21B03-Q52/LOC CTRL DC FILTER 2 LV-EARTH SWITCH LOCAL CTRL
463 =21B11-R5 SU200 BI Pole 1 DC Station Control Interface =21B11-R5/LOSS SF6 LVDC-VOLTAGE DIVIDER LOSS OF SF6
464 =21B11-R5 SU200 BI Pole 1 DC Station Control Interface =21B11-R5/SF6 TRP LVDC-VOLTAGE DIVIDER SF6 TRIP
465 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/OFF HSNBS CIRCUIT BREAKER OPEN
466 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/ON HSNBS CIRCUIT BREAKER CLOSED
467 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/GENERAL LOCK HSNBS CIRCUIT BREAKER GENERAL LOCKOUT
468 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/ON LOCK HSNBS CIRCUIT BREAKER ON_LOCKOUT
469 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/LOSS N2 HSNBS CIRCUIT BREAKER LOSS OF N2
470 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/LOSS SF6 HSNBS CIRCUIT BREAKER LOSS OF SF6
471 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/FLT HYDRAULIC HSNBS CIRCUIT BREAKER HYDRAULICSYS FAULT
472 =21B11-Q93 SU200 BI Pole 1 DC Station Control Interface =21B11-Q93/LOC CTRL HSNBS CIRCUIT BREAKER LOCAL CONTROL
474 =21B11+S1 SU200 BI Pole 1 DC Station Control Interface =21B11+S1/FLT AC SPLY DC-LOCAL CONTROL CUBICLE AC FAULT
475 =21B11+S1 SU200 BI Pole 1 DC Station Control Interface =21B11+S1/FLT DC SPLY DC-LOCAL CONTROL CUBICLE DC FAULT
476 =22B11+X1 SU200 BI Pole 1 DC Station Control Interface =22B11+X1/FLT DC SPLY DC CONTROL INTERFACE: DC POWER FAULT
477 =21B11+S1 SU200 BI Pole 1 DC Station Control Interface =21B11+S1/FENCE LOCKED DC FILTER FENCE LOCKED
478 =21B11+S1 SU200 BI Pole 1 DC Station Control Interface =21B11+S1/FENCE UNLOCKED DC FILTER FENCE UNLOCKED
Pole 1 DC Protection system 1
561 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CSCY TRP TRIP CONV SHORT CIRCUIT STAR WDG
562 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CSCD TRP TRIP CONV SHORT CIRCUIT DELTA WDG
563 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/50 51C 1 TRP TRIP: AC OVERCURRENT PROT, STAGE 1
564 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/50 51C 2 TRP TRIP: AC OVERCURRENT PROT. STAGE 2
565 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/50 51C 3 TRP TRIP: AC OVERCURRENT PROT. STAGE 3
566 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/50 51C 4 TRP TRIP: AC OVERCURRENT PROT. STAGE 4
567 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CBY 1 WRN WARN: BRIDGE DIFF, PROT, WYE STAGE 1
568 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CBY 2 TRP TRIP: BRIDGE DIFF. PROT. WYE STAGE 2
569 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CBD 1 WRN WARN: BRIDGE DIFF. PROT. DELTA STAGE 1
570 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CBD 2 TRP TRIP: BRIDGE DIFF. PROT. DELTA STAGE 2
571 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CG 1 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 1
572 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87CG 2 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 2
573 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87DCM TRP TRIP: DC DIFFERENTIAL PROTECTION
574 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/59ACVW WRN WARN: AC VALVE WINDING SUPERVISION
575 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/37MRTB WRN WARN: MRTB PROTECTION
576 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/37MRS WRN WARN: MRS PROTECTION
591 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87HV TRP TRIP: HIGH VOLTAGE DC BUSBAR PROTECTION
592 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87LV TRP TRIP: NEUTRAL BUSBAR DIFF. PROTECTION
593 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87DCB TRP TRIP: BACK-UP DIFFERENTIAL PROTECTION
594 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/76EL 1 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE1
595 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/60EL 2 TRP TRIP: ELECTRODE CURR. BAL. PROT. STAGE 2
596 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/600ECL TRP TRIP: OPEN CONDUCTOR ELECTR. LINE PROT.
597 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/76SG 1 WRN WARN: ST. GROUND OVERCURR. PROT. STAGE 1
598 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87EB TRP TRIP: ELECTRODE DIFF. PROTECTION MONOPOL
599 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/60EL TRP TRIP: ELECTRODE CURR. BAL. PROT. MONOPOL
600 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/76EL 2 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE2
601 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/59EL TRP TRIP: OPEN ELECTRODE PROTECTION
602 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/82HSNBS TRP TRIP: HSGS PROTECTION
603 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/82HSGS TRP TRIP: HSNBS PROTECTION
604 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/82MRTB TRP TRIP: MRTB PROTECTION
605 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/82MRS TRP TRIP: MRS PROTECTION
606 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/60EL WRN WARN: ELECTRODE CURR. BAL. PROT. BIPOLAR
607 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87EB WRN WARN: ELECTRODE DIFF. PROTECTION BIPOLAR
609 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/SGOP 2 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 2
610 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/SGOP 3 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 3
611 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/WFDPL TRP TRIP: WAVEFRONT PROTECTION
613 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/27 DU DT TRP TRIP: DC LINE UNDERVOLTAGE PROTECTION
614 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/TRP SSR TRIP: SUB SYNCHRONOUS RESONANCE PROT.
626 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/87DCL TRP TRIP: DC LINE DIFFERENTIAL PROTECTION
627 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/81 I U TRP TRIP: AC/DC CONDUCTOR CONTACT PROTECTON
628 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/81 50 1 WRN WARN: 50Hz PROTECTION STAGE 1
629 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/81 50 2 TRP TRIP: 50Hz PROTECTION STAGE 2
630 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/81 100 1 WRN WARN: 100HZ PROTECTION STAGE 1
631 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/81 100 2 TRP TRIP: 100HZ PROTECTION STAGE 2
633 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/59 37DC-1 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 1
634 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/59 37DC-2 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 2
635 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/59 37DC-3 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 3
636 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/27DC TRIP:UNDERVOLTAGE PROTECTION
640 =21R01+R1 SIMADYN D BI Pole 1 DC Protection system 1 =21R01+R1/MEAS FLT MEASUREMENT FAILURE
Pole 1 DC Protection system 2
641 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CSCY TRP TRIP CONV SHORT CIRCUIT STAR WDG
642 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CSCD TRP TRIP CONV SHORT CIRCUIT DELTA WDG
643 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/50 51C 1 TRP TRIP: AC OVERCURRENT PROT, STAGE 1
644 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/50 51C 2 TRP TRIP: AC OVERCURRENT PROT. STAGE 2
645 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/50 51C 3 TRP TRIP: AC OVERCURRENT PROT, STAGE 3
646 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/50 51C 4 TRP TRIP: AC OVERCURRENT PROT. STAGE 4
647 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CBY 1 WRN WARN: BRIDGE DIFF, PROT, WYE STAGE 1
648 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CBY 2 TRP TRIP: BRIDGE DIFF. PROT. WYE STAGE 2
649 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CBD 1 WRN WARN: BRIDGE DIFF. PROT. DELTA STAGE 1
650 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CBD 2 TRP TRIP: BRIDGE DIFF. PROT. DELTA STAGE 2
651 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CG 1 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 1
652 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87CG 2 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 2
653 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87DCM TRP TRIP: DC DIFFERENTIAL PROTECTION
654 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/59ACVW WRN WARN: AC VALVE WINDING SUPERVISION
655 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/37MRTB WRN WARN: MRTB PROTECTION
656 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/37MRS WRN WARN: MRS PROTECTION
671 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87HV TRP TRIP: HIGH VOLTAGE DC BUSBAR PROTECTION
672 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87LV TRP TRIP: NEUTRAL BUSBAR DIFF. PROTECTION
673 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87DCB TRP TRIP: BACK-UP DIFFERENTIAL PROTECTION
674 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/76EL 1 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE1
675 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/60EL 2 TRP TRIP: ELECTRODE CURR. BAL. PROT. STAGE 2
676 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/600ECL TRP TRIP: OPEN CONDUCTOR ELECTR. LINE PROT.
677 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/76SG 1 WRN WARN: ST. GROUND OVERCURR. PROT. STAGE 1
678 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87EB TRP TRIP: ELECTRODE DIFF. PROTECTION MONOPOL
679 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/60EL TRP TRIP: ELECTRODE CURR. BAL. PROT. MONOPOL
680 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/76EL 2 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE2
681 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/59EL TRP TRIP: OPEN ELECTRODE PROTECTION
682 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/82HSNBS TRP TRIP: HSGS PROTECTION
683 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/82HSGS TRP TRIP: HSNBS PROTECTION
684 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/82MRTB TRP TRIP: MRTB PROTECTION
685 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/82MRS TRP TRIP: MRS PROTECTION
686 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/60EL WRN WARN: ELECTRODE CURR. BAL. PROT. BIPOLAR
687 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87EB WRN WARN: ELECTRODE DIFF. PROTECTION BIPOLAR
689 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/SGOP 2 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 2
690 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/SGOP 3 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 3
691 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/WFDPL TRP TRIP: WAVEFRONT PROTECTION
693 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/27 DU DT TRP TRIP: DC LINE UNDERVOLTAGE PROTECTION
694 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/TRP SSR TRIP: SUB SYNCHRONOUS RESONANCE PROT.
706 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/87DCL TRP TRIP: DC LINE DIFFERENTIAL PROTECTION
707 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/81 I U TRP TRIP: AC/DC CONDUCTOR CONTACT PROTECTON
708 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/81 50 1 WRN WARN: 50Hz PROTECTION STAGE 1
709 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/81 50 2 TRP TRIP: 50Hz PROTECTION STAGE 2
710 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/81 100 1 WRN WARN: 100HZ PROTECTION STAGE 1
711 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/81 100 2 TRP TRIP: 100HZ PROTECTION STAGE 2
713 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/59 37DC-1 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 1
714 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/59 37DC-2 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 2
715 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/59 37DC-3 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 3
716 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/27DC TRIP:UNDERVOLTAGE PROTECTION
720 =21R01+R2 SIMADYN D BI Pole 1 DC Protection system 2 =21R01+R2/MEAS FLT MEASUREMENT FAILURE
Pole 1 DC Filter Protection system 1
921 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B02/50 51 OVCU TRP1 TRP: I>DF (51B02)
922 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B02/87DIFF TRP1 TRP: DIDF (87B02)
923 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B02/50 51DIC1 TRP1 TRP: DIC1 (51B02)
924 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B02/60 61 C1UN TRP1 TRP: DC1DF (60/61B02)
926 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B02/IM3FLT WRN1 WRN:IM3 MEASUREMENT FAILURE
937 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B03/50 51 OVCU TRP1 TRP: I>DF (51B03)
938 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B03/87DIFF TRP1 TRP: DIDF (87B03)
939 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B03/50 51DIC1 TRP1 TRP: DIC1 (51B03)
940 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B03/60 61 C1UN TRP1 TRP: DC1DF (60/61B03)
942 =21R04+R1 SIMADYN D BI Pole 1 DC Filter Protection system 1 =21B03/IM3FLT WRN1 WRN:IM3 MEASUREMENT FAILURE
Pole 1 DC Filter Protection system 2
961 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B02/50 51 OVCU TRP2 TRP: I>DF (51B02)
962 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B02/87DIFF TRP2 TRP: DIDF (87B02)
963 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B02/50 51DIC1 TRP2 TRP: DIC1 (51B02)
964 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B02/60 61 C1UN TRP2 TRP: DC1DF (60/61B02)
966 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B02/IM3FLT WRN2 WRN:IM3 MEASUREMENT FAILURE
977 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B03/50 51 OVCU TRP2 TRP: I>DF (51B03)
978 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B03/87DIFF TRP2 TRP: DIDF (87B03)
979 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B03/50 51DIC1 TRP2 TRP: DIC1 (51B03)
980 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B03/60 61 C1UN TRP2 TRP: DC1DF (60/61B03)
982 =21R04+R2 SIMADYN D BI Pole 1 DC Filter Protection system 2 =21B03/IM3FLT WRN2 WRN:IM3 MEASUREMENT FAILURE
Pole 2 Pole Control System
Event No. Device Device Type Input Type Panel Event Code Event Text
Pole 2 Converter Transformer Interface =22T01+X1
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L1 OIL TEMP L1 OIL TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L1 STAR TEMP L1 STAR WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L1 DELTA TEMP L1 DELTA WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L1 LINE TEMP L1 LINE WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L2 OIL TEMP L2 OIL TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L2 STAR TEMP L2 STAR WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L2 DELTA TEMP L2 DELTA WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L2 LINE TEMP L2 LINE WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L3 OIL TEMP L3 OIL TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L3 STAR TEMP L3 STAR WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L3 DELTA TEMP L3 DELTA WINDING TEMPERATURE
- =22T01 SU200 AI Pole 2 Converter Transformer Interface =22T01/L3 LINE TEMP L1 LINE WINDING TEMPERATURE
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L1 CMD RAISE L1 TAP CHANGER RAISE
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L1 CMD LOWER L1 TAP CHANGER LOWER
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L1 CMD COOl ON L1 COOLING ON
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L1 CMD COOl OFF L1 COOLING OFF
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L2 CMD RAISE L2 TAP CHANGER RAISE
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L2 CMD LOWER L2 TAP CHANGER LOWER
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L2 CMD COOl ON L2 COOLING ON
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L2 CMD COOl OFF L2 COOLING OFF
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L3 CMD RAISE L3 TAP CHANGER RAISE
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L3 CMD LOWER L3 TAP CHANGER LOWER
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L3 CMD COOl ON L3 COOLING ON
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =22T01/L3 CMD COOl OFF L3 COOLING OFF
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =20C10-Q9 EN INTERLOCK =20C10-Q9 ISO INTERLOCK
- =22T01 SU200 BO Pole 2 Converter Transformer Interface =20C10-Q8 EN INTERLOCK =20C10-Q8 ES INTERLOCK
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q1/OFF =20C10.A-Q1 ISOLATOR OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q1/ON =20C10.A-Q1 ISOLATOR CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q0/OFF =20C10.A-Q0 CB OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q0/ON =20C10.A-Q0 CB CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q6/OFF =20C10.A-Q6 ISOLATOR OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q6/ON =20C10.A-Q6 ISOLATOR CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.B-Q61/OFF =20C10.B-Q61 ISOLATOR OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.B-Q61/ON =20C10.B-Q61 ISOLATOR CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.B-Q0/OFF =20C10.B-Q0 CB OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.B-Q0/ON =20C10.B-Q0 CB CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.B-Q62/OFF =20C10.B-Q62 ISOLATOR OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.B-Q62/ON =20C10.B-Q62 ISOLATOR CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.C-Q6/OFF =20C10.C-Q6 ISOLATOR OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.C-Q6/ON =20C10.C-Q6 ISOLATOR CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.C-Q0/OFF =20C10.C-Q0 CB OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.C-Q0/ON =20C10.C-Q0 CB CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.C-Q2/OFF =20C10.C-Q2 ISOLATOR OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.C-Q2/ON =20C10.C-Q2 ISOLATOR CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q53/OFF =20C10.A-Q53 EARTH SWITCH OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q53/ON =20C10.A-Q53 EARTH SWITCH CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q9/OFF =20C10.A-Q9 ISOLATOR OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q9/ON =20C10.A-Q9 ISOLATOR CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10.A-Q8/OFF =20C10.A-Q8 EARTH SWITCH OPEN
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =20C10A-Q8/ON =20C10.A-Q8 EARTH SWITCH CLOSED
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/X1 SU200 ALARM RESET
6106 =22B01+X1 SU200 BI Pole 2 Converter Transformer Interface =22B01+X1/PWR SPLY FLT VALVE HALL POWER SUPPLY FAULT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 TAP POS BCD_1 TAP CHANGER L1 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 TAP POS BCD_2 TAP CHANGER L1 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 TAP POS BCD_4 TAP CHANGER L1 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 TAP POS BCD_8 TAP CHANGER L1 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 TAP POS BCD_10 TAP CHANGER L1 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 TAP POS BCD_20 TAP CHANGER L1 POSITION BIT
6127 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OLTC RUN TAP CHANGER L1 RUNNING
6128 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OLTC FLT TAP CHANGER L1 FAULT
6129 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OLTC LOC CTRL TAP CHANGER L1 LOCAL CONTROL
6130 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OLTC OILFILT FLT TAP CHANGER L1 OIL FILTER FAULT
6131 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OLTC OFF POS TAP CHANGER L1 OFF POSITION
6132 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 PWR SPLY FLT L1 AUXILIARY POWER SUPPLY FAULT
6133 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 FLT AC SPLY L1 AC SUPPLY FAULT
6134 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 CTRL SPLY FLT L1 CONTROL VOLTAGE FAULT
6135 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 FLT INT AC L1 INTERNAL 3PHASE FAULT
6136 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01+X1/SU1 ALR RES L1 ALARM-RESET
6137 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 COOL ON TRAFO COOLING SYSTEM L1 ON
6138 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 COOL OFF TRAFO COOLING SYSTEM L1 OFF
6139 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 BUCHHOLZ TRP L1 BUCHHOLZ RELAY MAIN TANK TRIP
6140 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 PRES MAIN TRP L1 PRESSURE RELIEF DEVICE MAIN TANK TRIP
6141 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OIL TEMP TRP L1 OIL TEMPERATURE TRIP
6142 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 WIND TEMP TRP L1 WINDING TEMPERATURE TRIP
6143 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 PROT DIV TRP L1 PROTECTION RELAY DIVERTER SWITCH TRIP
6144 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 PRES DIV TRP L1 PRESS. RELIEF DEV. DIVERTER SWITCH TR
6145 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 COOL FLT L1 COOLER GROUP FAULT
6147 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 HYDRAN GAS HI HYDRAN GAS MONITORING "GAS HI"
6148 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 HYDRAN GAS HI HI HYDRAN GAS MONITORING "GAS HI-HI"
6149 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 HYDRAN SYST FLT HYDRAN GAS MONITORING SYSTEM FAULT
6150 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 SF6 TRP L1 STAR SF6 TRIP
6151 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 SF6 ALR L1 STAR SF6 ALARM
6152 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 WIND TEMP ALR L1 WINDING TEMP. ALARM
6153 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 BUCHHOLZ ALR L1 BUCHHOLZ RELAY MAIN TANK ALARM
6154 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OIL TEMP ALR L1 OIL TEMPERATURE MAIN TANK ALARM
6156 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OIL LOW L1 LOW OIL LEVEL ALARM
6157 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L1 OIL HIGH L1 HIGH OIL LEVEL ALARM
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 TAP POS BCD_1 TAP CHANGER L2 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 TAP POS BCD_2 TAP CHANGER L2 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 TAP POS BCD_4 TAP CHANGER L2 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 TAP POS BCD_8 TAP CHANGER L2 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 TAP POS BCD_10 TAP CHANGER L2 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 TAP POS BCD_20 TAP CHANGER L2 POSITION BIT
6167 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OLTC RUN TAP CHANGER L2 RUNNING
6168 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OLTC FLT TAP CHANGER L2 FAULT
6169 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OLTC LOC CTRL TAP CHANGER L2 LOCAL CONTROL
6170 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OLTC OILFILT FLT TAP CHANGER L2 OIL FILTER FLT
6171 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OLTC OFF POS TAP CHANGER L2 OFF POSITION
6172 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 PWR SPLY FLT L2 AUXILIARY POWER SUPPLY FAULT
6173 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 FLT AC SPLY L2 AC SUPPLY FAULT
6174 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 CTRL SPLY FLT L2 CONTROL VOLTAGE FAULT
6175 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 FLT INT AC L2 INTERNAL 3PHASE FAULT
6176 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01+X1/SU2 ALR RES L2 ALARM-RESET
6177 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 COOL ON TRAFO COOLING SYSTEM L2 ON
6178 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 COOL OFF TRAFO COOLING SYSTEM L2 OFF
6179 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 BUCHHOLZ TRP L2 BUCHHOLZ RELAY FOR MAIN TANK TRIP
6180 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 PRES MAIN TRP L2 PRESSURE RELIEF DEVICE MAIN TANK TRIP
6181 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OIL TEMP TRP L2 OIL TEMPERATURE TRIP
6182 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 WIND TEMP TRP L2 WINDING TEMPERATURE TRIP
6183 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 PROT DIV TRP L2 PROTECTION RELAY DIVERTER SWITCH TRIP
6184 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 PRES DIV TRP L2 PRESS. RELIEF DEV. DIVERTER SWITCH TR
6185 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 COOL FLT L2 COOLER GROUP FAULT
6187 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 HYDRAN GAS HI HYDRAN GAS MONITORING "GAS HI"
6188 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 HYDRAN GAS HI HI HYDRAN GAS MONITORING "GAS HI-HI"
6189 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 HYDRAN SYST FLT HYDRAN GAS MONITORING SYSTEM FAULT
6190 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 SF6 TRP L2 STAR SF6 TRIP
6191 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 SF6 ALR L2 STAR SF6 ALARM
6192 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 WIND TEMP ALR L2 WINDING TEMP. ALARM
6193 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 BUCHHOLZ ALR L2 BUCHHOLZ RELAY FOR MAIN TANK ALARM
6194 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OIL TEMP ALR L2 OIL TEMPERATURE IN MAIN TANK ALARM
6196 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OIL LOW L2 LOW OIL LEVEL ALARM
6197 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L2 OIL HIGH L2 HIGH OIL LEVEL ALARM
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 TAP POS BCD_1 TAP CHANGER L3 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 TAP POS BCD_2 TAP CHANGER L3 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 TAP POS BCD_4 TAP CHANGER L3 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 TAP POS BCD_8 TAP CHANGER L3 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 TAP POS BCD_10 TAP CHANGER L3 POSITION BIT
- =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 TAP POS BCD_20 TAP CHANGER L3 POSITION BIT
6207 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OLTC RUN TAP CHANGER L3 RUNNING
6208 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OLTC FLT TAP CHANGER L3 FAULT
6209 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OLTC LOC CTRL TAP CHANGER L3 LOCAL CONTROL
6210 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OLTC OILFILT FLT TAP CHANGER L3 OIL FILTER FLT
6211 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OLTC OFF POS TAP CHANGER L3 OFF POSITION
6212 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 PWR SPLY FLT L3 AUXILIARY POWER SUPPLY FAULT
6213 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 FLT AC SPLY L3 AC SUPPLY FAULT
6214 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 CTRL SPLY FLT L3 CONTROL VOLTAGE FAULT
6215 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 FLT INT AC L3 INTERNAL 3PHASE FAULT
6216 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01+X1/SU3 ALR RES L3 ALARM-RESET
6217 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 COOL ON TRAFO COOLING SYSTEM L3 ON
6218 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 COOL OFF TRAFO COOLING SYSTEM L3 OFF
6219 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 BUCHHOLZ TRP L3 BUCHHOLZ RELAY FOR MAIN TANK TRIP
6220 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 PRES MAIN TRP L3 PRESSURE RELIEF DEVICE MAIN TANK TR.
6221 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OIL TEMP TRP L3 OIL TEMPERATURE TRIP
6222 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 WIND TEMP TRP L3 WINDING TEMPERATURE TRIP
6223 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 PROT DIV TRP L3 PROTECTION RELAY DIVERTER SWITCH TRIP
6224 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 PRES DIV TRP L3 PRESS, RELIEF DEV, DIVERTER SWITCH TR
6225 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 COOL FLT L3 COOLER GROUP FAULT
6227 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 HYDRAN GAS HI HYDRAN GAS MONITORING "GAS HI"
6228 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 HYDRAN GAS HI HI HYDRAN GAS MONITORING "GAS HI-HI"
6229 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 HYDRAN SYST FLT HYDRAN GAS MONITORING SYSTEM FAULT
6230 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 SF6 TRP L3 STAR SF6 TRIP
6231 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 SF6 ALR L3 STAR SF6 ALARM
6232 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 WIND TEMP ALR L3 WINDING TEMP. ALARM
6233 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 BUCHHOLZ ALR L3 BUCHHOLZ RELAY FOR MAIN TANK ALARM
6234 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OIL TEMP ALR L3 OIL TEMPERATURE IN MAIN TANK ALARM
6236 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OIL LOW L3 LOW OIL LEVEL ALARM
6237 =22T01 SU200 BI Pole 2 Converter Transformer Interface =22T01/L3 OIL HIGH L3 HIGH OIL LEVEL ALARM
Pole 2 Valve cooling system control
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/VC INLET TEMP VC INLET TEMPERATURE
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/VC OUTLET TEMP VC OUTLET TEMPERATURE
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/VC MAIN COND. VC MAIN CONDUCTIVITY
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/VC ION 1 COND. VC ION EXHANGER 1 CONDUCTIVITY
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/VC ION 2 COND. VC ION EXHANGER 2 CONDUCTIVITY
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/VC EXP. TANK LEVEL VC EXPANSION TANK LEVEL
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/VH TEMPERATURE VH TEMPERATURE
- =22U61 SU200 AI Pole 2 Valve cooling system control =22U61/AMBIENT TEMPERATURE AMBIENT TEMPERATURE
- =22U61 SU200 BO Pole 2 Valve cooling system control =22U61/VALVE ENRGISED VALVE ENERGISED
- =21U61 SU200 BO Pole 2 Valve cooling system control =22U61/REMOTE OFF VH VENTLN REMOTE OFF
- =21U61 SU200 BO Pole 2 Valve cooling system control =22U61/REMOTE ON VH VENTLN REMOTE ON
6241 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC OFF VALVE COOLING SYSTEM OFF
6242 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC ON VALVE COOLING SYSTEM ON
6243 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC SYS ALR SYSTEM ALARM
6244 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC TOWER FLT COOLING TOWER FAULT
6245 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC PUMP1 ON PUMP 1 ON
6246 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC PUMP2 ON PUMP 2 ON
6247 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC PUMP1 FLT PUMP 1 FAULT
6248 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC PUMP2 FLT PUMP 2 FAULT
6249 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC EXP TNK TRP EXPANSION TANK LOW TRIP
6250 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC INLET TEMP ALR INLET TEMPERATURE HIGH ALARM
6251 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC INLET TEMP TRP INLET TEMPERATURE VERY HIGH TRIP
6252 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC MAIN COND ALR MAIN CONDUCTIVITY HIGH ALARM
6253 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC MAIN COND TRP MAIN CONDUCTIVITY HIGH TRIP
6254 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC ION COND ALR IONEXCHANGE CONDUCTIVITY HIGH ALARM
6255 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC WATER FLOW ALR WATER FLOW ALARM
6256 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC WATER FLOW TRP WATER FLOW TRIP
6257 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC WATER LEAKAGE WATER LEAKAGE
6258 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC STOR TNK ALR STORAGE TANK LOW ALARM
6259 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC SPRAY ALR SPRAY WATER STORAGE TANK LOW ALARM
6260 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC SPRAY PMP FLT SPRAY PUMP FAILURE
6261 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC WATER TREAT FLT WATER TREATMENT FAILURE
6262 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC AC FLT AC FAILURE
6263 =22U61 SU200 BI Pole 2 Valve cooling system control =22U61/VC DC FLT DC FAILURE
6265 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV OFF VALVE HALL VENTILATION OFF
6266 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV ON VALVE HALL VENTILATION ON
6267 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV FAN 1 ON VALVE HALL VENTILATION FAN 1 ON
6268 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV FAN 2 ON VALVE HALL VENTILATION FAN 2 ON
6269 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV FAN 1 FLT VALVE HALL VENTILATION FAN 1 FAILURE
6270 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV FAN 2 FLT VALVE HALL VENTILATION FAN 2 FAILURE
6271 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV FILTER ALR VALVE HALL VENTILATION FILTER GLOGGED
6272 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV ROOM TEMP ALR VALVE HALL TEMPERATURE HIGH
6273 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV DAMP NOT CLOSED VALVE HALL VENTILATION DAMPER NOT CLOSED
6274 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV DAMP NOT OPENED VALVE HALL VENTILATION DAMPER NOT OPENED
6275 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV HEAT FLT VALVE HALL VENTILATION HEATER FAILURE
6276 =22U71 SU200 BI Pole 2 Valve cooling system control =22U71/VHV GEN ALR VALVE HALL VENTILATION GENERAL ALARM
Pole 2 Valve Hall Interface =22B01+X1
- =22B01-Q51 SU200 AI Pole 2 Valve Hall Interface =22B01/AMB_TEMP AMBIENT TEMPERATURE
- =22B01-Q51 SU200 BO Pole 2 Valve Hall Interface =22B01-Q51/CMD OFF TRANSF (STAR) EARTH SWITCH OPEN CMD
- =22B01-Q51 SU200 BO Pole 2 Valve Hall Interface =22B01-Q51/CMD ON TRANSF (STAR) EARTH SWITCH CLOSE CMD
- =22B01-Q51 SU200 BO Pole 2 Valve Hall Interface =22B01-Q51/CMD RELEASE TRANSF (STAR) EARTH SWITCH LOCAL CTRL REL
- =22B01-Q52 SU200 BO Pole 2 Valve Hall Interface =22B01-Q52/CMD OFF TRANSF (DELTA) EARTH SWITCH OPEN CMD
- =22B01-Q52 SU200 BO Pole 2 Valve Hall Interface =22B01-Q52/CMD ON TRANSF (DELTA) EARTH SWITCH CLOSE CMD
- =22B01-Q52 SU200 BO Pole 2 Valve Hall Interface =22B01-Q52/CMD RELEASE TRANSF (DELTA) EARTH SWITCH LOCAL CTRL REL
- =22B01-Q55 SU200 BO Pole 2 Valve Hall Interface =22B01-Q55/CMD OFF LV EARTH SWITCH OPEN CMD
- =22B01-Q55 SU200 BO Pole 2 Valve Hall Interface =22B01-Q55/CMD ON LV EARTH SWITCH CLOSE CMD
- =22B01-Q55 SU200 BO Pole 2 Valve Hall Interface =22B01-Q55/CMD RELEASE LV EARTH SWITCH LOCAL CTRL REL
- =22B01-L SU200 BO Pole 2 Valve Hall Interface =21B04-L/KEY RELEASE SMR KEY RELEASE +VE
- =22B01-L SU200 BO Pole 2 Valve Hall Interface =21B04-L/KEY RELEASE SMR KEY RELEASE -VE
- =22B01-Q54 SU200 BO Pole 2 Valve Hall Interface =22B01-Q54/CMD OFF HV EARTH SWITCH OPEN CMD
- =22B01-Q54 SU200 BO Pole 2 Valve Hall Interface =22B01-Q54/CMD ON HV EARTH SWITCH CLOSE CMD
- =22B01-Q54 SU200 BO Pole 2 Valve Hall Interface =22B01-Q54/CMD RELEASE HV EARTH SWITCH LOCAL CTRL REL
- =22B01 SU200 BO Pole 2 Valve Hall Interface =22B01/CMD DOOR RELEASE VH DOOR RELEASE
- =22B01 SU200 BO Pole 2 Valve Hall Interface =22B01/CMD DOOR LOCK ENABLE VH DOOR LOCK ENABLE
- =22B04 SU200 BO Pole 2 Valve Hall Interface =22B04+UT1/CMD SMR COOLING OFF SMR COOLING OFF
- =22B04 SU200 BO Pole 2 Valve Hall Interface =22B04+UT1/CMD SMR COOLING ON SMR COOLING ON
6321 =22B01-Q51 SU200 BI Pole 2 Valve Hall Interface =22B01-Q51/OFF TRANSF (STAR) EARTH SWITCH OPEN
6322 =22B01-Q51 SU200 BI Pole 2 Valve Hall Interface =22B01-Q51/ON TRANSF (STAR) EARTH SWITCH CLOSED
6323 =22B01-Q51 SU200 BI Pole 2 Valve Hall Interface =22B01-Q51/FLT TRANSF (STAR) EARTH SWITCH FAULT
6324 =22B01-Q51 SU200 BI Pole 2 Valve Hall Interface =22B01-Q51/LOC CTRL TRANSF (STAR) EARTH SWITCH LOCAL CONTROL
6325 =22B01-Q52 SU200 BI Pole 2 Valve Hall Interface =22B01-Q52/OFF TRANSF (DELTA) EARTH SWITCH OPEN
6326 =22B01-Q52 SU200 BI Pole 2 Valve Hall Interface =22B01-Q52/ON TRANSF (DELTA) EARTH SWITCH CLOSED
6327 =22B01-Q52 SU200 BI Pole 2 Valve Hall Interface =22B01-Q52/FLT TRANSF (DELTA) EARTH SWITCH FAULT
6328 =22B01-Q52 SU200 BI Pole 2 Valve Hall Interface =22B01-Q52/LOC CTRL TRANSF (DELTA) EARTH SWITCH LOCAL CTRL
6329 =22B01-Q55 SU200 BI Pole 2 Valve Hall Interface =22B01-Q55/OFF LV EARTH SWITCH OPEN
6330 =22B01-Q55 SU200 BI Pole 2 Valve Hall Interface =22B01-Q55/ON LV EARTH SWITCH CLOSED
6331 =22B01-Q55 SU200 BI Pole 2 Valve Hall Interface =22B01-Q55/FLT LV EARTH SWITCH FAULT
6332 =22B01-Q55 SU200 BI Pole 2 Valve Hall Interface =22B01-Q55/LOC CTRL LV EARTH SWITCH LOCAL CONTROL
6333 =22B01-Q54 SU200 BI Pole 2 Valve Hall Interface =22B01-Q54/OFF HV EARTH SWITCH OPEN
6334 =22B01-Q54 SU200 BI Pole 2 Valve Hall Interface =22B01-Q54/ON HV EARTH SWITCH CLOSED
6335 =22B01-Q54 SU200 BI Pole 2 Valve Hall Interface =22B01-Q54/FLT HV EARTH SWITCH FAULT
6336 =22B01-Q54 SU200 BI Pole 2 Valve Hall Interface =22B01-Q54/LOC CTRL HV EARTH SWITCH LOCAL CONTROL
6337 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B01/DOOR CLOSE VH MAIN DOOR CLOSED
6338 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B01/DOOR OPEN VH MAIN DOOR OPEN
6339 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B01/DOOR LOCK VH MAIN DOOR LOCKED
6340 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B01/DOOR LOCK REQ VH MAIN DOOR LOCK ENABLED
6341 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B04+UT1/COOL OFF SMR COOLING OFF
6342 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B04+UT1/COOL ON SMR COOLING ON
6343 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B04+UT1/POWER SUPPLY FAULT SMR COOLING POWER SUPPLY FAULT
6344 =22B01 SU200 BI Pole 2 Valve Hall Interface =22B04+UT1/COOL LOCAL CTRL SMR COOLING LOCAL CTRL
6345 =22B01-Z1 SU200 BI Pole 2 Valve Hall Interface =22B01-Z1/SF6 TRP DC BUSHING SF6 TRIP
6346 =22B01-Z1 SU200 BI Pole 2 Valve Hall Interface =22B01-Z1/SF6 ALR DC BUSHING SF6 ALARM
6353 =22T01 SU200 BI Pole 2 Valve Hall Interface =22T01/PWR SPLY FLT TRANSF. INTERFACE POWER SUPPLY FAULT
6354 =22B04-L SU200 BI Pole 2 Valve Hall Interface =22B04-L/FENCE_LOCKED SMOOTHING REACTOR AREA FENCE LOCKED
6355 =22B04-L SU200 BI Pole 2 Valve Hall Interface =22B04-L/FENCE_UNLOCKED SMOOTHING REACTOR AREA FENCE UNLOCKED
Pole 2 Valve Base Electronics
6361 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/TRIG PLS FLT TRIGGER PULSE FAULT
6362 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/NO THYR RED NO THYRISTOR REDUNDANCY
6363 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/PROT FIRE EX MAXIMUM NUMBER OF PROT. FIRING EXCEEDED
6365 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/PRINTER FLT PRINTER FAULT
6366 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/VALVECHECK NOK VALVE CHECK NOT O.K.
6367 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/VBE1 FLT VBE 1 FAULT
6368 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/VBE1 PWR FLT VBE 1 POWER SUPPLY FAULT
6369 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/MIN CHKBCK NOK MIN. NO. OF CHECK BACK SIGNALS NOT AVAIL
6370 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/THYR MON SUSP THYRISTOR MONITORING SUSPENDED
6375 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/VBE2 FLT VBE 2 FAULT
6376 =22V31 SU200 BI Pole 2 Valve Base Electronics =22V31/VBE2 PWR FLT VBE 2 POWER SUPPLY FAULT
6377 =22T01+R1 SU200 BI Pole 2 Valve Base Electronics =22T01+R1/87M1 TRP BANK DIFFERENTIAL PROTECTION OPERATED
6378 =22T01+R1 SU200 BI Pole 2 Valve Base Electronics =22T01+R1/87T REF TRP DIFF./REF. PROTECTION OPERATED
6379 =22T01+R1 SU200 BI Pole 2 Valve Base Electronics =22T01+R1/24 TRP OVERFLUXING RELAY OPERATED
6380 =22T01+R1 SU200 BI Pole 2 Valve Base Electronics =22T01+R1/86A.M1 86B.M1 TRP BANK DIFFERENTIAL PROTECTION OPERATED
6381 =22T01+R1 SU200 BI Pole 2 Valve Base Electronics =22T01+R1/86A.87T 86B.87T TRP TRIP RELAY OPERATED
6382 =22T01+R1 SU200 BI Pole 2 Valve Base Electronics =22T01+R1/87T REF TRP FIRE PROTECTION SYSTEM FAULT
6383 =22T01+R1 SU200 BI Pole 2 Valve Base Electronics =22T01+R1/PWR SUPPLY FLT PANEL SUPPLY DISTURBANCE
Pole 2 DC Station Control Interface =22B11+X1
- =22B02-Q1 SU200 BO Pole 2 DC Station Control Interface =22B02-Q1/CMD OFF DCF1 HV - DISCONNECTOR OFF CMD
- =22B02-Q1 SU200 BO Pole 2 DC Station Control Interface =22B02-Q1/CMD ON DCF1 HV - DISCONNECTOR ON CMD
- =22B02-Q2 SU200 BO Pole 2 DC Station Control Interface =22B02-Q2/CMD OFF DCF1 LV - DISCONNECTOR OFF CMD
- =22B02-Q2 SU200 BO Pole 2 DC Station Control Interface =22B02-Q2/CMD ON DCF1 LV - DISCONNECTOR ON CMD
- =22B02-Q51 SU200 BO Pole 2 DC Station Control Interface =22B02-Q51/CMD OFF DCF1 HV - EARTH SWITCH OFF CMD
- =22B02-Q51 SU200 BO Pole 2 DC Station Control Interface =22B02-Q51/CMD ON DCF1 HV - EARTH SWITCH ON CMD
- =22B02-Q52 SU200 BO Pole 2 DC Station Control Interface =22B02-Q52/CMD OFF DCF1 LV - EARTH SWITCH OFF CMD
- =22B02-Q52 SU200 BO Pole 2 DC Station Control Interface =22B02-Q52/CMD ON DCF1 LV - EARTH SWITCH ON CMD
- =22B02-Q1 SU201 BO Pole 2 DC Station Control Interface =22B02-Q1/CMD RELEASE DCF1 HV - DISCONNECTOR CMD REL
- =22B02-Q2 SU202 BO Pole 2 DC Station Control Interface =22B02-Q2/CMD RELEASE DCF1 LV - DISCONNECTOR CMD REL
- =22B02-Q51 SU203 BO Pole 2 DC Station Control Interface =22B02-Q51/CMD RELEASE DCF1 HV - EARTH SWITCH CMD REL
- =22B02-Q52 SU204 BO Pole 2 DC Station Control Interface =22B02-Q52/CMD RELEASE DCF1 LV - EARTH SWITCH CMD REL
- =22B03-Q1 SU205 BO Pole 2 DC Station Control Interface =22B03-Q1/CMD OFF DCF2 HV - DISCONNECTOR OFF CMD
- =22B03-Q1 SU200 BO Pole 2 DC Station Control Interface =22B03-Q1/CMD ON DCF2 HV - DISCONNECTOR ON CMD
- =22B03-Q2 SU200 BO Pole 2 DC Station Control Interface =22B03-Q2/CMD OFF DCF2 LV - DISCONNECTOR OFF CMD
- =22B03-Q2 SU200 BO Pole 2 DC Station Control Interface =22B03-Q2/CMD ON DCF2 LV - DISCONNECTOR ON CMD
- =22B03-Q51 SU200 BO Pole 2 DC Station Control Interface =22B03-Q51/CMD OFF DCF2 HV - EARTH SWITCH OFF CMD
- =22B03-Q51 SU200 BO Pole 2 DC Station Control Interface =22B03-Q51/CMD ON DCF2 HV - EARTH SWITCH ON CMD
- =22B03-Q52 SU200 BO Pole 2 DC Station Control Interface =22B03-Q52/CMD OFF DCF2 LV - EARTH SWITCH OFF CMD
- =22B03-Q52 SU200 BO Pole 2 DC Station Control Interface =22B03-Q52/CMD ON DCF2 LV - EARTH SWITCH ON CMD
- =22B03-Q93 SU200 BO Pole 2 DC Station Control Interface =22B03-Q93/CMD OFF HSNBS CMD OFF
- =22B03-Q93 SU200 BO Pole 2 DC Station Control Interface =22B03-Q93/CMD ON HSNBS CMD ON
- =22B03-Q93 SU200 BO Pole 2 DC Station Control Interface =22B03-Q93/EN LOCAL CTRL HSNBS LOCAL CTRL ENABLE
- =22B04-Q51 SU200 BO Pole 2 DC Station Control Interface =22B04-Q51/EN LOCAL CTRL =21B04-Q51 LOCAL CTRL ENABLE
- =22B04-Q9 SU200 BO Pole 2 DC Station Control Interface =22B04-Q9/EN LOCAL CTRL =21B04-Q9 HSNBS LOCAL CTRL ENABLE
- =22B03-Q1 SU201 BO Pole 2 DC Station Control Interface =22B03-Q1/CMD RELEASE DCF2 HV - DISCONNECTOR CMD REL
- =22B03-Q2 SU202 BO Pole 2 DC Station Control Interface =22B03-Q2/CMD RELEASE DCF2 LV - DISCONNECTOR CMD REL
- =22B03-Q51 SU203 BO Pole 2 DC Station Control Interface =22B03-Q51/CMD RELEASE DCF2 HV - EARTH SWITCH CMD REL
- =22B03-Q52 SU204 BO Pole 2 DC Station Control Interface =22B03-Q52/CMD RELEASE DCF2 LV - EARTH SWITCH CMD REL
6401 =22B02-Q1 SU200 BI Pole 2 DC Station Control Interface =22B02-Q1/OFF DC FILTER 1 HV-ISOLATOR OPEN
6402 =22B02-Q1 SU200 BI Pole 2 DC Station Control Interface =22B02-Q1/ON DC FILTER 1 HV-ISOLATOR CLOSED
6403 =22B02-Q1 SU200 BI Pole 2 DC Station Control Interface =22B02-Q1/FLT DC FILTER 1 HV-ISOLATOR FAULT
6404 =22B02-Q1 SU200 BI Pole 2 DC Station Control Interface =22B02-Q1/LOC CTRL DC FILTER 1 HV-ISOLATOR LOCAL CTRL
6405 =22B02-Q2 SU200 BI Pole 2 DC Station Control Interface =22B02-Q2/OFF DC FILTER 1 LV-ISOLATOR OPEN
6406 =22B02-Q2 SU200 BI Pole 2 DC Station Control Interface =22B02-Q2/ON DC FILTER 1 LV-ISOLATOR CLOSED
6407 =22B02-Q2 SU200 BI Pole 2 DC Station Control Interface =22B02-Q2/FLT DC FILTER 1 LV-ISOLATOR FAULT
6408 =22B02-Q2 SU200 BI Pole 2 DC Station Control Interface =22B02-Q2/LOC CTRL DC FILTER 1 LV-ISOLATOR LOCAL CTRL
6409 =22B02-Q51 SU200 BI Pole 2 DC Station Control Interface =22B02-Q51/OFF DC FILTER 1 HV-EARTH SWITCH OPEN
6410 =22B02-Q51 SU200 BI Pole 2 DC Station Control Interface =22B02-Q51/ON DC FILTER 1 HVDC-EARTH SWITCH CLOSED
6411 =22B02-Q51 SU200 BI Pole 2 DC Station Control Interface =22B02-Q51/FLT DC FILTER 1 HV-EARTH SWITCH FAULT
6412 =22B02-Q51 SU200 BI Pole 2 DC Station Control Interface =22B02-Q51/LOC CTRL DC FILTER 1 HV-EARTH SWITCH LOCAL CTRL
6413 =22B02-Q52 SU200 BI Pole 2 DC Station Control Interface =22B02-Q52/OFF DC FILTER 1 LV-EARTH SWITCH OPEN
6414 =22B02-Q52 SU200 BI Pole 2 DC Station Control Interface =22B02-Q52/ON DC FILTER 1 LV-EARTH SWITCH CLOSED
6415 =22B02-Q52 SU200 BI Pole 2 DC Station Control Interface =22B02-Q52/FLT DC FILTER 1 LV-EARTH SWITCH FAULT
6416 =22B02-Q52 SU200 BI Pole 2 DC Station Control Interface =22B02-Q52/LOC CTRL DC FILTER 1 LV-EARTH SWITCH LOCAL CTRL
6417 =22R04+R1 SU200 BI Pole 2 DC Station Control Interface =22R04+R1/PWR SPLY FLT DCFP SYS 1 POWER SUPPLY FAULT
6418 =22R04+R1 SU200 BI Pole 2 DC Station Control Interface =22R04+R1/TESTMODE DCFP SYS 1 TEST MODE
6419 =22R04+R1 SU200 BI Pole 2 DC Station Control Interface =22R04+R1-A1/SIMD HW FLT DCFP SYS 1 SIMADYN D HARDWARE FAULT
6420 =22R04+R1 SU200 BI Pole 2 DC Station Control Interface =22R04+R1-A1/SIMD FAN FLT DCFP SYS 1 SIMADYN D FAN FAULT
6421 =22R04+R1 SU200 BI Pole 2 DC Station Control Interface =22R04+R1-A1/SW FLT DCFP SYS 1 SOFTWARE FAULT
6422 =22R04+R1 SU200 BI Pole 2 DC Station Control Interface =22R04+R1-A1/SW WRN DCFP SYS 1 SOFTWARE WARNING
6423 =22R04+R2 SU200 BI Pole 2 DC Station Control Interface =22R04+R2/PWR SPLY FLT DCFP SYS 2 POWER SUPPLY FAULT
6424 =22R04+R2 SU200 BI Pole 2 DC Station Control Interface =22R04+R2/TESTMODE DCFP SYS 2 TEST MODE
6425 =22R04+R2 SU200 BI Pole 2 DC Station Control Interface =22R04+R2-A1/SIMD HW FLT DCFP SYS 2 SIMADYN D HARDWARE FAULT
6426 =22R04+R2 SU200 BI Pole 2 DC Station Control Interface =22R04+R2-A1/SIMD FAN FLT DCFP SYS 2 SIMADYN D FAN FAULT
6427 =22R04+R2 SU200 BI Pole 2 DC Station Control Interface =22R04+R2-A1/SW FLT DCFP SYS 2 SOFTWARE FAULT
6428 =22R04+R2 SU200 BI Pole 2 DC Station Control Interface =22R04+R2-A1/SW WRN DCFP SYS 2 SOFTWARE WARNING
6441 =22B03-Q1 SU200 BI Pole 2 DC Station Control Interface =22B03-Q1/OFF DC FILTER 2 HV-ISOLATOR OPEN
6442 =22B03-Q1 SU200 BI Pole 2 DC Station Control Interface =22B03-Q1/ON DC FILTER 2 HV-ISOLATOR CLOSED
6443 =22B03-Q1 SU200 BI Pole 2 DC Station Control Interface =22B03-Q1/FLT DC FILTER 2 HV-ISOLATOR FAULT
6444 =22B03-Q1 SU200 BI Pole 2 DC Station Control Interface =22B03-Q1/LOC CTRL DC FILTER 2 HV-ISOLATOR LOCAL CTRL
6445 =22B03-Q2 SU200 BI Pole 2 DC Station Control Interface =22B03-Q2/OFF DC FILTER 2 LV-ISOLATOR OPEN
6446 =22B03-Q2 SU200 BI Pole 2 DC Station Control Interface =22B03-Q2/ON DC FILTER 2 LV-ISOLATOR CLOSED
6447 =22B03-Q2 SU200 BI Pole 2 DC Station Control Interface =22B03-Q2/FLT DC FILTER 2 LVDC-ISOLATOR
6448 =22B03-Q2 SU200 BI Pole 2 DC Station Control Interface =22B03-Q2/LOC CTRL DC FILTER 2 LV-ISOLATOR LOCAL CTRL
6449 =22B03-Q51 SU200 BI Pole 2 DC Station Control Interface =22B03-Q51/OFF DC FILTER 2 HV-EARTH SWITCH OPEN
6450 =22B03-Q51 SU200 BI Pole 2 DC Station Control Interface =22B03-Q51/ON DC FILTER 2 HV-EARTH SWITCH CLOSED
6451 =22B03-Q51 SU200 BI Pole 2 DC Station Control Interface =22B03-Q51/FLT DC FILTER 2 HV-EARTH SWITCH FAULT
6452 =22B03-Q51 SU200 BI Pole 2 DC Station Control Interface =22B03-Q51/LOC CTRL DC FILTER 2 HV-EARTH SWITCH LOCAL CTRL
6453 =22B03-Q52 SU200 BI Pole 2 DC Station Control Interface =22B03-Q52/OFF DC FILTER 2 LV-EARTH SWITCH OPEN
6454 =22B03-Q52 SU200 BI Pole 2 DC Station Control Interface =22B03-Q52/ON DC FILTER 2 LV-EARTH SWITCH CLOSED
6455 =22B03-Q52 SU200 BI Pole 2 DC Station Control Interface =22B03-Q52/FLT DC FILTER 2 LV-EARTH SWITCH FAULT
6456 =22B03-Q52 SU200 BI Pole 2 DC Station Control Interface =22B03-Q52/LOC CTRL DC FILTER 2 LV-EARTH SWITCH LOCAL CTRL
6463 =22B11-R5 SU200 BI Pole 2 DC Station Control Interface =22B11-R5/LOSS SF6 LVDC-VOLTAGE DIVIDER LOSS OF SF6
6464 =22B11-R5 SU200 BI Pole 2 DC Station Control Interface =22B11-R5/SF6 TRP LVDC-VOLTAGE DIVIDER SF6 TRIP
6465 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/OFF HSNBS CIRCUIT BREAKER OPEN
6466 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/ON HSNBS CIRCUIT BREAKER CLOSED
6467 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/GENERAL LOCK HSNBS CIRCUIT BREAKER GENERAL LOCKOUT
6468 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/ON LOCK HSNBS CIRCUIT BREAKER ON_LOCKOUT
6469 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/LOSS N2 HSNBS CIRCUIT BREAKER LOSS OF N2
6470 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/LOSS SF6 HSNBS CIRCUIT BREAKER LOSS OF SF6
6471 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/FLT HYDRAULIC HSNBS CIRCUIT BREAKER HYDRAULICSYS FAULT
6472 =22B11-Q93 SU200 BI Pole 2 DC Station Control Interface =22B11-Q93/LOC CTRL HSNBS CIRCUIT BREAKER LOCAL CONTROL
6474 =22B11+S1 SU200 BI Pole 2 DC Station Control Interface =22B11+S1/FLT AC SPLY DC-LOCAL CONTROL CUBICLE
6475 =22B11+S1 SU200 BI Pole 2 DC Station Control Interface =22B11+S1/FLT DC SPLY DC-LOCAL CONTROL CUBICLE
6476 =21B11+X1 SU200 BI Pole 2 DC Station Control Interface =21B11+X1/FLT DC SPLY DC CONTROL INTERFACE CUBICLE
6477 =22B11+S1 SU200 BI Pole 2 DC Station Control Interface =22B11+S1/FENCE LOCKED DC FILTER FENCE LOCKED
6478 =22B11+S1 SU200 BI Pole 2 DC Station Control Interface =22B11+S1/FENCE UNLOCKED DC FILTER FENCE UNLOCKED
Pole 2 DC Protection system 1
6561 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CSCY TRP TRIP CONV SHORT CIRCUIT STAR WDG
6562 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CSCD TRP TRIP CONV SHORT CIRCUIT DELTA WDG
6563 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/50 51C 1 TRP TRIP: AC OVERCURRENT PROT, STAGE 1
6564 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/50 51C 2 TRP TRIP: AC OVERCURRENT PROT. STAGE 2
6565 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/50 51C 3 TRP TRIP: AC OVERCURRENT PROT, STAGE 3
6566 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/50 51C 4 TRP TRIP: AC OVERCURRENT PROT. STAGE 4
6567 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CBY 1 WRN WARN: BRIDGE DIFF, PROT, WYE STAGE 1
6568 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CBY 2 TRP TRIP: BRIDGE DIFF. PROT. WYE STAGE 2
6569 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CBD 1 WRN WARN: BRIDGE DIFF. PROT. DELTA STAGE 1
6570 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CBD 2 TRP TRIP: BRIDGE DIFF. PROT. DELTA STAGE 2
6571 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CG 1 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 1
6572 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87CG 2 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 2
6573 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87DCM TRP TRIP: DC DIFFERENTIAL PROTECTION
6574 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/59ACVW WRN WARN: AC VALVE WINDING SUPERVISION
6575 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/37MRTB WRN WARN: MRTB PROTECTION
6576 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/37MRS WRN WARN: MRS PROTECTION
6591 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87HV TRP TRIP: HIGH VOLTAGE DC BUSBAR PROTECTION
6592 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87LV TRP TRIP: NEUTRAL BUSBAR DIFF. PROTECTION
6593 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87DCB TRP TRIP: BACK-UP DIFFERENTIAL PROTECTION
6594 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/76EL 1 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE1
6595 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/60EL 2 TRP TRIP: ELECTRODE CURR. BAL. PROT. STAGE 2
6596 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/600ECL TRP TRIP: OPEN CONDUCTOR ELECTR. LINE PROT.
6597 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/76SG 1 WRN WARN: ST. GROUND OVERCURR. PROT. STAGE 1
6598 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87EB TRP TRIP: ELECTRODE DIFF. PROTECTION MONOPOL
6599 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/60EL TRP TRIP: ELECTRODE CURR. BAL. PROT. MONOPOL
6600 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/76EL 2 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE2
6601 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/59EL TRP TRIP: OPEN ELECTRODE PROTECTION
6602 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/82HSNBS TRP TRIP: HSGS PROTECTION
6603 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/82HSGS TRP TRIP: HSNBS PROTECTION
6604 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/82MRTB TRP TRIP: MRTB PROTECTION
6605 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/82MRS TRP TRIP: MRS PROTECTION
6606 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/60EL WRN WARN: ELECTRODE CURR. BAL. PROT. BIPOLAR
6607 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87EB WRN WARN: ELECTRODE DIFF. PROTECTION BIPOLAR
6609 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/SGOP 2 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 2
6610 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/SGOP 3 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 3
6611 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/WFDPL TRP TRIP: WAVEFRONT PROTECTION
6613 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/27 DU DT TRP TRIP: DC LINE UNDERVOLTAGE PROTECTION
6614 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/TRP SSR TRIP: SUB SYNCHRONOUS RESONANCE PROT.
6626 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/87DCL TRP TRIP: DC LINE DIFFERENTIAL PROTECTION
6627 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/81 I U TRP TRIP: AC/DC CONDUCTOR CONTACT PROTECTON
6628 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/81 50 1 WRN WARN: 50Hz PROTECTION STAGE 1
6629 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/81 50 2 TRP TRIP: 50Hz PROTECTION STAGE 2
6630 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/81 100 1 WRN WARN: 100HZ PROTECTION STAGE 1
6631 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/81 100 2 TRP TRIP: 100HZ PROTECTION STAGE 2
6633 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/59 37DC-1 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 1
6634 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/59 37DC-2 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 2
6635 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/59 37DC-3 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 3
6636 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/27DC TRIP:UNDERVOLTAGE PROTECTION
6640 =22R01+R1 SIMADYN D BI Pole 2 DC Protection system 1 =22R01+R1/MEAS FLT MEASUREMENT FAILURE
Pole 2 DC Protection system 2
6641 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CSCY TRP TRIP CONV SHORT CIRCUIT STAR WDG
6642 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CSCD TRP TRIP CONV SHORT CIRCUIT DELTA WDG
6643 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/50 51C 1 TRP TRIP: AC OVERCURRENT PROT, STAGE 1
6644 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/50 51C 2 TRP TRIP: AC OVERCURRENT PROT. STAGE 2
6645 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/50 51C 3 TRP TRIP: AC OVERCURRENT PROT, STAGE 3
6646 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/50 51C 4 TRP TRIP: AC OVERCURRENT PROT. STAGE 4
6647 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CBY 1 WRN WARN: BRIDGE DIFF, PROT, WYE STAGE 1
6648 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CBY 2 TRP TRIP: BRIDGE DIFF. PROT. WYE STAGE 2
6649 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CBD 1 WRN WARN: BRIDGE DIFF. PROT. DELTA STAGE 1
6650 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CBD 2 TRP TRIP: BRIDGE DIFF. PROT. DELTA STAGE 2
6651 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CG 1 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 1
6652 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87CG 2 TRP TRIP: GROUP DIFFERENTIAL PROT. STAGE 2
6653 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87DCM TRP TRIP: DC DIFFERENTIAL PROTECTION
6654 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/59ACVW WRN WARN: AC VALVE WINDING SUPERVISION
6655 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/37MRTB WRN WARN: MRTB PROTECTION
6656 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/37MRS WRN WARN: MRS PROTECTION
6671 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87HV TRP TRIP: HIGH VOLTAGE DC BUSBAR PROTECTION
6672 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87LV TRP TRIP: NEUTRAL BUSBAR DIFF. PROTECTION
6673 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87DCB TRP TRIP: BACK-UP DIFFERENTIAL PROTECTION
6674 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/76EL 1 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE1
6675 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/60EL 2 TRP TRIP: ELECTRODE CURR. BAL. PROT. STAGE 2
6676 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/600ECL TRP TRIP: OPEN CONDUCTOR ELECTR. LINE PROT.
6677 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/76SG 1 WRN WARN: ST. GROUND OVERCURR. PROT. STAGE 1
6678 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87EB TRP TRIP: ELECTRODE DIFF. PROTECTION MONOPOL
6679 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/60EL TRP TRIP: ELECTRODE CURR. BAL. PROT. MONOPOL
6680 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/76EL 2 TRP TRIP: ELECTR. OVERCURRENT PROT. EL-LINE2
6681 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/59EL TRP TRIP: OPEN ELECTRODE PROTECTION
6682 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/82HSNBS TRP TRIP: HSGS PROTECTION
6683 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/82HSGS TRP TRIP: HSNBS PROTECTION
6684 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/82MRTB TRP TRIP: MRTB PROTECTION
6685 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/82MRS TRP TRIP: MRS PROTECTION
6686 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/60EL WRN WARN: ELECTRODE CURR. BAL. PROT. BIPOLAR
6687 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87EB WRN WARN: ELECTRODE DIFF. PROTECTION BIPOLAR
6689 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/SGOP 2 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 2
6690 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/SGOP 3 TRP TRIP: ST. GROUND OVERCURR. PROT. STAGE 3
6691 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/WFDPL TRP TRIP: WAVEFRONT PROTECTION
6693 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/27 DU DT TRP TRIP: DC LINE UNDERVOLTAGE PROTECTION
6694 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/TRP SSR TRIP: SUB SYNCHRONOUS RESONANCE PROT.
6706 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/87DCL TRP TRIP: DC LINE DIFFERENTIAL PROTECTION
6707 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/81 I U TRP TRIP: AC/DC CONDUCTOR CONTACT PROTECTON
6708 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/81 50 1 WRN WARN: 50Hz PROTECTION STAGE 1
6709 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/81 50 2 TRP TRIP: 50Hz PROTECTION STAGE 2
6710 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/81 100 1 WRN WARN: 100HZ PROTECTION STAGE 1
6711 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/81 100 2 TRP TRIP: 100HZ PROTECTION STAGE 2
6713 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/59 37DC-1 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 1
6714 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/59 37DC-2 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 2
6715 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/59 37DC-3 TRP TRIP: DC OVERVOLTAGE PROTECTION STAGE 3
6716 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/27DC TRIP:UNDERVOLTAGE PROTECTION
6720 =22R01+R2 SIMADYN D BI Pole 2 DC Protection system 2 =22R01+R2/MEAS FLT MEASUREMENT FAILURE
Pole 2 DC Filter Protection system 1
6921 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B02/50 51 OVCU TRP1 TRP: I>DF (51B02)
6922 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B02/87DIFF TRP1 TRP: DIDF (87B02)
6923 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B02/50 51DIC1 TRP1 TRP: DIC1 (51B02)
6924 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B02/60 61 C1UN TRP1 TRP: DC1DF (60/61B02)
6926 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B02/IM3FLT WRN1 WRN:IM3 MEASUREMENT FAILURE
6937 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B03/50 51 OVCU TRP1 TRP: I>DF (51B03)
6938 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B03/87DIFF TRP1 TRP: DIDF (87B03)
6939 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B03/50 51DIC1 TRP1 TRP: DIC1 (51B03)
6940 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B03/60 61 C1UN TRP1 TRP: DC1DF (60/61B03)
6942 =22R04+R1 SIMADYN D BI Pole 2 DC Filter Protection system 1 =22B03/IM3FLT WRN1 WRN:IM3 MEASUREMENT FAILURE
Pole 2 DC Filter Protection system 2
6961 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B02/50 51 OVCU TRP2 TRP: I>DF (51B02)
6962 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B02/87DIFF TRP2 TRP: DIDF (87B02)
6963 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B02/50 51DIC1 TRP2 TRP: DIC1 (51B02)
6964 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B02/60 61 C1UN TRP2 TRP: DC1DF (60/61B02)
6966 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B02/IM3FLT WRN2 WRN:IM3 MEASUREMENT FAILURE
6977 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B03/50 51 OVCU TRP2 TRP: I>DF (51B03)
6978 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B03/87DIFF TRP2 TRP: DIDF (87B03)
6979 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B03/50 51DIC1 TRP2 TRP: DIC1 (51B03)
6980 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B03/60 61 C1UN TRP2 TRP: DC1DF (60/61B03)
6982 =22R04+R2 SIMADYN D BI Pole 2 DC Filter Protection system 2 =22B03/IM3FLT WRN2 WRN:IM3 MEASUREMENT FAILURE
DC Station Control
Event No. Device Device Type Input Type Panel Event Code Event Text
AC Station control Interface =20CF10+X1
- =20CF11-T3 SU200 AI =20CF10+X1 =20CF11-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF11-T15 SU200 AI =20CF10+X1 =20CF11-T15/UL1 AC FILTER BANK 1 VOLTAGE UL1-N
- =20CF11-T15 SU200 AI =20CF10+X1 =20CF11-T15/UL2 AC FILTER BANK 1 VOLTAGE UL2-N
- =20CF12-T3 SU200 AI =20CF10+X1 =20CF12-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF11-T15 SU200 AI =20CF10+X1 =20CF11-T15/UL2 AC FILTER BANK 1 VOLTAGE UL2-N
- =20CF11-T15 SU200 AI =20CF10+X1 =20CF11-T15/UL3 AC FILTER BANK 1 VOLTAGE UL3-N
- =20CF13-T3 SU200 AI =20CF10+X1 =20CF13-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF11-T15 SU200 AI =20CF10+X1 =20CF11-T15/UL3 AC FILTER BANK 1 VOLTAGE UL3-N
- =20CF11-T15 SU200 AI =20CF10+X1 =20CF11-T15/UL1 AC FILTER BANK 1 VOLTAGE UL1-N
- =20CF14-T3 SU200 AI =20CF10+X1 =20CF14-T3/Q SHUNT C SUB BANK REACTIVE POWER
- =20CF11-Q0 SU200 BO =20CF10+X1 =20CF11-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF11-Q0 SU200 BO =20CF10+X1 =20CF11-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF11-Q1 SU200 BO =20CF10+X1 =20CF11-Q1/CMD OFF ISOLATOR OPEN
- =20CF11-Q1 SU200 BO =20CF10+X1 =20CF11-Q1/CMD ON ISOLATOR CLOSE
- =20CF12-Q0 SU200 BO =20CF10+X1 =20CF12-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF12-Q0 SU200 BO =20CF10+X1 =20CF12-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF12-Q1 SU200 BO =20CF10+X1 =20CF12-Q1/CMD OFF ISOLATOR OPEN
- =20CF12-Q1 SU200 BO =20CF10+X1 =20CF12-Q1/CMD ON ISOLATOR CLOSE
- =20CF13-Q0 SU200 BO =20CF10+X1 =20CF13-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF13-Q0 SU200 BO =20CF10+X1 =20CF13-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF13-Q1 SU200 BO =20CF10+X1 =20CF13-Q1/CMD OFF ISOLATOR OPEN
- =20CF13-Q1 SU200 BO =20CF10+X1 =20CF13-Q1/CMD ON ISOLATOR CLOSE
- =20CF14-Q0 SU200 BO =20CF10+X1 =20CF14-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF14-Q0 SU200 BO =20CF10+X1 =20CF14-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF14-Q1 SU200 BO =20CF10+X1 =20CF14-Q1/CMD OFF ISOLATOR OPEN
- =20CF14-Q1 SU200 BO =20CF10+X1 =20CF14-Q1/CMD ON ISOLATOR CLOSE
12081 =20CF11-Q1 SU200 BI =20CF10+X1 =20CF11-Q1/OFF ISOLATOR OPEN
12082 =20CF11-Q1 SU200 BI =20CF10+X1 =20CF11-Q1/ON ISOLATOR CLOSED
12083 =20CF11-Q1 SU200 BI =20CF10+X1 =20CF11-Q1/FLT ISOLATOR FAILURE
12084 =20CF11-Q51 SU200 BI =20CF10+X1 =20CF11-Q51/OFF EARTH SWITCH OPEN
12085 =20CF11-Q51 SU200 BI =20CF10+X1 =20CF11-Q51/ON EARTH SWITCH CLOSED
12086 =20CF11-Q51 SU200 BI =20CF10+X1 =20CF11-Q51/FLT EARTH SWITCH FAILURE
12087 =20CF11-Q52 SU200 BI =20CF10+X1 =20CF11-Q52/OFF EARTH SWITCH OPEN
12088 =20CF11-Q52 SU200 BI =20CF10+X1 =20CF11-Q52/ON EARTH SWITCH CLOSED
12089 =20CF11-Q52 SU200 BI =20CF10+X1 =20CF11-Q52/FLT EARTH SWITCH FAILURE
12090 =20CF11-Q17 SU200 BI =20CF10+X1 =20CF11-Q17/OFF EARTH SWITCH OPEN
12091 =20CF11-Q17 SU200 BI =20CF10+X1 =20CF11-Q17/ON EARTH SWITCH CLOSED
12092 =20CF11-Q17 SU200 BI =20CF10+X1 =20CF11-Q17/FLT EARTH SWITCH FAILURE
12093 =20R11+R1 SU200 BI =20CF10+X1 =20CF11-T1/1 50ACF TRP TRIP OVERCURRENT PROTECTION
12094 =20R11+R1 SU200 BI =20CF10+X1 =20CF11-T1/1 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12095 =20R11+R1 SU200 BI =20CF10+X1 =20CF11-T1/1 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12096 =20R11+R1 SU200 BI =20CF10+X1 =20CF11-T41/1 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12097 =20R11+R1 SU200 BI =20CF10+X1 =20CF11-T42/1 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12098 =20R11+R1 SU200 BI =20CF10+X1 =20CF11-T2/1 50ACFL TRP TRIP OVERCUR. PROT. F. LOW VOLT. REAC.
12099 =20R11+R1 SU200 BI =20CF10+X1 =20CF11-T3/1 50ACFR TRP TRIP OVERCUR PROT F. LOW VOLT RESISTOR
12100 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/87ACFB 11 TRP AC FILTER 1 BANK DIFF. PROTECTION
12101 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/50BF 11 TRP AC FILTER 1 BANK BF. PROTECTION
12102 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/86A 86B 11 TRP AC FILTER 1 BANK TRIP RELAY
12103 =20R11+R2.C SU200 BI =20CF10+X1 =20R11+R2.C/20CF11 TC FLT AC FILTER 1 BANK TRIP CIRCUIT UNHEALTHY
12104 =20B10+X1 SU200 BI =20CF10+X1 =20B10+X1/FLT DC SPLY DC CONTROL INTERFACE CUBICLE
12105 =20CF10+S2 SU200 BI =20CF10+X1 =20CF10+S2/VT MCB TRP AC-LOCAL CONTROL: VOLT. TRANS. MCB TRIP
12106 =20C00+U1 SU200 BI =20CF10+X1 =20CF11-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12107 =20CF10+S1 SU200 BI =20CF10+X1 =20CF10+S1/FLT AC SPLY LOCAL INTERFACE CUBICLE
12108 =20CF10+S1 SU200 BI =20CF10+X1 =20CF10+S1/FLT DC SPLY LOCAL INTERFACE CUBICLE
12109 =20CF10+S1 SU200 BI =20CF10+X1 =20CF11/LOC CTRL ES DS LOCAL CONTROL
12110 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/OFF CIRCUIT BREAKER OPEN
12111 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/ON CIRCUIT BREAKER CLOSED
12113 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12114 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12115 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12116 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12117 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12118 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12119 =20CF11-Q0 SU200 BI =20CF10+X1 =20CF11-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12121 =20CF12-Q1 SU200 BI =20CF10+X1 =20CF12-Q1/OFF ISOLATOR OPEN
12122 =20CF12-Q1 SU200 BI =20CF10+X1 =20CF12-Q1/ON ISOLATOR CLOSED
12123 =20CF12-Q1 SU200 BI =20CF10+X1 =20CF12-Q1/FLT ISOLATOR FAILURE
12124 =20CF12-Q51 SU200 BI =20CF10+X1 =20CF12-Q51/OFF EARTH SWITCH OPEN
12125 =20CF12-Q51 SU200 BI =20CF10+X1 =20CF12-Q51/ON EARTH SWITCH CLOSED
12126 =20CF12-Q51 SU200 BI =20CF10+X1 =20CF12-Q51/FLT EARTH SWITCH FAILURE
12127 =20CF12-Q52 SU200 BI =20CF10+X1 =20CF12-Q52/OFF EARTH SWITCH OPEN
12128 =20CF12-Q52 SU200 BI =20CF10+X1 =20CF12-Q52/ON EARTH SWITCH CLOSED
12129 =20CF12-Q52 SU200 BI =20CF10+X1 =20CF12-Q52/FLT EARTH SWITCH FAILURE
12130 =20R11+R1 SU200 BI =20CF10+X1 =20CF12-T1/II 50ACF TRP TRIP OVERCURRENT PROTECTION
12131 =20R11+R1 SU200 BI =20CF10+X1 =20CF12-T1/II 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12132 =20R11+R1 SU200 BI =20CF10+X1 =20CF12-T1/II 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12133 =20R11+R1 SU200 BI =20CF10+X1 =20CF12-T41/II 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12134 =20R11+R1 SU200 BI =20CF10+X1 =20CF12-T42/II 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12135 =20R11+R1 SU200 BI =20CF10+X1 =20CF12-T2/II 50ACFL TRP TRIP OVERCUR. PROT. F. LOW VOLT. REAC.
12136 =20R11+R1 SU200 BI =20CF10+X1 =20CF12-T3/II 50ACFR TRP TRIP OVERCUR PROT F. LOW VOLT RESISTOR
12137 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/87ACFB 12 TRP AC FILTER 1 BANK DIFF. PROTECTION
12138 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/50BF 12 TRP AC FILTER 1 BANK BF. PROTECTION
12139 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/86A 86B 12 TRP AC FILTER 1 BANK TRIP RELAY
12140 =20R11+R2.C SU200 BI =20CF10+X1 =20R11+R2.C/20CF12 TC FLT AC FILTER 1 BANK TRIP CIRCUIT UNHEALTHY
12141 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/87BBM2 TRP AC FILTER 1 BANK PROTECTION
12142 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/27 59 TRP AC FILTER 1 BANK OVER/UNDERVOLT. PROTEC
12143 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/86A 86B M2 TRP AC FILTER 1 BANK DIFF, PROTECTION TRIP R
12144 =20R11+R2.A SU200 BI =20CF10+X1 =20R11+R2.A/MCB TRP AC FILTER 1 BANK PROT. CUBICLE MCB TRIP
12146 =20R11+R2 SU200 BI =20CF10+X1 =20R11+R2/RELAY 11 12 FLT AC FILTER 1 BANK PROT. RELAY FAULT
12147 =20R11+R2 SU200 BI =20CF10+X1 =20R11+R2/RELAY 13 14 FLT AC FILTER 1 BANK PROT. RELAY FAULT
12148 =20C00+U1 SU200 BI =20CF10+X1 =20CF12-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12149 =20CF10+S1 SU200 BI =20CF10+X1 =20CF12/LOC CTRL ES DS LOCAL CONTROL
12150 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/OFF CIRCUIT BREAKER OPEN
12151 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/ON CIRCUIT BREAKER CLOSED
12153 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12154 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12155 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12156 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12157 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12158 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12159 =20CF12-Q0 SU200 BI =20CF10+X1 =20CF12-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12161 =20CF13-Q1 SU200 BI =20CF10+X1 =20CF13-Q1/OFF ISOLATOR OPEN
12162 =20CF13-Q1 SU200 BI =20CF10+X1 =20CF13-Q1/ON ISOLATOR CLOSED
12163 =20CF13-Q1 SU200 BI =20CF10+X1 =20CF13-Q1/FLT ISOLATOR FAILURE
12164 =20CF13-Q51 SU200 BI =20CF10+X1 =20CF13-Q51/OFF EARTH SWITCH OPEN
12165 =20CF13-Q51 SU200 BI =20CF10+X1 =20CF13-Q51/ON EARTH SWITCH CLOSED
12166 =20CF13-Q51 SU200 BI =20CF10+X1 =20CF13-Q51/FLT EARTH SWITCH FAILURE
12167 =20CF13-Q52 SU200 BI =20CF10+X1 =20CF13-Q52/OFF EARTH SWITCH OPEN
12168 =20CF13-Q52 SU200 BI =20CF10+X1 =20CF13-Q52/ON EARTH SWITCH CLOSED
12169 =20CF13-Q52 SU200 BI =20CF10+X1 =20CF13-Q52/FLT EARTH SWITCH FAILURE
12170 =20R11+R1 SU200 BI =20CF10+X1 =20CF13-T1/III 50ACF TRP TRIP OVERCURRENT PROTECTION
12171 =20R11+R1 SU200 BI =20CF10+X1 =20CF13-T1/III 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12172 =20R11+R1 SU200 BI =20CF10+X1 =20CF13-T1/III 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12173 =20R11+R1 SU200 BI =20CF10+X1 =20CF13-T41/III 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12174 =20R11+R1 SU200 BI =20CF10+X1 =20CF13-T42/III 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12175 =20R11+R1 SU200 BI =20CF10+X1 =20CF13-T2/III 50ACFL TRP TRIP OVERCUR. PROT. F. LOW VOLT. REAC.
12176 =20R11+R1 SU200 BI =20CF10+X1 =20CF13-T3/III 50ACFR TRP TRIP OVERCUR PROT F. LOW VOLT RESISTOR
12177 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1/PWR SPLY FLT AC FILTER 1 SUBBANK MAIN PROTECTION
12178 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1/TESTMODE AC FILTER 1 SUBBANK MAIN PROTECTION
12179 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-A1/SIMD HW FLT AC FILTER 1 SUBBANK MAIN PROTECTION
12180 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-A1/SIMD FAN FLT AC FILTER 1 SUBBANK MAIN PROTECTION
12181 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-A1/SW WRN AC FILTER 1 SUBBANK MAIN PROTECTION
12182 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-A1/SW FLT AC FILTER 1 SUBBANK MAIN PROTECTION
12183 =20R11+R2.B SU200 BI =20CF10+X1 =20R11+R2.B/87ACFB 13 TRP AC FILTER 1 BANK DIFF, PROTECTION
12184 =20R11+R2.B SU200 BI =20CF10+X1 =20R11+R2.B/50BF 13 TRP AC FILTER 1 BANK BF. PROTECTION
12185 =20R11+R2.B SU200 BI =20CF10+X1 =20R11+R2.B/86A 86B 13 TRP AC FILTER 1 BANK TRIP RELAY
12186 =20R11+R2.C SU200 BI =20CF10+X1 =20R11+R2.C/20CF13 TC FLT AC FILTER 1 BANK TRIP CIRCUIT UNHEALTHY
12187 =20R11+R2.B SU200 BI =20CF10+X1 =20R11+R2.B/MCB TRP AC FILTER 1 BANK PROT. CUBICLE MCB TRIP
12188 =20C00+U1 SU200 BI =20CF10+X1 =20CF13-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12189 =20CF10+S1 SU200 BI =20CF10+X1 =20CF13/LOC CTRL ES DS LOCAL CONTROL
12190 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/OFF CIRCUIT BREAKER OPEN
12191 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/ON CIRCUIT BREAKER CLOSED
12193 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12194 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12195 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12196 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12197 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12198 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12199 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12196 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12197 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12198 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12199 =20CF13-Q0 SU200 BI =20CF10+X1 =20CF13-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12201 =20CF14-Q1 SU200 BI =20CF10+X1 =20CF14-Q1/OFF ISOLATOR OPEN
12202 =20CF14-Q1 SU200 BI =20CF10+X1 =20CF14-Q1/ON ISOLATOR CLOSED
12203 =20CF14-Q1 SU200 BI =20CF10+X1 =20CF14-Q1/FLT ISOLATOR FAILURE
12204 =20CF14-Q51 SU200 BI =20CF10+X1 =20CF14-Q51/OFF EARTH SWITCH OPEN
12205 =20CF14-Q51 SU200 BI =20CF10+X1 =20CF14-Q51/ON EARTH SWITCH CLOSED
12206 =20CF14-Q51 SU200 BI =20CF10+X1 =20CF14-Q51/FLT EARTH SWITCH FAILURE
12207 =20CF14-Q52 SU200 BI =20CF10+X1 =20CF14-Q52/OFF EARTH SWITCH OPEN
12208 =20CF14-Q52 SU200 BI =20CF10+X1 =20CF14-Q52/ON EARTH SWITCH CLOSED
12209 =20CF14-Q52 SU200 BI =20CF10+X1 =20CF14-Q52/FLT EARTH SWITCH FAILURE
12210 =20R11+R1 SU200 BI =20CF10+X1 =20CF14-T1/I 50CB TRP TRIP OVERCURRENT PROTECTION
12211 =20R11+R1 SU200 BI =20CF10+X1 =20CF14-T1/I 51CB TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12212 =20R11+R1 SU200 BI =20CF10+X1 =20CF14-T1/I 49 59CB TRP TRIP CAPACITOR OVERLOAD PROTECTION
12213 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F11/CPR97 FLT INTERNAL FAULT CPR97-F11
12214 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F12/CPR97 FLT INTERNAL FAULT CPR97-F12
12215 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F13/CPR97 FLT INTERNAL FAULT CPR97-F13
12216 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F21/CPR97 FLT INTERNAL FAULT CPR97-F21
12217 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F22/CPR97 FLT INTERNAL FAULT CPR97-F22
12218 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F23/CPR97 FLT INTERNAL FAULT CPR97-F23
12219 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F31/CPR97 FLT INTERNAL FAULT CPR97-F31
12220 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F32/CPR97 FLT INTERNAL FAULT CPR97-F32
12221 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F33/CPR97 FLT INTERNAL FAULT CPR97-F33
12222 =20R11+R1 SU200 BI =20CF10+X1 =20R11+R1-F41/CPR97 FLT INTERNAL FAULT CPR97-F41
12223 =20R11+R2.B SU200 BI =20CF10+X1 =20R11+R2.B/87ACB 14 TRP AC FILTER 1 BANK DIFF. PROTECTION
12224 =20R11+R2.B SU200 BI =20CF10+X1 =20R11+R2.B/50BF 14 TRP AC FILTER 1 BANK BF. PROTECTION
12225 =20R11+R2.B SU200 BI =20CF10+X1 =20R11+R2.B/86A 86B 14 TRP AC FILTER 1 BANK TRIP RELAY
12226 =20R11+R2.C SU200 BI =20CF10+X1 =20R11+R2.C/20CF14 TC FLT AC FILTER 1 BANK TRIP CIRCUIT UNHEALTHY
12227 =20R11+R2.C SU200 BI =20CF10+X1 =20R11+R2.C/MCB TRP AC FILTER 1 BANK PROT. CUBICLE MCB TRIP
12228 =20C00+U1 SU200 BI =20CF10+X1 =20CF14-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12229 =20CF10+S1 SU200 BI =20CF10+X1 =20CF14/LOC CTRL ES DS LOCAL CONTROL
12230 =20CF14-Q0 SU200 BI =20CF10+X1 =20CF14-Q0/OFF CIRCUIT BREAKER OPEN
12231 =20CF14-Q0 SU200 BI =20CF10+X1 =20CF14-Q0/ON CIRCUIT BREAKER CLOSED
12233 =20CF14-QO SU200 BI =20CF10+X1 =20CF14-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12234 =20CF14-Q0 SU200 BI =20CF10+X1 =20CF14-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12235 =20CF14-QO SU200 BI =20CF10+X1 =20CF14-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12236 =20CF14-Q0 SU200 BI =20CF10+X1 =20CF14-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12237 =20CF14-QO SU200 BI =20CF10+X1 =20CF14-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12238 =20CF14-Q0 SU200 BI =20CF10+X1 =20CF14-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12239 =20CF14-Q0 SU200 BI =20CF10+X1 =20CF14-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
AC Station control Interface =20CF20+X1
- =20CF21-T3 SU200 AI =20CF20+X1 =20CF21-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF21-T15 SU200 AI =20CF20+X1 =20CF21-T15/UL1 AC FILTER BANK 2 VOLTAGE UL1-N
- =20CF21-T15 SU200 AI =20CF20+X1 =20CF21-T15/UL2 AC FILTER BANK 2 VOLTAGE UL2-N
- =20CF22-T3 SU200 AI =20CF20+X1 =20CF22-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF22-T15 SU200 AI =20CF20+X1 =20CF22-T15/UL2 AC FILTER BANK 2 VOLTAGE UL2-N
- =20CF21-T15 SU200 AI =20CF20+X1 =20CF21-T15/UL3 AC FILTER BANK 2 VOLTAGE UL3-N
- =20CF23-T3 SU200 AI =20CF20+X1 =20CF23-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF21-T15 SU200 AI =20CF20+X1 =20CF21-T15/UL3 AC FILTER BANK 2 VOLTAGE UL3-N
- =20CF21-T15 SU200 AI =20CF20+X1 =20CF21-T15/UL1 AC FILTER BANK 2 VOLTAGE UL1-N
- =20CF21-Q0 SU200 BO =20CF20+X1 =20CF21-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF21-Q0 SU200 BO =20CF20+X1 =20CF21-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF21-Q1 SU200 BO =20CF20+X1 =20CF21-Q1/CMD OFF ISOLATOR OPEN
- =20CF21-Q1 SU200 BO =20CF20+X1 =20CF21-Q1/CMD ON ISOLATOR CLOSE
- =20CF22-Q0 SU200 BO =20CF20+X1 =20CF22-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF22-Q0 SU200 BO =20CF20+X1 =20CF22-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF22-Q1 SU200 BO =20CF20+X1 =20CF22-Q1/CMD OFF ISOLATOR OPEN
- =20CF22-Q1 SU200 BO =20CF20+X1 =20CF22-Q1/CMD ON ISOLATOR CLOSE
- =20CF23-Q0 SU200 BO =20CF20+X1 =20CF23-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF23-Q0 SU200 BO =20CF20+X1 =20CF23-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF23-Q1 SU200 BO =20CF20+X1 =20CF23-Q1/CMD OFF ISOLATOR OPEN
- =20CF23-Q1 SU200 BO =20CF20+X1 =20CF23-Q1/CMD ON ISOLATOR CLOSE
12241 =20CF21-Q1 SU200 BI =20CF20+X1 =20CF21-Q1/OFF ISOLATOR OPEN
12242 =20CF21-Q1 SU200 BI =20CF20+X1 =20CF21-Q1/ON ISOLATOR CLOSED
12243 =20CF21-Q1 SU200 BI =20CF20+X1 =20CF21-Q1/FLT ISOLATOR FAILURE
12244 =20CF21-Q51 SU200 BI =20CF20+X1 =20CF21-Q51/OFF EARTH SWITCH OPEN
12245 =20CF21-Q51 SU200 BI =20CF20+X1 =20CF21-Q51/ON EARTH SWITCH CLOSED
12246 =20CF21-Q51 SU200 BI =20CF20+X1 =20CF21-Q51/FLT EARTH SWITCH FAILURE
12247 =20CF21-Q52 SU200 BI =20CF20+X1 =20CF21-Q52/OFF EARTH SWITCH OPEN
12248 =20CF21-Q52 SU200 BI =20CF20+X1 =20CF21-Q52/ON EARTH SWITCH CLOSED
12249 =20CF21-Q52 SU200 BI =20CF20+X1 =20CF21-Q52/FLT EARTH SWITCH FAILURE
12250 =20CF21-Q17 SU200 BI =20CF20+X1 =20CF21-Q17/OFF EARTH SWITCH OPEN
12251 =20CF21-Q17 SU200 BI =20CF20+X1 =20CF21-Q17/ON EARTH SWITCH CLOSED
12252 =20CF21-Q17 SU200 BI =20CF20+X1 =20CF21-Q17/FLT EARTH SWITCH FAILURE
12253 =20R21+R1 SU200 BI =20CF20+X1 =20CF21-T1/1 50ACF TRP TRIP OVERCURRENT PROTECTION
12254 =20R21+R1 SU200 BI =20CF20+X1 =20CF21-T1/1 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12255 =20R21+R1 SU200 BI =20CF20+X1 =20CF21-T1/1 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12256 =20R21+R1 SU200 BI =20CF20+X1 =20CF21-T41/1 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12257 =20R21+R1 SU200 BI =20CF20+X1 =20CF21-T42/1 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12258 =20R21+R1 SU200 BI =20CF20+X1 =20CF21-T2/1 50ACFL TRP TRIP OVERCUR. PROT. F. LOW VOLT. REAC.
12259 =20R21+R1 SU200 BI =20CF20+X1 =20CF21-T3/1 50ACFR TRP TRIP OVERCUR PROT F. LOW VOLT RESISTOR
12260 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/87ACFB 21 TRP AC FILTER 2 BANK DIFF. PROTECTION
12261 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/50BF 21 TRP AC FILTER 2 BANK BF. PROTECTION
12262 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/86A 86B 21 TRP AC FILTER 2 BANK TRIP RELAY
12263 =20R21+R2.C SU200 BI =20CF20+X1 =20R21+R2.C/20CF21 TC FLT AC FILTER 2 BANK TRIP CIRCUIT UNHEALTHY
12264 =20CF20+X2 SU200 BI =20CF20+X1 =20CF20+X2/FLT DC SPLY INTERFACE CUBICLE
12265 =20CF20+S1 SU200 BI =20CF20+X1 =20CF20+S1/VT MCB TRP AC-LOCAL CONTROL: VOLT. TRANS. MCB TRIP
12266 =20C00+U1 SU200 BI =20CF20+X1 =20CF21-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12267 =20CF20+S1 SU200 BI =20CF20+X1 =20CF20+S1/FLT AC SPLY LOCAL INTERFACE CUBICLE
12268 =20CF20+S1 SU200 BI =20CF20+X1 =20CF20+S1/FLT DC SPLY LOCAL INTERFACE CUBICLE
12269 =20CF20+S1 SU200 BI =20CF20+X1 =20CF21/LOC CTRL ES DS LOCAL CONTROL
12270 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/OFF CIRCUIT BREAKER OPEN
12271 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/ON CIRCUIT BREAKER CLOSED
12273 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/SPRING UNLOAD CB SPRING UNLOADED
12274 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12275 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12276 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12277 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12278 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12279 =20CF21-Q0 SU200 BI =20CF20+X1 =20CF21-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12281 =20CF22-Q1 SU200 BI =20CF20+X1 =20CF22-Q1/OFF ISOLATOR OPEN
12282 =20CF22-Q1 SU200 BI =20CF20+X1 =20CF22-Q1/ON ISOLATOR CLOSED
12283 =20CF22-Q1 SU200 BI =20CF20+X1 =20CF22-Q1/FLT ISOLATOR FAILURE
12284 =20CF22-Q51 SU200 BI =20CF20+X1 =20CF22-Q51/OFF EARTH SWITCH OPEN
12285 =20CF22-Q51 SU200 BI =20CF20+X1 =20CF22-Q51/ON EARTH SWITCH CLOSED
12286 =20CF22-Q51 SU200 BI =20CF20+X1 =20CF22-Q51/FLT EARTH SWITCH FAILURE
12287 =20CF22-Q52 SU200 BI =20CF20+X1 =20CF22-Q52/OFF EARTH SWITCH OPEN
12288 =20CF22-Q52 SU200 BI =20CF20+X1 =20CF22-Q52/ON EARTH SWITCH CLOSED
12289 =20CF22-Q52 SU200 BI =20CF20+X1 =20CF22-Q52/FLT EARTH SWITCH FAILURE
12290 =20R21+R1 SU200 BI =20CF20+X1 =20CF22-T1/II 50ACF TRP TRIP OVERCURRENT PROTECTION
12291 =20R21+R1 SU200 BI =20CF20+X1 =20CF22-T1/II 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12292 =20R21+R1 SU200 BI =20CF20+X1 =20CF22-T1/II 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12293 =20R21+R1 SU200 BI =20CF20+X1 =20CF22-T41/II 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12294 =20R21+R1 SU200 BI =20CF20+X1 =20CF22-T42/II 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12295 =20R21+R1 SU200 BI =20CF20+X1 =20CF22-T2/II 50ACFL TRP TRIP OVERCUR. PROT. F. LOW VOLT. REAC.
12296 =20R21+R1 SU200 BI =20CF20+X1 =20CF22-T3/II 50ACFR TRP TRIP OVERCUR PROT F. LOW VOLT RESISTOR
12297 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/87ACFB 22 TRP AC FILTER 2 BANK DIFF. PROTECTION
12298 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/50BF 22 TRP AC FILTER 2 BANK BF. PROTECTION
12299 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/86A 86B 22 TRP AC FILTER 2 BANK TRIP RELAY
12300 =20R21+R2.C SU200 BI =20CF20+X1 =20R21+R2.C/20CF22 TC FLT AC FILTER 2 BANK TRIP CIRCUIT UNHEALTHY
12301 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/87BBM2 TRP AC FILTER 2 BANK PROTECTION
12302 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/27 59 TRP AC FILTER 2 BANK OVER/UNDERVOLT. PROTEC
12303 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/86A 86B M2 TRP AC FILTER 2 BANK DIFF, PROTECTION TRIP R
12304 =20R21+R2.A SU200 BI =20CF20+X1 =20R21+R2.A/MCB TRP AC FILTER 2 BANK PROT. CUBICLE MCB TRIP
12308 =20C00+U1 SU200 BI =20CF20+X1 =20CF22-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12309 =20CF20+S1 SU200 BI =20CF20+X1 =20CF22/LOC CTRL ES DS LOCAL CONTROL
12310 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/OFF CIRCUIT BREAKER OPEN
12311 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/ON CIRCUIT BREAKER CLOSED
12313 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/SPRING UNLOAD CB SPRING UNLOADED
12314 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12315 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12316 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12317 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12318 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12319 =20CF22-Q0 SU200 BI =20CF20+X1 =20CF22-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12321 =20CF23-Q1 SU200 BI =20CF20+X1 =20CF23-Q1/OFF ISOLATOR OPEN
12322 =20CF23-Q1 SU200 BI =20CF20+X1 =20CF23-Q1/ON ISOLATOR CLOSED
12323 =20CF23-Q1 SU200 BI =20CF20+X1 =20CF23-Q1/FLT ISOLATOR FAILURE
12324 =20CF23-Q51 SU200 BI =20CF20+X1 =20CF23-Q51/OFF EARTH SWITCH OPEN
12325 =20CF23-Q51 SU200 BI =20CF20+X1 =20CF23-Q51/ON EARTH SWITCH CLOSED
12326 =20CF23-Q51 SU200 BI =20CF20+X1 =20CF23-Q51/FLT EARTH SWITCH FAILURE
12327 =20CF23-Q52 SU200 BI =20CF20+X1 =20CF23-Q52/OFF EARTH SWITCH OPEN
12328 =20CF23-Q52 SU200 BI =20CF20+X1 =20CF23-Q52/ON EARTH SWITCH CLOSED
12329 =20CF23-Q52 SU200 BI =20CF20+X1 =20CF23-Q52/FLT EARTH SWITCH FAILURE
12330 =20R21+R1 SU200 BI =20CF20+X1 =20CF23-T1/III 50ACF TRP TRIP OVERCURRENT PROTECTION
12331 =20R21+R1 SU200 BI =20CF20+X1 =20CF23-T1/III 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12332 =20R21+R1 SU200 BI =20CF20+X1 =20CF23-T1/III 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12333 =20R21+R1 SU200 BI =20CF20+X1 =20CF23-T41/III 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12334 =20R21+R1 SU200 BI =20CF20+X1 =20CF23-T42/III 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12335 =20R21+R1 SU200 BI =20CF20+X1 =20CF23-T2/III 50ACFL TRP TRIP OVERCUR. PROT. F. LOW VOLT. REAC.
12336 =20R21+R1 SU200 BI =20CF20+X1 =20CF23-T3/III 50ACFR TRP TRIP OVERCUR PROT F. LOW VOLT RESISTOR
12337 =20R21+R2.B SU200 BI =20CF20+X1 =20R21+R2.B/87ACFB 23 TRP AC FILTER 2 BANK DIFF. PROTECTION
12338 =20R21+R2.B SU200 BI =20CF20+X1 =20R21+R2.B/50BF 23 TRP AC FILTER 2 BANK BF. PROTECTION
12339 =20R21+R2.B SU200 BI =20CF20+X1 =20R21+R2.B/86A 86B 23 TRP AC FILTER 2 BANK TRIP RELAY
12340 =20R21+R2.C SU200 BI =20CF20+X1 =20R21+R2.C/20CF23 TC FLT AC FILTER 2 BANK TRIP CIRCUIT UNHEALTHY
12348 =20C00+U1 SU200 BI =20CF20+X1 =20CF23-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12349 =20CF20+S1 SU200 BI =20CF20+X1 =20CF23/LOC CTRL ES DS LOCAL CONTROL
12350 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/OFF CIRCUIT BREAKER OPEN
12351 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/ON CIRCUIT BREAKER CLOSED
12353 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/SPRING UNLOAD CB SPRING UNLOADED
12354 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12355 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12356 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12357 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12358 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12359 =20CF23-Q0 SU200 BI =20CF20+X1 =20CF23-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
AC Station control Interface =20CF20+X2
- =20CF24-T3 SU200 AI =20CF20+X2 =20CF24-T3/Q SHUNT C SUB BANK REACTIVE POWER
- =20CF25-T3 SU200 AI =20CF20+X2 =20CF25-T3/Q SHUNT C SUB BANK REACTIVE POWER
- =20CF24-Q0 SU200 BO =20CF20+X2 =20CF24-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF24-Q0 SU200 BO =20CF20+X2 =20CF24-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF24-Q1 SU200 BO =20CF20+X2 =20CF24-Q1/CMD OFF ISOLATOR OPEN
- =20CF24-Q1 SU200 BO =20CF20+X2 =20CF24-Q1/CMD ON ISOLATOR CLOSE
- =20CF25-Q0 SU200 BO =20CF20+X2 =20CF25-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF25-Q0 SU200 BO =20CF20+X2 =20CF25-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF25-Q1 SU200 BO =20CF20+X2 =20CF25-Q1/CMD OFF ISOLATOR OPEN
- =20CF25-Q1 SU200 BO =20CF20+X2 =20CF25-Q1/CMD ON ISOLATOR CLOSE
12361 =20CF24-Q1 SU200 BI =20CF20+X2 =20CF24-Q1/OFF ISOLATOR OPEN
12362 =20CF24-Q1 SU200 BI =20CF20+X2 =20CF24-Q1/ON ISOLATOR CLOSED
12363 =20CF24-Q1 SU200 BI =20CF20+X2 =20CF24-Q1/FLT ISOLATOR FAILURE
12364 =20CF24-Q51 SU200 BI =20CF20+X2 =20CF24-Q51/OFF EARTH SWITCH OPEN
12365 =20CF24-Q51 SU200 BI =20CF20+X2 =20CF24-Q51/ON EARTH SWITCH CLOSED
12366 =20CF24-Q51 SU200 BI =20CF20+X2 =20CF24-Q51/FLT EARTH SWITCH FAILURE
12367 =20CF24-Q52 SU200 BI =20CF20+X2 =20CF24-Q52/OFF EARTH SWITCH OPEN
12368 =20CF24-Q52 SU200 BI =20CF20+X2 =20CF24-Q52/ON EARTH SWITCH CLOSED
12369 =20CF24-Q52 SU200 BI =20CF20+X2 =20CF24-Q52/FLT EARTH SWITCH FAILURE
12370 =20R21+R1 SU200 BI =20CF20+X2 =20CF24-T1/1 50CB TRP TRIP OVERCURRENT PROTECTION
12371 =20R21+R1 SU200 BI =20CF20+X2 =20CF24-T1/1 51CB TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12372 =20R21+R1 SU200 BI =20CF20+X2 =20CF24-T1/1 49 59CB TRP TRIP CAPACITOR OVERLOAD PROTECTION
12373 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1/PWR SPLY FLT AC FILTER 2 SUBBANK MAIN PROTECTION
12374 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1/TESTMODE AC FILTER 2 SUBBANK MAIN PROTECTION
12375 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-A1/SIMD HW FLT AC FILTER 2 SUBBANK MAIN PROTECTION
12376 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-A1/SIMD FAN FLT AC FILTER 2 SUBBANK MAIN PROTECTION
12377 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-A1/SW WRN AC FILTER 2 SUBBANK MAIN PROTECTION
12378 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-A1/SW FLT AC FILTER 2 SUBBANK MAIN PROTECTION
12379 =20R21+R2.B SU200 BI =20CF20+X2 =20R21+R2.B/87ACB 24 TRP AC FILTER 2 BANK DIFF. PROTECTION
12380 =20R21+R2.B SU200 BI =20CF20+X2 =20R21+R2.B/50BF 24 TRP AC FILTER 2 BANK BF. PROTECTION
12381 =20R21+R2.B SU200 BI =20CF20+X2 =20R21+R2.B/86A 86B 24 TRP AC FILTER 2 BANK TRIP RELAY
12382 =20R21+R2.C SU200 BI =20CF20+X2 =20R21+R2.C/20CF24 TC FLT AC FILTER 2 BANK TRIP CIRCUIT UNHEALTHY
12384 =20CF10+X1 SU200 BI =20CF20+X2 =20CF20+X1/FLT DC SPLY DC STATION INTERFACE MCB TRIP
12388 =20C00+U1 SU200 BI =20CF20+X2 =20CF24-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12389 =20CF20+S1 SU200 BI =20CF20+X2 =20CF24/LOC CTRL ES DS LOCAL CONTROL
12390 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/OFF CIRCUIT BREAKER OPEN
12391 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/ON CIRCUIT BREAKER CLOSED
12393 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12394 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12395 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12396 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12397 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12398 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12399 =20CF24-Q0 SU200 BI =20CF20+X2 =20CF24-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12401 =20CF25-Q1 SU200 BI =20CF20+X2 =20CF25-Q1/OFF ISOLATOR OPEN
12402 =20CF25-Q1 SU200 BI =20CF20+X2 =20CF25-Q1/ON ISOLATOR CLOSED
12403 =20CF25-Q1 SU200 BI =20CF20+X2 =20CF25-Q1/FLT ISOLATOR FAILURE
12404 =20CF25-Q51 SU200 BI =20CF20+X2 =20CF25-Q51/OFF EARTH SWITCH OPEN
12405 =20CF25-Q51 SU200 BI =20CF20+X2 =20CF25-Q51/ON EARTH SWITCH CLOSED
12406 =20CF25-Q51 SU200 BI =20CF20+X2 =20CF25-Q51/FLT EARTH SWITCH FAILURE
12407 =20CF25-Q52 SU200 BI =20CF20+X2 =20CF25-Q52/OFF EARTH SWITCH OPEN
12408 =20CF25-Q52 SU200 BI =20CF20+X2 =20CF25-Q52/ON EARTH SWITCH CLOSED
12409 =20CF25-Q52 SU200 BI =20CF20+X2 =20CF25-Q52/FLT EARTH SWITCH FAILURE
12410 =20R21+R1 SU200 BI =20CF20+X2 =20CF25-T1/II 50CB TRP TRIP OVERCURRENT PROTECTION
12411 =20R21+R1 SU200 BI =20CF20+X2 =20CF25-T1/II 51CB TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12412 =20R21+R1 SU200 BI =20CF20+X2 =20CF25-T1/II 49 59CB TRP TRIP CAPACITOR OVERLOAD PROTECTION
12413 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F11/CPR97 FLT INTERNAL FAULT CPR97-F11
12414 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F12/CPR97 FLT INTERNAL FAULT CPR97-F12
12415 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F13/CPR97 FLT INTERNAL FAULT CPR97-F13
12416 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F21/CPR97 FLT INTERNAL FAULT CPR97-F21
12417 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F22/CPR97 FLT INTERNAL FAULT CPR97-F22
12418 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F23/CPR97 FLT INTERNAL FAULT CPR97-F23
12419 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F31/CPR97 FLT INTERNAL FAULT CPR97-F31
12420 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F32/CPR97 FLT INTERNAL FAULT CPR97-F32
12421 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F33/CPR97 FLT INTERNAL FAULT CPR97-F33
12422 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F41/CPR97 FLT INTERNAL FAULT CPR97-F41
12423 =20R21+R1 SU200 BI =20CF20+X2 =20R21+R1-F51/CPR97 FLT INTERNAL FAULT CPR97-F51
12424 =20R21+R2.B SU200 BI =20CF20+X2 =20R21+R2.B/87ACB 25 TRP AC FILTER 2 BANK DIFF. PROTECTION
12425 =20R21+R2.B SU200 BI =20CF20+X2 =20R21+R2.B/50BF 25 TRP AC FILTER 2 BANK BF. PROTECTION
12426 =20R21+R2.B SU200 BI =20CF20+X2 =20R21+R2.B/86A 86B 25 TRP AC FILTER 2 BANK TRIP RELAY
12427 =20R21+R2.C SU200 BI =20CF20+X2 =20R21+R2.C/20CF25 TC FLT AC FILTER 2 BANK TRIP CIRCUIT UNHEALTHY
12428 =20C00+U1 SU200 BI =20CF20+X2 =20CF25-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12429 =20CF20+S1 SU200 BI =20CF20+X2 =20CF25/LOC CTRL ES DS LOCAL CONTROL
12430 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/OFF CIRCUIT BREAKER OPEN
12431 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/ON CIRCUIT BREAKER CLOSED
12433 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12434 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12435 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12436 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12437 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12438 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12439 =20CF25-Q0 SU200 BI =20CF20+X2 =20CF25-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
AC Station control Interface =20CF20+X3
- =20CF26-T3/Q SU200 AI =20CF20+X3 =20CF26-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF27-T3/Q SU200 AI =20CF20+X3 =20CF27-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF36-T3/Q SU200 AI =20CF20+X3 =20CF36-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF26-Q0 SU200 BO =20CF20+X3 =20CF26-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF26-Q0 SU200 BO =20CF20+X3 =20CF26-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF26-Q1 SU200 BO =20CF20+X3 =20CF26-Q1/CMD OFF ISOLATOR OPEN
- =20CF26-Q1 SU200 BO =20CF20+X3 =20CF26-Q1/CMD ON ISOLATOR CLOSE
- =20CF27-Q0 SU200 BO =20CF20+X3 =20CF27-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF27-Q0 SU200 BO =20CF20+X3 =20CF27-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF27-Q1 SU200 BO =20CF20+X3 =20CF27-Q1/CMD OFF ISOLATOR OPEN
- =20CF27-Q1 SU200 BO =20CF20+X3 =20CF27-Q1/CMD ON ISOLATOR CLOSE
- =20CF36-Q0 SU200 BO =20CF20+X3 =20CF36-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF36-Q0 SU200 BO =20CF20+X3 =20CF36-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF36-Q1 SU200 BO =20CF20+X3 =20CF36-Q1/CMD OFF ISOLATOR OPEN
- =20CF36-Q1 SU200 BO =20CF20+X3 =20CF36-Q1/CMD ON ISOLATOR CLOSE
- =20CF26-Q1 SU200 BI =20CF20+X3 =20CF26-Q1/OFF ISOLATOR OPEN
- =20CF26-Q1 SU200 BI =20CF20+X3 =20CF26-Q1/ON ISOLATOR CLOSED
- =20CF26-Q1 SU200 BI =20CF20+X3 =20CF26-Q1/FLT ISOLATOR FAILURE
- =20CF26-Q51 SU200 BI =20CF20+X3 =20CF26-Q51/OFF EARTH SWITCH OPEN
- =20CF26-Q51 SU200 BI =20CF20+X3 =20CF26-Q51/ON EARTH SWITCH CLOSED
- =20CF26-Q51 SU200 BI =20CF20+X3 =20CF26-Q51/FLT EARTH SWITCH FAILURE
- =20CF26-Q52 SU200 BI =20CF20+X3 =20CF26-Q52/OFF EARTH SWITCH OPEN
- =20CF26-Q52 SU200 BI =20CF20+X3 =20CF26-Q52/ON EARTH SWITCH CLOSED
- =20CF26-Q52 SU200 BI =20CF20+X3 =20CF26-Q52/FLT EARTH SWITCH FAILURE
- =20R21+R3 SU200 BI =20CF20+X3 =20CF26-T1/I 50ACF TRP TRIP OVERCURRENT PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF26-T1/1 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF26-T1/1 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF26-T41/1 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
- =20R21+R3 SU200 BI =20CF20+X3 =20CF26-T42/1 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
- =20R21+R3 SU200 BI =20CF20+X3 =20CF26-T2/1 50ACFL TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE REACTOR
- =20R21+R3 SU200 BI =20CF20+X3 =20CF26-T3/1 50ACFR TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE RESISTOR
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/87ACFB 31 TRP AC FILTER2 BANK DIFF. PROTECTION
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/50BF 31 TRP AC FILTER 2 BANK BF. PROTECTION
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/86A 86B 31 TRP AC FILTER2 BANK TRIP RELAY
- =20R23+R2.C SU200 BI =20CF20+X3 =20R23+R2.C/20CF31 TC FLT AC FILTER2 BANK TRIP CIRCUIT UNHEALTHY
- =20R21+R2.D SU200 BI =20CF20+X3 =20R21+R2.D/MCB TRIP INTERFACE CUBICLE
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF20+S3/FLT AC SUPPLY AC-LOCAL CONTROL: FLT AC SUPPLY
- =20R21+R2.D SU200 BI =20CF20+X3 =20R21+R2.D/26/27 FLT PROTECTION RELAY FAULTY
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF20+S3/FLT DC SPLY LOCAL INTERFACE CUBICLE
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF26-Q1/LOC CTRL ES DS LOCAL CONTROL
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/OFF CIRCUIT BREAKER OPEN
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/ON CIRCUIT BREAKER CLOSED
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/MOTOR FLT CB SPRING MOTOR FAULT
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/POLE DISCREP CB PHASES NOT TOGETHER
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
- =20CF27-Q1 SU200 BI =20CF20+X3 =20CF27-Q1/OFF ISOLATOR OPEN
- =20CF27-Q1 SU200 BI =20CF20+X3 =20CF27-Q1/ON ISOLATOR CLOSED
- =20CF27-Q1 SU200 BI =20CF20+X3 =20CF27-Q1/FLT ISOLATOR FAILURE
- =20CF27-Q51 SU200 BI =20CF20+X3 =20CF27-Q51/OFF EARTH SWITCH OPEN
- =20CF27-Q51 SU200 BI =20CF20+X3 =20CF27-Q51/ON EARTH SWITCH CLOSED
- =20CF27-Q51 SU200 BI =20CF20+X3 =20CF27-Q51/FLT EARTH SWITCH FAILURE
- =20CF27-Q52 SU200 BI =20CF20+X3 =20CF27-Q52/OFF EARTH SWITCH OPEN
- =20CF27-Q52 SU200 BI =20CF20+X3 =20CF27-Q52/ON EARTH SWITCH CLOSED
- =20CF27-Q52 SU200 BI =20CF20+X3 =20CF27-Q52/FLT EARTH SWITCH FAILURE
- =20R21+R3 SU200 BI =20CF20+X3 =20CF27-T1/I 50ACF TRP TRIP OVERCURRENT PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF27-T1/1 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF27-T1/1 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF27-T41/1 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
- =20R21+R3 SU200 BI =20CF20+X3 =20CF27-T42/1 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
- =20R21+R3 SU200 BI =20CF20+X3 =20CF27-T2/1 50ACFL TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE REACTOR
- =20R21+R3 SU200 BI =20CF20+X3 =20CF27-T3/1 50ACFR TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE RESISTOR
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/87ACFB 27 TRP AC FILTER2 BANK DIFF. PROTECTION
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/50BF 27 TRP AC FILTER 2 BANK BF. PROTECTION
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/86A 86B 27 TRP AC FILTER2 BANK TRIP RELAY
- =20R23+R2.C SU200 BI =20CF20+X3 =20R23+R2.C/20CF27 TC FLT AC FILTER2 BANK TRIP CIRCUIT UNHEALTHY
- =20R21+R2.D SU200 BI =20CF20+X3 =20R21+R2.D/MCB TRIP INTERFACE CUBICLE
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF20+S3/FLT AC SUPPLY AC-LOCAL CONTROL: FLT AC SUPPLY
- =20R21+R2.D SU200 BI =20CF20+X3 =20R21+R2.D/26/27 FLT PROTECTION RELAY FAULTY
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF20+S3/FLT DC SPLY LOCAL INTERFACE CUBICLE
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF27-Q1/LOC CTRL ES DS LOCAL CONTROL
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/OFF CIRCUIT BREAKER OPEN
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/ON CIRCUIT BREAKER CLOSED
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/MOTOR FLT CB SPRING MOTOR FAULT
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/POLE DISCREP CB PHASES NOT TOGETHER
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
- =20CF36-Q1 SU200 BI =20CF20+X3 =20CF36-Q1/OFF ISOLATOR OPEN
- =20CF36-Q1 SU200 BI =20CF20+X3 =20CF36-Q1/ON ISOLATOR CLOSED
- =20CF36-Q1 SU200 BI =20CF20+X3 =20CF36-Q1/FLT ISOLATOR FAILURE
- =20CF36-Q51 SU200 BI =20CF20+X3 =20CF36-Q51/OFF EARTH SWITCH OPEN
- =20CF36-Q51 SU200 BI =20CF20+X3 =20CF36-Q51/ON EARTH SWITCH CLOSED
- =20CF36-Q51 SU200 BI =20CF20+X3 =20CF36-Q51/FLT EARTH SWITCH FAILURE
- =20CF36-Q52 SU200 BI =20CF20+X3 =20CF36-Q52/OFF EARTH SWITCH OPEN
- =20CF36-Q52 SU200 BI =20CF20+X3 =20CF36-Q52/ON EARTH SWITCH CLOSED
- =20CF36-Q52 SU200 BI =20CF20+X3 =20CF36-Q52/FLT EARTH SWITCH FAILURE
- =20R21+R3 SU200 BI =20CF20+X3 =20CF36-T1/I 50ACF TRP TRIP OVERCURRENT PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF36-T1/1 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF36-T1/1 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
- =20R21+R3 SU200 BI =20CF20+X3 =20CF36-T41/1 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
- =20R21+R3 SU200 BI =20CF20+X3 =20CF36-T42/1 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
- =20R21+R3 SU200 BI =20CF20+X3 =20CF36-T2/1 50ACFL TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE REACTOR
- =20R21+R3 SU200 BI =20CF20+X3 =20CF36-T3/1 50ACFR TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE RESISTOR
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/87ACFB 27 TRP AC FILTER2 BANK DIFF. PROTECTION
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/50BF 27 TRP AC FILTER 2 BANK BF. PROTECTION
- =20R23+R2.A SU200 BI =20CF20+X3 =20R23+R2.A/86A 86B 27 TRP AC FILTER2 BANK TRIP RELAY
- =20R23+R2.C SU200 BI =20CF20+X3 =20R23+R2.C/20CF27 TC FLT AC FILTER2 BANK TRIP CIRCUIT UNHEALTHY
- =20R21+R2.D SU200 BI =20CF20+X3 =20R21+R2.D/MCB TRIP INTERFACE CUBICLE
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF20+S3/FLT AC SUPPLY AC-LOCAL CONTROL: FLT AC SUPPLY
- =20R21+R2.D SU200 BI =20CF20+X3 =20R21+R2.D/26/27 FLT PROTECTION RELAY FAULTY
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF20+S3/FLT DC SPLY LOCAL INTERFACE CUBICLE
- =20CF20+S3 SU200 BI =20CF20+X3 =20CF36-Q1/LOC CTRL ES DS LOCAL CONTROL
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/OFF CIRCUIT BREAKER OPEN
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/ON CIRCUIT BREAKER CLOSED
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/MOTOR FLT CB SPRING MOTOR FAULT
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/POLE DISCREP CB PHASES NOT TOGETHER
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
- =20C00_U2 SU200 BI =20CF20+X3 =20C00_U2/POW PWR FAULT POW POWER SUPPLY FAULT
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/DEVICE FAULT POW FAULT
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/SYNC DATA ERR POW SYNC ERROR
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/SWITCHING FAULT POW SWITCHING FAULT
- =20CF26-Q0 SU200 BI =20CF20+X3 =20CF26-Q0/POW BYPASS POW BYPASSED
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/DEVICE FAULT POW FAULT
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/SYNC DATA ERR POW SYNC ERROR
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/SWITCHING FAULT POW SWITCHING FAULT
- =20CF27-Q0 SU200 BI =20CF20+X3 =20CF27-Q0/POW BYPASS POW BYPASSED
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/DEVICE FAULT POW FAULT
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/SYNC DATA ERR POW SYNC ERROR
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/SWITCHING FAULT POW SWITCHING FAULT
- =20CF36-Q0 SU200 BI =20CF20+X3 =20CF36-Q0/POW BYPASS POW BYPASSED
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F11/CPR04 FLT INTERNAL FAULT CPR04-F11
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F12/CPR04 FLT INTERNAL FAULT CPR04-F12
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F13/CPR04 FLT INTERNAL FAULT CPR04-F13
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F21/CPR04 FLT INTERNAL FAULT CPR04-F21
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F22/CPR04 FLT INTERNAL FAULT CPR04-F22
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F23/CPR04 FLT INTERNAL FAULT CPR04-F23
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F31/CPR04 FLT INTERNAL FAULT CPR04-F31
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F32/CPR04 FLT INTERNAL FAULT CPR04-F32
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3-F33/CPR04 FLT INTERNAL FAULT CPR04-F33
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3/PWR FLT POWER SUPPLY FAULT
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3/TEST MODE TEST MODE
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3/HW FLT HARDWARE FAULT
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3/FAN FLT SIMADYN FAN FAULT
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3/SW FLT SOFTWARE FAULT
- =20R21+R3 SU200 BI =20CF20+X3 =20R21+R3/SW WRN SOFTWARE WARNING
AC Station control Interface =20CF30+X1
- =20CF31-T3 SU200 AI =20CF30+X1 =20CF31-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF31-T15 SU200 AI =20CF30+X1 =20CF31-T15/UL1 AC FILTER BANK 3 VOLTAGE UL1-N
- =20CF31-T15 SU200 AI =20CF30+X1 =20CF31-T15/UL2 AC FILTER BANK 3 VOLTAGE UL2-N
- =20CF32-T3 SU200 AI =20CF30+X1 =20CF32-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF31-T15 SU200 AI =20CF30+X1 =20CF31-T15/UL2 AC FILTER BANK 3 VOLTAGE UL2-N
- =20CF31-T15 SU200 AI =20CF30+X1 =20CF31-T15/UL3 AC FILTER BANK 3 VOLTAGE UL3-N
- =20CF33-T3 SU200 AI =20CF30+X1 =20CF33-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF31-T15 SU200 AI =20CF30+X1 =20CF31-T15/UL3 AC FILTER BANK 3 VOLTAGE UL3-N
- =20CF31-T15 SU200 AI =20CF30+X1 =20CF31-T15/UL1 AC FILTER BANK 3 VOLTAGE UL1-N
- =20CF31-Q0 SU200 BO =20CF30+X1 =20CF31-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF31-Q0 SU200 BO =20CF30+X1 =20CF31-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF31-Q1 SU200 BO =20CF30+X1 =20CF31-Q1/CMD OFF ISOLATOR OPEN
- =20CF31-Q1 SU200 BO =20CF30+X1 =20CF31-Q1/CMD ON ISOLATOR CLOSE
- =20CF32-Q0 SU200 BO =20CF30+X1 =20CF32-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF32-Q0 SU200 BO =20CF30+X1 =20CF32-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF32-Q1 SU200 BO =20CF30+X1 =20CF32-Q1/CMD OFF ISOLATOR OPEN
- =20CF32-Q1 SU200 BO =20CF30+X1 =20CF32-Q1/CMD ON ISOLATOR CLOSE
- =20CF33-Q0 SU200 BO =20CF30+X1 =20CF33-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF33-Q0 SU200 BO =20CF30+X1 =20CF33-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF33-Q1 SU200 BO =20CF30+X1 =20CF33-Q1/CMD OFF ISOLATOR OPEN
- =20CF33-Q1 SU200 BO =20CF30+X1 =20CF33-Q1/CMD ON ISOLATOR CLOSE
12441 =20CF31-Q1 SU200 BI =20CF30+X1 =20CF31-Q1/OFF ISOLATOR OPEN
12442 =20CF31-Q1 SU200 BI =20CF30+X1 =20CF31-Q1/ON ISOLATOR CLOSED
12443 =20CF31-Q1 SU200 BI =20CF30+X1 =20CF31-Q1/FLT ISOLATOR FAILURE
12444 =20CF31-Q51 SU200 BI =20CF30+X1 =20CF31-Q51/OFF EARTH SWITCH OPEN
12445 =20CF31-Q51 SU200 BI =20CF30+X1 =20CF31-Q51/ON EARTH SWITCH CLOSED
12446 =20CF31-Q51 SU200 BI =20CF30+X1 =20CF31-Q51/FLT EARTH SWITCH FAILURE
12447 =20CF31-Q52 SU200 BI =20CF30+X1 =20CF31-Q52/OFF EARTH SWITCH OPEN
12448 =20CF31-Q52 SU200 BI =20CF30+X1 =20CF31-Q52/ON EARTH SWITCH CLOSED
12449 =20CF31-Q52 SU200 BI =20CF30+X1 =20CF31-Q52/FLT EARTH SWITCH FAILURE
12450 =20CF31-Q17 SU200 BI =20CF30+X1 =20CF31-Q17/OFF EARTH SWITCH OPEN
12451 =20CF31-Q17 SU200 BI =20CF30+X1 =20CF31-Q17/ON EARTH SWITCH CLOSED
12452 =20CF31-Q17 SU200 BI =20CF30+X1 =20CF31-Q17/FLT EARTH SWITCH FAILURE
12453 =20R31+R1 SU200 BI =20CF30+X1 =20CF31-T1/I 50ACF TRP TRIP OVERCURRENT PROTECTION
12454 =20R31+R1 SU200 BI =20CF30+X1 =20CF31-T1/1 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12455 =20R31+R1 SU200 BI =20CF30+X1 =20CF31-T1/1 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12456 =20R31+R1 SU200 BI =20CF30+X1 =20CF31-T41/1 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12457 =20R31+R1 SU200 BI =20CF30+X1 =20CF31-T42/1 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12458 =20R31+R1 SU200 BI =20CF30+X1 =20CF31-T2/1 50ACFL TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE REACTOR
12459 =20R31+R1 SU200 BI =20CF30+X1 =20CF31-T3/1 50ACFR TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE RESISTOR
12460 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/87ACFB 31 TRP AC FILTER 3 BANK DIFF. PROTECTION
12461 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/50BF 31 TRP AC FILTER 3 BANK BF. PROTECTION
12462 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/86A 86B 31 TRP AC FILTER 3 BANK TRIP RELAY
12463 =20R31+R2.C SU200 BI =20CF30+X1 =20R31+R2.C/20CF31 TC FLT AC FILTER 3 BANK TRIP CIRCUIT UNHEALTHY
12464 =20CF30+X2 SU200 BI =20CF30+X1 =20CF30+X2/FLT DC SPLY INTERFACE CUBICLE
12465 =20CF30+S1 SU200 BI =20CF30+X1 =20CF30+S1/VT MCB TRP AC-LOCAL CONTROL: VOLT. TRANS. MCB TRIP
12466 =20C00+U1 SU200 BI =20CF30+X1 =20CF31-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12467 =20CF30+S1 SU200 BI =20CF30+X1 =20CF30+S1/FLT AC SPLY LOCAL INTERFACE CUBICLE
12468 =20CF30+S1 SU200 BI =20CF30+X1 =20CF30+S1/FLT DC SPLY LOCAL INTERFACE CUBICLE
12469 =20CF30+S1 SU200 BI =20CF30+X1 =20CF31/LOC CTRL ES DS LOCAL CONTROL
12470 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/OFF CIRCUIT BREAKER OPEN
12471 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/ON CIRCUIT BREAKER CLOSED
12473 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12474 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12475 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12476 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12477 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12478 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12479 =20CF31-Q0 SU200 BI =20CF30+X1 =20CF31-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12481 =20CF32-Q1 SU200 BI =20CF30+X1 =20CF32-Q1/OFF ISOLATOR OPEN
12482 =20CF32-Q1 SU200 BI =20CF30+X1 =20CF32-Q1/ON ISOLATOR CLOSED
12483 =20CF32-Q1 SU200 BI =20CF30+X1 =20CF32-Q1/FLT ISOLATOR FAILURE
12484 =20CF32-Q51 SU200 BI =20CF30+X1 =20CF32-Q51/OFF EARTH SWITCH OPEN
12485 =20CF32-Q51 SU200 BI =20CF30+X1 =20CF32-Q51/ON EARTH SWITCH CLOSED
12486 =20CF32-Q51 SU200 BI =20CF30+X1 =20CF32-Q51/FLT EARTH SWITCH FAILURE
12487 =20CF32-Q52 SU200 BI =20CF30+X1 =20CF32-Q52/OFF EARTH SWITCH OPEN
12488 =20CF32-Q52 SU200 BI =20CF30+X1 =20CF32-Q52/ON EARTH SWITCH CLOSED
12489 =20CF32-Q52 SU200 BI =20CF30+X1 =20CF32-Q52/FLT EARTH SWITCH FAILURE
12490 =20R31+R1 SU200 BI =20CF30+X1 =20CF32-T1/II 50ACF TRP TRIP OVERCURRENT PROTECTION
12491 =20R31+R1 SU200 BI =20CF30+X1 =20CF32-T1/II 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12492 =20R31+R1 SU200 BI =20CF30+X1 =20CF32-T1/II 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12493 =20R31+R1 SU200 BI =20CF30+X1 =20CF32-T41/II 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12494 =20R31+R1 SU200 BI =20CF30+X1 =20CF32-T42/II 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12495 =20R31+R1 SU200 BI =20CF30+X1 =20CF32-T2/II 50ACFL TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE REACTOR
12496 =20R31+R1 SU200 BI =20CF30+X1 =20CF32-T3/II 50ACFR TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE RESISTOR
12497 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/87ACFB 32 TRP AC FILTER 3 BANK DIFF. PROTECTION
12498 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/50BF 32 TRP AC FILTER 3 BANK BF. PROTECTION
12499 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/86A 86B 32 TRP AC FILTER 3 BANK TRIP RELAY
12500 =20R31+R2.C SU200 BI =20CF30+X1 =20R31+R2.C/20CF32 TC FLT AC FILTER 3 BANK TRIP CIRCUIT UNHEALTHY
12501 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/87BBM2 TRP AC FILTER 3 BANK PROTECTION
12502 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/27 59 TRP AC FILTER 3 BANK OVER/UNDERVOLT. PROTEC
12503 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/86A 86B M2 TRP AC FILTER 3 BANK DIFF, PROTECTION TRIP R
12504 =20R31+R2.A SU200 BI =20CF30+X1 =20R31+R2.A/MCB TRP AC FILTER 3 BANK PROT. CUBICLE MCB TRIP
12508 =20C00+U1 SU200 BI =20CF30+X1 =20CF32-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12509 =20CF30+S1 SU200 BI =20CF30+X1 =20CF32/LOC CTRL ES DS LOCAL CONTROL
12510 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/OFF CIRCUIT BREAKER OPEN
12511 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/ON CIRCUIT BREAKER CLOSED
12513 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12514 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12515 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12516 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12517 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12518 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12519 =20CF32-Q0 SU200 BI =20CF30+X1 =20CF32-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12521 =20CF33-Q1 SU200 BI =20CF30+X1 =20CF33-Q1/OFF ISOLATOR OPEN
12522 =20CF33-Q1 SU200 BI =20CF30+X1 =20CF33-Q1/ON ISOLATOR CLOSED
12523 =20CF33-Q1 SU200 BI =20CF30+X1 =20CF33-Q1/FLT ISOLATOR FAILURE
12524 =20CF33-Q51 SU200 BI =20CF30+X1 =20CF33-Q51/OFF EARTH SWITCH OPEN
12525 =20CF33-Q51 SU200 BI =20CF30+X1 =20CF33-Q51/ON EARTH SWITCH CLOSED
12526 =20CF33-Q51 SU200 BI =20CF30+X1 =20CF33-Q51/FLT EARTH SWITCH FAILURE
12527 =20CF33-Q52 SU200 BI =20CF30+X1 =20CF33-Q52/OFF EARTH SWITCH OPEN
12528 =20CF33-Q52 SU200 BI =20CF30+X1 =20CF33-Q52/ON EARTH SWITCH CLOSED
12529 =20CF33-Q52 SU200 BI =20CF30+X1 =20CF33-Q52/FLT EARTH SWITCH FAILURE
12530 =20R31+R1 SU200 BI =20CF30+X1 =20CF33-T1/III 50ACF TRP TRIP OVERCURRENT PROTECTION
12531 =20R31+R1 SU200 BI =20CF30+X1 =20CF33-T1/III 51ACF TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12532 =20R31+R1 SU200 BI =20CF30+X1 =20CF33-T1/III 49 59ACF TRP TRIP CAPACITOR OVERLOAD PROTECTION
12533 =20R31+R1 SU200 BI =20CF30+X1 =20CF33-T41/III 51ACFL TRP TRIP OVLD PROT F. LOW VOLT PARAL. REAC
12534 =20R31+R1 SU200 BI =20CF30+X1 =20CF33-T42/III 51ACFR TRP TRIP OVLD PROT LOWER LOW VOLT PAR CI
12535 =20R31+R1 SU200 BI =20CF30+X1 =20CF33-T2/III 50ACFL TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE REACTOR
12536 =20R31+R1 SU200 BI =20CF30+X1 =20CF33-T3/III 50ACFR TRP TRIP OVERCURRENT PROTECTION FOR LOW VOLTAGE RESISTOR
12537 =20R31+R2.B SU200 BI =20CF30+X1 =20R31+R2.B/87ACFB 33 TRP AC FILTER 3 BANK DIFF. PROTECTION
12538 =20R31+R2.B SU200 BI =20CF30+X1 =20R31+R2.B/50BF 33 TRP AC FILTER 3 BANK BF. PROTECTION
12539 =20R31+R2.B SU200 BI =20CF30+X1 =20R31+R2.B/86A 86B 33 TRP AC FILTER 3 BANK TRIP RELAY
12540 =20R31+R2.C SU200 BI =20CF30+X1 =20R31+R2.C/20CF33 TC FLT AC FILTER 3 BANK TRIP CIRCUIT UNHEALTHY
12548 =20C00+U1 SU200 BI =20CF30+X1 =20CF33-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12549 =20CF30+S1 SU200 BI =20CF30+X1 =20CF33/LOC CTRL ES DS LOCAL CONTROL
12550 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/OFF CIRCUIT BREAKER OPEN
12551 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/ON CIRCUIT BREAKER CLOSED
12553 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12554 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12555 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12556 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12557 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12558 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12559 =20CF33-Q0 SU200 BI =20CF30+X1 =20CF33-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
AC Station control Interface =20CF30+X2
- =20CF34-T3 SU200 AI =20CF30+X2 =20CF31-T3/Q SHUNT C SUB BANK REACTIVE POWER
- =20CF31-T15 SU200 AI =20CF30+X2 =20CF31-T15/UL1 AC FILTER BANK 1 VOLTAGE UL1-N
- =20CF31-T15 SU200 AI =20CF30+X2 =20CF31-T15/UL2 AC FILTER BANK 1 VOLTAGE UL2-N
- =20CF35-T3 SU200 AI =20CF30+X2 =20CF35-T3/Q AC FILTER SUB BANK REACTIVE POWER
- =20CF31-T15 SU200 AI =20CF30+X2 =20CF11-T15/UL2 AC FILTER BANK 3 VOLTAGE UL2-N
- =20CF31-T15 SU200 AI =20CF30+X2 =20CF11-T15/UL3 AC FILTER BANK 3 VOLTAGE UL3-N
- =20CF34-Q0 SU200 BO =20CF30+X1 =20CF34-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF34-Q0 SU200 BO =20CF30+X1 =20CF34-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF34-Q1 SU200 BO =20CF30+X1 =20CF34-Q1/CMD OFF ISOLATOR OPEN
- =20CF34-Q1 SU200 BO =20CF30+X1 =20CF34-Q1/CMD ON ISOLATOR CLOSE
- =20CF35-Q0 SU200 BO =20CF30+X1 =20CF35-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20CF35-Q0 SU200 BO =20CF30+X1 =20CF35-Q0/CMD ON CIRCUIT BREAKER CLOSE
- =20CF35-Q1 SU200 BO =20CF30+X1 =20CF35-Q1/CMD OFF ISOLATOR OPEN
- =20CF35-Q1 SU200 BO =20CF30+X1 =20CF35-Q1/CMD ON ISOLATOR CLOSE
12561 =20CF34-Q1 SU200 BI =20CF30+X2 =20CF34-Q1/OFF ISOLATOR OPEN
12562 =20CF34-Q1 SU200 BI =20CF30+X2 =20CF34-Q1/ON ISOLATOR CLOSED
12563 =20CF34-Q1 SU200 BI =20CF30+X2 =20CF34-Q1/FLT ISOLATOR FAILURE
12564 =20CF34-Q51 SU200 BI =20CF30+X2 =20CF34-Q51/OFF EARTH SWITCH OPEN
12565 =20CF34-Q51 SU200 BI =20CF30+X2 =20CF34-Q51/ON EARTH SWITCH CLOSED
12566 =20CF34-Q51 SU200 BI =20CF30+X2 =20CF34-Q51/FLT EARTH SWITCH FAILURE
12567 =20CF34-Q52 SU200 BI =20CF30+X2 =20CF34-Q52/OFF EARTH SWITCH OPEN
12568 =20CF34-Q52 SU200 BI =20CF30+X2 =20CF34-Q52/ON EARTH SWITCH CLOSED
12569 =20CF34-Q52 SU200 BI =20CF30+X2 =20CF34-Q52/FLT EARTH SWITCH FAILURE
12570 =20R31+R1 SU200 BI =20CF30+X2 =20CF34-T1/1 50CB TRP TRIP OVERCURRENT PROTECTION
12571 =20R31+R1 SU200 BI =20CF30+X2 =20CF34-T1/I 51CB TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12572 =20R31+R1 SU200 BI =20CF30+X2 =20CF34-T1/1 49 59CB TRP TRIP CAPACITOR OVERLOAD PROTECTION
12573 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1/PWR SPLY FLT AC FILTER 3 SUBBANK MAIN PROTECTION
12574 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1/TESTMODE AC FILTER 3 SUBBANK MAIN PROTECTION
12575 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-A1/SIMD HW FLT AC FILTER 3 SUBBANK MAIN PROTECTION
12576 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-A1/SIMD FAN FLT AC FILTER 3 SUBBANK MAIN PROTECTION
12577 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-A1/SW WRN AC FILTER 3 SUBBANK MAIN PROTECTION
12578 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-A1/SW FLT AC FILTER 3 SUBBANK MAIN PROTECTION
12579 =20R31+R2.B SU200 BI =20CF30+X2 =20R31+R2.B/87ACB 34 TRP AC FILTER 3 BANK DIFF. PROTECTION
12580 =20R31+R2.B SU200 BI =20CF30+X2 =20R31+R2.B/50BF 34 TRP AC FILTER 3 BANK BF. PROTECTION
12581 =20R31+R2.B SU200 BI =20CF30+X2 =20R31+R2.B/86A 86B 34 TRP AC FILTER 3 BANK TRIP RELAY
12582 =20R31+R2.C SU200 BI =20CF30+X2 =20R31+R2.C/20CF34 TC FLT AC FILTER 3 BANK TRIP CIRCUIT UNHEALTHY
12584 =20CF30+X1 SU200 BI =20CF30+X2 =20CF30+X1/FLT DC SPLY INTERFACE CUBICLE
12588 =20C00+U1 SU200 BI =20CF30+X2 =20CF34-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12589 =20CF30+S1 SU200 BI =20CF30+X2 =20CF34/LOC CTRL ES DS LOCAL CONTROL
12590 =20CF34-Q0 SU200 BI =20CF30+X2 =20CF34-Q0/OFF CIRCUIT BREAKER OPEN
12591 =20CF34-Q0 SU200 BI =20CF30+X2 =20CF34-Q0/ON CIRCUIT BREAKER CLOSED
12593 =20CF34-QO SU200 BI =20CF30+X2 =20CF34-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12594 =20CF34-Q0 SU200 BI =20CF30+X2 =20CF34-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12595 =20CF34-QO SU200 BI =20CF30+X2 =20CF34-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12596 =20CF34-Q0 SU200 BI =20CF30+X2 =20CF34-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12597 =20CF34-QO SU200 BI =20CF30+X2 =20CF34-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12598 =20CF34-Q0 SU200 BI =20CF30+X2 =20CF34-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12599 =20CF34-Q0 SU200 BI =20CF30+X2 =20CF34-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
12601 =20CF35-Q1 SU200 BI =20CF30+X2 =20CF35-Q1/OFF ISOLATOR OPEN
12602 =20CF35-Q1 SU200 BI =20CF30+X2 =20CF35-Q1/ON ISOLATOR CLOSED
12603 =20CF35-Q1 SU200 BI =20CF30+X2 =20CF35-Q1/FLT ISOLATOR FAILURE
12604 =20CF35-Q51 SU200 BI =20CF30+X2 =20CF35-Q51/OFF EARTH SWITCH OPEN
12605 =20CF35-Q51 SU200 BI =20CF30+X2 =20CF35-Q51/ON EARTH SWITCH CLOSED
12606 =20CF35-Q51 SU200 BI =20CF30+X2 =20CF35-Q51/FLT EARTH SWITCH FAILURE
12607 =20CF35-Q52 SU200 BI =20CF30+X2 =20CF35-Q52/OFF EARTH SWITCH OPEN
12608 =20CF35-Q52 SU200 BI =20CF30+X2 =20CF35-Q52/ON EARTH SWITCH CLOSED
12609 =20CF35-Q52 SU200 BI =20CF30+X2 =20CF35-Q52/FLT EARTH SWITCH FAILURE
12610 =20R31+R1 SU200 BI =20CF30+X2 =20CF35-T1/II 50CB TRP TRIP OVERCURRENT PROTECTION
12611 =20R31+R1 SU200 BI =20CF30+X2 =20CF35-T1/II 51CB TRP TRIP INVERSE OVERCUR. -TIME PROTECTION
12612 =20R31+R1 SU200 BI =20CF30+X2 =20CF35-T1/II 49 59CB TRP TRIP CAPACITOR OVERLOAD PROTECTION
12613 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F11/CPR97 FLT INTERNAL FAULT CPR97-F11
12614 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F12/CPR97 FLT INTERNAL FAULT CPR97-F12
12615 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F13/CPR97 FLT INTERNAL FAULT CPR97-F13
12616 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F21/CPR97 FLT INTERNAL FAULT CPR97-F21
12617 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F22/CPR97 FLT INTERNAL FAULT CPR97-F22
12618 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F23/CPR97 FLT INTERNAL FAULT CPR97-F23
12619 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F31/CPR97 FLT INTERNAL FAULT CPR97-F31
12620 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F32/CPR97 FLT INTERNAL FAULT CPR97-F32
12621 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F33/CPR97 FLT INTERNAL FAULT CPR97-F33
12622 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F41/CPR97 FLT INTERNAL FAULT CPR97-F41
12623 =20R31+R1 SU200 BI =20CF30+X2 =20R31+R1-F51/CPR97 FLT INTERNAL FAULT CPR97-F51
12624 =20R31+R2.B SU200 BI =20CF30+X2 =20R31+R2.B/87ACFB 35 TRP AC FILTER 3 BANK DIFF. PROTECTION
12625 =20R31+R2.B SU200 BI =20CF30+X2 =20R31+R2.B/50BF 35 TRP AC FILTER 3 BANK BF. PROTECTION
12626 =20R31+R2.B SU200 BI =20CF30+X2 =20R31+R2.B/86A 86B 35 TRP AC FILTER 3 BANK TRIP RELAY
12627 =20R31+R2.C SU200 BI =20CF30+X2 =20R31+R2.C/20CF35 TC FLT AC FILTER 3 BANK TRIP CIRCUIT UNHEALTHY
12628 =20C00+U1 SU200 BI =20CF30+X2 =20CF35-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
12629 =20CF30+S1 SU200 BI =20CF30+X2 =20CF35/LOC CTRL ES DS LOCAL CONTROL
12630 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/OFF CIRCUIT BREAKER OPEN
12631 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/ON CIRCUIT BREAKER CLOSED
12633 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
12634 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
12635 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/MOTOR FLT CB SPRING MOTOR FAULT
12636 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
12637 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
12638 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/POLE DISCREP CB PHASES NOT TOGETHER
12639 =20CF35-Q0 SU200 BI =20CF30+X2 =20CF35-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
ACF 1 Main Protection
12641 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF11/87ACF TRP =20CF11 DIFFERENTIAL PROT
12642 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF11/60 61ACFC1 1 WRN =20CF11 C1 UNBALANCE PROT STAGE 1 WARN
12643 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF11/60 61ACFC1 2 WRN =20CF11 C1 UNBALANCE PROT STAGE 2 WARN
12644 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF11/60 61ACFC1 2 TRP =20CF11 C1 UNBALANCE PROT STAGE 2 TRIP
12645 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF11/60 61ACFC1 3 TRP =20CF11 C1 UNBALANCE PROT STAGE 3 TRIP
12648 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF11/IM3 FLT IM3 BOARD FAULTY
12649 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF12/87ACF TRP =20CF12 DIFFERENTIAL PROT
12650 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF12/60 61ACFC1 1 WRN =20CF12 C1 UNBALANCE PROT STAGE 1 WARN
12651 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF12/60 61ACFC1 2 WRN =20CF12 C1 UNBALANCE PROT STAGE 2 WARN
12652 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF12/60 61ACFC1 2 TRP =20CF12 C1 UNBALANCE PROT STAGE 2 TRIP
12653 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF12/60 61ACFC1 3 TRP =20CF12 C1 UNBALANCE PROT STAGE 3 TRIP
12656 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF12/IM3 FLT IM3 BOARD FAULTY
12657 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF13/87ACF TRP =20CF13 DIFFERENTIAL PROT
12658 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF13/60 61ACFC1 1 WRN =20CF13 C1 UNBALANCE PROT STAGE 1 WARN
12659 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF13/60 61ACFC1 2 WRN =20CF13 C1 UNBALANCE PROT STAGE 2 WARN
12660 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF13/60 61ACFC1 2 TRP =20CF13 C1 UNBALANCE PROT STAGE 2 TRIP
12661 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF13/60 61ACFC1 3 TRP =20CF13 C1 UNBALANCE PROT STAGE 3 TRIP
12664 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF13/IM3 FLT IM3 BOARD FAULTY
12665 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF14/87CB TRP =20CF14 DIFFERENTIAL PROT
12666 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF14/60 61CBC1 1 WRN =20CF14 C1 UNBALANCE PROT STAGE 1 WARN
12667 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF14/60 61CBC1 2 WRN =20CF14 C1 UNBALANCE PROT STAGE 2 WARN
12668 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF14/60 61CBC1 2 TRP =20CF14 C1 UNBALANCE PROT STAGE 2 TRIP
12669 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF14/60 61CBC1 3 TRP =20CF14 C1 UNBALANCE PROT STAGE 3 TRIP
12672 =20R11+R1 SU200 BI ACF 1 Main Protection =20CF14/M3 FLT IM3 BOARD FAULTY
ACF 2 Main Protection
12681 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF21/87ACF TRP =20CF21 DIFFERENTIAL PROT
12682 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF21/60 61ACFC1 1 WRN =20CF21 C1 UNBALANCE PROT STAGE 1 WARN
12683 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF21/60 61ACFC1 2 WRN =20CF21 C1 UNBALANCE PROT STAGE 2 WARN
12684 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF21/60 61ACFC1 2 TRP =20CF21 C1 UNBALANCE PROT STAGE 2 TRIP
12685 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF21/60 61ACFC1 3 TRP =20CF21 C1 UNBALANCE PROT STAGE 3 TRIP
12688 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF21/M3 FLT IM3 BOARD FAULTY
12689 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF22/87ACF TRP =20CF22 DIFFERENTIAL PROT
12690 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF22/60 61ACFC1 1 WRN =20CF22 C1 UNBALANCE PROT STAGE 1 WARN
12691 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF22/60 61ACFC1 2 WRN =20CF22 C1 UNBALANCE PROT STAGE 2 WARN
12692 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF22/60 61ACFC1 2 TRP =20CF22 C1 UNBALANCE PROT STAGE 2 TRIP
12693 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF22/60 61ACFC1 3 TRP =20CF22 C1 UNBALANCE PROT STAGE 3 TRIP
12696 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF22/M3 FLT IM3 BOARD FAULTY
12697 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF23/87ACF TRP =20CF23 DIFFERENTIAL PROT
12698 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF23/60 61ACFC1 1 WRN =20CF23 C1 UNBALANCE PROT STAGE 1 WARN
12699 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF23/60 61ACFC1 2 WRN =20CF23 C1 UNBALANCE PROT STAGE 2 WARN
12700 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF23/60 61ACFC1 2 TRP =20CF23 C1 UNBALANCE PROT STAGE 2 TRIP
12701 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF23/60 61ACFC1 3 TRP =20CF23 C1 UNBALANCE PROT STAGE 3 TRIP
12704 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF23/M3 FLT IM3 BOARD FAULTY
12705 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF24/87CB TRP =20CF24 DIFFERENTIAL PROT
12706 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF24/60 61CBC1 1 WRN =20CF24 C1 UNBALANCE PROT STAGE 1 WARN
12707 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF24/60 61CBC1 2 WRN =20CF24 C1 UNBALANCE PROT STAGE 2 WARN
12708 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF24/60 61CBC1 2 TRP =20CF24 C1 UNBALANCE PROT STAGE 2 TRIP
12709 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF24/60 61CBC1 3 TRP =20CF24 C1 UNBALANCE PROT STAGE 3 TRIP
12712 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF24/M3 FLT IM3 BOARD FAULTY
12713 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF25/87CB TRP =20CF25 DIFFERENTIAL PROT
12714 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF25/60 61CBC1 1 WRN =20CF25 C1 UNBALANCE PROT STAGE 1 WARN
12715 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF25/60 61CBC1 2 WRN =20CF25 C1 UNBALANCE PROT STAGE 2 WARN
12716 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF25/60 61CBC1 2 TRP =20CF25 C1 UNBALANCE PROT STAGE 2 TRIP
12717 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF25/60 61CBC1 3 TRP =20CF25 C1 UNBALANCE PROT STAGE 3 TRIP
12720 =20R21+R1 SU200 BI ACF 2 Main Protection =20CF25/M3 FLT IM3 BOARD FAULTY
ACF 2 Main Protection
- =20R21+R3 SU200 BI ACF 2 Main Protection =20CF26/87ACF TRP =20CF26 DIFFERENTIAL PROT
- =20R21+R4 SU200 BI ACF 2 Main Protection =20CF26/60 61ACFC1 1 WRN =20CF26 C1 UNBALANCE PROT STAGE 1 WARN
- =20R21+R5 SU200 BI ACF 2 Main Protection =20CF26/60 61ACFC1 2 WRN =20CF26 C1 UNBALANCE PROT STAGE 2 WARN
- =20R21+R6 SU200 BI ACF 2 Main Protection =20CF26/60 61ACFC1 2 TRP =20CF26 C1 UNBALANCE PROT STAGE 2 TRIP
- =20R21+R7 SU200 BI ACF 2 Main Protection =20CF26/60 61ACFC1 3 TRP =20CF26 C1 UNBALANCE PROT STAGE 3 TRIP
- =20R21+R8 SU200 BI ACF 2 Main Protection =20CF26/M3 FLT IM3 BOARD FAULTY
- =20R21+R9 SU200 BI ACF 2 Main Protection =20CF27/87ACF TRP =20CF27 DIFFERENTIAL PROT
- =20R21+R10 SU200 BI ACF 2 Main Protection =20CF27/60 61ACFC1 1 WRN =20CF27 C1 UNBALANCE PROT STAGE 1 WARN
- =20R21+R11 SU200 BI ACF 2 Main Protection =20CF27/60 61ACFC1 2 WRN =20CF27 C1 UNBALANCE PROT STAGE 2 WARN
- =20R21+R12 SU200 BI ACF 2 Main Protection =20CF27/60 61ACFC1 2 TRP =20CF27 C1 UNBALANCE PROT STAGE 2 TRIP
- =20R21+R13 SU200 BI ACF 2 Main Protection =20CF27/60 61ACFC1 3 TRP =20CF27 C1 UNBALANCE PROT STAGE 3 TRIP
- =20R21+R14 SU200 BI ACF 2 Main Protection =20CF27/M3 FLT IM3 BOARD FAULTY
- =20R21+R15 SU200 BI ACF 2 Main Protection =20CF36/87ACF TRP =20CF36 DIFFERENTIAL PROT
- =20R21+R16 SU200 BI ACF 2 Main Protection =20CF36/60 61ACFC1 1 WRN =20CF36 C1 UNBALANCE PROT STAGE 1 WARN
- =20R21+R17 SU200 BI ACF 2 Main Protection =20CF36/60 61ACFC1 2 WRN =20CF36 C1 UNBALANCE PROT STAGE 2 WARN
- =20R21+R18 SU200 BI ACF 2 Main Protection =20CF36/60 61ACFC1 2 TRP =20CF36 C1 UNBALANCE PROT STAGE 2 TRIP
- =20R21+R19 SU200 BI ACF 2 Main Protection =20CF36/60 61ACFC1 3 TRP =20CF36 C1 UNBALANCE PROT STAGE 3 TRIP
- =20R21+R20 SU200 BI ACF 2 Main Protection =20CF36/M3 FLT IM3 BOARD FAULTY
ACF 3 Main Protection
12721 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF31/87ACF TRP =20CF31 DIFFERENTIAL PROT
12722 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF31/60 61ACFC1 1 WRN =20CF31 C1 UNBALANCE PROT STAGE 1 WARN
12723 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF31/60 61ACFC1 2 WRN =20CF31 C1 UNBALANCE PROT STAGE 2 WARN
12724 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF31/60 61ACFC1 2 TRP =20CF31 C1 UNBALANCE PROT STAGE 2 TRIP
12725 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF31/60 61ACFC1 3 TRP =20CF31 C1 UNBALANCE PROT STAGE 3 TRIP
12728 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF31/M3 FLT IM3 BOARD FAULTY
12729 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF32/87ACF TRP =20CF32 DIFFERENTIAL PROT
12730 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF32/60 61ACFC1 1 WRN =20CF32 C1 UNBALANCE PROT STAGE 1 WARN
12731 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF32/60 61ACFC1 2 WRN =20CF32 C1 UNBALANCE PROT STAGE 2 WARN
12732 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF32/60 61ACFC1 2 TRP =20CF32 C1 UNBALANCE PROT STAGE 2 TRIP
12733 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF32/60 61ACFC1 3 TRP =20CF32 C1 UNBALANCE PROT STAGE 3 TRIP
12736 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF32/M3 FLT IM3 BOARD FAULTY
12737 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF33/87ACF TRP =20CF33 DIFFERENTIAL PROT
12738 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF33/60 61ACFC1 1 WRN =20CF33 C1 UNBALANCE PROT STAGE 1 WARN
12739 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF33/60 61ACFC1 2 WRN =20CF33 C1 UNBALANCE PROT STAGE 2 WARN
12740 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF33/60 61ACFC1 2 TRP =20CF33 C1 UNBALANCE PROT STAGE 2 TRIP
12741 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF33/60 61ACFC1 3 TRP =20CF33 C1 UNBALANCE PROT STAGE 3 TRIP
12744 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF33/M3 FLT IM3 BOARD FAULTY
12745 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF34/87CB TRP =20CF34 DIFFERENTIAL PROT
12746 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF34/60 61CBC1 1 WRN =20CF34 C1 UNBALANCE PROT STAGE 1 WARN
12747 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF34/60 61CBC1 2 WRN =20CF34 C1 UNBALANCE PROT STAGE 2 WARN
12748 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF34/60 61CBC1 2 TRP =20CF34 C1 UNBALANCE PROT STAGE 2 TRIP
12749 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF34/60 61CBC1 3 TRP =20CF34 C1 UNBALANCE PROT STAGE 3 TRIP
12752 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF34/M3 FLT IM3 BOARD FAULTY
12753 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF35/87CB TRP =20CF35 DIFFERENTIAL PROT
12754 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF35/60 61CBC1 1 WRN =20CF35 C1 UNBALANCE PROT STAGE 1 WARN
12755 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF35/60 61CBC1 2 WRN =20CF35 C1 UNBALANCE PROT STAGE 2 WARN
12756 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF35/60 61CBC1 2 TRP =20CF35 C1 UNBALANCE PROT STAGE 2 TRIP
12757 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF35/60 61CBC1 3 TRP =20CF35 C1 UNBALANCE PROT STAGE 3 TRIP
12760 =20R31+R1 SU200 BI ACF 3 Main Protection =20CF35/M3 FLT IM3 BOARD FAULTY
DC Station control Interface =20B10+X1
- =20B10-Q51 SU200 BO =20B10+X1 =20B10-Q51/CMD OFF EARTH SWITCH OPEN CMD
- =20B10-Q51 SU200 BO =20B10+X1 =20B10-Q51/CMD ON EARTH SWITCH CLOSE CMD
- =20B10-Q52 SU200 BO =20B10+X1 =20B10-Q52/CMD OFF EARTH SWITCH OPEN CMD
- =20B10-Q52 SU200 BO =20B10+X1 =20B10-Q52/CMD ON EARTH SWITCH CLOSE CMD
- =20B10-Q53 SU200 BO =20B10+X1 =20B10-Q53/CMD OFF EARTH SWITCH OPEN CMD
- =20B10-Q53 SU200 BO =20B10+X1 =20B10-Q53/CMD ON EARTH SWITCH CLOSE CMD
- =20B10-Q55 SU200 BO =20B10+X1 =20B10-Q55/CMD OFF EARTH SWITCH OPEN CMD
- =20B10-Q55 SU200 BO =20B10+X1 =20B10-Q55/CMD ON EARTH SWITCH CLOSE CMD
- =20B10-Q56 SU200 BO =20B10+X1 =20B10-Q56/CMD OFF EARTH SWITCH OPEN CMD
- =20B10-Q56 SU200 BO =20B10+X1 =20B10-Q56/CMD ON EARTH SWITCH CLOSE CMD
- =20B10-Q1 SU200 BO =20B10+X1 =20B10-Q1/CMD OFF ISOLATOR OPEN CMD
- =20B10-Q1 SU200 BO =20B10+X1 =20B10-Q1/CMD ON ISOLATOR CLOSE CMD
- =20B10-Q2 SU200 BO =20B10+X1 =20B10-Q2/CMD OFF ISOLATOR OPEN CMD
- =20B10-Q2 SU200 BO =20B10+X1 =20B10-Q2/CMD ON ISOLATOR CLOSE CMD
- =20B10-Q5 SU200 BO =20B10+X1 =20B10-Q5/CMD OFF ISOLATOR OPEN CMD
- =20B10-Q5 SU200 BO =20B10+X1 =20B10-Q5/CMD ON ISOLATOR CLOSE CMD
- =20B10-Q7 SU200 BO =20B10+X1 =20B10-Q7/CMD OFF ISOLATOR OPEN CMD
- =20B10-Q7 SU200 BO =20B10+X1 =20B10-Q7/CMD ON ISOLATOR CLOSE CMD
- =20B10-Q11 SU200 BO =20B10+X1 =20B10-Q11/CMD OFF ISOLATOR OPEN CMD
- =20B10-Q11 SU200 BO =20B10+X1 =20B10-Q11/CMD ON ISOLATOR CLOSE CMD
- =20B10-Q12 SU200 BO =20B10+X1 =20B10-Q12/CMD OFF ISOLATOR OPEN CMD
- =20B10-Q12 SU200 BO =20B10+X1 =20B10-Q12/CMD ON ISOLATOR CLOSE CMD
- =20B10-Q96 SU200 BO =20B10+X1 =20B10-Q96/CMD OFF ISOLATOR OPEN CMD
- =20B10-Q96 SU200 BO =20B10+X1 =20B10-Q96/CMD ON ISOLATOR CLOSE CMD
- =20B10-Q96 SU200 BO =20B10+X1 =20B10-Q96/EN LOC CTRL ENABLE LOCAL CONTROL
- =21B04-Q51 SU200 BO =20B10+X1 =21B04-Q51/CMD OFF EARTH SWITCH OPEN CMD
- =21B04-Q51 SU200 BO =20B10+X1 =21B04-Q51/CMD ON EARTH SWITCH CLOSE CMD
- =21B04-Q53 SU200 BO =20B10+X1 =21B04-Q53/CMD OFF EARTH SWITCH OPEN CMD
- =21B04-Q53 SU200 BO =20B10+X1 =21B04-Q53/CMD ON EARTH SWITCH CLOSE CMD
- =21B04-Q9 SU200 BO =20B10+X1 =21B04-Q9/CMD OFF ISOLATOR OPEN CMD
- =21B04-Q9 SU200 BO =20B10+X1 =21B04-Q9/CMD ON ISOLATOR CLOSE CMD
- =21B04-Q91 SU200 BO =20B10+X1 =21B04-Q91/CMD OFF ISOLATOR OPEN CMD
- =21B04-Q91 SU200 BO =20B10+X1 =21B04-Q91/CMD ON ISOLATOR CLOSE CMD
- =22B04-Q51 SU200 BO =20B10+X1 =22B04-Q51/CMD OFF EARTH SWITCH OPEN CMD
- =22B04-Q51 SU200 BO =20B10+X1 =22B04-Q51/CMD ON EARTH SWITCH CLOSE CMD
- =22B04-Q53 SU200 BO =20B10+X1 =22B04-Q53/CMD OFF EARTH SWITCH OPEN CMD
- =22B04-Q53 SU200 BO =20B10+X1 =22B04-Q53/CMD ON EARTH SWITCH CLOSE CMD
- =22B04-Q9 SU200 BO =20B10+X1 =22B04-Q9/CMD OFF ISOLATOR OPEN CMD
- =22B04-Q9 SU200 BO =20B10+X1 =22B04-Q9/CMD ON ISOLATOR CLOSE CMD
- =22B04-Q91 SU200 BO =20B10+X1 =22B04-Q91/CMD OFF ISOLATOR OPEN CMD
- =22B04-Q91 SU200 BO =20B10+X1 =22B04-Q91/CMD ON ISOLATOR CLOSE CMD
12761 =20B10-Q51 SU200 BI =20B10+X1 =20B10-Q51/OFF EARTH SWITCH OPEN
12762 =20B10-Q51 SU200 BI =20B10+X1 =20B10-Q51/ON EARTH SWITCH CLOSED
12763 =20B10-Q51 SU200 BI =20B10+X1 =20B10-Q51/FLT EARTH SWITCH FAULT
12764 =20B10-Q51 SU200 BI =20B10+X1 =20B10-Q51/LOC CTRL EARTH SWITCH LOCAL CONTROL
12765 =20B10-Q52 SU200 BI =20B10+X1 =20B10-Q52/OFF EARTH SWITCH OPEN
12766 =20B10-Q52 SU200 BI =20B10+X1 =20B10-Q52/ON EARTH SWITCH CLOSED
12767 =20B10-Q52 SU200 BI =20B10+X1 =20B10-Q52/FLT EARTH SWITCH FAULT
12768 =20B10-Q52 SU200 BI =20B10+X1 =20B10-Q52/LOC CTRL EARTH SWITCH LOCAL CONTROL
12769 =20B10-Q53 SU200 BI =20B10+X1 =20B10-Q53/OFF EARTH SWITCH OPEN
12770 =20B10-Q53 SU200 BI =20B10+X1 =20B10-Q53/ON EARTH SWITCH CLOSED
12771 =20B10-Q53 SU200 BI =20B10+X1 =20B10-Q53/FLT EARTH SWITCH FAULT
12772 =20B10-Q53 SU200 BI =20B10+X1 =20B10-Q53/LOC CTRL EARTH SWITCH LOCAL CONTROL
12777 =20B10-Q55 SU200 BI =20B10+X1 =20B10-Q55/OFF EARTH SWITCH OPEN
12778 =20B10-Q55 SU200 BI =20B10+X1 =20B10-Q55/ON EARTH SWITCH CLOSED
12779 =20B10-Q55 SU200 BI =20B10+X1 =20B10-Q55/FLT EARTH SWITCH FAULT
12780 =20B10-Q55 SU200 BI =20B10+X1 =20B10-Q55/LOC CTRL EARTH SWITCH LOCAL CONTROL
12781 =20B10-Q56 SU200 BI =20B10+X1 =20B10-Q56/OFF EARTH SWITCH OPEN
12782 =20B10-Q56 SU200 BI =20B10+X1 =20B10-Q56/ON EARTH SWITCH CLOSED
12783 =20B10-Q56 SU200 BI =20B10+X1 =20B10-Q56/FLT EARTH SWITCH FAULT
12784 =20B10-Q56 SU200 BI =20B10+X1 =20B10-Q56/LOC CTRL EARTH SWITCH LOCAL CONTROL
12793 =20B10+S1 SU200 BI =20B10+X1 =20B10+S1/FLT AC SPLY DC-LOCAL CONTROL CUBICLE
12794 =20B10+S1 SU200 BI =20B10+X1 =20B10+S1/FLT DC SPLY DC-LOCAL CONTROL CUBICLE
12795 =20CF10+X1 SU200 BI =20B10+X1 =20CF10+X1/FLT DC SPLY INTERFACE CUBICLE
12801 =20B10-Q1 SU200 BI =20B10+X1 =20B10-Q1/OFF ISOLATOR OPEN
12802 =20B10-Q1 SU200 BI =20B10+X1 =20B10-Q1/ON ISOLATOR CLOSED
12803 =20B10-Q1 SU200 BI =20B10+X1 =20B10-Q1/FLT ISOLATOR FAULT
12804 =20B10-Q1 SU200 BI =20B10+X1 =20B10-Q1/LOC CTRL ISOLATOR LOCAL CONTROL
12805 =20B10-Q2 SU200 BI =20B10+X1 =20B10-Q2/OFF ISOLATOR OPEN
12806 =20B10-Q2 SU200 BI =20B10+X1 =20B10-Q2/ON ISOLATOR CLOSED
12807 =20B10-Q2 SU200 BI =20B10+X1 =20B10-Q2/FLT ISOLATOR FAULT
12808 =20B10-Q2 SU200 BI =20B10+X1 =20B10-Q2/LOC CTRL ISOLATOR LOCAL CONTROL
12817 =20B10-Q5 SU200 BI =20B10+X1 =20B10-Q5/OFF ISOLATOR OPEN
12818 =20B10-Q5 SU200 BI =20B10+X1 =20B10-Q5/ON ISOLATOR CLOSED
12819 =20B10-Q5 SU200 BI =20B10+X1 =20B10-Q5/FLT ISOLATOR FAULT
12820 =20B10-Q5 SU200 BI =20B10+X1 =20B10-Q5/LOC CTRL ISOLATOR LOCAL CONTROL
12825 =20B10-Q7 SU200 BI =20B10+X1 =20B10-Q7/OFF ISOLATOR OPEN
12826 =20B10-Q7 SU200 BI =20B10+X1 =20B10-Q7/ON ISOLATOR CLOSED
12827 =20B10-Q7 SU200 BI =20B10+X1 =20B10-Q7/FLT ISOLATOR FAULT
12828 =20B10-Q7 SU200 BI =20B10+X1 =20B10-Q7/LOC CTRL ISOLATOR LOCAL CONTROL
12829 =20B10-Q11 SU200 BI =20B10+X1 =20B10-Q11/OFF ISOLATOR OPEN
12830 =20B10-Q11 SU200 BI =20B10+X1 =20B10-Q11/ON ISOLATOR CLOSED
12831 =20B10-Q11 SU200 BI =20B10+X1 =20B10-Q11/FLT ISOLATOR FAULT
12832 =20B10-Q11 SU200 BI =20B10+X1 =20B10-Q11/LOC CTRL ISOLATOR LOCAL CONTROL
12833 =20B10-Q12 SU200 BI =20B10+X1 =20B10-Q12/OFF ISOLATOR OPEN
12834 =20B10-Q12 SU200 BI =20B10+X1 =20B10-Q12/ON ISOLATOR CLOSED
12835 =20B10-Q12 SU200 BI =20B10+X1 =20B10-Q12/FLT ISOLATOR FAULT
12836 =20B10-Q12 SU200 BI =20B10+X1 =20B10-Q12/LOC CTRL ISOLATOR LOCAL CONTROL
12861 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/OFF HSGS CIRCUIT BREAKER OPEN
12862 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/ON HSGS CIRCUIT BREAKER CLOSED
12863 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/GENERAL LOCK HSGS CIRCUIT BREAKER GENERAL LOCKOUT
12864 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/ON LOCK HSGS CIRCUIT BREAKER ON-LOCKOUT
12865 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/LOSS N2 HSGS CIRCUIT BREAKER LOSS OF N2
12866 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/LOSS SF6 HSGS CIRCUIT BREAKER LOSS OF SF6
12867 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/FLT HYDRAULIC HSGS CIRCUIT BREAKER HYDRAULIC FAULT
12870 =20B10-Q96 SU200 BI =20B10+X1 =20B10-Q96/LOC CTRL HSGS CIRCUIT BREAKER LOCAL CONTROL
12881 =21B04-Q51 SU200 BI =20B10+X1 =21B04-Q51/OFF HV BUS EARTH SWITCH OPEN
12882 =21B04-Q51 SU200 BI =20B10+X1 =21B04-Q51/ON HV BUS EARTH SWITCH CLOSED
12883 =21B04-Q51 SU200 BI =20B10+X1 =21B04-Q51/FLT HV BUS EARTH SWITCH FAULT
12884 =21B04-Q51 SU200 BI =20B10+X1 =21B04-Q51/LOC CTRL HV BUS EARTH SWITCH LOCAL CONTROL
12885 =21B04-Q53 SU200 BI =20B10+X1 =21B04-Q53/OFF DC LINE EARTH SWITCH OPEN
12886 =21B04-Q53 SU200 BI =20B10+X1 =21B04-Q53/ON DC LINE EARTH SWITCH CLOSED
12887 =21B04-Q53 SU200 BI =20B10+X1 =21B04-Q53/FLT DC LINE EARTH SWITCH FAULT
12888 =21B04-Q53 SU200 BI =20B10+X1 =21B04-Q53/LOC CTRL DC LINE EARTH SWITCH LOCAL CONTROL
12889 =21B04-Q9 SU200 BI =20B10+X1 =21B04-Q9/OFF HV BUS ISOLATOR OPEN
12890 =21B04-Q9 SU200 BI =20B10+X1 =21B04-Q9/ON HV BUS ISOLATOR CLOSED
12891 =21B04-Q9 SU200 BI =20B10+X1 =21B04-Q9/FLT HV BUS ISOLATOR FAULT
12892 =21B04-Q9 SU200 BI =20B10+X1 =21B04-Q9/LOC CTRL HV BUS ISOLATOR LOCAL CONTROL
12893 =21B04-Q91 SU200 BI =20B10+X1 =21B04-Q91/OFF TRANSFER BUS ISOLATOR OPEN
12894 =21B04-Q91 SU200 BI =20B10+X1 =21B04-Q91/ON TRANSFER BUS ISOLATOR CLOSED
12895 =21B04-Q91 SU200 BI =20B10+X1 =21B04-Q91/FLT TRANSFER BUS ISOLATOR FAULT
12896 =21B04-Q91 SU200 BI =20B10+X1 =21B04-Q91/LOC CTRL TRANSFER BUS ISOLATOR LOCAL CONTROL
12897 =22B04-Q51 SU200 BI =20B10+X1 =22B04-Q51/OFF HV BUS EARTH SWITCH OPEN
12898 =22B04-Q51 SU200 BI =20B10+X1 =22B04-Q51/ON HV BUS EARTH SWITCH CLOSED
12899 =22B04-Q51 SU200 BI =20B10+X1 =22B04-Q51/FLT HV BUS EARTH SWITCH FAULT
12900 =22B04-Q51 SU200 BI =20B10+X1 =22B04-Q51/LOC CTRL HV BUS EARTH SWITCH LOCAL CONTROL
12901 =22B04-Q53 SU200 BI =20B10+X1 =22B04-Q53/OFF DC LINE EARTH SWITCH OPEN
12902 =22B04-Q53 SU200 BI =20B10+X1 =22B04-Q53/ON DC LINE EARTH SWITCH CLOSED
12903 =22B04-Q53 SU200 BI =20B10+X1 =22B04-Q53/FLT DC LINE EARTH SWITCH FAULT
12904 =22B04-Q53 SU200 BI =20B10+X1 =22B04-Q53/LOC CTRL DC LINE EARTH SWITCH LOCAL CONTROL
12905 =22B04-Q9 SU200 BI =20B10+X1 =22B04-Q9/OFF HV BUS ISOLATOR OPEN
12906 =22B04-Q9 SU200 BI =20B10+X1 =22B04-Q9/ON HV BUS ISOLATOR CLOSED
12907 =22B04-Q9 SU200 BI =20B10+X1 =22B04-Q9/FLT HV BUS ISOLATOR FAULT
12908 =22B04-Q9 SU200 BI =20B10+X1 =22B04-Q9/LOC CTRL HV BUS ISOLATOR LOCAL CONTROL
12909 =22B04-Q91 SU200 BI =20B10+X1 =22B04-Q91/OFF TRANSFER BUS ISOLATOR OPEN
12910 =22B04-Q91 SU200 BI =20B10+X1 =22B04-Q91/ON TRANSFER BUS ISOLATOR CLOSED
12911 =22B04-Q91 SU200 BI =20B10+X1 =22B04-Q91/FLT TRANSFER BUS ISOLATOR FAULT
12912 =22B04-Q91 SU200 BI =20B10+X1 =22B04-Q91/LOC CTRL TRANSFER BUS ISOLATOR LOCAL CONTROL
SER Interface =20X51+X51
12921 =21R01+R1 SU200 BI =20X51+X51 =21R01+R1/PWR SPLY FLT POWER SUPPLY FAULT
12922 =21R01+R1 SU200 BI =20X51+X51 =21R01+R1-A1/SIMD HW FLT SIMADYN D HARDWARE FAULT
12923 =21R01+R1 SU200 BI =20X51+X51 =21R01+R1-A1/SIMD FAN FLT SIMADYN D FAN FAULT
12924 =21R01+R1 SU200 BI =20X51+X51 =21R01+R1-A1/SOFTWARE FLT SOFTWARE FAULT
12925 =21R01+R1 SU200 BI =20X51+X51 =21R01+R1-A1/SOFTWARE WRN SOFTWARE WARNING
12926 =21R01+R1 SU200 BI =20X51+X51 =21R01+R1/TESTMODE TEST MODE
12929 =21R01+R2 SU200 BI =20X51+X51 =21R01+R2/PWR SPLY FLT POWER SUPPLY FAULT
12930 =21R01+R2 SU200 BI =20X51+X51 =21R01+R2-A1/SIMD HW FLT SIMADYN D HARDWARE FAULT
12931 =21R01+R2 SU200 BI =20X51+X51 =21R01+R2-A1/SIMD FAN FLT SIMADYN D FAN FAULT
12932 =21R01+R2 SU200 BI =20X51+X51 =21R01+R2-A1/SOFTWARE FLT SOFTWARE FAULT
12933 =21R01+R2 SU200 BI =20X51+X51 =21R01+R2-A1/SOFTWARE WRN SOFTWARE WARNING
12934 =21R01+R2 SU200 BI =20X51+X51 =21R01+R2/TESTMODE TEST MODE
12937 =21V01+U1 SU200 BI =20X51+X51 =21V00+U1/PWR SPLY FLT POWER SUPPLY FAULT
12938 =21V01+U1 SU200 BI =20X51+X51 =21V00+U1/ESOF BY PC EMERGENCY SWITCH OFF BY POLE CONTROL
12939 =21V01+U1 SU200 BI =20X51+X51 =21V00+U1/MAN MODE SSC MANUAL MODE OF SYSTEM SELECTION
12940 =21V01+U1 SU200 BI =20X51+X51 =21V01+U1/PWR SPLY FLT POWER SUPPLY FAULT
12941 =21V01+U1 SU200 BI =20X51+X51 =21V01+U1/SIMD HW FLT SIMADYN D HARDWARE FAULT
12942 =21V01+U1 SU200 BI =20X51+X51 =21V01+U1/SIMD FAN FLT SIMADYN D FAN FAULT
12945 =21V02+U2 SU200 BI =20X51+X51 =21V02+U2/PWR SPLY FLT POWER SUPPLY FAULT
12946 =21V02+U2 SU200 BI =20X51+X51 =21V02+U2/SIMD HW FLT SIMADYN D HARDWARE FAULT
12947 =21V02+U2 SU200 BI =20X51+X51 =21V02+U2/SIMD FAN FLT SIMADYN D FAN FAULT
12953 =21X61+X61 SU200 BI =20X51+X51 =21X61+X61/FLT DC SPLY DC POWER SUPPLY FAULT
12954 =21X61+X61 SU200 BI =20X51+X51 =21X61+X61/FLT SYS SYSTEM FAULT & WATCHDOG ALARM
12955 =21X61+X61 SU200 BI =20X51+X51 =21X61+X61/RECORD RECORDING EVENT
12956 =21X61+X61 SU200 BI =20X51+X51 =21X61+X61/TIME SYNC FLT TIME SYNCHRONISATION FAULT
12957 =21Q00+Q1 SU200 BI =20X51+X51 =21Q00+Q1/PWR SPLY FLT POWER SUPPLY FAULT
12961 =22R01+R1 SU200 BI =20X51+X51 =22R01+R1/PWR SPLY FLT POWER SUPPLY FAULT
12962 =22R01+R1 SU200 BI =20X51+X51 =22R01+R1-A1/SIMD HW FLT SIMADYN D HARDWARE FAULT
12963 =22R01+R1 SU200 BI =20X51+X51 =22R01+R1-A1/SIMD FAN FLT SIMADYN D FAN FAULT
12964 =22R01+R1 SU200 BI =20X51+X51 =22R01+R1-A1/SOFTWARE FLT SOFTWARE FAULT
12965 =22R01+R1 SU200 BI =20X51+X51 =22R01+R1-A1/SOFTWARE WRN SOFTWARE WARNING
12966 =22R01+R1 SU200 BI =20X51+X51 =22R01+R1/TESTMODE TEST MODE
12969 =22R01+R2 SU200 BI =20X51+X51 =22R01+R2/PWR SPLY FLT POWER SUPPLY FAULT
12970 =22R01+R2 SU200 BI =20X51+X51 =22R01+R2-A1/SIMD HW FLT SIMADYN D HARDWARE FAULT
12971 =22R01+R2 SU200 BI =20X51+X51 =22R01+R2-A1/SIMD FAN FLT SIMADYN D FAN FAULT
12972 =22R01+R2 SU200 BI =20X51+X51 =22R01+R2-A1/SOFTWARE FLT SOFTWARE FAULT
12973 =22R01+R2 SU200 BI =20X51+X51 =22R01+R2-A1/SOFTWARE WRN SOFTWARE WARNING
12974 =22R01+R2 SU200 BI =20X51+X51 =22R01+R2/TESTMODE TEST MODE
12977 =22V01+U1 SU200 BI =20X51+X51 =22V00+U1/PWR SPLY FLT POWER SUPPLY FAULT
12978 =22V01+U1 SU200 BI =20X51+X51 =22V00+U1/ESOF BY PC EMERGENCY SWITCH OFF BY POLE CONTROL
12979 =22V01+U1 SU200 BI =20X51+X51 =22V00+U1/MAN MODE SSC MANUAL MODE OF SYSTEM SELECTION
12980 =22V01+U1 SU200 BI =20X51+X51 =22V01+U1/PWR SPLY FLT POWER SUPPLY FAULT
12981 =22V01+U1 SU200 BI =20X51+X51 =22V01+U1/SIMD HW FLT SIMADYN D HARDWARE FAULT
12982 =22V01+U1 SU200 BI =20X51+X51 =22V01+U1/SIMD FAN FLT SIMADYN D FAN FAULT
12985 =22V02+U2 SU200 BI =20X51+X51 =22V02+U2/PWR SPLY FLT POWER SUPPLY FAULT
12986 =22V02+U2 SU200 BI =20X51+X51 =22V02+U2/SIMD HW FLT SIMADYN D HARDWARE FAULT
12987 =22V02+U2 SU200 BI =20X51+X51 =22V02+U2/SIMD FAN FLT SIMADYN D FAN FAULT
12993 =22X61+X61 SU200 BI =20X51+X51 =22X61+X61/FLT DC SPLY DC POWER SUPPLY FAULT
12994 =22X61+X61 SU200 BI =20X51+X51 =22X61+X61/FLT SYS SYSTEM FAULT & WATCHDOG ALARM
12995 =22X61+X61 SU200 BI =20X51+X51 =22X61+X61/RECORD RECORDING EVENT
12996 =22X61+X61 SU200 BI =20X51+X51 =22X61+X61/TIME SYNC FLT TIME SYNCHRONISATION FAULT
12997 =22Q00+Q1 SU200 BI =20X51+X51 =22Q00+Q1/PWR SPLY FLT POWER SUPPLY FAULT
13001 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/PWR SPLY1 FLT POWER SUPPLY FAULT AT SYSTEM 1
13002 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/PWR SPLY2 FLT POWER SUPPLY FAULT AT SYSTEM 2
13003 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/SIG PWR FLT POWER SUPPLY FAULT AT SIGNAL CIRCUITS
13004 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/LAN1 FLT AC CONTROL INTERFACE TO LAN 1 FAULT
13005 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/LAN2 FLT AC CONTROL INTERFACE TO LAN 2 FAULT
13006 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/FAN1 FLT FAN FAULT AT SYSTEM 1
13007 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/FAN2 FLT FAN FAULT AT SYSTEM 2
13008 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/CTRL SYS1 FLT AC/DC CONTROL SYSTEM 1 INTERNAL FAULT
13009 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/CTRL SYS2 FLT AC/DC CONTROL SYSTEM 2 INTERNAL FAULT
13010 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/MSTR CLK1 FLT MASTERCLOCK FAULT AT SYSTEM 1
13011 =20XJ02+XJ2 SU200 BI =20X51+X51 =20XJ02+XJ2/MSTR CLK2 FLT MASTERCLOCK FAULT AT SYSTEM 2
13012 =20XW10+XW1 SU200 BI =20X51+X51 =20XW10+XW1/CUB FLT CUBICLE FAILURE
13013 =20XW10+XW1 SU200 BI =20X51+X51 =20XW10+XW1/PEMO OFFL PEMO OFFLINE
13014 =20XW10+XW1 SU200 BI =20X51+X51 =20XW10+XW1/SYS WRN SYSTEM WARNING
13015 =20XW10+XW1 SU200 BI =20X51+X51 =20XW10+XW1/ELC LIN FLT ELECTRODE LINE FAULTY
13016 =20XW10+XW1 SU200 BI =20X51+X51 =20XW10+XW1/GPS WRN GPS CLOCK WARNING
13017 =20P01+P1 SU200 BI =20X51+X51 =20P01+P1-U201/LAN1 FLT LAN SWITCH 1 FAULT
13018 =20P01+P1 SU200 BI =20X51+X51 =20P01+P1-U202/LAN2 FLT LAN SWITCH 2 FAULT
13019 =20P01+P1 SU200 BI =20X51+X51 =20P01+P1-U201/PWR SPLY1 FLT LAN SWITCH 1 POWER SUPPLY FAULT
13020 =20P01+P1 SU200 BI =20X51+X51 =20P01+P1-U202/PWR SPLY2 FLT LAN SWITCH 2 POWER SUPPLY FAULT
13033 =20X71+X71 SU200 BI =20X51+X51 =20X71+X71/LFL MAJOR LINE FAULT LOCATOR MAJOR
13034 =20X71+X71 SU200 BI =20X51+X51 =20X71+X71/LFL MINOR LINE FAULT LOCATOR MINOR
13035 =20X71+X71 SU200 BI =20X51+X51 =20X71+X71/LFL OPERATED LINE FAULT LOCATOR OPERATED
13036 =20X71+X71 SU200 BI =20X51+X51 =20X71+X71/LFL SELF TEST LINE FAULT LOCATOR SELF TEST
13040 =20X40+X40 SU200 BI =20X51+X51 =20X40+X40/CUB FLT CUBICLE FAILURE
TELECOM Interface =20X40+X40
13041 =20Y01+Y21 SU200 BI =20X40+X40 =20Y01+Y11/PLC LNK1T FLT PLC EQUIPMENT LINK 1 FAULT
13042 =20Y01+Y22 SU200 BI =20X40+X40 =20Y01+Y12/PLC LNK2T FLT PLC EQUIPMENT LINK 2 FAULT
13043 =20Y01+Y23 SU200 BI =20X40+X40 =20Y01+Y13/PLC LNK3T FLT PLC EQUIPMENT LINK 3 FAULT
13044 =20Y01+Y24 SU200 BI =20X40+X40 =20Y01+Y14/PLC LNK4T FLT PLC EQUIPMENT LINK 4 FAULT
13045 =20Y01+Y25 SU200 BI =20X40+X40 =20Y01+Y15/PLC LNK5T FLT PLC EQUIPMENT LINK 5 FAULT
13046 =20Y01+Y26 SU200 BI =20X40+X40 =20Y01+Y16/PLC LNK6T FLT PLC EQUIPMENT LINK 6 FAULT
13047 =20Y01+Y27 SU200 BI =20X40+X40 =20Y01+Y17/PLC LNK7T FLT PLC EQUIPMENT LINK 7 FAULT
13048 =20Y01+Y28 SU200 BI =20X40+X40 =20Y01+Y18/PLC LNK8T FLT PLC EQUIPMENT LINK 8 FAULT
13049 =20Y01+Y29 SU200 BI =20X40+X40 =20Y01+Y19/PLC LNK9T FLT PLC EQUIPMENT LINK 9 FAULT
13057 =30Y01+Y11 SU200 BI =20X40+X40 =30Y01+Y11/PLC LNK1RT FLT PLC EQUIPMENT LINK 1 TO TALCHER FAULT
13058 =30Y01+Y12 SU200 BI =20X40+X40 =30Y01+Y12/PLC LNK2RT FLT PLC EQUIPMENT LINK 2 TO TALCHER FAULT
13059 =30Y01+Y13 SU200 BI =20X40+X40 =30Y01+Y13/PLC LNK3RT FLT PLC EQUIPMENT LINK 3 TO TALCHER FAULT
13060 =30Y01+Y14 SU200 BI =20X40+X40 =30Y01+Y14/PLC LNK4RT FLT PLC EQUIPMENT LINK 4 TO TALCHER FAULT
13061 =30Y01+Y15 SU200 BI =20X40+X40 =30Y01+Y15/PLC LNK5RT FLT PLC EQUIPMENT LINK 5 TO TALCHER FAULT
13062 =30Y01+Y16 SU200 BI =20X40+X40 =30Y01+Y16/PLC LNK6RT FLT PLC EQUIPMENT LINK 6 TO TALCHER FAULT
13063 =30Y01+Y17 SU200 BI =20X40+X40 =30Y01+Y17/PLC LNK7RT FLT PLC EQUIPMENT LINK 7 TO TALCHER FAULT
13064 =30Y01+Y18 SU200 BI =20X40+X40 =30Y01+Y18/PLC LNK8RT FLT PLC EQUIPMENT LINK 8 TO TALCHER FAULT
13065 =30Y01+Y19 SU200 BI =20X40+X40 =30Y01+Y19/PLC LNK9RT FLT PLC EQUIPMENT LINK 9 TO TALCHER FAULT
13081 =30Y01+Y21 SU200 BI =20X40+X40 =30Y01+Y21/PLC LNK1RK FLT PLC EQUIPMENT LINK 1 TO KOLAR FAULT
13082 =30Y01+Y22 SU200 BI =20X40+X40 =30Y01+Y22/PLC LNK2RK FLT PLC EQUIPMENT LINK 2 TO KOLAR FAULT
13083 =30Y01+Y23 SU200 BI =20X40+X40 =30Y01+Y23/PLC LNK3RK FLT PLC EQUIPMENT LINK 3 TO KOLAR FAULT
13084 =30Y01+Y24 SU200 BI =20X40+X40 =30Y01+Y24/PLC LNK4RK FLT PLC EQUIPMENT LINK 4 TO KOLAR FAULT
13085 =30Y01+Y25 SU200 BI =20X40+X40 =30Y01+Y25/PLC LNK5RK FLT PLC EQUIPMENT LINK 5 TO KOLAR FAULT
13086 =30Y01+Y26 SU200 BI =20X40+X40 =30Y01+Y26/PLC LNK6RK FLT PLC EQUIPMENT LINK 6 TO KOLAR FAULT
13087 =30Y01+Y27 SU200 BI =20X40+X40 =30Y01+Y27/PLC LNK7RK FLT PLC EQUIPMENT LINK 7 TO KOLAR FAULT
13088 =30Y01+Y28 SU200 BI =20X40+X40 =30Y01+Y28/PLC LNK8RK FLT PLC EQUIPMENT LINK 8 TO KOLAR FAULT
13089 =30Y01+Y29 SU200 BI =20X40+X40 =30Y01+Y29/PLC LNK9RK FLT PLC EQUIPMENT LINK 9 TO KOLAR FAULT
13097 =30NE01+NE01 SU200 BI =20X40+X40 =30NE01+NE01/AC FLT 415 VAC MAIN DISTR. AUX POWER FAULT
13098 =30NE01+NE01 SU200 BI =20X40+X40 =30NE01+NE01/AC 415V FLT1 415 VAC MAIN DISTRIBUTION 1 FAULT
13099 =30NE01+NE01 SU200 BI =20X40+X40 =30NE01+NE01/AC 415V FLT2 415 VAC MAIN DISTRIBUTION 2 FAULT
13100 =30NQ11+NQ11 SU200 BI =20X40+X40 =30NQ11+NQ11/DC 48V FLT1 48 VDC DISTRIBUTION 1 FAULT
13101 =30NQ21+NQ11 SU200 BI =20X40+X40 =30NQ21+NQ11/DC 48V FLT2 48 VDC DISTRIBUTION 2 FAULT
13102 =30NQ11+G11 SU200 BI =20X40+X40 =30NQ11+G11/CHARGER FLT1 48 V DC CHARGER 1 FAULT
13103 =30NQ11+G12 SU200 BI =20X40+X40 =30NQ11+G12/CHARGER FLT2 48 V DC CHARGER 2 FAULT
13104 =30NQ21+G11 SU200 BI =20X40+X40 =30NQ21+G11/CHARGER FLT3 48 V DC CHARGER 3 FAULT
13105 =30A00 SU200 BI =20X40+X40 =30NQ21+G11/FIRE ALARM BUILDING FIRE ALARM
13106 =30A00 SU200 BI =20X40+X40 =30NQ21+G11/AIR COND FLT BUILDING AIR CONDITION FAULT
13107 =30X71+X71 SU200 BI =20X40+X40 =30X71+X71/LFL MAYOR LINE FAULT LOCATOR MAJOR
13108 =30X71+X71 SU200 BI =20X40+X40 =30X71+X71/LFL MINOR LINE FAULT LOCATOR MINOR
13109 =30X71+X71 SU200 BI =20X40+X40 =30X71+X71/LFL OPERATED LINE FAULT LOCATOR OPERATED
13110 =30X71+X71 SU200 BI =20X40+X40 =30X71+X71/LFL SELF TEST LINE FAULT LOCATOR SELF TEST
13111 =31B01-Q51 SU200 BI =20X40+X40 =31B01-Q51/ON DC LINE EARTH SWITCH CLOSED
13112 =31B01-Q51 SU200 BI =20X40+X40 =31B01-Q51/OFF DC LINE EARTH SWITCH OPEN
13113 =32B02-Q51 SU200 BI =20X40+X40 =32B02-Q51/ON DC LINE EARTH SWITCH CLOSED
13114 =32B02-Q51 SU200 BI =20X40+X40 =32B02-Q51/OFF DC LINE EARTH SWITCH OPEN
13115 =30G01+G1 SU200 BI =20X40+X40 =30G01+G1/DG ENGINE FLT1 DIESEL GENERATOR 1 CHARGER FAULT
13116 =30G01+G2 SU200 BI =20X40+X40 =30G01+G2/DG ENGINE FLT2 DIESEL GENERATOR 2 CHARGER FAULT
13117 =30G01+G1 SU200 BI =20X40+X40 =30G01+G1/ST CHARG FLT1 DIESEL GENERATOR 1 CHARGER FAULT
13118 =30G01+G2 SU200 BI =20X40+X40 =30G01+G2/ST CHARG FLT2 DIESEL GENERATOR 2 CHARGER FAULT
13160 =20X51+X51 SU200 BI =20X40+X40 =20X51+X51/MCB TRP SER INTERFACE CUBICLE MCB TRIP
AC Station Control
Event No. Device Device Type Input Type Panel Event Code Event Text
AC Station control Interface =20C07+X1
- =20C07.C-T1 SU200 AI =20C07+X1 =20C07.C-T1 IDL ACF1 BANK CURRENT
- =20C07.C-T1 SU200 AI =20C07+X1 =20C07.C-T1 Q ACF1 BANK REACTIVE POWER
- =20C07.A-Q1 SU200 BO =20C07+X1 =20C07.A-Q1/CMD OFF ISOLATOR OPEN CMD
- =20C07.A-Q1 SU200 BO =20C07+X1 =20C07.A-Q1/CMD ON ISOLATOR CLOSE CMD
- =20C07.B-Q0 SU200 BO =20C07+X1 =20C07.B-Q0/CMD OFF CB OPEN CMD
- =20C07.B-Q0 SU200 BO =20C07+X1 =20C07.B-Q0/CMD ON CB CLOSE CMD
- =20C07.B-Q61 SU200 BO =20C07+X1 =20C07.B-Q61/CMD OFF ISOLATOR OPEN CMD
- =20C07.B-Q61 SU200 BO =20C07+X1 =20C07.B-Q61/CMD ON ISOLATOR CLOSE CMD
- =20C07.B-Q62 SU200 BO =20C07+X1 =20C07.B-Q62/CMD OFF ISOLATOR OPEN CMD
- =20C07.B-Q62 SU200 BO =20C07+X1 =20C07.B-Q62/CMD ON ISOLATOR CLOSE CMD
- =20C07.C-Q0 SU200 BO =20C07+X1 =20C07.C-Q0/CMD OFF CB OPEN CMD
- =20C07.C-Q0 SU200 BO =20C07+X1 =20C07.C-Q0/CMD ON CB CLOSE CMD
- =20C07.C-Q2 SU200 BO =20C07+X1 =20C07.C-Q2/CMD OFF ISOLATOR OPEN CMD
- =20C07.C-Q2 SU200 BO =20C07+X1 =20C07.C-Q2/CMD ON ISOLATOR CLOSE CMD
- =20C07.C-Q6 SU200 BO =20C07+X1 =20C07.C-Q6/CMD OFF ISOLATOR OPEN CMD
- =20C07.C-Q6 SU200 BO =20C07+X1 =20C07.C-Q6/CMD ON ISOLATOR CLOSE CMD
15081 =20C07.A-Q1 SU200 BI =20C07+X1 =20C07.A-Q1/OFF ISOLATOR OPEN
15082 =20C07.A-Q1 SU200 BI =20C07+X1 =20C07.A-Q1/ON ISOLATOR CLOSED
15083 =20C07.A-Q1 SU200 BI =20C07+X1 =20C07.A-Q1/FLT ISOLATOR FAULT
15084 =20C07.B-Q61 SU200 BI =20C07+X1 =20C07.B-Q61/OFF ISOLATOR OPEN
15085 =20C07.B-Q61 SU200 BI =20C07+X1 =20C07.B-Q61/ON ISOLATOR CLOSED
15086 =20C07.B-Q61 SU200 BI =20C07+X1 =20C07.B-Q61/FLT ISOLATOR FAULT
15087 =20C07.B-Q62 SU200 BI =20C07+X1 =20C07.B-Q62/OFF ISOLATOR OPEN
15088 =20C07.B-Q62 SU200 BI =20C07+X1 =20C07.B-Q62/ON ISOLATOR CLOSED
15089 =20C07.B-Q62 SU200 BI =20C07+X1 =20C07.B-Q62/FLT ISOLATOR FAILURE
15096 =20C07.A-Q51 SU200 BI =20C07+X1 =20C07.A-Q51/OFF EARTH SWITCH OPEN
15097 =20C07.A-Q51 SU200 BI =20C07+X1 =20C07.A-Q51/ON EARTH SWITCH CLOSED
15098 =20C07.A-Q51 SU200 BI =20C07+X1 =20C07.A-Q51/FLT EARTH SWITCH FAULT
15099 =20C07.B-Q51 SU200 BI =20C07+X1 =20C07.B-Q51/OFF EARTH SWITCH OPEN
15100 =20C07.B-Q51 SU200 BI =20C07+X1 =20C07.B-Q51/ON EARTH SWITCH CLOSED
15101 =20C07.B-Q51 SU200 BI =20C07+X1 =20C07.B-Q51/FLT EARTH SWITCH FAULT
15102 =20C07.B-Q52 SU200 BI =20C07+X1 =20C07.B-Q52/OFF EARTH SWITCH OPEN
15103 =20C07.B-Q52 SU200 BI =20C07+X1 =20C07.B-Q52/ON EARTH SWITCH CLOSED
15104 =20C07.B-Q52 SU200 BI =20C07+X1 =20C07.B-Q52/FLT EARTH SWITCH FAULT
15109 =20C07+S1 SU200 BI =20C07+X1 =20C07.B/LOC CTRL ES DS LOCAL CONTROL
15110 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/OFF CIRCUIT BREAKER OPEN
15111 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/ON CIRCUIT BREAKER CLOSED
15113 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15114 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15115 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15116 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15117 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15118 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15119 =20C07.B-Q0 SU200 BI =20C07+X1 =20C07.B-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15124 =20C07.C-Q2 SU200 BI =20C07+X1 =20C07.C-Q2/OFF ISOLATOR OPEN
15125 =20C07.C-Q2 SU200 BI =20C07+X1 =20C07.C-Q2/ON ISOLATOR CLOSED
15126 =20C07.C-Q2 SU200 BI =20C07+X1 =20C07.C-Q2/FLT ISOLATOR FAILURE
15127 =20C07.C-Q6 SU200 BI =20C07+X1 =20C07.C-Q6/OFF ISOLATOR OPEN
15128 =20C07.C-Q6 SU200 BI =20C07+X1 =20C07.C-Q6/ON ISOLATOR CLOSED
15129 =20C07.C-Q6 SU200 BI =20C07+X1 =20C07.C-Q6/FLT ISOLATOR FAILURE
15133 =20C07.C-Q51 SU200 BI =20C07+X1 =20C07.C-Q51/OFF EARTH SWITCH OPEN
15134 =20C07.C-Q51 SU200 BI =20C07+X1 =20C07.C-Q51/ON EARTH SWITCH CLOSED
15135 =20C07.C-Q51 SU200 BI =20C07+X1 =20C07.C-Q51/FLT EARTH SWITCH FAILURE
15136 =20C07.C-Q52 SU200 BI =20C07+X1 =20C07.C-Q52/OFF EARTH SWITCH OPEN
15137 =20C07.C-Q52 SU200 BI =20C07+X1 =20C07.C-Q52/ON EARTH SWITCH CLOSED
15138 =20C07.C-Q52 SU200 BI =20C07+X1 =20C07.C-Q52/FLT EARTH SWITCH FAILURE
15149 =20C07+S1 SU200 BI =20C07+X1 =20C07.C/LOC CTRL ES DS LOCAL CONTROL
15150 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/OFF CIRCUIT BREAKER OPEN
15151 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/ON CIRCUIT BREAKER CLOSED
15153 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15154 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15155 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15156 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15157 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15158 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15159 =20C07.C-Q0 SU200 BI =20C07+X1 =20C07.C-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15193 =20C08+X1 SU200 BI =20C07+X1 =20C08+X1/FLT DC SPLY AC CONTROL INTERFACE CUBICLE
15194 =20C07+S1 SU200 BI =20C07+X1 =20C07+S1/VT MCB TRP AC-LOCAL CONTROL: VOLT. TRANS. MCB TRIP
15196 =20C07+S1 SU200 BI =20C07+X1 =20C07+S1/FLT AC SPLY AC-LOCAL CONTROL CUBICLE
15197 =20C07+S1 SU200 BI =20C07+X1 =20C07+S1/FLT DC SPLY AC-LOCAL CONTROL CUBICLE
AC Station control Interface =20C08+X1
- =20C08.A-T1 SU200 AI =20C08+X1 =20C08.A-T1 IDL ACF2 BANK CURRENT
- =20C08.A-T1 SU200 AI =20C08+X1 =20C08.A-T1 Q ACF2 BANK REACTIVE POWER
- =20C09-T15/UL1 SU200 AI =20C08+X1 =20C09-T15/UL1 BUSBAR 1A VOLTAGE UL1-N
- =20C09-T15/UL2 SU200 AI =20C08+X1 =20C09-T15/UL2 BUSBAR 1A VOLTAGE UL2-N
- =20C09-T15/UL3 SU200 AI =20C08+X1 =20C09-T15/UL3 BUSBAR 1A VOLTAGE UL3-N
- =20C09-T25/UL1 SU200 AI =20C08+X1 =20C09-T25/UL1 BUSBAR 2A VOLTAGE UL1-N
- =20C09-T25/UL2 SU200 AI =20C08+X1 =20C09-T25/UL2 BUSBAR 2A VOLTAGE UL2-N
- =20C09-T25/UL3 SU200 AI =20C08+X1 =20C09-T25/UL3 BUSBAR 2A VOLTAGE UL3-N
- =20C09-T15/UL1 SU200 AI =20C08+X1 =20C09-T15/UL1 BUSBAR 1A VOLTAGE UL1-N
- =20C09-T15/UL2 SU200 AI =20C08+X1 =20C09-T15/UL2 BUSBAR 1A VOLTAGE UL2-N
- =20C09-T15/UL3 SU200 AI =20C08+X1 =20C09-T15/UL3 BUSBAR 1A VOLTAGE UL3-N
- =20C09-T25/UL1 SU200 AI =20C08+X1 =20C09-T25/UL1 BUSBAR 2A VOLTAGE UL1-N
- =20C09-T25/UL2 SU200 AI =20C08+X1 =20C09-T25/UL2 BUSBAR 2A VOLTAGE UL2-N
- =20C09-T25/UL3 SU200 AI =20C08+X1 =20C09-T25/UL3 BUSBAR 2A VOLTAGE UL3-N
- =20C08.A-Q0 SU200 BO =20C08+X1 =20C08.A-Q0/CMD OFF CB OPEN CMD
- =20C08.A-Q0 SU200 BO =20C08+X1 =20C08.A-Q0/CMD ON CB CLOSE CMD
- =20C08.A-Q1 SU200 BO =20C08+X1 =20C08.A-Q1/CMD OFF ISOLATOR OPEN CMD
- =20C08.A-Q1 SU200 BO =20C08+X1 =20C08.A-Q1/CMD ON ISOLATOR OPEN CMD
- =20C08.A-Q6 SU200 BO =20C08+X1 =20C08.A-Q6/CMD OFF ISOLATOR OPEN CMD
- =20C08.A-Q6 SU200 BO =20C08+X1 =20C08.A-Q6/CMD ON ISOLATOR CLOSE CMD
- =20C08.B-Q0 SU200 BO =20C08+X1 =20C08.B-Q0/CMD OFF CB OPEN CMD
- =20C08.B-Q0 SU200 BO =20C08+X1 =20C08.B-Q0/CMD ON CB CLOSE CMD
- =20C08.B-Q61 SU200 BO =20C08+X1 =20C08.B-Q61/CMD OFF ISOLATOR OPEN CMD
- =20C08.B-Q61 SU200 BO =20C08+X1 =20C08.B-Q61/CMD ON ISOLATOR CLOSE CMD
- =20C08.B-Q62 SU200 BO =20C08+X1 =20C08.B-Q62/CMD OFF ISOLATOR OPEN CMD
- =20C08.B-Q62 SU200 BO =20C08+X1 =20C08.B-Q62/CMD ON ISOLATOR CLOSE CMD
- =20C08.C-Q0 SU200 BO =20C08+X1 =20C08.C-Q0/CMD OFF CB OPEN CMD
- =20C08.C-Q0 SU200 BO =20C08+X1 =20C08.C-Q0/CMD ON CB CLOSE CMD
- =20C08.C-Q2 SU200 BO =20C08+X1 =20C08.C-Q2/CMD OFF ISOLATOR OPEN CMD
- =20C08.C-Q2 SU200 BO =20C08+X1 =20C08.C-Q2/CMD ON ISOLATOR CLOSE CMD
- =20C08.C-Q6 SU200 BO =20C08+X1 =20C08.C-Q6/CMD OFF ISOLATOR OPEN CMD
- =20C08.C-Q6 SU200 BO =20C08+X1 =20C08.C-Q6/CMD ON ISOLATOR CLOSE CMD
- =20C08.C-Q9 SU200 BO =20C08+X1 =20C08.C-Q9/CMD OFF ISOLATOR OPEN CMD
- =20C08.C-Q9 SU200 BO =20C08+X1 =20C08.C-Q9/CMD ON ISOLATOR CLOSE CMD
15201 =20C08.A-Q1 SU200 BI =20C08+X1 =20C08.A-Q1/OFF ISOLATOR OPEN
15202 =20C08.A-Q1 SU200 BI =20C08+X1 =20C08.A-Q1/ON ISOLATOR CLOSED
15203 =20C08.A-Q1 SU200 BI =20C08+X1 =20C08.A-Q1/FLT ISOLATOR FAILURE
15204 =20C08.A-Q6 SU200 BI =20C08+X1 =20C08.A-Q6/OFF ISOLATOR OPEN
15205 =20C08.A-Q6 SU200 BI =20C08+X1 =20C08.A-Q6/ON ISOLATOR CLOSED
15206 =20C08.A-Q6 SU200 BI =20C08+X1 =20C08.A-Q6/FLT ISOLATOR FAILURE
15213 =20C08.A-Q51 SU200 BI =20C08+X1 =20C08.A-Q51/OFF EARTH SWITCH OPEN
15214 =20C08.A-Q51 SU200 BI =20C08+X1 =20C08.A-Q51/ON EARTH SWITCH CLOSED
15215 =20C08.A-Q51 SU200 BI =20C08+X1 =20C08.A-Q51/FLT EARTH SWITCH FAILURE
15216 =20C08.A-Q52 SU200 BI =20C08+X1 =20C08.A-Q52/OFF EARTH SWITCH OPEN
15217 =20C08.A-Q52 SU200 BI =20C08+X1 =20C08.A-Q52/ON EARTH SWITCH CLOSED
15218 =20C08.A-Q52 SU200 BI =20C08+X1 =20C08.A-Q52/FLT EARTH SWITCH FAILURE
15229 =20C08+S1 SU200 BI =20C08+X1 =20C08.A/LOC CTRL ES DS LOCAL CONTROL
15230 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/OFF CIRCUIT BREAKER OPEN
15231 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/ON CIRCUIT BREAKER CLOSED
15233 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15234 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15235 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15236 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15237 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15238 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15239 =20C08.A-Q0 SU200 BI =20C08+X1 =20C08.A-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15241 =20C08.B-Q61 SU200 BI =20C08+X1 =20C08.B-Q61/OFF ISOLATOR OPEN
15242 =20C08.B-Q61 SU200 BI =20C08+X1 =20C08.B-Q61/ON ISOLATOR CLOSED
15243 =20C08.B-Q61 SU200 BI =20C08+X1 =20C08.B-Q61/FLT ISOLATOR FAILURE
15244 =20C08.B-Q62 SU200 BI =20C08+X1 =20C08.B-Q62/OFF ISOLATOR OPEN
15245 =20C08.B-Q62 SU200 BI =20C08+X1 =20C08.B-Q62/ON ISOLATOR CLOSED
15246 =20C08.B-Q62 SU200 BI =20C08+X1 =20C08.B-Q62/FLT ISOLATOR FAILURE
15253 =20C08.B-Q51 SU200 BI =20C08+X1 =20C08.B-Q51/OFF EARTH SWITCH OPEN
15254 =20C08.B-Q51 SU200 BI =20C08+X1 =20C08.B-Q51/ON EARTH SWITCH CLOSED
15255 =20C08.B-Q51 SU200 BI =20C08+X1 =20C08.B-Q51/FLT EARTH SWITCH FAILURE
15256 =20C08.B-Q52 SU200 BI =20C08+X1 =20C08.B-Q52/OFF EARTH SWITCH OPEN
15257 =20C08.B-Q52 SU200 BI =20C08+X1 =20C08.B-Q52/ON EARTH SWITCH CLOSED
15258 =20C08.B-Q52 SU200 BI =20C08+X1 =20C08.B-Q52/FLT EARTH SWITCH FAILURE
15268 =20C00+U1 SU200 BI =20C08+X1 =20C08.B-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
15269 =20C08+S1 SU200 BI =20C08+X1 =20C08.B/LOC CTRL ES DS LOCAL CONTROL
15270 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/OFF CIRCUIT BREAKER OPEN
15271 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/ON CIRCUIT BREAKER CLOSED
15273 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15274 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15275 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15276 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15277 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15278 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15279 =20C08.B-Q0 SU200 BI =20C08+X1 =20C08.B-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15284 =20C08.C-Q2 SU200 BI =20C08+X1 =20C08.C-Q2/OFF ISOLATOR OPEN
15285 =20C08.C-Q2 SU200 BI =20C08+X1 =20C08.C-Q2/ON ISOLATOR CLOSED
15286 =20C08.C-Q2 SU200 BI =20C08+X1 =20C08.C-Q2/FLT ISOLATOR FAILURE
15287 =20C08.C-Q6 SU200 BI =20C08+X1 =20C08.C-Q6/OFF ISOLATOR OPEN
15288 =20C08.C-Q6 SU200 BI =20C08+X1 =20C08.C-Q6/ON ISOLATOR CLOSED
15289 =20C08.C-Q6 SU200 BI =20C08+X1 =20C08.C-Q6/FLT ISOLATOR FAILURE
15290 =20C08.C-Q9 SU200 BI =20C08+X1 =20C08.C-Q9/OFF ISOLATOR OPEN
15291 =20C08.C-Q9 SU200 BI =20C08+X1 =20C08.C-Q9/ON ISOLATOR CLOSED
15292 =20C08.C-Q9 SU200 BI =20C08+X1 =20C08.C-Q9/FLT ISOLATOR FAILURE
15293 =20C08.C-Q51 SU200 BI =20C08+X1 =20C08.C-Q51/OFF EARTH SWITCH OPEN
15294 =20C08.C-Q51 SU200 BI =20C08+X1 =20C08.C-Q51/ON EARTH SWITCH CLOSED
15295 =20C08.C-Q51 SU200 BI =20C08+X1 =20C08.C-Q51/FLT EARTH SWITCH FAILURE
15296 =20C08.C-Q52 SU200 BI =20C08+X1 =20C08.C-Q52/OFF EARTH SWITCH OPEN
15297 =20C08.C-Q52 SU200 BI =20C08+X1 =20C08.C-Q52/ON EARTH SWITCH CLOSED
15298 =20C08.C-Q52 SU200 BI =20C08+X1 =20C08.C-Q52/FLT EARTH SWITCH FAILURE
15299 =20C08.C-Q53 SU200 BI =20C08+X1 =20C08.C-Q53/OFF EARTH SWITCH OPEN
15300 =20C08.C-Q53 SU200 BI =20C08+X1 =20C08.C-Q53/ON EARTH SWITCH CLOSED
15301 =20C08.C-Q53 SU200 BI =20C08+X1 =20C08.C-Q53/FLT EARTH SWITCH FAILURE
15302 =20C08.C-Q8 SU200 BI =20C08+X1 =20C08.C-Q8/OFF EARTH SWITCH OPEN
15303 =20C08.C-Q8 SU200 BI =20C08+X1 =20C08.C-Q8/ON EARTH SWITCH CLOSED
15304 =20C08.C-Q8 SU200 BI =20C08+X1 =20C08.C-Q8/FLT EARTH SWITCH FAILURE
15308 =20C00+U1 SU200 BI =20C08+X1 =20C08.C-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
15309 =20C08+S1 SU200 BI =20C08+X1 =20C08.C/LOC CTRL ES DS LOCAL CONTROL
15310 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/OFF CIRCUIT BREAKER OPEN
15311 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/ON CIRCUIT BREAKER CLOSED
15313 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15314 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15315 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15316 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15317 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15318 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15319 =20C08.C-Q0 SU200 BI =20C08+X1 =20C08.C-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15353 =20C07+X1 SU200 BI =20C08+X1 =20C07+X1/FLT DC SPLY AC CONTROL INTERFACE CUBICLE
15354 =20C08+S1 SU200 BI =20C08+X1 =20C08+S1/VT MCB TRP AC-LOCAL CONTROL: VOLT. TRANS. MCB TRIP
15356 =20C08+S1 SU200 BI =20C08+X1 =20C08+S1/FLT AC SPLY AC-LOCAL CONTROL CUBICLE
15357 =20C08+S1 SU200 BI =20C08+X1 =20C08+S1/FLT DC SPLY AC-LOCAL CONTROL CUBICLE
AC Station control Interface =20C09+X1
- =20C09-T11/IL1 SU200 AI =20C09+X1 =20C09-T11/IL1 BUSBAR 1 CURRENT PHASE L1
- =20C09-T15/UL1 SU200 AI =20C09+X1 =20C09-T15/UL1 BUSBAR 1A VOLTAGE UL1-N
- =20C10C-T16/UL1 SU200 AI =20C09+X1 =20C10C-T16/UL1 BUSBAR 1B VOLTAGE UL1-N
- =20C09-T15/FL1 SU200 AI =20C09+X1 =20C09-T15/FL1 BUSBAR 1A FREQUENCY UL1-N
- =20C10C-T16/FL1 SU200 AI =20C09+X1 =20C10C-T16/FL1 BUSBAR 1B FREQUENCY UL1-N
- =20C09-T21/IL1 SU200 AI =20C09+X1 =20C09-T21/IL1 BUSBAR 2 CURRENT PHASE L1
- =20C09-T25/UL1 SU200 AI =20C09+X1 =20C09-T25/UL1 BUSBAR 2A VOLTAGE UL1-N
- =20C10C-T26/UL1 SU200 AI =20C09+X1 =20C10C-T26/UL1 BUSBAR 2B VOLTAGE UL1-N
- =20C09-T25/FL1 SU200 AI =20C09+X1 =20C09-T25/FL1 BUSBAR 2A FREQUENCY UL1-N
- =20C10C-T26/FL1 SU200 AI =20C09+X1 =20C10C-T26/FL1 BUSBAR 2B FREQUENCY UL1-N
- =20C09-Q01 SU200 BO =20C09+X1 =20C09-Q01/CMD OFF CIRCUIT BREAKER OPEN
- =20C09-Q01 SU200 BO =20C09+X1 =20C09-Q01/CMD ON CIRCUIT BREAKER CLOSED
- =20C09-Q11 SU200 BO =20C09+X1 =20C09-Q11/CMD OFF ISOLATOR OPEN
- =20C09-Q11 SU200 BO =20C09+X1 =20C09-Q11/CMD ON ISOLATOR CLOSED
- =20C09-Q12 SU200 BO =20C09+X1 =20C09-Q12/CMD OFF ISOLATOR OPEN
- =20C09-Q12 SU200 BO =20C09+X1 =20C09-Q12/CMD ON ISOLATOR CLOSED
- =20C09-Q21 SU200 BO =20C09+X1 =20C09-Q21/CMD ON ISOLATOR OPEN
- =20C09-Q21 SU200 BO =20C09+X1 =20C09-Q21/CMD OFF ISOLATOR CLOSED
- =20C09-Q22 SU200 BO =20C09+X1 =20C09-Q22/CMD OFF ISOLATOR OPEN
- =20C09-Q22 SU200 BO =20C09+X1 =20C09-Q22/CMD ON ISOLATOR CLOSED
- =20C09-Q02 SU200 BO =20C09+X1 =20C09-Q02/CMD OFF CIRCUIT BREAKER OPEN
- =20C09-Q02 SU200 BO =20C09+X1 =20C09-Q02/CMD ON CIRCUIT BREAKER CLOSED
15361 =20C09-Q11 SU200 BI =20C09+X1 =20C09-Q11/OFF ISOLATOR OPEN
15362 =20C09-Q11 SU200 BI =20C09+X1 =20C09-Q11/ON ISOLATOR CLOSED
15363 =20C09-Q11 SU200 BI =20C09+X1 =20C09-Q11/FLT ISOLATOR FAILURE
15364 =20C09-Q12 SU200 BI =20C09+X1 =20C09-Q12/OFF ISOLATOR OPEN
15365 =20C09-Q12 SU200 BI =20C09+X1 =20C09-Q12/ON ISOLATOR CLOSED
15366 =20C09-Q12 SU200 BI =20C09+X1 =20C09-Q12/FLT ISOLATOR FAILURE
15367 =20C09-Q21 SU200 BI =20C09+X1 =20C09-Q21/OFF ISOLATOR OPEN
15368 =20C09-Q21 SU200 BI =20C09+X1 =20C09-Q21/ON ISOLATOR CLOSED
15369 =20C09-Q21 SU200 BI =20C09+X1 =20C09-Q21/FLT ISOLATOR FAILURE
15370 =20C09-Q22 SU200 BI =20C09+X1 =20C09-Q22/OFF ISOLATOR OPEN
15371 =20C09-Q22 SU200 BI =20C09+X1 =20C09-Q22/ON ISOLATOR CLOSED
15372 =20C09-Q22 SU200 BI =20C09+X1 =20C09-Q22/FLT ISOLATOR FAILURE
15373 =20C09-Q15 SU200 BI =20C09+X1 =20C09-Q15/OFF EARTH SWITCH OPEN
15374 =20C09-Q15 SU200 BI =20C09+X1 =20C09-Q15/ON EARTH SWITCH CLOSED
15375 =20C09-Q15 SU200 BI =20C09+X1 =20C09-Q15/FLT EARTH SWITCH FAILURE
15376 =20C09-Q16 SU200 BI =20C09+X1 =20C09-Q16/OFF EARTH SWITCH OPEN
15377 =20C09-Q16 SU200 BI =20C09+X1 =20C09-Q16/ON EARTH SWITCH CLOSED
15378 =20C09-Q16 SU200 BI =20C09+X1 =20C09-Q16/FLT EARTH SWITCH FAILURE
15379 =20C09-Q25 SU200 BI =20C09+X1 =20C09-Q25/OFF EARTH SWITCH OPEN
15380 =20C09-Q25 SU200 BI =20C09+X1 =20C09-Q25/ON EARTH SWITCH CLOSED
15381 =20C09-Q25 SU200 BI =20C09+X1 =20C09-Q25/FLT EARTH SWITCH FAILURE
15382 =20C09-Q26 SU200 BI =20C09+X1 =20C09-Q26/OFF EARTH SWITCH OPEN
15383 =20C09-Q26 SU200 BI =20C09+X1 =20C09-Q26/ON EARTH SWITCH CLOSED
15384 =20C09-Q26 SU200 BI =20C09+X1 =20C09-Q26/FLT EARTH SWITCH FAILURE
15385 =20C09+X1 SU200 BI =20C09+X1 =20C09+X1/FLT BIN TRSD AC CONTROL INTERFACE ???
15386 =20C09+X1 SU200 BI =20C09+X1 =20C09+X1/FLT OLM 1 FIELDBUS 1 OLM FAULTY
15387 =20C09+X1 SU200 BI =20C09+X1 =20C09+X1/FLT OLM 2 FIELDBUS 2 OLM FAULTY
15389 =20C09+S1 SU200 BI =20C09+X1 =20C09/LOC CTRL ES DS LOCAL CONTROL
15390 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/OFF CIRCUIT BREAKER OPEN
15391 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/ON CIRCUIT BREAKER CLOSED
15393 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15394 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15395 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15396 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/OIL SYS FLT CB OIL SYSTEM FAULTY
15397 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15398 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/POLE DISCREP CB PHASES NOT TOGETHER
15399 =20C09-Q01 SU200 BI =20C09+X1 =20C09-Q01/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15401 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF07B TRP BREAKER FAILURE PROTECTION
15402 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF07C TRP BREAKER FAILURE PROTECTION
15403 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF08A TRP BREAKER FAILURE PROTECTION
15404 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF08B TRP BREAKER FAILURE PROTECTION
15405 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF08C TRP BREAKER FAILURE PROTECTION
15406 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF09Q01 TRP BREAKER FAILURE PROTECTION
15407 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF09Q02 TRP BREAKER FAILURE PROTECTION
15408 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF10A TRP BREAKER FAILURE PROTECTION
15409 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF10B TRP BREAKER FAILURE PROTECTION
15410 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/50BF10C TRP BREAKER FAILURE PROTECTION
15411 =20C00+R1 SU200 BI =20C09+X1 =20C00+R1/MCB TRP BREAKER FAILURE PROT. PANEL MCB TRIP
15412 =20C00+R2.A SU200 BI =20C09+X1 =20C00+R2.A/20C07B TC FLT TRIP CIRCUIT PROTECTION
15413 =20C00+R2.A SU200 BI =20C09+X1 =20C00+R2.A/20C07C TC FLT TRIP CIRCUIT PROTECTION
15414 =20C00+R2.A SU200 BI =20C09+X1 =20C00+R2.A/20C08A TC FLT TRIP CIRCUIT PROTECTION
15415 =20C00+R2.A SU200 BI =20C09+X1 =20C00+R2.A/20C08B TC FLT TRIP CIRCUIT PROTECTION
15416 =20C00+R2.B SU200 BI =20C09+X1 =20C00+R2.B/20C08C TC FLT TRIP CIRCUIT PROTECTION
15417 =20C00+R2.B SU200 BI =20C09+X1 =20C00+R2.B/20C09 TC1 FLT TRIP CIRCUIT PROTECTION
15418 =20C00+R2.B SU200 BI =20C09+X1 =20C00+R2.B/20C09 TC2 FLT TRIP CIRCUIT PROTECTION
15419 =20C00+R2.B SU200 BI =20C09+X1 =20C00+R2.B/20C10A TC FLT TRIP CIRCUIT PROTECTION
15420 =20C00+R2.C SU200 BI =20C09+X1 =20C00+R2.C/20C10B TC FLT TRIP CIRCUIT PROTECTION
15421 =20C00+R2.C SU200 BI =20C09+X1 =20C00+R2.C/20C10C TC FLT TRIP CIRCUIT PROTECTION
15422 =20C00+R2.A SU200 BI =20C09+X1 =20C00+R2.A/MCB TRP TRIP CIRCUIT PROTECTION PANEL MCB TRIP
15425 =20C10+X1 SU200 BI =20C09+X1 =20C10+X1/FLT DC SPLY AC CONTROL INTERFACE CUBICLE
15426 =20C09+S1 SU200 BI =20C09+X1 =20C09+S1/VT MCB TRP AC-LOCAL CONTROL: VOLT. TRANS. MCB TRIP
15428 =20C09+S1 SU200 BI =20C09+X1 =20C09+S1/FLT AC SPLY AC-LOCAL CONTROL CUBICLE
15429 =20C09+S1 SU200 BI =20C09+X1 =20C09+S1/FLT DC SPLY AC-LOCAL CONTROL CUBICLE
15430 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/OFF CIRCUIT BREAKER OPEN
15431 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/ON CIRCUIT BREAKER CLOSED
15433 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15434 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15435 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15436 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/OIL SYS FLT CB OIL SYSTEM FAULTY
15437 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15438 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/POLE DISCREP CB PHASES NOT TOGETHER
15439 =20C09-Q02 SU200 BI =20C09+X1 =20C09-Q02/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
AC Station control Interface =20C10+X1
- =20C10.C-T16/UL1 SU200 AI =20C10+X1 =20C10.C-T16/UL1 BUSBAR 1B VOLATGE UL1-N
- =20C10.C-T16/UL2 SU200 AI =20C10+X1 =20C10.C-T16/UL2 BUSBAR 1B VOLATGE UL2-N
- =20C10.C-T16/UL3 SU200 AI =20C10+X1 =20C10.C-T16/UL3 BUSBAR 1B VOLATGE UL3-N
- =20C10.C-T26/UL1 SU200 AI =20C10+X1 =20C10.C-T26/UL1 BUSBAR 2B VOLATGE UL1-N
- =20C10.C-T26/UL2 SU200 AI =20C10+X1 =20C10.C-T26/UL2 BUSBAR 2B VOLATGE UL2-N
- =20C10.C-T26/UL3 SU200 AI =20C10+X1 =20C10.C-T26/UL3 BUSBAR 2B VOLATGE UL3-N
- =20C10.C-T1/IDL2 SU200 AI =20C10+X1 =20C10.C-T1/IDL2 AC FILTER BANK 3 CURRENT
- =20C10.C-T1/Q SU200 AI =20C10+X1 =20C10.C-T1/Q AC FILTER BANK 3 REACTIVE POWER
- =20C10.A-Q0 SU200 BO =20C10+X1 =20C10.A-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20C10.A-Q0 SU200 BO =20C10+X1 =20C10.A-Q0/CMD ON CIRCUIT BREAKER CLOSED
- =20C10.A-Q1 SU200 BO =20C10+X1 =20C10.A-Q0/CMD OFF ISOLATOR OPEN
- =20C10.A-Q1 SU200 BO =20C10+X1 =20C10.A-Q0/CMD ON ISOLATOR CLOSED
- =20C10.A-Q6 SU200 BO =20C10+X1 =20C10.A-Q6/CMD OFF ISOLATOR OPEN
- =20C10.A-Q6 SU200 BO =20C10+X1 =20C10.A-Q6/CMD ON ISOLATOR CLOSED
- =20C10.A-Q9 SU200 BO =20C10+X1 =20C10.A-Q9/CMD OFF ISOLATOR OPEN
- =20C10.A-Q9 SU200 BO =20C10+X1 =20C10.A-Q9/CMD ON ISOLATOR CLOSED
- =20C10.B-Q0 SU200 BO =20C10+X1 =20C10.B-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20C10.B-Q0 SU200 BO =20C10+X1 =20C10.B-Q0/CMD ON CIRCUIT BREAKER CLOSED
- =20C10.B-Q61 SU200 BO =20C10+X1 =20C10.B-Q61/CMD OFF ISOLATOR OPEN
- =20C10.B-Q61 SU200 BO =20C10+X1 =20C10.B-Q61/CMD ON ISOLATOR CLOSED
- =20C10.B-Q62 SU200 BO =20C10+X1 =20C10.B-Q62/CMD OFF ISOLATOR OPEN
- =20C10.B-Q62 SU200 BO =20C10+X1 =20C10.B-Q62/CMD ON ISOLATOR CLOSED
- =20C10.C-Q0 SU200 BO =20C10+X1 =20C10.C-Q0/CMD OFF CIRCUIT BREAKER OPEN
- =20C10.C-Q0 SU200 BO =20C10+X1 =20C10.C-Q0/CMD ON CIRCUIT BREAKER CLOSED
- =20C10.C-Q2 SU200 BO =20C10+X1 =20C10.C-Q2/CMD OFF ISOLATOR OPEN
- =20C10.C-Q2 SU200 BO =20C10+X1 =20C10.C-Q2/CMD ON ISOLATOR CLOSED
- =20C10.C-Q6 SU200 BO =20C10+X1 =20C10.C-Q6/CMD OFF ISOLATOR OPEN
- =20C10.C-Q6 SU200 BO =20C10+X1 =20C10.C-Q6/CMD ON ISOLATOR CLOSED
15441 =20C10.A-Q1 SU200 BI =20C10+X1 =20C10.A-Q1/OFF ISOLATOR OPEN
15442 =20C10.A-Q1 SU200 BI =20C10+X1 =20C10.A-Q1/ON ISOLATOR CLOSED
15443 =20C10.A-Q1 SU200 BI =20C10+X1 =20C10.A-Q1/FLT ISOLATOR FAILURE
15444 =20C10.A-Q6 SU200 BI =20C10+X1 =20C10.A-Q6/OFF ISOLATOR OPEN
15445 =20C10.A-Q6 SU200 BI =20C10+X1 =20C10.A-Q6/ON ISOLATOR CLOSED
15446 =20C10.A-Q6 SU200 BI =20C10+X1 =20C10.A-Q6/FLT ISOLATOR FAILURE
15447 =20C10.A-Q9 SU200 BI =20C10+X1 =20C10.A-Q9/OFF ISOLATOR OPEN
15448 =20C10.A-Q9 SU200 BI =20C10+X1 =20C10.A-Q9/ON ISOLATOR CLOSED
15449 =20C10.A-Q9 SU200 BI =20C10+X1 =20C10.A-Q9/FLT ISOLATOR FAILURE
15453 =20C10.A-Q51 SU200 BI =20C10+X1 =20C10.A-Q51/OFF EARTH SWITCH OPEN
15454 =20C10.A-Q51 SU200 BI =20C10+X1 =20C10.A-Q51/ON EARTH SWITCH CLOSED
15455 =20C10.A-Q51 SU200 BI =20C10+X1 =20C10.A-Q51/FLT EARTH SWITCH FAILURE
15456 =20C10.A-Q52 SU200 BI =20C10+X1 =20C10.A-Q52/OFF EARTH SWITCH OPEN
15457 =20C10.A-Q52 SU200 BI =20C10+X1 =20C10.A-Q52/ON EARTH SWITCH CLOSED
15458 =20C10.A-Q52 SU200 BI =20C10+X1 =20C10.A-Q52/FLT EARTH SWITCH FAILURE
15459 =20C10.A-Q53 SU200 BI =20C10+X1 =20C10.A-Q53/OFF EARTH SWITCH OPEN
15460 =20C10.A-Q53 SU200 BI =20C10+X1 =20C10.A-Q53/ON EARTH SWITCH CLOSED
15461 =20C10.A-Q53 SU200 BI =20C10+X1 =20C10.A-Q53/FLT EARTH SWITCH FAILURE
15462 =20C10.A-Q8 SU200 BI =20C10+X1 =20C10.A-Q8/OFF EARTH SWITCH OPEN
15463 =20C10.A-Q8 SU200 BI =20C10+X1 =20C10.A-Q8/ON EARTH SWITCH CLOSED
15464 =20C10.A-Q8 SU200 BI =20C10+X1 =20C10.A-Q8/FLT EARTH SWITCH FAILURE
15468 =20C00+U1 SU200 BI =20C10+X1 =20C10.A-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
15469 =20C10+S1 SU200 BI =20C10+X1 =20C10.A/LOC CTRL ES DS LOCAL CONTROL
15470 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/OFF CIRCUIT BREAKER OPEN
15471 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/ON CIRCUIT BREAKER CLOSED
15473 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15474 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15475 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15476 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15477 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15478 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15479 =20C10.A-Q0 SU200 BI =20C10+X1 =20C10.A-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15481 =20C10.B-Q61 SU200 BI =20C10+X1 =20C10.B-Q61/OFF ISOLATOR OPEN
15482 =20C10.B-Q61 SU200 BI =20C10+X1 =20C10.B-Q61/ON ISOLATOR CLOSED
15483 =20C10.B-Q61 SU200 BI =20C10+X1 =20C10.B-Q61/FLT ISOLATOR FAILURE
15484 =20C10.B-Q62 SU200 BI =20C10+X1 =20C10.B-Q62/OFF ISOLATOR OPEN
15485 =20C10.B-Q62 SU200 BI =20C10+X1 =20C10.B-Q62/ON ISOLATOR CLOSED
15486 =20C10.B-Q62 SU200 BI =20C10+X1 =20C10.B-Q62/FLT ISOLATOR FAILURE
15493 =20C10.B-Q51 SU200 BI =20C10+X1 =20C10.B-Q51/OFF EARTH SWITCH OPEN
15494 =20C10.B-Q51 SU200 BI =20C10+X1 =20C10.B-Q51/ON EARTH SWITCH CLOSED
15495 =20C10.B-Q51 SU200 BI =20C10+X1 =20C10.B-Q51/FLT EARTH SWITCH FAILURE
15496 =20C10.B-Q52 SU200 BI =20C10+X1 =20C10.B-Q52/OFF EARTH SWITCH OPEN
15497 =20C10.B-Q52 SU200 BI =20C10+X1 =20C10.B-Q52/ON EARTH SWITCH CLOSED
15498 =20C10.B-Q52 SU200 BI =20C10+X1 =20C10.B-Q52/FLT EARTH SWITCH FAILURE
15508 =20C00+U1 SU200 BI =20C10+X1 =20C10.B-Q0/POW BYPS CB POINT ON WAVE BYPASS OR FAULT
15509 =20C10+S1 SU200 BI =20C10+X1 =20C10.B/LOC CTRL ES DS LOCAL CONTROL
15510 =20C10.B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/OFF CIRCUIT BREAKER OPEN
15511 =20C10.B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/ON CIRCUIT BREAKER CLOSED
15513 =20C10.B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15514 =20C10.B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15515 =20C10.B-QO SU200 BI =20C10+X1 =20C10.B-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15516 =20C10,B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15517 =20C10.B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15518 =20C10.B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15519 =20C10.B-Q0 SU200 BI =20C10+X1 =20C10.B-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15524 =20C10.C-Q2 SU200 BI =20C10+X1 =20C10.C-Q2/OFF ISOLATOR OPEN
15525 =20C10.C-Q2 SU200 BI =20C10+X1 =20C10.C-Q2/ON ISOLATOR CLOSED
15526 =20C10.C-Q2 SU200 BI =20C10+X1 =20C10.C-Q2/FLT ISOLATOR FAILURE
15527 =20C10.C-Q6 SU200 BI =20C10+X1 =20C10.C-Q6/OFF ISOLATOR OPEN
15528 =20C10.C-Q6 SU200 BI =20C10+X1 =20C10.C-Q6/ON ISOLATOR CLOSED
15529 =20C10.C-Q6 SU200 BI =20C10+X1 =20C10.C-Q6/FLT ISOLATOR FAILURE
15533 =20C10.C-Q51 SU200 BI =20C10+X1 =20C10.C-Q51/OFF EARTH SWITCH OPEN
15534 =20C10.C-Q51 SU200 BI =20C10+X1 =20C10.C-Q51/ON EARTH SWITCH CLOSED
15535 =20C10.C-Q51 SU200 BI =20C10+X1 =20C10.C-Q51/FLT EARTH SWITCH FAILURE
15536 =20C10.C-Q52 SU200 BI =20C10+X1 =20C10.C-Q52/OFF EARTH SWITCH OPEN
15537 =20C10.C-Q52 SU200 BI =20C10+X1 =20C10.C-Q52/ON EARTH SWITCH CLOSED
15538 =20C10.C-Q52 SU200 BI =20C10+X1 =20C10.C-Q52/FLT EARTH SWITCH FAILURE
15549 =20C10+S1 SU200 BI =20C10+X1 =20C10.C/LOC CTRL ES DS LOCAL CONTROL
15550 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/OFF CIRCUIT BREAKER OPEN
15551 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/ON CIRCUIT BREAKER CLOSED
15553 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/SPRING UNLOAD CB SPRING MECHANISM UNLOADED
15554 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/CTRL VOLT FLT CB CONTROL VOLTAGE FAULT
15555 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/MOTOR FLT CB SPRING MOTOR FAULT
15556 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/SF6 1ST STAGE CB SF6 GAS DENSITY FIRST STAGE
15557 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/SF6 2ND STAGE CB SF6 GAS DENSITY SECOND STAGE
15558 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/POLE DISCREP CB PHASES NOT TOGETHER
15559 =20C10.C-Q0 SU200 BI =20C10+X1 =20C10.C-Q0/LOC CTRL CIRCUIT BREAKER LOCAL CONTROL
15593 =20C09+X1 SU200 BI =20C10+X1 =20C09+X1/FLT DC SPLY AC CONTROL INTERFACE CUBICLE
15594 =20C10+S1 SU200 BI =20C10+X1 =20C10+S1/VT MCB TRP AC-LOCAL CONTROL: VOLT. TRANS. MCB TRIP
15596 =20C10+S1 SU200 BI =20C10+X1 =20C10+S1/FLT AC SPLY AC-LOCAL CONTROL CUBICLE
15597 =20C10+S1 SU200 BI =20C10+X1 =20C10+S1/FLT DC SPLY AC-LOCAL CONTROL CUBICLE
AC Station Owner Interface =20XX00+X2
- =20C01.A-T1/P SU200 AI =20XX00+X2 =20C01.A-T1/P AUTO TANSFORMER ACTIVE POWER
- =20C01.A-T1/Q SU200 AI =20XX00+X2 =20C01.A-T1/Q AUTO TRANSFORMER REACTIVE POWER
- =20C02.A-T1/P SU200 AI =20XX00+X2 =20C02.A-T1/P LINE ACTIVE POWER
- =20C02.A-T1/Q SU200 AI =20XX00+X2 =20C02.A-T1/Q LINE REACTIVE POWER
- =20C02.C-T1/P SU200 AI =20XX00+X2 =20C02.C-T1/P LINE ACTIVE POWER
- =20C02.C-T1/Q SU200 AI =20XX00+X2 =20C02.C-T1/Q LINE REACTIVE POWER
- =20C03.A-T1/P SU200 AI =20XX00+X2 =20C03.A-T1/P LINE ACTIVE POWER
- =20C03.A-T1/Q SU200 AI =20XX00+X2 =20C03.A-T1/Q LINE REACTIVE POWER
- =20C03.C-T1/P SU200 AI =20XX00+X2 =20C03.C-T1/P LINE ACTIVE POWER
- =20C03.C-T1/Q SU200 AI =20XX00+X2 =20C03.C-T1/Q LINE REACTIVE POWER
- =20C07.A-Q1 SU200 BO =20XX00+X2 =20C07.A-Q1/OFF CIRCUIT BREAKER OPEN
- =20C07.A-Q1 SU200 BO =20XX00+X2 =20C07.A-Q1/ON CIRCUIT BREAKER CLOSED
- =20C07.B-Q0 SU200 BO =20XX00+X2 =20C07.B-Q0/OFF CIRCUIT BREAKER OPEN
- =20C07.B-Q0 SU200 BO =20XX00+X2 =20C07.B-Q0/ON CIRCUIT BREAKER CLOSED
- =20C07.C-Q0 SU200 BO =20XX00+X2 =20C07.C-Q0/OFF CIRCUIT BREAKER OPEN
- =20C07.C-Q0 SU200 BO =20XX00+X2 =20C07.C-Q0/ON CIRCUIT BREAKER CLOSED
- =20C08.A-Q0 SU200 BO =20XX00+X2 =20C08.A-Q0/OFF CIRCUIT BREAKER OPEN
- =20C08.A-Q0 SU200 BO =20XX00+X2 =20C08.A-Q0/ON CIRCUIT BREAKER CLOSED
- =20C08.B-Q0 SU200 BO =20XX00+X2 =20C08.B-Q0/OFF CIRCUIT BREAKER OPEN
- =20C08.B-Q0 SU200 BO =20XX00+X2 =20C08.B-Q0/ON CIRCUIT BREAKER CLOSED
- =20C08.C-Q0 SU200 BO =20XX00+X2 =20C08.C-Q0/OFF CIRCUIT BREAKER OPEN
- =20C08.C-Q0 SU200 BO =20XX00+X2 =20C08.C-Q0/ON CIRCUIT BREAKER CLOSED
- =20C09-Q01 SU200 BO =20XX00+X2 =20C09-Q01/OFF CIRCUIT BREAKER OPEN
- =20C09-Q01 SU200 BO =20XX00+X2 =20C09-Q01/ON CIRCUIT BREAKER CLOSED
- =20C09-Q02 SU200 BO =20XX00+X2 =20C09-Q02/OFF CIRCUIT BREAKER OPEN
- =20C09-Q02 SU200 BO =20XX00+X2 =20C09-Q02/ON CIRCUIT BREAKER CLOSED
- =20C10.A-Q0 SU200 BO =20XX00+X2 =20C10.A-Q0/OFF CIRCUIT BREAKER OPEN
- =20C10.A-Q0 SU200 BO =20XX00+X2 =20C10.A-Q0/ON CIRCUIT BREAKER CLOSED
- =20C10.B-Q0 SU200 BO =20XX00+X2 =20C10.B-Q0/OFF CIRCUIT BREAKER OPEN
- =20C10.B-Q0 SU200 BO =20XX00+X2 =20C10.B-Q0/ON CIRCUIT BREAKER CLOSED
- =20C10.C-Q0 SU200 BO =20XX00+X2 =20C10.C-Q0/OFF CIRCUIT BREAKER OPEN
- =20C10.C-Q0 SU200 BO =20XX00+X2 =20C10.C-Q0/ON CIRCUIT BREAKER CLOSED
- =20C07.B-Q0 SU200 BO =20XX00+X2 =20C07.B-Q0/TRP CIRCUIT BREAKER TRIP
- =20C07.C-Q0 SU200 BO =20XX00+X2 =20C07.C-Q0/TRP CIRCUIT BREAKER TRIP
- =20C08.A-Q0 SU200 BO =20XX00+X2 =20C08.A-Q0/TRP CIRCUIT BREAKER TRIP
- =20C08.B-Q0 SU200 BO =20XX00+X2 =20C08.B-Q0/TRP CIRCUIT BREAKER TRIP
- =20C08.C-Q0 SU200 BO =20XX00+X2 =20C08.C-Q0/TRP CIRCUIT BREAKER TRIP
- =20C09-Q01 SU200 BO =20XX00+X2 =20C09-Q01/TRP CIRCUIT BREAKER TRIP
- =20C09-Q02 SU200 BO =20XX00+X2 =20C09-Q02/TRP CIRCUIT BREAKER TRIP
- =20C10.A-Q0 SU200 BO =20XX00+X2 =20C10.A-Q0/TRP CIRCUIT BREAKER TRIP
- =20C10.B-Q0 SU200 BO =20XX00+X2 =20C10.B-Q0/TRP CIRCUIT BREAKER TRIP
- =20C10.C-Q0 SU200 BO =20XX00+X2 =20C10.C-Q0/TRP CIRCUIT BREAKER TRIP
- =20C01.C-Q0 SU200 BO =20XX00+X2 =20C01.C-Q0/CMD OFF CIRCUIT BREAKER OPEN COMMAND
- =20C02.C-Q0 SU200 BO =20XX00+X2 =20C01.C-Q0/CMD OFF CIRCUIT BREAKER OPEN COMMAND
- =20C03.C-Q0 SU200 BO =20XX00+X2 =20C03.C-Q1/CMD OFF CIRCUIT BREAKER OPEN COMMAND
- =20C04.A-Q0 SU200 BO =20XX00+X2 =20C04.A-Q0/CMD OFF CIRCUIT BREAKER OPEN COMMAND
- =20C05.A-Q0 SU200 BO =20XX00+X2 =20C05.A-Q0/CMD OFF CIRCUIT BREAKER OPEN COMMAND
- =21V00+U1-A1 SU200 BO =20XX00+X2 =21V00+U1-A1/POLE_DBLK POLE 1 DEBLOCKED
- =21V00+U1-A1 SU200 BO =20XX00+X2 =21V00+U1-A1/POLE_BLK POLE 1 BLOCKED
- =21V00+U1-A1 SU200 BO =20XX00+X2 =21V00+U1-A1/DC_LINE_FLT POLE 1 DC LINE FAULT RECOVERYSEQUENCE ACTIVE
- =22V00+U1-A1 SU200 BO =20XX00+X2 =22V00+U1-A1/POLE_DBLK POLE 2 DEBLOCKED
- =22V00+U1-A1 SU200 BO =20XX00+X2 =22V00+U1-A1/POLE_BLK POLE 2 BLOCKED
- =22V00+U1-A1 SU200 BO =20XX00+X2 =22V00+U1-A1/DC_LINE_FLT POLE 2 DC LINE FAULT RECOVERYSEQUENCE ACTIVE
- =21V00-A1 SU200 BO =20XX00+X2 =21V00-A1/ACT_P_B1 POLE 1 POWER BITCODE1
- =21V00-A1 SU200 BO =20XX00+X2 =21V00-A1/ACT_P_B2 POLE 1 POWER BITCODE2
- =21V00-A1 SU200 BO =20XX00+X2 =21V00-A1/ACT_P_B3 POLE 1 POWER BITCODE3
- =21V00-A1 SU200 BO =20XX00+X2 =21V00-A1/ACT_P_B4 POLE 1 POWER BITCODE4
- =22V00-A1 SU200 BO =20XX00+X2 =22V00-A1/ACT_P_B1 POLE 2 POWER BITCODE 1
- =22V00-A1 SU200 BO =20XX00+X2 =22V00-A1/ACT_P_B2 POLE 2 POWER BITCODE 2
- =22V00-A1 SU200 BO =20XX00+X2 =22V00-A1/ACT_P_B3 POLE 2 POWER BITCODE 3
- =22V00-A1 SU200 BO =20XX00+X2 =22V00-A1/ACT_P_B4 POLE 2 POWER BITCODE 4
- =20XJ02 SU200 BO =20XX00+X2 =20XJ02/AC_SPLIT AC YARD SPLIT CONFIGURATION.POLE 2
- =20XJ02 SU200 BO =20XX00+X2 =20XJ02/AC_ISLAND AC YARD ISLAND CONFIGURATION.POLE1+2
15601 =20C01.A-Q0 SU200 BI =20XX00+X2 =20C01.A-Q0/OFF CIRCUIT BREAKER OPEN
15602 =20C01.A-Q0 SU200 BI =20XX00+X2 =20C01.A-Q0/ON CIRCUIT BREAKER CLOSED
15603 =20C01.A-Q1 SU200 BI =20XX00+X2 =20C01.A-Q1/OFF ISOLATOR OPEN
15604 =20C01.A-Q1 SU200 BI =20XX00+X2 =20C01.A-Q1/ON ISOLATOR CLOSED
15605 =20C01.A-Q6 SU200 BI =20XX00+X2 =20C01.A-Q6/OFF ISOLATOR OPEN
15606 =20C01.A-Q6 SU200 BI =20XX00+X2 =20C01.A-Q6/ON ISOLATOR CLOSED
15607 =20C01.A-Q9 SU200 BI =20XX00+X2 =20C01.A-Q9/OFF ISOLATOR OPEN
15608 =20C01.A-Q9 SU200 BI =20XX00+X2 =20C01.A-Q9/ON ISOLATOR CLOSED
15609 =20C01.B-Q0 SU200 BI =20XX00+X2 =20C01.B-Q0/OFF CIRCUIT BREAKER OPEN
15610 =20C01.B-Q0 SU200 BI =20XX00+X2 =20C01.B-Q0/ON CIRCUIT BREAKER CLOSED
15611 =20C01.B-Q61 SU200 BI =20XX00+X2 =20C01.B-Q61/OFF ISOLATOR OPEN
15612 =20C01.B-Q61 SU200 BI =20XX00+X2 =20C01.B-Q61/ON ISOLATOR CLOSED
15613 =20C01.B-Q62 SU200 BI =20XX00+X2 =20C01.B-Q62/OFF ISOLATOR OPEN
15614 =20C01.B-Q62 SU200 BI =20XX00+X2 =20C01.B-Q62/ON ISOLATOR CLOSED
15615 =20C01.C-Q2 SU200 BI =20XX00+X2 =20C01.C-Q2/OFF ISOLATOR OPEN
15616 =20C01.C-Q2 SU200 BI =20XX00+X2 =20C01.C-Q2/ON ISOLATOR CLOSED
15641 =20C02.A-Q0 SU200 BI =20XX00+X2 =20C02.A-Q0/OFF CIRCUIT BREAKER OPEN
15642 =20C02.A-Q0 SU200 BI =20XX00+X2 =20C02.A-Q0/ON CIRCUIT BREAKER CLOSED
15643 =20C02.A-Q1 SU200 BI =20XX00+X2 =20C02.A-Q1/OFF ISOLATOR OPEN
15644 =20C02.A-Q1 SU200 BI =20XX00+X2 =20C02.A-Q1/ON ISOLATOR CLOSED
15645 =20C02.A-Q6 SU200 BI =20XX00+X2 =20C02.A-Q6/OFF ISOLATOR OPEN
15646 =20C02.A-Q6 SU200 BI =20XX00+X2 =20C02.A-Q6/ON ISOLATOR CLOSED
15647 =20C02.A-Q9 SU200 BI =20XX00+X2 =20C02.A-Q9/OFF ISOLATOR OPEN
15648 =20C02.A-Q9 SU200 BI =20XX00+X2 =20C02.A-Q9/ON ISOLATOR CLOSED
15649 =20C02.B-Q0 SU200 BI =20XX00+X2 =20C02.B-Q0/OFF CIRCUIT BREAKER OPEN
15650 =20C02.B-Q0 SU200 BI =20XX00+X2 =20C02.B-Q0/ON CIRCUIT BREAKER CLOSED
15651 =20C02.B-Q61 SU200 BI =20XX00+X2 =20C02.B-Q61/OFF ISOLATOR OPEN
15652 =20C02.B-Q61 SU200 BI =20XX00+X2 =20C02.B-Q61/ON ISOLATOR CLOSED
15653 =20C02.B-Q62 SU200 BI =20XX00+X2 =20C02.B-Q62/OFF ISOLATOR OPEN
15654 =20C02.B-Q62 SU200 BI =20XX00+X2 =20C02.B-Q62/ON ISOLATOR CLOSED
15655 =20C02.C-Q0 SU200 BI =20XX00+X2 =20C02.C-Q0/OFF CIRCUIT BREAKER OPEN
15656 =20C02.C-Q0 SU200 BI =20XX00+X2 =20C02.C-Q0/ON CIRCUIT BREAKER CLOSED
15657 =20C02.C-Q2 SU200 BI =20XX00+X2 =20C02.C-Q2/OFF ISOLATOR OPEN
15658 =20C02.C-Q2 SU200 BI =20XX00+X2 =20C02.C-Q2/ON ISOLATOR CLOSED
15659 =20C02.C-Q6 SU200 BI =20XX00+X2 =20C02.C-Q6/OFF ISOLATOR OPEN
15660 =20C02.C-Q6 SU200 BI =20XX00+X2 =20C02.C-Q6/ON ISOLATOR CLOSED
15661 =20C02.C-Q9 SU200 BI =20XX00+X2 =20C02.C-Q9/OFF ISOLATOR OPEN
15662 =20C02.C-Q9 SU200 BI =20XX00+X2 =20C02.C-Q9/ON ISOLATOR CLOSED
15681 =20C03.A-Q0 SU200 BI =20XX00+X2 =20C03.A-Q0/OFF CIRCUIT BREAKER OPEN
15682 =20C03.A-Q0 SU200 BI =20XX00+X2 =20C03.A-Q0/ON CIRCUIT BREAKER CLOSED
15683 =20C03.A-Q1 SU200 BI =20XX00+X2 =20C03.A-Q1/OFF ISOLATOR OPEN
15684 =20C03.A-Q1 SU200 BI =20XX00+X2 =20C03.A-Q1/ON ISOLATOR CLOSED
15685 =20C03.A-Q6 SU200 BI =20XX00+X2 =20C03.A-Q6/OFF ISOLATOR OPEN
15686 =20C03.A-Q6 SU200 BI =20XX00+X2 =20C03.A-Q6/ON ISOLATOR CLOSED
15687 =20C03.A-Q9 SU200 BI =20XX00+X2 =20C03.A-Q9/OFF ISOLATOR OPEN
15688 =20C03.A-Q9 SU200 BI =20XX00+X2 =20C03.A-Q9/ON ISOLATOR CLOSED
15689 =20C03.B-Q0 SU200 BI =20XX00+X2 =20C03.B-Q0/OFF CIRCUIT BREAKER OPEN
15690 =20C03.B-Q0 SU200 BI =20XX00+X2 =20C03.B-Q0/ON CIRCUIT BREAKER CLOSED
15691 =20C03.B-Q61 SU200 BI =20XX00+X2 =20C03.B-Q61/OFF ISOLATOR OPEN
15692 =20C03.B-Q61 SU200 BI =20XX00+X2 =20C03.B-Q61/ON ISOLATOR CLOSED
15693 =20C03.B-Q62 SU200 BI =20XX00+X2 =20C03.B-Q62/OFF ISOLATOR OPEN
15694 =20C03.B-Q62 SU200 BI =20XX00+X2 =20C03.B-Q62/ON ISOLATOR CLOSED
15695 =20C03.C-Q0 SU200 BI =20XX00+X2 =20C03.C-Q0/OFF CIRCUIT BREAKER OPEN
15696 =20C03.C-Q0 SU200 BI =20XX00+X2 =20C03.C-Q0/ON CIRCUIT BREAKER CLOSED
15697 =20C03.C-Q2 SU200 BI =20XX00+X2 =20C03.C-Q2/OFF ISOLATOR OPEN
15698 =20C03.C-Q2 SU200 BI =20XX00+X2 =20C03.C-Q2/ON ISOLATOR CLOSED
15699 =20C03.C-Q6 SU200 BI =20XX00+X2 =20C03.C-Q6/OFF ISOLATOR OPEN
15700 =20C03.C-Q6 SU200 BI =20XX00+X2 =20C03.C-Q6/ON ISOLATOR CLOSED
15701 =20C03.C-Q9 SU200 BI =20XX00+X2 =20C03.C-Q9/OFF ISOLATOR OPEN
15702 =20C03.C-Q9 SU200 BI =20XX00+X2 =20C03.C-Q9/ON ISOLATOR CLOSED
15705 =20C03.A-Q15 SU200 BI =20XX00+X2 =20C03.A-Q15/OFF BB EARTH SWITCH OPEN
15706 =20C03.A-Q15 SU200 BI =20XX00+X2 =20C03.A-Q15/ON BB EARTH SWITCH CLOSED
15707 =20C03.C-Q25 SU200 BI =20XX00+X2 =20C03.C-Q25/OFF BB EARTH SWITCH OPEN
15708 =20C03.C-Q25 SU200 BI =20XX00+X2 =20C03.C-Q25/ON BB EARTH SWITCH CLOSED
15709 =20C04.A-Q15 SU200 BI =20XX00+X2 =20C04.A-Q15/OFF BB EARTH SWITCH OPEN
15710 =20C04.A-Q15 SU200 BI =20XX00+X2 =20C04.A-Q15/ON BB EARTH SWITCH CLOSED
15711 =20C04.C-Q25 SU200 BI =20XX00+X2 =20C04.C-Q25/OFF BB EARTH SWITCH OPEN
15712 =20C04.C-Q25 SU200 BI =20XX00+X2 =20C04.C-Q25/ON BB EARTH SWITCH CLOSED
15719 =20XX00+X3 SU200 BI =20XX00+X2 =20XX00+X3/FLT DC SPLY OWNER INTERFACE CUBICLE FAULT
AC Station Owner Interface =20XX00+X3
- =20C04.A-T1/P SU200 AI =20XX00+X3 =20C04.A-T1/P LINE ACTIVE POWER
- =20C04.A-T1/Q SU200 AI =20XX00+X3 =20C04.A-T1/Q LINE REACTIVE POWER
- =20C04.C-T1/P SU200 AI =20XX00+X3 =20C04.C-T1/P LINE ACTIVE POWER
- =20C04.C-T1/Q SU200 AI =20XX00+X3 =20C04.C-T1/Q LINE REACTIVE POWER
- =20C01.ICT BD1 SU200 AI =20XX00+X3 =20C01.ICT BD1 BLOCKING DEVICE CURRENT SCR
- =20C01_2_3-Q0 SU200 BO =20XX00+X3 =20C01_2_3-Q0/BUS 2A CMD OFF CIRCUIT BREAKER OPEN COMMAND
- =20C04_5-Q0 SU200 BO =20XX00+X3 =20C04_5-Q0/BUS 1B CMD OFF CIRCUIT BREAKER OPEN COMMAND
- =20T01-Q0 SU200 BO =20XX00+X3 =20T01-Q0 EN_INTERLOCK HVDC FEEDER1 AUX READY
- =20T02-Q0 SU200 BO =20XX00+X3 =20T02-Q0 EN_INTERLOCK HVDC FEEDER2 AUX READY
- =20T03-Q0 SU200 BO =20XX00+X3 =20T03-Q0 EN_INTERLOCK HVDC FEEDER3 AUX READY
15721 =20C04.A-Q0 SU200 BI =20XX00+X3 =20C04.A-Q0/OFF CIRCUIT BREAKER OPEN
15722 =20C04.A-Q0 SU200 BI =20XX00+X3 =20C04.A-Q0/ON CIRCUIT BREAKER CLOSED
15723 =20C04.A-Q1 SU200 BI =20XX00+X3 =20C04.A-Q1/OFF ISOLATOR OPEN
15724 =20C04.A-Q1 SU200 BI =20XX00+X3 =20C04.A-Q1/ON ISOLATOR CLOSED
15725 =20C04.A-Q6 SU200 BI =20XX00+X3 =20C04.A-Q6/OFF ISOLATOR OPEN
15726 =20C04.A-Q6 SU200 BI =20XX00+X3 =20C04.A-Q6/ON ISOLATOR CLOSED
15727 =20C04.A-Q9 SU200 BI =20XX00+X3 =20C04.A-Q9/OFF ISOLATOR OPEN
15728 =20C04.A-Q9 SU200 BI =20XX00+X3 =20C04.A-Q9/ON ISOLATOR CLOSED
15729 =20C04.B-Q0 SU200 BI =20XX00+X3 =20C04.B-Q0/OFF CIRCUIT BREAKER OPEN
15730 =20C04.B-Q0 SU200 BI =20XX00+X3 =20C04.B-Q0/ON CIRCUIT BREAKER CLOSED
15731 =20C04.B-Q61 SU200 BI =20XX00+X3 =20C04.B-Q61/OFF ISOLATOR OPEN
15732 =20C04.B-Q61 SU200 BI =20XX00+X3 =20C04.B-Q61/ON ISOLATOR CLOSED
15733 =20C04.B-Q62 SU200 BI =20XX00+X3 =20C04.B-Q62/OFF ISOLATOR OPEN
15734 =20C04.B-Q62 SU200 BI =20XX00+X3 =20C04.B-Q62/ON ISOLATOR CLOSED
15735 =20C04.C-Q0 SU200 BI =20XX00+X3 =20C04.C-Q0/OFF CIRCUIT BREAKER OPEN
15736 =20C04.C-Q0 SU200 BI =20XX00+X3 =20C04.C-Q0/ON CIRCUIT BREAKER CLOSED
15737 =20C04.C-Q2 SU200 BI =20XX00+X3 =20C04.C-Q2/OFF ISOLATOR OPEN
15738 =20C04.C-Q2 SU200 BI =20XX00+X3 =20C04.C-Q2/ON ISOLATOR CLOSED
15739 =20C04.C-Q6 SU200 BI =20XX00+X3 =20C04.C-Q6/OFF ISOLATOR OPEN
15740 =20C04.C-Q6 SU200 BI =20XX00+X3 =20C04.C-Q6/ON ISOLATOR CLOSED
15741 =20C04.C-Q9 SU200 BI =20XX00+X3 =20C04.C-Q9/OFF ISOLATOR OPEN
15742 =20C04.C-Q9 SU200 BI =20XX00+X3 =20C04.C-Q9/ON ISOLATOR CLOSED
15761 =20C05.A-Q0 SU200 BI =20XX00+X3 =20C05.A-Q0/OFF CIRCUIT BREAKER OPEN
15762 =20C05.A-Q0 SU200 BI =20XX00+X3 =20C05.A-Q0/ON CIRCUIT BREAKER CLOSED
15763 =20C05.A-Q1 SU200 BI =20XX00+X3 =20C05.A-Q1/OFF ISOLATOR OPEN
15764 =20C05.A-Q1 SU200 BI =20XX00+X3 =20C05.A-Q1/ON ISOLATOR CLOSED
15765 =20C05.A-Q6 SU200 BI =20XX00+X3 =20C05.A-Q6/OFF ISOLATOR OPEN
15766 =20C05.A-Q6 SU200 BI =20XX00+X3 =20C05.A-Q6/ON ISOLATOR CLOSED
15767 =20C05.A-Q9 SU200 BI =20XX00+X3 =20C05.A-Q9/OFF ISOLATOR OPEN
15768 =20C05.A-Q9 SU200 BI =20XX00+X3 =20C05.A-Q9/ON ISOLATOR CLOSED
15769 =20C05.B-Q0 SU200 BI =20XX00+X3 =20C05.B-Q0/OFF CIRCUIT BREAKER OPEN
15770 =20C05.B-Q0 SU200 BI =20XX00+X3 =20C05.B-Q0/ON CIRCUIT BREAKER CLOSED
15771 =20C05.B-Q61 SU200 BI =20XX00+X3 =20C05.B-Q61/OFF ISOLATOR OPEN
15772 =20C05.B-Q61 SU200 BI =20XX00+X3 =20C05.B-Q61/ON ISOLATOR CLOSED
15773 =20C05.B-Q62 SU200 BI =20XX00+X3 =20C05.B-Q62/OFF ISOLATOR OPEN
15774 =20C05.B-Q62 SU200 BI =20XX00+X3 =20C05.B-Q62/ON ISOLATOR CLOSED
15775 =20C05.C-Q0 SU200 BI =20XX00+X3 =20C05.C-Q0/OFF CIRCUIT BREAKER OPEN (FUTURE)
15776 =20C05.C-Q0 SU200 BI =20XX00+X3 =20C05.C-Q0/ON CIRCUIT BREAKER CLOSED (FUTURE)
15777 =20C05.C-Q2 SU200 BI =20XX00+X3 =20C05.C-Q2/OFF ISOLATOR OPEN
15778 =20C05.C-Q2 SU200 BI =20XX00+X3 =20C05.C-Q2/ON ISOLATOR CLOSED
15779 =20C05.C-Q6 SU200 BI =20XX00+X3 =20C05.C-Q6/OFF ISOLATOR OPEN (FUTURE)
15780 =20C05.C-Q6 SU200 BI =20XX00+X3 =20C05.C-Q6/ON ISOLATOR CLOSED (FUTURE)
15785 =20T11-Q0 SU200 BI =20XX00+X3 =20T11-Q0/OFF 33 KV AUX. FEEDER 1 (OWNER) CB OFF
15786 =20T12-Q0 SU200 BI =20XX00+X3 =20T12-Q0/OFF 33 KV AUX. FEEDER (OWNER) CB OFF
15787 =20T13-Q0 SU200 BI =20XX00+X3 =20T13-Q0/OFF 33 KV AUX. FEEDER 3 (OWNER) CB OFF
15795 =20XX00+X3 SU200 BI =20XX00+X3 =20XX00+X3/FLT BIN TRSD AC CONTROL INTERFACE ???
15796 =20XX00+X3 SU200 BI =20XX00+X3 =20XX00+X3/FLT OLM 1 FIELDBUS 1 OLM FAULTY
15797 =20XX00+X3 SU200 BI =20XX00+X3 =20XX00+X3/FLT OLM 2 FIELDBUS 2 OLM FAULTY
15798 =20XX00+X3 SU200 BI =20XX00+X3 =20XX00+X3/FLT TIME SYNC NO TIME SYNCH SIGNAL
15799 =20XX00+X2 SU200 BI =20XX00+X3 =20XX00+X2/FLT DC SPLY OWNER INTERFACE CUBICLE FAULT
AC Station Service Interface =20XX00+X1
- =20NE01-UL1-2 SU200 AI =20XX00+X1 =20NE01-UL1-2/SEC/A 415V AC MAIN DISTR.BUSBAR VOLTAGE
- =20NE01-UL1-2 SU200 AI =20XX00+X1 =20NE01-UL1-2/SEC/B 415V AC MAIN DISTR.BUSBAR VOLTAGE
- =20NE01-T1 SU200 AI =20XX00+X1 =20NE01-T1-IL2 415V AC MAIN DISTR.INCOMING CURRENT
- =20NE01-T2 SU200 AI =20XX00+X1 =20NE01-T2-IL2 415V AC MAIN DISTR.INCOMING CURRENT
- =20NE01-T3 SU200 AI =20XX00+X1 =20NE01-T3-IL2 415V AC MAIN DISTR.INCOMING CURRENT
- =21T01+BD1 SU200 AI =20XX00+X1 =21T01+BD1 I_SCR BLOCKING DEVICE SCR
- =22T01+BD1 SU200 AI =20XX00+X1 =22T01+BD1 I_SCR BLOCKING DEVICE SCR
- =20NE01-T1 SU200 AI =20XX00+X1 =20NE01-T1-P 415V AC MAIN DISTR.INCOMING POWER
- =20NE01-T2 SU200 AI =20XX00+X1 =20NE01-T2-P 415V AC MAIN DISTR.INCOMING POWER
- =20NE01-T3 SU200 AI =20XX00+X1 =20NE01-T3-P 415V AC MAIN DISTR.INCOMING POWER
- =20NE01-T1 SU200 AI =20XX00+X1 =20NE01-T1-Q 415V AC MAIN DISTR.INCOMING REACTIVE POWER
- =20NE01-T2 SU200 AI =20XX00+X1 =20NE01-T2-Q 415V AC MAIN DISTR.INCOMING REACTIVE POWER
- =20NE01-T3 SU200 AI =20XX00+X1 =20NE01-T3-Q 415V AC MAIN DISTR.INCOMING REACTIVE POWER
- =21NE01-UL1 SU200 AI =20XX00+X1 =21NE01-UL1-2 415V AC POWER CENTRE BUSBAR VOLTAGE
- =21NE02-UL1 SU200 AI =20XX00+X1 =21NE02-UL1-2 415V AC POWER CENTRE BUSBAR VOLTAGE
- =21NE01-UL1 SU200 AI =20XX00+X1 =22NE01-UL1-2 415V AC POWER CENTRE BUSBAR VOLTAGE
- =22NE02-UL1 SU200 AI =20XX00+X1 =22NE02-UL1-2 415V AC POWER CENTRE BUSBAR VOLTAGE
- =21NE01-TL1 SU200 AI =20XX00+X1 =21NE01-TL1-IL2 415V AC POWER CENTRE INCOMING CURRENT
- =21NE02-TL1 SU200 AI =20XX00+X1 =21NE02-TL1-IL2 415V AC POWER CENTRE INCOMING CURRENT
- =22NE01-TL1 SU200 AI =20XX00+X1 =22NE01-TL1-IL2 415V AC POWER CENTRE INCOMING CURRENT
- =22NE02-TL1 SU200 AI =20XX00+X1 =22NE02-TL1-IL2 415V AC POWER CENTRE INCOMING CURRENT
- =21NE01-TL2 SU200 AI =20XX00+X1 =21NE01-TL2-IL2 415V AC DIESEL GENERATOR CURRENT
- =21NE01-TL2 SU200 AI =20XX00+X1 =21NE01-TL2-P 415V AC DIESEL GENERATOR ACT POWER
- =21NE01-TL2 SU200 AI =20XX00+X1 =21NE01-TL2-Q 415V AC DIESEL GENERATOR REACT. POWER
- =22NE01-TL2 SU200 AI =20XX00+X1 =22NE01-TL2-IL2 415V AC DIESEL GENERATOR CURRENT
- =22NE01-TL2 SU200 AI =20XX00+X1 =22NE01-TL2-P 415V AC DIESEL GENERATOR ACT POWER
- =22NE01-TL2 SU200 AI =20XX00+X1 =22NE01-TL2-Q 415V AC DIESEL GENERATOR REACT. POWER
15881 =20NE01-Q01 SU200 BI =20XX00+X1 =20NE01-Q01/OFF 415 VAC MAIN DISTR. CB OPEN
15882 =20NE01-Q01 SU200 BI =20XX00+X1 =20NE01-Q01/ON 415 VAC MAIN DISTR. CB CLOSED
15883 =20NE01-Q02 SU200 BI =20XX00+X1 =20NE01-Q02/OFF 415 VAC MAIN DISTR. CB OPEN
15884 =20NE01-Q02 SU200 BI =20XX00+X1 =20NE01-Q02/ON 415 VAC MAIN DISTR. CB CLOSED
15885 =20NE01-Q03 SU200 BI =20XX00+X1 =20NE01-Q03/OFF 415 VAC MAIN DISTR. CB OPEN
15886 =20NE01-Q03 SU200 BI =20XX00+X1 =20NE01-Q03/ON 415 VAC MAIN DISTR. CB CLOSED
15887 =20NE01-Q04 SU200 BI =20XX00+X1 =20NE01-Q04/OFF 415 VAC MAIN DISTR. CB OPEN
15888 =20NE01-Q04 SU200 BI =20XX00+X1 =20NE01-Q04/ON 415 VAC MAIN DISTR. CB CLOSED
15889 =21NE01-Q01 SU200 BI =20XX00+X1 =21NE01-Q01/OFF 415 VAC INCOMING FEEDER CB OPEN
15890 =21NE01-Q01 SU200 BI =20XX00+X1 =21NE01-Q01/ON 415 VAC INCOMING FEEDER CB CLOSED
15891 =21NE01-Q02 SU200 BI =20XX00+X1 =21NE01-Q02/OFF 415 VAC INCOMING FEEDER CB OPEN
15892 =21NE01-Q02 SU200 BI =20XX00+X1 =21NE01-Q02/ON 415 VAC INCOMING FEEDER CB CLOSED
15893 =21NE02-Q01 SU200 BI =20XX00+X1 =21NE02-Q01/OFF 415 VAC INCOMING FEEDER CB OPEN
15894 =21NE02-Q01 SU200 BI =20XX00+X1 =21NE02-Q01/ON 415 VAC INCOMING FEEDER CB CLOSED
15895 =22NE01-Q01 SU200 BI =20XX00+X1 =22NE01-Q01/OFF 415 VAC INCOMING FEEDER CB OPEN
15896 =22NE01-Q01 SU200 BI =20XX00+X1 =22NE01-Q01/ON 415 VAC INCOMING FEEDER CB CLOSED
15897 =22NE01-Q02 SU200 BI =20XX00+X1 =22NE01-Q02/OFF 415 VAC INCOMING FEEDER CB OPEN
15898 =22NE01-Q02 SU200 BI =20XX00+X1 =22NE01-Q02/ON 415 VAC INCOMING FEEDER CB CLOSED
15899 =22NE02-Q01 SU200 BI =20XX00+X1 =22NE02-Q01/OFF 415 VAC INCOMING FEEDER CB OPEN
15900 =22NE02-Q01 SU200 BI =20XX00+X1 =22NE02-Q01/ON 415 VAC INCOMING FEEDER CB CLOSED
15901 =21NE03-Q03 SU200 BI =20XX00+X1 =21NE03-Q03/OFF 415 VAC POWER CENTRE BUS COUPLER OPEN
15902 =21NE03-Q03 SU200 BI =20XX00+X1 =21NE03-Q03/ON 415 VAC POWER CENTRE BUS COUPLER CLOSED
15903 =21NE02-Q02 SU200 BI =20XX00+X1 =21NE02-Q02/OFF 415 VAC POWER CENTRE BUS COUPLER OPEN
15904 =21NE02-Q02 SU200 BI =20XX00+X1 =21NE02-Q02/ON 415 VAC POWER CENTRE BUS COUPLER CLOSED
15907 =22NE03-Q03 SU200 BI =20XX00+X1 =22NE03-Q03/OFF 415 VAC POWER CENTRE BUS COUPLER OPEN
15908 =22NE03-Q03 SU200 BI =20XX00+X1 =22NE03-Q03/ON 415 VAC POWER CENTRE BUS COUPLER CLOSED
15913 =20T11 SU200 BI =20XX00+X1 =20T11/OIL TEMP WRN AUX.TRAFO 1 OIL TEMPERATURE WARNING
15914 =20T11 SU200 BI =20XX00+X1 =20T11/OIL TEMP TRP AUX.TRAFO 1 OIL TEMPERATURE TRIP
15915 =20T12 SU200 BI =20XX00+X1 =20T12/OIL TEMP WRN AUX.TRAFO 2 OIL TEMPERATURE WARNING
15916 =20T12 SU200 BI =20XX00+X1 =20T12/OIL TEMP TRP AUX.TRAFO 2 OIL TEMPERATURE TRIP
15917 =20T13 SU200 BI =20XX00+X1 =20T13/OIL TEMP WRN AUX.TRAFO 3 OIL TEMPERATURE WARNING
15918 =20T13 SU200 BI =20XX00+X1 =20T13/OIL TEMP TRP AUX.TRAFO 3 OIL TEMPERATURE TRIP
15921 =20T11 SU200 BI =20XX00+X1 =20T11/BUCHHOLZ TRP AUX.TRAFO 1 BUCHHOLZ TRIP
15922 =20T11 SU200 BI =20XX00+X1 =20T11/BUCHHOLZ WRN AUX.TRAFO 1 BUCHHOLZ WARNING
15923 =20T11 SU200 BI =20XX00+X1 =20T11/WDG TEMP TRP AUX.TRAFO 1 WINDING TEMPERATURE TRIP
15924 =20T11 SU200 BI =20XX00+X1 =20T11/WDG TEMP WRN AUX.TRAFO 1 WINDING TEMPERATURE WARNING
15925 =20T12 SU200 BI =20XX00+X1 =20T12/BUCHHOLZ TRP AUX.TRAFO 2 BUCHHOLZ TRIP
15926 =20T12 SU200 BI =20XX00+X1 =20T12/BUCHHOLZ WRN AUX.TRAFO 2 BUCHHOLZ WARNING
15927 =20T12 SU200 BI =20XX00+X1 =20T12/WDG TEMP TRP AUX.TRAFO 2 WINDING TEMPERATURE TRIP
15928 =20T12 SU200 BI =20XX00+X1 =20T12/WDG TEMP WRN AUX.TRAFO 2 WINDING TEMPERATURE WARNING
15929 =20T13 SU200 BI =20XX00+X1 =20T13/BUCHHOLZ TRP AUX.TRAFO 3 BUCHHOLZ TRIP
15930 =20T13 SU200 BI =20XX00+X1 =20T13/BUCHHOLZ WRN AUX.TRAFO 3 BUCHHOLZ WARNING
15931 =20T13 SU200 BI =20XX00+X1 =20T13/WDG TEMP TRP AUX.TRAFO 3 WINDING TEMPERATURE TRIP
15932 =20T13 SU200 BI =20XX00+X1 =20T13/WDG TEMP WRN AUX.TRAFO 3 WINDING TEMPERATURE WARNING
15933 =20T11 SU200 BI =20XX00+X1 =20T11/DIFF PROT TRP AUX.TRAFO 1 DIFF PROTECTION TRIP
15934 =20T12 SU200 BI =20XX00+X1 =20T12/DIFF PROT TRP AUX.TRAFO 2 DIFF PROTECTION TRIP
15935 =20T13 SU200 BI =20XX00+X1 =20T13/DIFF PROT TRP AUX. TRAFO 3 DIFF PROTECTION TRIP
15937 =21NE00-G01 SU200 BI =20XX00+X1 =21NE00-G01/RUN DIESEL GENERATOR SET 1 RUNNING
15938 =21NE00-G01 SU200 BI =20XX00+X1 =21NE00-G01/FLT DIESEL GENERATOR SET 1 FAULT
15939 =21NE00-G01 SU200 BI =20XX00+X1 =21NE00-G01/CHARGER FLT DIESEL GENERATOR SET 1 CHARGER FAULT
15941 =21NE00-G01 SU200 BI =20XX00+X1 =21NE00-G01/TANK ALR DIESEL GENERATOR SET 1 TANK LEVEL ALARM
15942 =22NE00-G01 SU200 BI =20XX00+X1 =22NE00-G01/RUN DIESEL GENERATOR SET 2 RUNNING
15943 =22NE00-G01 SU200 BI =20XX00+X1 =22NE00-G01/FLT DIESEL GENERATOR SET 2 FAULT
15944 =22NE00-G01 SU200 BI =20XX00+X1 =22NE00-G01/CHARGER FLT DIESEL GENERATOR SET 2 CHARGER FAULT
15946 =22NE00-G01 SU200 BI =20XX00+X1 =22NE00-G01/TANK ALR DIESEL GENERATOR SET 2 TANK LEVEL ALARM
15947 =20T11 SU200 BI =20XX00+X1 =20T11/OVERCURRENT TRP AUX.TRAFO 1 OVERCURRENT TRIP -K50
15948 =20T11 SU200 BI =20XX00+X1 =20T11/EARTH FLT TRP AUX.TRAFO 1 EARTHFAULT TRIP -K56
15949 =20T11 SU200 BI =20XX00+X1 =20T11/UNDERVOLT TRP AUX.TRAFO 1 UNDERVOLTAGE TRIP -K31
15951 =20T12 SU200 BI =20XX00+X1 =20T12/OVERCURRENT TRP AUX.TRAFO 2OVERCURRENT TRIP -K50
15952 =20T12 SU200 BI =20XX00+X1 =20T12/EARTH FLT TRP AUX.TRAFO 2 EARTHFAULT TRIP -K56
15953 =20T12 SU200 BI =20XX00+X1 =20T12/UNDERVOLT TRP AUX.TRAFO 2 UNDERVOLTAGE TRIP-K31
15955 =20T13 SU200 BI =20XX00+X1 =20T13/OVERCURRENT TRP AUX.TRAFO 3 OVERCURRENT TRIP -K50
15956 =20T13 SU200 BI =20XX00+X1 =20T13/EARTH FLT TRP AUX,TRAFO 3 EARTHFAULT TRIP -K56
15957 =20T13 SU200 BI =20XX00+X1 =20T13/UNDERVOLT TRP AUX, TRAFO 3 UNDERVOLTAGE TRIP-K31
15961 =20NK11+G11 SU200 BI =20XX00+X1 =20NK11+G11/CHARGER FLT 220 V DC CHARGER 1 FAULT
15964 =20NK11+G12 SU200 BI =20XX00+X1 =20NK11+G12/CHARGER FLT 220 V DC CHARGER 2 FAULT
15967 =20NK21+G11 SU200 BI =20XX00+X1 =20NK21+G11/CHARGER FLT 220 V DC CHARGER 3 FAULT
15969 =21NU11+G11 SU200 BI =20XX00+X1 =21NU11+G11/CHARGER FLT 24 V DC CHARGER 1 FAULT
15971 =21NU11+G12 SU200 BI =20XX00+X1 =21NU11+G12/CHARGER FLT 24 V DC CHARGER 2 FAULT
15973 =22NU11+G11 SU200 BI =20XX00+X1 =22NU11+G11/CHARGER FLT 24 V DC CHARGER 1 FAULT
15975 =22NU11+G12 SU200 BI =20XX00+X1 =22NU11+G12/CHARGER FLT 24 V DC CHARGER 2 FAULT
15977 =22NU21+G11 SU200 BI =20XX00+X1 =22NU21+G11/CHARGER FLT 24 V DC CHARGER 3 FAULT
15985 =20NQ11+G11 SU200 BI =20XX00+X1 =20NQ11+G11/CHARGER FLT 48 V DC CHARGER 1 FAULT
15987 =20NQ11+G12 SU200 BI =20XX00+X1 =20NQ11+G12/CHARGER FLT 48 V DC CHARGER 2 FAULT
15989 =20NQ21+G11 SU200 BI =20XX00+X1 =20NQ21+G11/CHARGER FLT 48 V DC CHARGER 3 FAULT
15993 =20NG11+G11 SU200 BI =20XX00+X1 =20NG11+G11/CHARGER FLT 240 V UPS CHARGER 1 FAULT
15995 =20NG21+G11 SU200 BI =20XX00+X1 =20NG21+G11/CHARGER FLT 240 V UPS CHARGER 2 FAULT
16001 =21U61+NG1 SU200 BI =20XX00+X1 =21U61+NG1/INVERTER FLT VALVE COOLING UPS 1 INVERTER FAULT
16002 =21U61+NG2 SU200 BI =20XX00+X1 =21U61+NG2/INVERTER FLT VALVE COOLING UPS 2 INVERTER FAULT
16003 =22U61+NG1 SU200 BI =20XX00+X1 =22U61+NG1/INVERTER FLT VALVE COOLING UPS 1 INVERTER FAULT
16004 =22U61+NG2 SU200 BI =20XX00+X1 =22U61+NG2/INVERTER FLT VALVE COOLING UPS 2 INVERTER FAULT
16009 =20NE01 SU200 BI =20XX00+X1 =20NE01/PWR SPLY FLT 400 V MAIN DISTRIBUTION AUX POWER FAULT
16010 =21NE01 SU200 BI =20XX00+X1 =21NE01/PWR SPLY FLT 400 V POWER CENTRE 1 AUX POWER FAULT
16011 =21NE01 SU200 BI =20XX00+X1 =21NE01/UNDERVOLT 400 V POWER CENTRE 1 UNDERVOLTAGE 1
16012 =21NE02 SU200 BI =20XX00+X1 =21NE02/PWR SPLY FLT 400 V POWER CENTRE 1 AUX POWER FAULT
16013 =21NE02 SU200 BI =20XX00+X1 =21NE02/UNDERVOLT 400 V POWER CENTRE 1 UNDERVOLTAGE 2
16014 =22NE01 SU200 BI =20XX00+X1 =22NE01/PWR SPLY FLT 400 V POWER CENTRE 2 AUX POWER FAULT
16015 =22NE01 SU200 BI =20XX00+X1 =22NE01/UNDERVOLT 400 V POWER CENTRE 2 UNDERVOLTAGE 1
16016 =22NE02 SU200 BI =20XX00+X1 =22NE02/PWR SPLY FLT 400 V POWER CENTRE 2 AUX POWER FAULT
16017 =22NE02 SU200 BI =20XX00+X1 =22NE02/UNDERVOLT 400 V POWER CENTRE 2 UNDERVOLTAGE 2
16018 =20T11-Q1 SU200 BI =20XX00+X1 =20T11-Q1/VOLTAGE AVAIBL 33 KV AUX. FEEDER 1 LINE VOLTAGE AVAIL
16019 =20T11-Q1 SU200 BI =20XX00+X1 =20T11-Q1/OFF 33 KV AUX. FEEDER 1 ISOLATOR OFF
16020 =20T11-Q1 SU200 BI =20XX00+X1 =20T11-Q1/ON 33 KV AUX. FEEDER 1 ISOLATOR ON
16021 =20T11-Q1 SU200 BI =20XX00+X1 =20T11-Q1/ADV OFF TRP 33 KV AUX. FEEDER 1 ADVANCE OFF TRIP
16023 =20T12-Q1 SU200 BI =20XX00+X1 =20T12-Q1/VOLTAGE AVAIBL 33 KV AUX. FEEDER 2 LINE VOLTAGE AVAIL
16024 =20T12-Q1 SU200 BI =20XX00+X1 =20T12-Q1/OFF 33 KV AUX. FEEDER 2 SOLATOR OFF
16025 =20T12-Q1 SU200 BI =20XX00+X1 =20T12-Q1/ON 33 KV AUX. FEEDER 2 ISOLATOR ON
16026 =20T12-Q1 SU200 BI =20XX00+X1 =20T12-Q1/ADV OFF TRP 33 KV AUX. FEEDER 2 ADVANCE OFF TRIP
16028 =20T13-Q1 SU200 BI =20XX00+X1 =20T13-Q1/VOLTAGE AVAIBL 33 KV AUX. FEEDER 3 LINE VOLTAGE AVAIL
16029 =20T13-Q1 SU200 BI =20XX00+X1 =20T13-Q1/OFF 33 KV AUX. FEEDER 3 ISOLATOR OFF
16030 =20T13-Q1 SU200 BI =20XX00+X1 =20T13-Q1/ON 33 KV AUX. FEEDER 3 ISOLATOR ON
16031 =20T13-Q1 SU200 BI =20XX00+X1 =20T13-Q1/ADV OFF TRP 33 KV AUX. FEEDER 3 ADVANCE OFF TRIP
16041 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/PWR SPLY1 FLT POWER SUPPLY FAULT AT SYSTEM 1
16042 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/PWR SPLY2 FLT POWER SUPPLY FAULT AT SYSTEM 2
16043 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/SIG PWR FLT POWER SUPPLY FAULT AT SIGNAL CIRCUITS
16044 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/LAN1 FLT DC CONTROL INTERFACE TO LAN 1 FAULT
16045 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/LAN2 FLT DC CONTROL INTERFACE TO LAN 2 FAULT
16046 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/FAN1 FLT FAN FAULT AT SYSTEM 1
16047 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/FAN2 FLT FAN FAULT AT SYSTEM 2
16048 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/CTRL SYS1 FLT AC/DC CONTROL SYSTEM 1 INTERNAL FAULT
16049 =20XJ01+XJ1 SU200 BI =20XX00+X1 =20XJ01+XJ1/CTRL SYS2 FLT AC/DC CONTROL SYSTEM 2 INTERNAL FAULT
16053 =20X61+X61 SU200 BI =20XX00+X1 =20X61+X61/FLT DC SPLY DC POWER SUPPLY FAULT
16054 =20X61+X61 SU200 BI =20XX00+X1 =20X61+X61/FLT SYS SYSTEM FAULT & WATCHDOG ALARM
16055 =20X61+X61 SU200 BI =20XX00+X1 =20X61+X61/RECORD RECORDING EVENT
16056 =20X61+X61 SU200 BI =20XX00+X1 =20X61+X61/TIME SYNC FLT TIME SYNCHRONISATION FAULT
16057 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/PWR SPLY FLT POWER SUPPLY FAULT
16058 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/INT RCI FLT INTERNAL RC FAILURE
16059 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/LAN1 FLT RCI LAN 1 FAULT
16060 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/LAN2 FLT RCI LAN 2 FAULT
16061 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/TELE1 FLT TELECOMMUNICATION 1FAULT
16062 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/TELE2 FLT TELECOMMUNICATION 2FAULT
16063 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/TELECOUNT FLT TELECOUNT FAULT
16064 =20XX12+XX12 SU200 BI =20XX00+X1 =20XX12+XX12/INTERSTATION FLT INTERSTATION FAULT
16065 =20Q02+Q1 SU200 BI =20XX00+X1 =20Q02+Q1/METERING FLT ENERGY METERING SYSTEM FAULT
16066 =20Q02+Q1 SU200 BI =20XX00+X1 =20Q02+Q1/FLT DC SPLY ENERGY METERING DC POWER SUPPLY FAULT
16067 =20Q02+Q1 SU200 BI =20XX00+X1 =20Q02+Q1/FLT AC SPLY ENERGY METERING AC POWER SUPPLY FAULT
16068 =20C00+U1 SU200 BI =20XX00+X1 =20C00+U1/PWR SPLY FLT POINT ON WAVE CONTROL POWER SUPPLY FAULT
16069 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/PWR SPLY FLT POWER SUPPLY FAULT
16070 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/LAN1 FLT MIMIC BOARD LAN 1 FAULT
16071 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/LAN2 FLT MIMIC BOARD LAN 2 FAULT
16072 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/MB FB FLT MIMIC BOARD FIELD BUS FAULT
16073 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/CTRL FLT MIMIC INTERFACE FAULT
16074 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/ESOF P1 EMERGENCY SWITCH OFF POLE 1
16075 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/ESOF P2 EMERGENCY SWITCH OFF POLE 2
16076 =20W01+W1 SU200 BI =20XX00+X1 =20W01+W1/RES HORN RESET ALARM HORN
16077 =20P01+P1 SU200 BI =20XX00+X1 =20P01+P1/ESOF P1 EMERGENCY SWITCH OFF POLE 1
16078 =20P01+P1 SU200 BI =20XX00+X1 =20P01+P1/ESOF P2 EMERGENCY SWITCH OFF POLE 2
16080 =20XX00+X1 SU200 BI =20XX00+X1 =20XX00+X1/FLT DC SPLY STATION SERVICE INTERFACE CUBICLE
SU200 Signal list 11T01+X1
Converter Transformer Interface Pole-1
Binary Outputs -A201
BO-1 L1 Tap changer raise command
BO-2 L1 Tap changer lower command
BO-3 L1 Cooling ON command
BO-4 L1 Cooling OFF command
BO-21 SU-1 Major alarm
BO-22 SU-1 Warning
BO-23 SU-1 Minor alarm
Binary Outputs -A202
BO-1 L2 Tap changer raise command
BO-2 L2 Tap changer lower command
BO-3 L2 Cooling ON command
BO-4 L2 Cooling OFF command
BO-21 SU-2 Major alarm
BO-22 SU-2 Warning
BO-23 SU-2 Minor alarm
Binary Outputs -A203
BO-1 L3 Tap changer raise command
BO-2 L3 Tap changer lower command
BO-3 L3 Cooling ON command
BO-4 L3 Cooling OFF command
BO-21 SU-3 Major alarm
BO-22 SU-3 Warning
BO-23 SU-3 Minor alarm
Binary Outputs -A204
BO-5 10C05-Q9 Interlock Enable
BO-6 10C05-Q8 Interlock Enable
BO-21 SU-4 Major alarm
BO-22 SU-4 Warning
BO-23 SU-4 Minor alarm
Analog Inputs -A201
AI-1 L1 Oil temperature
AI-2 L1 Line winding temperature
AI-3 L1 Star winding temperature
AI-4 L1 Delta winding temperature
Analog Inputs -A202
AI-1 L2 Oil temperature
AI-2 L2 Line winding temperature
AI-3 L2 Star winding temperature
AI-4 L2 Delta winding temperature
Analog Inputs -A203
AI-1 L3 Oil temperature
AI-2 L3 Line winding temperature
AI-3 L3 Star winding temperature
AI-4 L3 Delta winding temperature
Binary Inputs -A201
BI-1 L1 tap position BCD-1
BI-2 L1 tap position BCD-2
BI-3 L1 tap position BCD-4
BI-4 L1 tap position BCD-8
BI-5 L1 tap position BCD-10
BI-6 L1 tap position BCD-20
BI-7 L1 Tap changer Running
BI-8 L1 Tap changer Fault
BI-9 L1 OLTC Local control
BI-10 L1 OLTC Oil filter fault
BI-11 L1 OLTC OFF position
BI-12 L1 Auxiliary power supply fault
BI-13 L1 AC supply fault
BI-14 L1 control voltage fault
BI-15 L1 Internal 3-ph fault
BI-16 SU-1 Reset alarm annunciation
BI-17 L1 Cooling ON
BI-18 L1 Cooling OFF
BI-19 L1 Buchholz Main tank trip
BI-20 L1 PRD Main tank trip
BI-21 L1 OTI trip
BI-22 L1 WTI trip
BI-23 L1 OSR Diverter switch trip
BI-24 L1 PRD Diverter switch trip
BI-25 L1 One cooler group fault
BI-26 L1 More than One cooler group fault
BI-27 L1 Hydran gas monitoring "Gas HI"
BI-28 L1 Hydran gas monitoring " Gas HI-HI"
BI-29 L1 Hydran gas monitoring fault
BI-30 L1 star bushing SF6 trip
BI-31 L1 star bushing SF6 alarm
BI-32 L1 WTI alarm
BI-33 L1 Buchholz Main tank alarm
BI-34 L1 OTI alarm
BI-36 L1 Oil low level alarm
BI-37 L1 Oil high level alarm
Binary Inputs -A202
BI-1 L2 tap position BCD-1
BI-2 L2 tap position BCD-2
BI-3 L2 tap position BCD-4
BI-4 L2 tap position BCD-8
BI-5 L2 tap position BCD-10
BI-6 L2 tap position BCD-20
BI-7 L2 Tap changer Running
BI-8 L2 Tap changer Fault
BI-9 L2 OLTC Local control
BI-10 L2 OLTC Oil filter fault
BI-11 L2 OLTC OFF position
BI-12 L2 Auxiliary power supply fault
BI-13 L2 AC supply fault
BI-14 L2 control voltage fault
BI-15 L2 Internal 3-ph fault
BI-16 SU-2 Reset alarm annunciation
BI-17 L2 Cooling ON
BI-18 L2 Cooling OFF
BI-19 L2 Buchholz Main tank trip
BI-20 L2 PRD Main tank trip
BI-21 L2 OTI trip
BI-22 L2 WTI trip
BI-23 L2 OSR Diverter switch trip
BI-24 L2 PRD Diverter switch trip
BI-25 L2 One cooler group fault
BI-26 L2 More than One cooler group fault
BI-27 L2 Hydran gas monitoring "Gas HI"
BI-28 L2 Hydran gas monitoring " Gas HI-HI"
BI-29 L2 Hydran gas monitoring fault
BI-30 L2 star bushing SF6 trip
BI-31 L2 star bushing SF6 alarm
BI-32 L2 WTI alarm
BI-33 L2 Buchholz Main tank alarm
BI-34 L2 OTI alarm
BI-36 L2 Oil low level alarm
BI-37 L2 Oil high level alarm
Binary Inputs -A203
BI-1 L3 tap position BCD-1
BI-2 L3 tap position BCD-2
BI-3 L3 tap position BCD-4
BI-4 L3 tap position BCD-8
BI-5 L3 tap position BCD-10
BI-6 L3 tap position BCD-20
BI-7 L3 Tap changer Running
BI-8 L3 Tap changer Fault
BI-9 L3 OLTC Local control
BI-10 L3 OLTC Oil filter fault
BI-11 L3 OLTC OFF position
BI-12 L3 Auxiliary power supply fault
BI-13 L3 AC supply fault
BI-14 L3 control voltage fault
BI-15 L3 Internal 3-ph fault
BI-16 SU-3 Reset alarm annunciation
BI-17 L3 Cooling ON
BI-18 L3 Cooling OFF
BI-19 L3 Buchholz Main tank trip
BI-20 L3 PRD Main tank trip
BI-21 L3 OTI trip
BI-22 L3 WTI trip
BI-23 L3 OSR Diverter switch trip
BI-24 L3 PRD Diverter switch trip
BI-25 L3 One cooler group fault
BI-26 L3 More than One cooler group fault
BI-27 L3 Hydran gas monitoring "Gas HI"
BI-28 L3 Hydran gas monitoring " Gas HI-HI"
BI-29 L3 Hydran gas monitoring fault
BI-30 L3 star bushing SF6 trip
BI-31 L3 star bushing SF6 alarm
BI-32 L3 WTI alarm
BI-33 L3 Buchholz Main tank alarm
BI-34 L3 OTI alarm
BI-36 L3 Oil low level alarm
BI-37 L3 Oil high level alarm
Binary Inputs -A204
BI-1 10C05A-Q1 OFF
BI-2 10C05A-Q1 ON
BI-3 10C05A-Q0 OFF
BI-4 10C05A-Q0 ON
BI-5 10C05A-Q6 OFF
BI-6 10C05A-Q6 ON
BI-7 10C05B-Q61 OFF
BI-8 10C05B-Q61 ON
BI-9 10C05B-Q0 OFF
BI-10 10C05B-Q0 ON
BI-11 10C05B-Q62 OFF
BI-12 10C05B-Q62 ON
BI-13 10C05C-Q6 OFF
BI-14 10C05C-Q6 ON
BI-15 10C05C-Q0 OFF
BI-16 10C05C-Q0 ON
BI-17 10C05C-Q2 OFF
BI-18 10C05C-Q2 ON
BI-19 10C05A-Q53-OFF
BI-20 10C05A-Q53-ON
BI-21 10C05A-Q9-OFF
BI-22 10C05A-Q9-ON
BI-23 10C05A-Q8-OFF
BI-24 10C05A-Q8-ON
BI-25 SU-4 Reset Alarm annunciation
BI-26 11B01+X1 VH Interface Power supply fault
BI-33 10T11 Spare trafo cooling system fault
BI-35 10T11 Spare trafo group alarm
BI-38 10T11 Spare trafo power supply fault
SU200 Signal list 12T01+X1
Converter Transformer Interface Pole-2
Binary Outputs -A201
BO-1 L1 Tap changer raise command
BO-2 L1 Tap changer lower command
BO-3 L1 Cooling ON command
BO-4 L1 Cooling OFF command
BO-21 SU-1 Major alarm
BO-22 SU-1 Warning
BO-23 SU-1 Minor alarm
Binary Outputs -A202
BO-1 L2 Tap changer raise command
BO-2 L2 Tap changer lower command
BO-3 L2 Cooling ON command
BO-4 L2 Cooling OFF command
BO-21 SU-2 Major alarm
BO-22 SU-2 Warning
BO-23 SU-2 Minor alarm
Binary Outputs -A203
BO-1 L3 Tap changer raise command
BO-2 L3 Tap changer lower command
BO-3 L3 Cooling ON command
BO-4 L3 Cooling OFF command
BO-21 SU-3 Major alarm
BO-22 SU-3 Warning
BO-23 SU-3 Minor alarm
Binary Outputs -A204
BO-5 10C03-Q9 Interlock Enable
BO-6 10C03-Q8 Interlock Enable
BO-21 SU-4 Major alarm
BO-22 SU-4 Warning
BO-23 SU-4 Minor alarm
Analog Inputs -A201
AI-1 L1 Oil temperature
AI-2 L1 Line winding temperature
AI-3 L1 Star winding temperature
AI-4 L1 Delta winding temperature
Analog Inputs -A202
AI-1 L2 Oil temperature
AI-2 L2 Line winding temperature
AI-3 L2 Star winding temperature
AI-4 L2 Delta winding temperature
Analog Inputs -A203
AI-1 L3 Oil temperature
AI-2 L3 Line winding temperature
AI-3 L3 Star winding temperature
AI-4 L3 Delta winding temperature
Binary Inputs -A201
BI-1 L1 tap position BCD-1
BI-2 L1 tap position BCD-2
BI-3 L1 tap position BCD-4
BI-4 L1 tap position BCD-8
BI-5 L1 tap position BCD-10
BI-6 L1 tap position BCD-20
BI-7 L1 Tap changer Running
BI-8 L1 Tap changer Fault
BI-9 L1 OLTC Local control
BI-10 L1 OLTC Oil filter fault
BI-11 L1 OLTC OFF position
BI-12 L1 Auxiliary power supply fault
BI-13 L1 AC supply fault
BI-14 L1 control voltage fault
BI-15 L1 Internal 3-ph fault
BI-16 SU-1 Reset alarm annunciation
BI-17 L1 Cooling ON
BI-18 L1 Cooling OFF
BI-19 L1 Buchholz Main tank trip
BI-20 L1 PRD Main tank trip
BI-21 L1 OTI trip
BI-22 L1 WTI trip
BI-23 L1 OSR Diverter switch trip
BI-24 L1 PRD Diverter switch trip
BI-25 L1 One cooler group fault
BI-26 L1 More than One cooler group fault
BI-27 L1 Hydran gas monitoring "Gas HI"
BI-28 L1 Hydran gas monitoring " Gas HI-HI"
BI-29 L1 Hydran gas monitoring fault
BI-30 L1 star bushing SF6 trip
BI-31 L1 star bushing SF6 alarm
BI-32 L1 WTI alarm
BI-33 L1 Buchholz Main tank alarm
BI-34 L1 OTI alarm
BI-36 L1 Oil low level alarm
BI-37 L1 Oil high level alarm
Binary Inputs -A202
BI-1 L2 tap position BCD-1
BI-2 L2 tap position BCD-2
BI-3 L2 tap position BCD-4
BI-4 L2 tap position BCD-8
BI-5 L2 tap position BCD-10
BI-6 L2 tap position BCD-20
BI-7 L2 Tap changer Running
BI-8 L2 Tap changer Fault
BI-9 L2 OLTC Local control
BI-10 L2 OLTC Oil filter fault
BI-11 L2 OLTC OFF position
BI-12 L2 Auxiliary power supply fault
BI-13 L2 AC supply fault
BI-14 L2 control voltage fault
BI-15 L2 Internal 3-ph fault
BI-16 SU-2 Reset alarm annunciation
BI-17 L2 Cooling ON
BI-18 L2 Cooling OFF
BI-19 L2 Buchholz Main tank trip
BI-20 L2 PRD Main tank trip
BI-21 L2 OTI trip
BI-22 L2 WTI trip
BI-23 L2 OSR Diverter switch trip
BI-24 L2 PRD Diverter switch trip
BI-25 L2 One cooler group fault
BI-26 L2 More than One cooler group fault
BI-27 L2 Hydran gas monitoring "Gas HI"
BI-28 L2 Hydran gas monitoring " Gas HI-HI"
BI-29 L2 Hydran gas monitoring fault
BI-30 L2 star bushing SF6 trip
BI-31 L2 star bushing SF6 alarm
BI-32 L2 WTI alarm
BI-33 L2 Buchholz Main tank alarm
BI-34 L2 OTI alarm
BI-36 L2 Oil low level alarm
BI-37 L2 Oil high level alarm
Binary Inputs -A203
BI-1 L3 tap position BCD-1
BI-2 L3 tap position BCD-2
BI-3 L3 tap position BCD-4
BI-4 L3 tap position BCD-8
BI-5 L3 tap position BCD-10
BI-6 L3 tap position BCD-20
BI-7 L3 Tap changer Running
BI-8 L3 Tap changer Fault
BI-9 L3 OLTC Local control
BI-10 L3 OLTC Oil filter fault
BI-11 L3 OLTC OFF position
BI-12 L3 Auxiliary power supply fault
BI-13 L3 AC supply fault
BI-14 L3 control voltage fault
BI-15 L3 Internal 3-ph fault
BI-16 SU-3 Reset alarm annunciation
BI-17 L3 Cooling ON
BI-18 L3 Cooling OFF
BI-19 L3 Buchholz Main tank trip
BI-20 L3 PRD Main tank trip
BI-21 L3 OTI trip
BI-22 L3 WTI trip
BI-23 L3 OSR Diverter switch trip
BI-24 L3 PRD Diverter switch trip
BI-25 L3 One cooler group fault
BI-26 L3 More than One cooler group fault
BI-27 L3 Hydran gas monitoring "Gas HI"
BI-28 L3 Hydran gas monitoring " Gas HI-HI"
BI-29 L3 Hydran gas monitoring fault
BI-30 L3 star bushing SF6 trip
BI-31 L3 star bushing SF6 alarm
BI-32 L3 WTI alarm
BI-33 L3 Buchholz Main tank alarm
BI-34 L3 OTI alarm
BI-36 L3 Oil low level alarm
BI-37 L3 Oil high level alarm
Binary Inputs -A204
BI-1 10C03A-Q1 OFF
BI-2 10C03A-Q1 ON
BI-3 10C03A-Q0 OFF
BI-4 10C03A-Q0 ON
BI-5 10C03A-Q6 OFF
BI-6 10C03A-Q6 ON
BI-7 10C03B-Q61 OFF
BI-8 10C03B-Q61 ON
BI-9 10C03B-Q0 OFF
BI-10 10C03B-Q0 ON
BI-11 10C03B-Q62 OFF
BI-12 10C03B-Q62 ON
BI-13 10C03C-Q6 OFF
BI-14 10C03C-Q6 ON
BI-15 10C03C-Q0 OFF
BI-16 10C03C-Q0 ON
BI-17 10C03C-Q2 OFF
BI-18 10C03C-Q2 ON
BI-19 10C03C-Q53-OFF
BI-20 10C03C-Q53-ON
BI-21 10C03C-Q9-OFF
BI-22 10C03C-Q9-ON
BI-23 10C03C-Q8-OFF
BI-24 10C03C-Q8-ON
BI-25 SU-4 Reset Alarm annunciation
BI-26 12B01+X1 VH Interface Power supply fault
SU200 Signal list 11B01+X1
Valve Hall Interface Pole-1
Binary Outputs -A11
BO-1 11B01-Q51 OFF command
BO-2 11B01-Q51 ON command
BO-3 11B01-Q51 Local control
BO-5 11B01-Q52 OFF command
BO-6 11B01-Q52 ON command
BO-7 11B01-Q52 Local control
BO-9 11B01-Q55 OFF command
BO-10 11B01-Q55 ON command
BO-11 11B01-Q55 Local control
BO-12 11B04-SMR Key release
BO-13 11B01-Q54 OFF command
BO-14 11B01-Q54 ON command
BO-15 11B01-Q54 Local control
BO-17 11B01 Door release command
BO-18 11B01 Door lock enable command
BO-19 11B04+UT1 SMR cooling OFF command
BO-20 11B04+UT1 SMR cooling ON command
Analog Inputs -A11
AI-1 Ambient temperature
Binary Inputs -A11
BI-1 11B01-Q51 OFF
BI-2 11B01-Q51 ON
BI-3 11B01-Q51 Fault
BI-4 11B01-Q51 Local
BI-5 11B01-Q52 OFF
BI-6 11B01-Q52 ON
BI-7 11B01-Q52 Fault
BI-8 11B01-Q52 Local
BI-9 11B01-Q55 OFF
BI-10 11B01-Q55 ON
BI-11 11B01-Q55 Fault
BI-12 11B01-Q55 Local
BI-13 11B01-Q54 OFF
BI-14 11B01-Q54 ON
BI-15 11B01-Q54 Fault
BI-16 11B01-Q54 Local
BI-17 11B01 Door closed
BI-18 11B01 Door open
BI-19 11B01 Door locked
BI-20 11B01 Door lock request
BI-21 11B04+UT1 SMR cooling OFF
BI-22 11B04+UT1 SMR cooling ON
BI-23 11B04+UT1 SMR power supply fault
BI-24 11B04+UT1 SMR cooling Local control
BI-25 11B01-Z1 DC Bushing SF6 Trip
BI-26 11B01-Z1 DC Bushing SF6 Alarm
BI-27 11U72+UT1 Valve hall air cooling units OFF
BI-28 11U72+UT1 Valve hall air cooling units ON
BI-29 11U72+UT1 Valve hall air cooling units fault
BI-33 11T01 Transformer interface power supply fault
BI-34 11B04 SMR Fence Locked
BI-35 11B04 SMR Fence Unlocked
SU200 Signal list 12B01+X1
Valve Hall Interface Pole-2
Binary Outputs -A11
BO-1 12B01-Q51 OFF command
BO-2 12B01-Q51 ON command
BO-3 12B01-Q51 Local control
BO-5 12B01-Q52 OFF command
BO-6 12B01-Q52 ON command
BO-7 12B01-Q52 Local control
BO-9 12B01-Q55 OFF command
BO-10 12B01-Q55 ON command
BO-11 12B01-Q55 Local control
BO-12 12B04-SMR Key release
BO-13 12B01-Q54 OFF command
BO-14 12B01-Q54 ON command
BO-15 12B01-Q54 Local control
BO-17 12B01 Door release command
BO-18 12B01 Door lock enable command
BO-19 12B04+UT1 SMR cooling OFF command
BO-20 12B04+UT1 SMR cooling ON command
Analog Inputs -A11
AI-1 Ambient temperature
Binary Inputs -A11
BI-1 12B01-Q51 OFF
BI-2 12B01-Q51 ON
BI-3 12B01-Q51 Fault
BI-4 12B01-Q51 Local
BI-5 12B01-Q52 OFF
BI-6 12B01-Q52 ON
BI-7 12B01-Q52 Fault
BI-8 12B01-Q52 Local
BI-9 12B01-Q55 OFF
BI-10 12B01-Q55 ON
BI-11 12B01-Q55 Fault
BI-12 12B01-Q55 Local
BI-13 12B01-Q54 OFF
BI-14 12B01-Q54 ON
BI-15 12B01-Q54 Fault
BI-16 12B01-Q54 Local
BI-17 12B01 Door closed
BI-18 12B01 Door open
BI-19 12B01 Door locked
BI-20 12B01 Door lock request
BI-21 12B04+UT1 SMR cooling OFF
BI-22 12B04+UT1 SMR cooling ON
BI-23 12B04+UT1 SMR power supply fault
BI-24 12B04+UT1 SMR cooling Local control
BI-25 12B01-Z1 DC Bushing SF6 Trip
BI-26 12B01-Z1 DC Bushing SF6 Alarm
BI-27 12U72+UT1 Valve hall air cooling units OFF
BI-28 12U72+UT1 Valve hall air cooling units ON
BI-29 12U72+UT1 Valve hall air cooling units fault
BI-33 12T01 Transformer interface power supply fault
BI-34 12B04 SMR Fence Locked
BI-35 12B04 SMR Fence Unlocked
SU200 Signal list VBE
Valve Base Electronics Pole-1
Binary Inputs -A9
BI-1 Trigger pulse failure
BI-2 No thyristor redundancy
BI-3 Protective firing exceeded
BI-5 Printer fault
BI-6 Valve check NOT OK
BI-7 VBE1 fault
BI-8 VBE1 Power fault
BI-9 Minimum checkback not available TRIP
BI-10 Thyristor monitoring suspended
BI-15 VBE2 fault
BI-16 VBE2 Power fault
BI-17 11T01+R1 Power supply fault
BI-18 11T01+R1 87 M1 Trip
BI-19 11T01+R1 87T REF Trip
BI-20 11T01+R1 50 51 Trip
BI-21 11T01+R1 24 Trip
BI-22 11T01+R1 86A 86B Trip
BI-23 11T01+R1 Relay fault
BI-24 11T01+R1 Fire fighting
BI-25 11T01+R1 Enable to VHV system
BI-26 11T01+R1 Trip signal
BI-27 11T01+R1 Action signal
BI-28 11T01+R1 Alert signal
BI-29 11T01+R1 VESDA trouble
Valve Base Electronics Pole-2
Binary Inputs -A9
BI-1 Trigger pulse failure
BI-2 No thyristor redundancy
BI-3 Protective firing exceeded
BI-5 Printer fault
BI-6 Valve check NOT OK
BI-7 VBE1 fault
BI-8 VBE1 Power fault
BI-9 Minimum checkback not available TRIP
BI-10 Thyristor monitoring suspended
BI-15 VBE2 fault
BI-16 VBE2 Power fault
BI-17 12T01+R1 Power supply fault
BI-18 12T01+R1 87 M1 Trip
BI-19 12T01+R1 87T REF Trip
BI-20 12T01+R1 50 51 Trip
BI-21 12T01+R1 24 Trip
BI-22 12T01+R1 86A 86B Trip
BI-23 12T01+R1 Relay fault
BI-24 12T01+R1 Fire fighting
BI-25 12T01+R1 Enable to VHV system
BI-26 12T01+R1 Trip signal
BI-27 12T01+R1 Action signal
BI-28 12T01+R1 Alert signal
BI-29 12T01+R1 VESDA trouble
SU200 Signal list Valve Cooling
Binary Inputs -A300
BI-1 Valve Cooling system OFF
BI-2 Valve Cooling system ON
BI-3 Valve Cooling system ALARM
BI-4 Valve Cooling system Cooling tower fault
BI-7 Pump 1 failure
BI-8 Pump 2 failure
BI-9 Expansion tank low trip
BI-10 Water inlet temp. high Alarm
BI-11 Water inlet temp. high Trip
BI-12 Main conductivity high alarm
BI-13 Main conductivity high trip
BI-14 Ion exchange conductivity high alarm
BI-15 Water flow low alarm
BI-16 Water flow low trip
BI-17 Water leakage
BI-18 Storage tank low alarm
BI-19 Spray water storage tank low alarm
BI-20 Spray pump failure
BI-21 Water treatment failure
BI-22 AC Failure
BI-23 DC failure
BI-25 Valve hall ventilation OFF
BI-26 Valve hall ventilation ON
BI-27 VHV fan1 ON
BI-28 VHV fan2 ON
BI-29 VHV fan1 fault
BI-30 VHV fan2 fault
BI-31 VHV filter alarm
BI-32 VHV room temperature alarm
BI-33 VHV damper not closed
BI-34 VHV damper not opened
BI-35 VHV heater fault
BI-36 VHV general alarm
BI-40 Alarm reset
Analog Inputs -A300
AI-1 Valve cooling Inlet temperature
AI-2 Valve cooling Outlet temperature
AI-3 Valve Cooling main conductivity
AI-4 Valve Cooling Deionizer 1 conductivity
AI-5 Valve Cooling Deionizer 2 conductivity
AI-6 Valve Cooling expansion tank level
AI-7 Valve hall temperature
AI-8 Ambient temperature
Binary Inputs -A300
BI-1 Valve Cooling system OFF
BI-2 Valve Cooling system ON
BI-3 Valve Cooling system ALARM
BI-4 Valve Cooling system Cooling tower fault
BI-7 Pump 1 failure
BI-8 Pump 2 failure
BI-9 Expansion tank low trip
BI-10 Water inlet temp. high Alarm
BI-11 Water inlet temp. high Trip
BI-12 Main conductivity high alarm
BI-13 Main conductivity high trip
BI-14 Ion exchange conductivity high alarm
BI-15 Water flow low alarm
BI-16 Water flow low trip
BI-17 Water leakage
BI-18 Storage tank low alarm
BI-19 Spray water storage tank low alarm
BI-20 Spray pump failure
BI-21 Water treatment failure
BI-22 AC Failure
BI-23 DC failure
BI-25 Valve hall ventilation OFF
BI-26 Valve hall ventilation ON
BI-27 VHV fan1 ON
BI-28 VHV fan2 ON
BI-29 VHV fan1 fault
BI-30 VHV fan2 fault
BI-31 VHV filter alarm
BI-32 VHV room temperature alarm
BI-33 VHV damper not closed
BI-34 VHV damper not opened
BI-35 VHV heater fault
BI-36 VHV general alarm
BI-40 Alarm reset
Analog Inputs -A300
AI-1 Valve cooling Inlet temperature
AI-2 Valve cooling Outlet temperature
AI-3 Valve Cooling main conductivity
AI-4 Valve Cooling Deionizer 1 conductivity
AI-5 Valve Cooling Deionizer 2 conductivity
AI-6 Valve Cooling expansion tank level
AI-7 Valve hall temperature
AI-8 Ambient temperature
SU200 Signal list 10X51+X51
Binary Inputs -A201
BI-1 11R01+R1 Power supply fault
BI-2 11R01+R1-A1 Simadyn Hardware fault
BI-3 11R01+R1-A1 Simadyn Fan fault
BI-4 11R01+R1-A1 Simadyn Software fault
BI-5 11R01+R1-A1 Software warning
BI-6 11R01+R1 Test Mode
BI-9 11R01+R2 Power supply fault
BI-10 11R01+R2-A1 Simadyn Hardware fault
BI-11 11R01+R2-A1 Simadyn Fan fault
BI-12 11R01+R2-A1 Simadyn Software fault
BI-13 11R01+R2-A1 Software warning
BI-14 11R01+R2 Test Mode
BI-17 11V00+U1 Power supply fault
BI-18 11V00+U1 ESOF by Pole control
BI-19 11V00+U1 Manual mode selection
BI-20 11V01+U1 Power supply fault
BI-21 11V01+U1 Simadyn Hardware fault
BI-22 11V01+U1 Simadyn fan fault
BI-25 11V02+U2 Power supply fault
BI-26 11V02+U2 Simadyn Hardware fault
BI-27 11V02+U2 Simadyn fan fault
BI-33 11X61+X61 Power supply fault
BI-34 11X61+X61 Watchdog fault
BI-35 11X61+X61 TFR recording
BI-36 11X61+X61 Time sync fault
BI-37 11Q00+Q1 AC power supply fault
Binary Inputs -A202
BI-1 12R01+R1 Power supply fault
BI-2 12R01+R1-A1 Simadyn Hardware fault
BI-3 12R01+R1-A1 Simadyn Fan fault
BI-4 12R01+R1-A1 Simadyn Software fault
BI-5 12R01+R1-A1 Software warning
BI-6 12R01+R1 Test Mode
BI-9 12R01+R2 Power supply fault
BI-10 12R01+R2-A1 Simadyn Hardware fault
BI-11 12R01+R2-A1 Simadyn Fan fault
BI-12 12R01+R2-A1 Simadyn Software fault
BI-13 12R01+R2-A1 Software warning
BI-14 12R01+R2 Test Mode
BI-17 12V00+U1 Power supply fault
BI-18 12V00+U1 ESOF by Pole control
BI-19 12V00+U1 Manual mode selection
BI-20 12V01+U1 Power supply fault
BI-21 12V01+U1 Simadyn Hardware fault
BI-22 12V01+U1 Simadyn fan fault
BI-25 12V02+U2 Power supply fault
BI-26 12V02+U2 Simadyn Hardware fault
BI-27 12V02+U2 Simadyn fan fault
BI-33 12X61+X61 Power supply fault
BI-34 12X61+X61 Watchdog fault
BI-35 12X61+X61 TFR recording
BI-36 12X61+X61 Time sync fault
BI-37 12Q00+Q1 AC power supply fault
Binary Inputs -A203
BI-1 10XJ02+XJ2 Power supply fault system 1
BI-2 10XJ02+XJ2 Power supply fault system 2
BI-3 10XJ02+XJ2 Power supply fault at signal circuits
BI-4 10XJ02+XJ2 LAN 1 fault
BI-5 10XJ02+XJ2 LAN 2 fault
BI-6 10XJ02+XJ2 Fan fault System 1
BI-7 10XJ02+XJ2 Fan fault System 2
BI-8 10XJ02+XJ2 System 1 Internal fault
BI-9 10XJ02+XJ2 System 2 Internal fault
BI-10 10XJ02+XJ2 Masterclock fault system 1
BI-11 10XJ02+XJ2 Masterclock fault system 2
BI-12 10XW10+XW1 cubicle failure
BI-13 10XW10+XW1 PEMO Offline
BI-14 10XW10+XW1 System warning
BI-15 10XW10+XW1 Electrode line faulty
BI-16 10XW10+XW1 GPS clock warning
BI-17 10P01+P1- U201 LAN switch 1 fault
BI-18 10P01+P1- U202 LAN switch 2 fault
BI-19 10P01+P1- U201 LAN switch 1 power supply fault
BI-20 10P01+P1- U202 LAN switch 2 power supply fault
BI-33 10X71+X71 LFL Major
BI-34 10X71+X71 LFL Minor
BI-35 10X71+X71 LFL Operated
BI-36 10X71+X71 LFL Self test
BI-40 10X40+X40 Cubicle failure
Binary Inputs -A204
BI-1 10XJ01+XJ1 Power supply fault system 1
BI-2 10XJ01+XJ1 Power supply fault system 2
BI-3 10XJ01+XJ1 Power supply fault at signal circuits
BI-4 10XJ01+XJ1 LAN 1 fault
BI-5 10XJ01+XJ1 LAN 2 fault
BI-6 10XJ01+XJ1 Fan fault System 1
BI-7 10XJ01+XJ1 Fan fault System 2
BI-8 10XJ01+XJ1 System 1 Internal fault
BI-9 10XJ01+XJ1 System 2 Internal fault
BI-13 10X61+X61 Power supply fault
BI-14 10X61+X61 Watchdog fault
BI-15 10X61+X61 TFR recording
BI-16 10X61+X61 Time sync fault
BI-17 10XX12+XX12 RCI Power supply fault
BI-18 10XX12+XX12 RCI Internal fault
BI-19 10XX12+XX12 RCI LAN 1 fault
BI-20 10XX12+XX12 RCI LAN 2 fault
BI-21 10XX12+XX12 RCI Telecommunication 1 fault
BI-22 10XX12+XX12 RCI Telecommunication 2 fault
BI-23 10XX12+XX12 RCI Telecount fault
BI-24 10XX12+XX12 RCI Interstation fault
BI-25 10Q02+Q1 Energy metering fault
BI-26 10Q02+Q1 DC power supply fault
BI-27 10Q02+Q1 AC power supply fault
BI-28 10C00+U1 Power supply fault
BI-29 10W01+W1 Power supply fault
BI-30 10W01+W1 LAN 1 fault
BI-31 10W01+W1 LAN 2 fault
BI-32 10W01+W1 Mimic board fieldbus fault
BI-33 10W01+W1 Mimic interface fault
BI-34 10W01+W1 ESOF Pole-1
BI-35 10W01+W1 ESOF pole-2
BI-36 10W01+W1 Reset alarm horn
BI-37 10P01+P1 ESOF Pole-1
BI-38 10P01+P1 ESOF Pole-2
BI-40 10XX00+X1 Power supply fault
SU200 Signal list 10B10+X1
DC Station Control interface
Binary Outputs -A200
BO-1 10B10-Q51 OFF command
BO-2 10B10-Q51 ON command
BO-3 10B10-Q52 OFF command
BO-4 10B10-Q52 ON command
BO-5 10B10-Q53 OFF command
BO-6 10B10-Q53 ON command
BO-7 10B10-Q54 OFF command
BO-8 10B10-Q54 ON command
BO-9 10B10-Q55 OFF command
BO-10 10B10-Q55 ON command
BO-11 10B10-Q56 OFF command
BO-12 10B10-Q56 ON command
BO-21 10B10+X1 SU-1 Major
BO-22 10B10+X1 SU-1 Minor
BO-23 10B10+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10B10-Q1 OFF command
BO-2 10B10-Q1 ON command
BO-3 10B10-Q2 OFF command
BO-4 10B10-Q2 ON command
BO-5 10B10-Q3 OFF command
BO-6 10B10-Q3 ON command
BO-7 10B10-Q4 OFF command
BO-8 10B10-Q4 ON command
BO-9 10B10-Q5 OFF command
BO-10 10B10-Q5 ON command
BO-11 10B10-Q6 OFF command
BO-12 10B10-Q6 ON command
BO-13 10B10-Q7 OFF command
BO-14 10B10-Q7 ON command
BO-15 10B10-Q11 OFF command
BO-16 10B10-Q11 ON command
BO-17 10B10-Q12 OFF command
BO-18 10B10-Q12 ON command
BO-21 10B10+X1 SU-2 Major
BO-22 10B10+X1 SU-2 Minor
BO-23 10B10+X1 SU-2 Warning
Binary Outputs -A202
BO-1 10B10-Q94 OFF command
BO-2 10B10-Q94 ON command
BO-3 10B10-Q94 Local control command
BO-5 10B10-Q95 OFF command
BO-6 10B10-Q95 ON command
BO-7 10B10-Q95 Local control command
BO-9 10B10-Q96 OFF command
BO-10 10B10-Q96 ON command
BO-11 10B10-Q96 Local control command
BO-21 10B10+X1 SU-3 Major
BO-22 10B10+X1 SU-3 Minor
BO-23 10B10+X1 SU-3 Warning
Binary Outputs -A203
BO-1 11B04-Q51 OFF command
BO-2 11B04-Q51 ON command
BO-3 11B04-Q53 OFF command
BO-4 11B04-Q53 ON command
BO-5 11B04-Q9 OFF command
BO-6 11B04-Q9 ON command
BO-7 11B04-Q91 OFF command
BO-8 11B04-Q91 ON command
BO-11 12B04-Q51 OFF command
BO-12 12B04-Q51 ON command
BO-13 12B04-Q53 OFF command
BO-14 12B04-Q53 ON command
BO-15 12B04-Q9 OFF command
BO-16 12B04-Q9 ON command
BO-17 12B04-Q91 OFF command
BO-18 12B04-Q91 ON command
BO-21 10B10+X1 SU-4 Major
BO-22 10B10+X1 SU-4 Minor
BO-23 10B10+X1 SU-4 Warning
Binary Inputs -A200
BI-1 10B10-Q51 OFF
BI-2 10B10-Q51 ON
BI-3 10B10-Q51 Fault
BI-4 10B10-Q51 Local
BI-5 10B10-Q52 OFF
BI-6 10B10-Q52 ON
BI-7 10B10-Q52 Fault
BI-8 10B10-Q52 rLocal
BI-9 10B10-Q53 OFF
BI-10 10B10-Q53 ON
BI-11 10B10-Q53 Fault
BI-12 10B10-Q53 Local
BI-13 10B10-Q54 OFF
BI-14 10B10-Q54 ON
BI-15 10B10-Q54 Fault
BI-16 10B10-Q54 Local
BI-17 10B10-Q55 OFF
BI-18 10B10-Q55 ON
BI-19 10B10-Q55 Fault
BI-20 10B10-Q55 Local
BI-21 10B10-Q56 OFF
BI-22 10B10-Q56 ON
BI-23 10B10-Q56 Fault
BI-24 10B10-Q56 Local
BI-33 10B10+S1 AC Supply fault
BI-34 10B10+S1 DC Supply fault
BI-35 10CF10+X1 DC Supply fault
BI-40 10B10+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10B10-Q1 OFF
BI-2 10B10-Q1 ON
BI-3 10B10-Q1 Fault
BI-4 10B10-Q1 Local
BI-5 10B10-Q2 OFF
BI-6 10B10-Q2 ON
BI-7 10B10-Q2 Fault
BI-8 10B10-Q2 Local
BI-9 10B10-Q3 OFF
BI-10 10B10-Q3 ON
BI-11 10B10-Q3 Fault
BI-12 10B10-Q3 Local
BI-13 10B10-Q4 OFF
BI-14 10B10-Q4 ON
BI-15 10B10-Q4 Fault
BI-16 10B10-Q4 Local
BI-17 10B10-Q5 OFF
BI-18 10B10-Q5 ON
BI-19 10B10-Q5 Fault
BI-20 10B10-Q5 Local
BI-21 10B10-Q6 OFF
BI-22 10B10-Q6 ON
BI-23 10B10-Q6 Fault
BI-24 10B10-Q6 Local
BI-25 10B10-Q7 OFF
BI-26 10B10-Q7 ON
BI-27 10B10-Q7 Fault
BI-28 10B10-Q7 Local
BI-29 10B10-Q11 OFF
BI-30 10B10-Q11 ON
BI-31 10B10-Q11 Fault
BI-32 10B10-Q11 Local
BI-33 10B10-Q12 OFF
BI-34 10B10-Q12 ON
BI-35 10B10-Q12 Fault
BI-36 10B10-Q12 Local
BI-40 10B10+X1 SU-2 Reset
Binary Inputs -A202
BI-1 10B10-Q94 OFF
BI-2 10B10-Q94 ON
BI-3 10B10-Q94 general lockout
BI-4 10B10-Q94 ON Lockout
BI-5 10B10-Q94 Loss of N2
BI-6 10B10-Q94 Loss of SF6
BI-7 10B10-Q94 Hydraulic fault
BI-10 10B10-Q94 Local
BI-11 10B10-Q95 OFF
BI-12 10B10-Q95 ON
BI-13 10B10-Q95 general lockout
BI-14 10B10-Q95 ON Lockout
BI-15 10B10-Q95 Loss of N2
BI-16 10B10-Q95 Loss of SF6
BI-17 10B10-Q95 Hydraulic fault
BI-20 10B10-Q95 Local
BI-21 10B10-Q96 OFF
BI-22 10B10-Q96 ON
BI-23 10B10-Q96 general lockout
BI-24 10B10-Q96 ON Lockout
BI-25 10B10-Q96 Loss of N2
BI-26 10B10-Q96 Loss of SF6
BI-27 10B10-Q96 Hydraulic fault
BI-30 10B10-Q96 Local
BI-40 10B10+X1 SU-3 Reset
Binary Inputs -A203
BI-1 11B04-Q51 OFF
BI-2 11B04-Q51 ON
BI-3 11B04-Q51 Fault
BI-4 11B04-Q51 Local
BI-5 11B04-Q53 OFF
BI-6 11B04-Q53 ON
BI-7 11B04-Q53 Fault
BI-8 11B04-Q53 Local
BI-9 11B04-Q9 OFF
BI-10 11B04-Q9 ON
BI-11 11B04-Q9 Fault
BI-12 11B04-Q9 Local
BI-13 11B04-Q91 OFF
BI-14 11B04-Q91 ON
BI-15 11B04-Q91 Fault
BI-16 11B04-Q91 Local
BI-17 12B04-Q51 OFF
BI-18 12B04-Q51 ON
BI-19 12B04-Q51 Fault
BI-20 12B04-Q51 Local
BI-21 12B04-Q53 OFF
BI-22 12B04-Q53 ON
BI-23 12B04-Q53 Fault
BI-24 12B04-Q53 Local
BI-25 12B04-Q9 OFF
BI-26 12B04-Q9 ON
BI-27 12B04-Q9 Fault
BI-28 12B04-Q9 Local
BI-29 12B04-Q91 OFF
BI-30 12B04-Q91 ON
BI-31 12B04-Q91 Fault
BI-32 12B04-Q91 Local
BI-33 11B11-Q93 OFF
BI-34 11B11-Q93 ON
BI-35 12B11-Q93 OFF
BI-36 12B11-Q93 ON
BI-40 10B10+X1 SU-4 Reset
SU200 Signal list 11B11+X1
DC Station Control interface
Binary Outputs -A200
BO-1 11B02-Q1 OFF command
BO-2 11B02-Q1 ON command
BO-3 11B02-Q2 OFF command
BO-4 11B02-Q2 ON command
BO-5 11B02-Q51 OFF command
BO-6 11B02-Q51 ON command
BO-7 11B02-Q52 OFF command
BO-8 11B02-Q52 ON command
BO-17 11B02-Q1 Local command
BO-18 11B02-Q2 Local command
BO-19 11B02-Q51 Local command
BO-20 11B02-Q52 Local command
BO-21 11B11+X1 SU-1 Major
BO-22 11B11+X1 SU-1 Minor
BO-23 11B11+X1 SU-1 Warning
Binary Outputs -A201
BO-1 11B03-Q1 OFF command
BO-2 11B03-Q1 ON command
BO-3 11B03-Q2 OFF command
BO-4 11B03-Q2 ON command
BO-5 11B03-Q51 OFF command
BO-6 11B03-Q51 ON command
BO-7 11B03-Q52 OFF command
BO-8 11B03-Q52 ON command
BO-9 11B11-Q93 OFF command
BO-10 11B11-Q93 ON command
BO-11 11B11-Q93 Local command
BO-13 11B04-Q9 Local command
BO-17 11B03-Q1 Local command
BO-18 11B03-Q2 Local command
BO-19 11B03-Q51 Local command
BO-20 11B03-Q52 Local command
BO-21 11B11+X1 SU-2 Major
BO-22 11B11+X1 SU-2 Minor
BO-23 11B11+X1 SU-2 Warning
Binary Inputs -A200
BI-1 11B02-Q1 OFF
BI-2 11B02-Q1 ON
BI-3 11B02-Q1 Fault
BI-4 11B02-Q1 Local
BI-5 11B02-Q2 OFF
BI-6 11B02-Q2 ON
BI-7 11B02-Q2 Fault
BI-8 11B02-Q2 Local
BI-9 11B02-Q51 OFF
BI-10 11B02-Q51 ON
BI-11 11B02-Q51 Fault
BI-12 11B02-Q51 Local
BI-13 11B02-Q52 OFF
BI-14 11B02-Q52 ON
BI-15 11B02-Q52 Fault
BI-16 11B02-Q52 Local
BI-17 11R04+R1 Power supply fault
BI-18 11R04+R1 Test mode
BI-19 11R04+R1-A1 Simadyn hardware fault
BI-20 11R04+R1-A1 Simadyn fan fault
BI-21 11R04+R1-A1 Software fault
BI-22 11R04+R1-A1 Software warning
BI-23 11R04+R2 Power supply fault
BI-24 11R04+R2 Test mode
BI-25 11R04+R2-A1 Simadyn hardware fault
BI-26 11R04+R2-A1 Simadyn fan fault
BI-27 11R04+R2-A1 Software fault
BI-28 11R04+R2-A1 Software warning
BI-40 11B11+X1 SU-1 Reset
Binary Inputs -A201
BI-1 11B03-Q1 OFF
BI-2 11B03-Q1 ON
BI-3 11B03-Q1 Fault
BI-4 11B03-Q1 Local
BI-5 11B03-Q2 OFF
BI-6 11B03-Q2 ON
BI-7 11B03-Q2 Fault
BI-8 11B03-Q2 Local
BI-9 11B03-Q51 OFF
BI-10 11B03-Q51 ON
BI-11 11B03-Q51 Fault
BI-12 11B03-Q51 Local
BI-13 11B03-Q52 OFF
BI-14 11B03-Q52 ON
BI-15 11B03-Q52 Fault
BI-16 11B03-Q52 Local
BI-23 11B11-R5 DCVD Loss of SF6 alarm
BI-24 11B11-R5 DCVD SF6 Trip
BI-25 11B11-Q93 OFF
BI-26 11B11-Q93 ON
BI-27 11B11-Q93 General Lockout
BI-28 11B11-Q93 ON Lockout
BI-29 11B11-Q93 Loss of N2
BI-30 11B11-Q93 Loss of SF6
BI-31 11B11-Q93 Hydraulic fault
BI-32 11B11-Q93 Local control
BI-34 11B11+S1 AC supply fault
BI-35 11B11+S1 DC supply fault
BI-36 12B11+X1 DC supply fault
BI-40 11B11+X1 SU-2 Reset
SU200 Signal list 12B11+X1
DC Station Control interface
Binary Outputs -A200
BO-1 12B02-Q1 OFF command
BO-2 12B02-Q1 ON command
BO-3 12B02-Q2 OFF command
BO-4 12B02-Q2 ON command
BO-5 12B02-Q51 OFF command
BO-6 12B02-Q51 ON command
BO-7 12B02-Q52 OFF command
BO-8 12B02-Q52 ON command
BO-17 12B02-Q1 Local command
BO-18 12B02-Q2 Local command
BO-19 12B02-Q51 Local command
BO-20 12B02-Q52 Local command
BO-21 12B11+X1 SU-1 Major
BO-22 12B11+X1 SU-1 Minor
BO-23 12B11+X1 SU-1 Warning
Binary Outputs -A201
BO-1 12B03-Q1 OFF command
BO-2 12B03-Q1 ON command
BO-3 12B03-Q2 OFF command
BO-4 12B03-Q2 ON command
BO-5 12B03-Q51 OFF command
BO-6 12B03-Q51 ON command
BO-7 12B03-Q52 OFF command
BO-8 12B03-Q52 ON command
BO-9 12B11-Q93 OFF command
BO-10 12B11-Q93 ON command
BO-11 12B11-Q93 Local command
BO-13 12B04-Q9 Local command
BO-17 12B03-Q1 Local command
BO-18 12B03-Q2 Local command
BO-19 12B03-Q51 Local command
BO-20 12B03-Q52 Local command
BO-21 12B11+X1 SU-2 Major
BO-22 12B11+X1 SU-2 Minor
BO-23 12B11+X1 SU-2 Warning
Binary Inputs -A200
BI-1 12B02-Q1 OFF
BI-2 12B02-Q1 ON
BI-3 12B02-Q1 Fault
BI-4 12B02-Q1 Local
BI-5 12B02-Q2 OFF
BI-6 12B02-Q2 ON
BI-7 12B02-Q2 Fault
BI-8 12B02-Q2 Local
BI-9 12B02-Q51 OFF
BI-10 12B02-Q51 ON
BI-11 12B02-Q51 Fault
BI-12 12B02-Q51 Local
BI-13 12B02-Q52 OFF
BI-14 12B02-Q52 ON
BI-15 12B02-Q52 Fault
BI-16 12B02-Q52 Local
BI-17 12R04+R1 Power supply fault
BI-18 12R04+R1 Test mode
BI-19 12R04+R1-A1 Simadyn hardware fault
BI-20 12R04+R1-A1 Simadyn fan fault
BI-21 12R04+R1-A1 Software fault
BI-22 12R04+R1-A1 Software warning
BI-23 12R04+R2 Power supply fault
BI-24 12R04+R2 Test mode
BI-25 12R04+R2-A1 Simadyn hardware fault
BI-26 12R04+R2-A1 Simadyn fan fault
BI-27 12R04+R2-A1 Software fault
BI-28 12R04+R2-A1 Software warning
BI-40 12B11+X1 SU-1 Reset
Binary Inputs -A201
BI-1 12B03-Q1 OFF
BI-2 12B03-Q1 ON
BI-3 12B03-Q1 Fault
BI-4 12B03-Q1 Local
BI-5 12B03-Q2 OFF
BI-6 12B03-Q2 ON
BI-7 12B03-Q2 Fault
BI-8 12B03-Q2 Local
BI-9 12B03-Q51 OFF
BI-10 12B03-Q51 ON
BI-11 12B03-Q51 Fault
BI-12 12B03-Q51 Local
BI-13 12B03-Q52 OFF
BI-14 12B03-Q52 ON
BI-15 12B03-Q52 Fault
BI-16 12B03-Q52 Local
BI-23 12B11-R5 DCVD Loss of SF6 alarm
BI-24 12B11-R5 DCVD SF6 Trip
BI-25 12B11-Q93 OFF
BI-26 12B11-Q93 ON
BI-27 12B11-Q93 General Lockout
BI-28 12B11-Q93 ON Lockout
BI-29 12B11-Q93 Loss of N2
BI-30 12B11-Q93 Loss of SF6
BI-31 12B11-Q93 Hydraulic fault
BI-32 12B11-Q93 Local control
BI-34 12B11+S1 AC supply fault
BI-35 12B11+S1 DC supply fault
BI-36 11B11+X1 DC supply fault
BI-40 12B11+X1 SU-2 Reset
SU200 Signal list 10C03+X1
AC Station Control interface
Binary Outputs -A200
BO-1 10C03A-Q0 OFF command
BO-2 10C03A-Q0 ON command
BO-3 10C03A-Q1 OFF command
BO-4 10C03A-Q1 ON command
BO-5 10C03A-Q6 OFF command
BO-6 10C03A-Q6 ON command
BO-21 10C03+X1 SU-1 Major
BO-22 10C03+X1 SU-1 Minor
BO-23 10C03+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10C03B-Q0 OFF command
BO-2 10C03B-Q0 ON command
BO-3 10C03B-Q61 OFF command
BO-4 10C03B-Q61 ON command
BO-5 10C03B-Q62 OFF command
BO-6 10C03B-Q62 ON command
BO-21 10C03+X1 SU-2 Major
BO-22 10C03+X1 SU-2 Minor
BO-23 10C03+X1 SU-2 Warning
Binary Outputs -A202
BO-1 10C03C-Q0 OFF command
BO-2 10C03C-Q0 ON command
BO-3 10C03C-Q2 OFF command
BO-4 10C03C-Q2 ON command
BO-5 10C03C-Q6 OFF command
BO-6 10C03C-Q6 ON command
BO-7 10C03C-Q9 OFF command
BO-8 10C03C-Q9 ON command
BO-21 10C03+X1 SU-3 Major
BO-22 10C03+X1 SU-3 Minor
BO-23 10C03+X1 SU-3 Warning
Analog Inputs -A200
AI-1 10C03A-T1 ACF-3 Current
AI-2 10C03A-T1 ACF-3 Reactive power
Binary Inputs -A200
BI-1 10C03A-Q1 OFF
BI-2 10C03A-Q1 ON
BI-3 10C03A-Q1 Fault
BI-4 10C03A-Q6 OFF
BI-5 10C03A-Q6 ON
BI-6 10C03A-Q6 Fault
BI-7 10C03+S1 DC supply fault
BI-8 10C03+S1 AC supply fault
BI-9 10C03+S1 VT MCB fault
BI-13 10C03A-Q51 OFF
BI-14 10C03A-Q51 ON
BI-15 10C03A-Q51 fault
BI-16 10C03A-Q52 OFF
BI-17 10C03A-Q52 ON
BI-18 10C03A-Q52 fault
BI-25 10C03A-Q15 OFF
BI-26 10C03A-Q15 ON
BI-27 10C03A-Q15 fault
BI-29 10C03+S1 ES DS Local control
BI-30 10C03A-Q0 OFF
BI-31 10C03A-Q0 ON
BI-33 10C03A-Q0 Spring unloaded
BI-34 10C03A-Q0 Control voltage fault
BI-35 10C03A-Q0 Motor fault
BI-36 10C03A-Q0 SF6 1st stage
BI-37 10C03A-Q0 SF6 2nd stage
BI-38 10C03A-Q0 Pole Discrepency
BI-39 10C03A-Q0 Local control
BI-40 10C03+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10C03B-Q61 OFF
BI-2 10C03B-Q61 ON
BI-3 10C03B-Q61 fault
BI-4 10C03B-Q62 OFF
BI-5 10C03B-Q62 ON
BI-6 10C03B-Q62 fault
BI-13 10C03B-Q51 OFF
BI-14 10C03B-Q51 ON
BI-15 10C03B-Q51 fault
BI-16 10C03B-Q52 OFF
BI-17 10C03B-Q52 ON
BI-18 10C03B-Q52 fault
BI-28 10C03B-Q0 Point on wave bypass or fault
BI-29 10C03+S1 ES DS Local control
BI-30 10C03B-Q0 OFF
BI-31 10C03B-Q0 ON
BI-33 10C03B-Q0 Spring unloaded
BI-34 10C03B-Q0 Control voltage fault
BI-35 10C03B-Q0 Motor fault
BI-36 10C03B-Q0 SF6 1st stage
BI-37 10C03B-Q0 SF6 2nd stage
BI-38 10C03B-Q0 Pole Discrepency
BI-39 10C03B-Q0 Local control
BI-40 10C03+X1 SU-2 Reset
Binary Inputs -A202
BI-1 10C03C-Q2 OFF
BI-2 10C03C-Q2 ON
BI-3 10C03C-Q2 Fault
BI-4 10C03C-Q6 OFF
BI-5 10C03C-Q6 ON
BI-6 10C03C-Q6 Fault
BI-9 10C03C-Q0 Point on wave bypass or fault
BI-10 10C03C-Q9 OFF
BI-11 10C03C-Q9 ON
BI-12 10C03C-Q9 fault
BI-13 10C03C-Q51 OFF
BI-14 10C03C-Q51 ON
BI-15 10C03C-Q51 fault
BI-16 10C03C-Q52 OFF
BI-17 10C03C-Q52 ON
BI-18 10C03C-Q52 fault
BI-19 10C03C-Q53 OFF
BI-20 10C03C-Q53 ON
BI-21 10C03C-Q53 fault
BI-22 10C03C-Q8 OFF
BI-23 10C03C-Q8 ON
BI-24 10C03C-Q8 fault
BI-25 10C03C-Q25 OFF
BI-26 10C03C-Q25 ON
BI-27 10C03C-Q25 fault
BI-28 10C03+X1 DC supply fault
BI-29 10C03+S1 ES DS Local control
BI-30 10C03C-Q0 OFF
BI-31 10C03C-Q0 ON
BI-33 10C03C-Q0 Spring unloaded
BI-34 10C03C-Q0 Control voltage fault
BI-35 10C03C-Q0 Motor fault
BI-36 10C03C-Q0 SF6 1st stage
BI-37 10C03C-Q0 SF6 2nd stage
BI-38 10C03C-Q0 Pole Discrepency
BI-39 10C03C-Q0 Local control
BI-40 10C03+X1 SU-3 Reset
SU200 Signal list 10C03+X2
AC Station Control interface
Binary Outputs -A200
BO-1 10C01A-Q1 OFF command
BO-2 10C01A-Q1 ON command
BO-3 10C01C-Q1 OFF command
BO-4 10C01C-Q1 ON command
BO-7 10C01A-Q1 Enable interlock command
BO-8 10C01A-Q51 Enable interlock command
BO-9 10C01C-Q2 Enable interlock command
BO-10 10C01C-Q51 Enable interlock command
BO-21 10C03+X2 SU-1 Major
BO-22 10C03+X2 SU-1 Minor
BO-23 10C03+X2 SU-1 Warning
Binary Outputs -A201
BO-21 10C03+X2 SU-2 Major
BO-22 10C03+X2 SU-2 Minor
BO-23 10C03+X2 SU-2 Warning
Binary Inputs -A200
BI-1 10C01A-Q1 OFF
BI-2 10C01A-Q1 ON
BI-3 10C01A-Q1 Fault
BI-4 10C01A-Q51 OFF
BI-5 10C01A-Q51 ON
BI-6 10C01A-Q51 fault
BI-7 10C01C-Q2 OFF
BI-8 10C01C-Q2 ON
BI-9 10C01C-Q2 fault
BI-10 10C01C-Q51 OFF
BI-11 10C01C-Q51 ON
BI-12 10C01C-Q51 fault
BI-13 10C01+S1 10C01A Local
BI-14 10C01+S1 10C01C Local
BI-40 10C03+X2 SU-1 Reset
Binary Inputs -A201
BI-33 10C03+X1 DC supply fault
BI-36 10C01+S1 AC supply fault
BI-37 10C01+S1 DC supply fault
BI-40 10C03+X2 SU-2 Reset
SU200 Signal list 10C04+X1
AC Station Control interface
Binary Outputs -A200
BO-1 10C04-Q01 OFF command
BO-2 10C04-Q01 ON command
BO-3 10C04-Q11 OFF command
BO-4 10C04-Q11 ON command
BO-5 10C04-Q12 OFF command
BO-6 10C04-Q12 ON command
BO-7 10C04-Q21 OFF command
BO-8 10C04-Q21 ON command
BO-9 10C04-Q22 OFF command
BO-10 10C04-Q22 ON command
BO-21 10C04+X1 SU-1 Major
BO-22 10C04+X1 SU-1 Minor
BO-23 10C04+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10C04-Q02 OFF command
BO-2 10C04-Q02 ON command
BO-21 10C04+X1 SU-2 Major
BO-22 10C04+X1 SU-2 Minor
BO-23 10C04+X1 SU-2 Warning
Analog Inputs -A200
AI-1 10C04-T11 IL1 Busbar 1 phase current L1
AI-2 10C04-T15 UL1 Busbar 1A voltage
AI-3 10C04-T16 UL1 Busbar 1B voltage
AI-4 10C04-T15 FL1 Busbar 1A frequency
AI-5 10C04-T16 FL1 Busbar 1B frequency
Analog Inputs -A201
AI-1 10C04-T21 IL1 Busbar 2 phase current L1
AI-2 10C04-T25 UL1 Busbar 2A voltage
AI-3 10C04-T26 UL1 Busbar 2B voltage
AI-4 10C04-T25 FL1 Busbar 2A frequency
AI-5 10C04-T26 FL1 Busbar 2B frequency
Binary Inputs -A200
BI-1 10C04-Q11 OFF
BI-2 10C04-Q11 ON
BI-3 10C04-Q11 fault
BI-4 10C04-Q12 OFF
BI-5 10C04-Q12 ON
BI-6 10C04-Q12 fault
BI-7 10C04-Q21 OFF
BI-8 10C04-Q21 ON
BI-9 10C04-Q21 fault
BI-10 10C04-Q22 OFF
BI-11 10C04-Q22 ON
BI-12 10C04-Q22 fault
BI-13 10C04-Q15 OFF
BI-14 10C04-Q15 ON
BI-15 10C04-Q15 fault
BI-16 10C04-Q16 OFF
BI-17 10C04-Q16 ON
BI-18 10C04-Q16 fault
BI-19 10C04-Q25 OFF
BI-20 10C04-Q25 ON
BI-21 10C04-Q25 fault
BI-22 10C04-Q26 OFF
BI-23 10C04-Q26 ON
BI-24 10C04-Q26 fault
BI-25 10C04+X1 Binary transducer fault
BI-26 10C04+X1 OLM 1 fault
BI-27 10C04+X1 OLM 2 fault
BI-29 10C04+S1 ES DS Local control
BI-30 10C04-Q01 OFF
BI-31 10C04-Q01 ON
BI-33 10C04-Q01 Spring unloaded
BI-34 10C04-Q01 Control voltage fault
BI-35 10C04-Q01 Motor fault
BI-36 10C04-Q01 SF6 1st stage
BI-37 10C04-Q01 SF6 2nd stage
BI-38 10C04-Q01 Pole Discrepency
BI-39 10C04-Q01 Local control
BI-40 10C04+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10C00+R1A busbar fault
BI-2 10C00+R1A busbar protection operated
BI-3 BB 50BF03B trip
BI-4 BB 50BF05B trip
BI-5 BB MCB fault
BI-6 10C03A Trip circuit fault
BI-7 10C03B Trip circuit fault
BI-8 10C03C Trip circuit fault
BI-9 10C04-Q01 Trip circuit fault
BI-10 10C04-Q02 Trip circuit fault
BI-11 10C05A Trip circuit fault
BI-12 10C05B Trip circuit fault
BI-13 10C05C Trip circuit fault
BI-14 10C06A Trip circuit fault
BI-15 10C06C Trip circuit fault
BI-16 10C00+R2A MCB fault
BI-23 10C04+S1 BB3 VT MCB fault
BI-24 10C04+S1 BB4 VT MCB fault
BI-25 10C04+X1 DC supply fault
BI-26 10C04+S1 BB1 VT MCB fault
BI-27 10C04+S1 BB2 VT MCB fault
BI-28 10C04+S1 AC supply fault
BI-29 10C04+S1 DC supply fault
BI-30 10C04-Q02 OFF
BI-31 10C04-Q02 ON
BI-33 10C04-Q02 Spring unloaded
BI-34 10C04-Q02 Control voltage fault
BI-35 10C04-Q02 Motor fault
BI-36 10C04-Q02 SF6 1st stage
BI-37 10C04-Q02 SF6 2nd stage
BI-38 10C04-Q02 Pole Discrepency
BI-39 10C04-Q02 Local control
BI-40 10C04+X1 SU-2 Reset
SU200 Signal list 10C05+X1
AC Station Control interface
Binary Outputs -A200
BO-1 10C05A-Q0 OFF command
BO-2 10C05A-Q0 ON command
BO-3 10C05A-Q1 OFF command
BO-4 10C05A-Q1 ON command
BO-5 10C05A-Q6 OFF command
BO-6 10C05A-Q6 ON command
BO-7 10C05A-Q9 OFF command
BO-8 10C05A-Q9 ON command
BO-9 10C05+S1 AC supply fault
BO-10 10C05+S1 DC supply fault
BO-21 10C05+X1 SU-1 Major
BO-22 10C05+X1 SU-1 Minor
BO-23 10C05+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10C05B-Q0 OFF command
BO-2 10C05B-Q0 ON command
BO-3 10C05B-Q61 OFF command
BO-4 10C05B-Q61 ON command
BO-5 10C05B-Q62 OFF command
BO-6 10C05B-Q62 ON command
BO-21 10C05+X1 SU-2 Major
BO-22 10C05+X1 SU-2 Minor
BO-23 10C05+X1 SU-2 Warning
Binary Outputs -A202
BO-1 10C05C-Q0 OFF command
BO-2 10C05C-Q0 ON command
BO-3 10C05C-Q2 OFF command
BO-4 10C05C-Q2 ON command
BO-5 10C05C-Q6 OFF command
BO-6 10C05C-Q6 ON command
BO-21 10C03+X1 SU-3 Major
BO-22 10C03+X1 SU-3 Minor
BO-23 10C03+X1 SU-3 Warning
Analog Inputs -A202
AI-1 10C05C-T1 ACF-2 Current
AI-2 10C05C-T1 Reactive power
Binary Inputs -A200
BI-1 10C05A-Q1 OFF
BI-2 10C05A-Q1 ON
BI-3 10C05A-Q1 Fault
BI-4 10C05A-Q6 OFF
BI-5 10C05A-Q6 ON
BI-6 10C05A-Q6 Fault
BI-7 10C05+S1 AC supply fault
BI-8 10C05+S1 DC supply fault
BI-9 10C05+S1 VT MCB fault
BI-10 10C05A-Q9 OFF
BI-11 10C05A-Q9 ON
BI-12 10C05A-Q9 fault
BI-13 10C05A-Q51 OFF
BI-14 10C05A-Q51 ON
BI-15 10C05A-Q51 fault
BI-16 10C05A-Q52 OFF
BI-17 10C05A-Q52 ON
BI-18 10C05A-Q52 fault
BI-19 10C05A-Q53 OFF
BI-20 10C05A-Q53 ON
BI-21 10C05A-Q53 fault
BI-22 10C05A-Q8 OFF
BI-23 10C05A-Q8 ON
BI-24 10C05A-Q8 fault
BI-25 10C05A-Q15 OFF
BI-26 10C05A-Q15 ON
BI-27 10C05A-Q15 fault
BI-28 10C05A -Q0 point on wave bypass or fault
BI-29 10C05+S1 ES DS Local control
BI-30 10C05A-Q0 OFF
BI-31 10C05A-Q0 ON
BI-33 10C05A-Q0 Spring unloaded
BI-34 10C05A-Q0 Control voltage fault
BI-35 10C05A-Q0 Motor fault
BI-36 10C05A-Q0 SF6 1st stage
BI-37 10C05A-Q0 SF6 2nd stage
BI-38 10C05A-Q0 Pole Discrepency
BI-39 10C05A-Q0 Local control
BI-40 10C05+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10C05B-Q61 OFF
BI-2 10C05B-Q61 ON
BI-3 10C05B-Q61 fault
BI-4 10C05B-Q62 OFF
BI-5 10C05B-Q62 ON
BI-6 10C05B-Q62 fault
BI-13 10C05B-Q51 OFF
BI-14 10C05B-Q51 ON
BI-15 10C05B-Q51 fault
BI-16 10C05B-Q52 OFF
BI-17 10C05B-Q52 ON
BI-18 10C05B-Q52 fault
BI-28 10C05B-Q0 Point on wave bypass or fault
BI-29 10C05+S1 ES DS Local control
BI-30 10C05B-Q0 OFF
BI-31 10C05B-Q0 ON
BI-33 10C05B-Q0 Spring unloaded
BI-34 10C05B-Q0 Control voltage fault
BI-35 10C05B-Q0 Motor fault
BI-36 10C05B-Q0 SF6 1st stage
BI-37 10C05B-Q0 SF6 2nd stage
BI-38 10C05B-Q0 Pole Discrepency
BI-39 10C05B-Q0 Local control
BI-40 10C05+X1 SU-2 Reset
Binary Inputs -A202
BI-1 10C05C-Q2 OFF
BI-2 10C05C-Q2 ON
BI-3 10C05C-Q2 Fault
BI-4 10C05C-Q6 OFF
BI-5 10C05C-Q6 ON
BI-6 10C05C-Q6 Fault
BI-13 10C05C-Q51 OFF
BI-14 10C05C-Q51 ON
BI-15 10C05C-Q51 fault
BI-16 10C05C-Q52 OFF
BI-17 10C05C-Q52 ON
BI-18 10C05C-Q52 fault
BI-25 10C05C-Q25 OFF
BI-26 10C05C-Q25 ON
BI-27 10C05C-Q25 fault
BI-28 10C05+X1 DC supply fault
BI-29 10C05+S1 ES DS Local control
BI-30 10C05C-Q0 OFF
BI-31 10C05C-Q0 ON
BI-33 10C05C-Q0 Spring unloaded
BI-34 10C05C-Q0 Control voltage fault
BI-35 10C05C-Q0 Motor fault
BI-36 10C05C-Q0 SF6 1st stage
BI-37 10C05C-Q0 SF6 2nd stage
BI-38 10C05C-Q0 Pole Discrepency
BI-39 10C05C-Q0 Local control
BI-40 10C05+X1 SU-3 Reset
SU200 Signal list 10C05+X2
AC Station Control interface
Binary Outputs -A200
BO-1 10C02A-Q1 OFF command
BO-2 10C02A-Q1 ON command
BO-3 10C02C-Q2 OFF command
BO-4 10C02C-Q2 ON command
BO-7 10C02A-Q1 Enable interlock command
BO-8 10C02A-Q51 Enable interlock command
BO-9 10C02C-Q2 Enable interlock command
BO-10 10C02C-Q51 Enable interlock command
BO-21 10C05+X2 SU-1 Major
BO-22 10C05+X2 SU-1 Minor
BO-23 10C05+X2 SU-1 Warning
Binary Outputs -A201
BO-21 10C05+X2 SU-2 Major
BO-22 10C05+X2 SU-2 Minor
BO-23 10C05+X2 SU-2 Warning
Binary Inputs -A200
BI-1 10C02A-Q1 OFF
BI-2 10C02A-Q1 ON
BI-3 10C02A-Q1 Fault
BI-4 10C02A-Q51 OFF
BI-5 10C02A-Q51 ON
BI-6 10C02A-Q51 fault
BI-7 10C02C-Q2 OFF
BI-8 10C02C-Q2 ON
BI-9 10C02C-Q2 fault
BI-10 10C02C-Q51 OFF
BI-11 10C02C-Q51 ON
BI-12 10C02C-Q51 fault
BI-13 10C02+S1 10C01A Local
BI-14 10C02+S1 10C01C Local
BI-40 10C05+X2 SU-1 Reset
Binary Inputs -A201
BI-33 10C06+X1 DC supply fault
BI-36 10C02+S1 AC supply fault
BI-37 10C02+S1 DC supply fault
BI-40 10C05+X2 SU-2 Reset
SU200 Signal list 10C06+X1
AC Station Control interface
Binary Outputs -A200
BO-1 10C06A-Q0 OFF command
BO-2 10C06A-Q0 ON command
BO-3 10C06A-Q1 OFF command
BO-4 10C06A-Q1 ON command
BO-5 10C06A-Q6 OFF command
BO-6 10C06A-Q6 ON command
BO-21 10C06+X1 SU-1 Major
BO-22 10C06+X1 SU-1 Minor
BO-23 10C06+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10C06C-Q0 OFF command
BO-2 10C06C-Q0 ON command
BO-3 10C06C-Q2 OFF command
BO-4 10C06C-Q2 ON command
BO-5 10C06C-Q6 OFF command
BO-6 10C06C-Q6 ON command
BO-21 10C06+X1 SU-2 Major
BO-22 10C06+X1 SU-2 Minor
BO-23 10C06+X1 SU-2 Warning
Binary Outputs -A202
BO-21 10C06+X1 SU-3 Major
BO-22 10C06+X1 SU-3 Minor
BO-23 10C06+X1 SU-3 Warning
Analog Inputs -A201
AI-1 10C06C-T1 ACF-1 Current
AI-2 10C06C-T1 ACF-1 Reactive power
Binary Inputs -A200
BI-1 10C06A-Q1 OFF
BI-2 10C06A-Q1 ON
BI-3 10C06A-Q1 Fault
BI-4 10C06A-Q6 OFF
BI-5 10C06A-Q6 ON
BI-6 10C06A-Q6 Fault
BI-13 10C06A-Q51 OFF
BI-14 10C06A-Q51 ON
BI-15 10C06A-Q51 fault
BI-16 10C06A-Q52 OFF
BI-17 10C06A-Q52 ON
BI-18 10C06A-Q52 fault
BI-29 10C06+S1 ES DS Local control
BI-30 10C06A-Q0 OFF
BI-31 10C06A-Q0 ON
BI-33 10C06A-Q0 Spring unloaded
BI-34 10C06A-Q0 Control voltage fault
BI-35 10C06A-Q0 Motor fault
BI-36 10C06A-Q0 SF6 1st stage
BI-37 10C06A-Q0 SF6 2nd stage
BI-38 10C06A-Q0 Pole Discrepency
BI-39 10C06A-Q0 Local control
BI-40 10C06+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10C06C-Q2 OFF
BI-2 10C06C-Q2 ON
BI-3 10C06C-Q2 Fault
BI-4 10C06C-Q6 OFF
BI-5 10C06C-Q6 ON
BI-6 10C06C-Q6 Fault
BI-13 10C06C-Q51 OFF
BI-14 10C06C-Q51 ON
BI-15 10C06C-Q51 fault
BI-16 10C06C-Q52 OFF
BI-17 10C06C-Q52 ON
BI-18 10C06C-Q52 fault
BI-29 10C06+S1 ES DS Local control
BI-30 10C06C-Q0 OFF
BI-31 10C06C-Q0 ON
BI-33 10C06C-Q0 Spring unloaded
BI-34 10C06C-Q0 Control voltage fault
BI-35 10C06C-Q0 Motor fault
BI-36 10C06C-Q0 SF6 1st stage
BI-37 10C06C-Q0 SF6 2nd stage
BI-38 10C06C-Q0 Pole Discrepency
BI-39 10C06C-Q0 Local control
BI-40 10C06+X1 SU-2 Reset
Binary Inputs -A202
BI-33 10C05+X2 DC Supply fault
BI-36 10C06+S1 AC supply fault
BI-37 10C06+S1 DC supply fault
BI-40 10C06+X1 SU-3 Reset
SU200 Signal list 10CF10+X1
AC Station Control interface
Binary Outputs -A200
BO-1 10CF11-Q0 OFF command
BO-2 10CF11-Q0 ON command
BO-3 10CF11-Q1 OFF command
BO-4 10CF11-Q1 ON command
BO-21 10CF10+X1 SU-1 Major
BO-22 10CF10+X1 SU-1 Minor
BO-23 10CF10+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10CF12-Q0 OFF command
BO-2 10CF12-Q0 ON command
BO-3 10CF12-Q1 OFF command
BO-4 10CF12-Q1 ON command
BO-21 10CF10+X1 SU-2 Major
BO-22 10CF10+X1 SU-2 Minor
BO-23 10CF10+X1 SU-2 Warning
Binary Outputs -A202
BO-1 10CF13-Q0 OFF command
BO-2 10CF13-Q0 ON command
BO-3 10CF13-Q1 OFF command
BO-4 10CF13-Q1 ON command
BO-21 10CF10+X1 SU-3 Major
BO-22 10CF10+X1 SU-3 Minor
BO-23 10CF10+X1 SU-3 Warning
Binary Outputs -A203
BO-1 10CF14-Q0 OFF command
BO-2 10CF14-Q0 ON command
BO-3 10CF14-Q1 OFF command
BO-4 10CF14-Q1 ON command
BO-21 10CF10+X1 SU-4 Major
BO-22 10CF10+X1 SU-4 Minor
BO-23 10CF10+X1 SU-4 Warning
Analog Inputs -A200
AI-1 10CF11-T3 Reactive power
Analog Inputs -A201
AI-1 10CF12-T3 Reactive power
Analog Inputs -A202
AI-1 10CF13-T3 Reactive power
Analog Inputs -A203
AI-1 10CF14-T3 Reactive power
Binary Inputs -A200
BI-1 10CF11-Q1 OFF
BI-2 10CF11-Q1 ON
BI-3 10CF11-Q1 Fault
BI-4 10CF11-Q51 OFF
BI-5 10CF11-Q51 ON
BI-6 10CF11-Q51 Fault
BI-7 10CF11-Q52 OFF
BI-8 10CF11-Q52 ON
BI-9 10CF11-Q52 Fault
BI-10 10CF11-Q17 OFF
BI-11 10CF11-Q17 ON
BI-12 10CF11-Q17 fault
BI-13 10CF11-T1 50 ACF trip
BI-14 10CF11-T1 51 ACF trip
BI-15 10CF11-T1 49_59 ACF trip
BI-16 10CF11-T41 51 ACFL trip
BI-17 10CF11-T42 51 ACFR trip
BI-18 10CF11-T41 50 ACFL trip
BI-19 10CF11-T42 50 ACFR trip
BI-20 10R11+R2A 87ACFB 11 trip
BI-21 10R11+R2A 50BF 11 trip
BI-22 10R11+R2A 86A_86B 11 trip
BI-23 10CF11 TC fault
BI-24 10B10+X1 DC supply fault
BI-25 10CF10+S1 VT MCB fault
BI-26 10CF11-Q0 CB point on wave bypass or fault
BI-27 10CF10+S1 AC supply fault
BI-28 10CF10+S1 DC supply fault
BI-29 10CF10+S1 ES DS local control
BI-30 10CF11-Q0 OFF
BI-31 10CF11-Q0 ON
BI-33 10CF11-Q0 Spring unloaded
BI-34 10CF11-Q0 Control voltage fault
BI-35 10CF11-Q0 Motor fault
BI-36 10CF11-Q0 SF6 1st stage
BI-37 10CF11-Q0 SF6 2nd stage
BI-38 10CF11-Q0 Pole Discrepency
BI-39 10CF11-Q0 Local control
BI-40 10CF10+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10CF12-Q1 OFF
BI-2 10CF12-Q1 ON
BI-3 10CF12-Q1 Fault
BI-4 10CF12-Q51 OFF
BI-5 10CF12-Q51 ON
BI-6 10CF12-Q51 Fault
BI-7 10CF12-Q52 OFF
BI-8 10CF12-Q52 ON
BI-9 10CF12-Q52 Fault
BI-10 10CF12-T1 50 ACF trip
BI-11 10CF12-T1 51 ACF trip
BI-12 10CF12-T1 49_59 ACF trip
BI-13 10CF12-T41 51 ACFL trip
BI-14 10CF12-T42 51 ACFR trip
BI-15 10CF12-T41 50 ACFL trip
BI-16 10CF12-T42 50 ACFR trip
BI-17 10R11+R2A 87ACFB 12 trip
BI-18 10R11+R2A 50BF 12 trip
BI-19 10R11+R2A 86A_86B 12 trip
BI-20 10R11+R2C 10CF12 TC fault
BI-21 10R11+R2A 87BBM2 trip
BI-22 10R11+R2A 27_59 trip
BI-23 10R11+R2A 86A_86B_M2 trip
BI-24 10R11+R2A MCB fault
BI-25 10R04+R2 relay 24_34 fault
BI-26 10R11+R2 relay 11_12 fault
BI-27 10R11+R2 relay 13_14 fault
BI-28 10CF12-Q0 CB point on wave bypass or fault
BI-29 10CF10+S1 ES DS local control
BI-30 10CF12-Q0 OFF
BI-31 10CF12-Q0 ON
BI-33 10CF12-Q0 Spring unloaded
BI-34 10CF12-Q0 Control voltage fault
BI-35 10CF12-Q0 Motor fault
BI-36 10CF12-Q0 SF6 1st stage
BI-37 10CF12-Q0 SF6 2nd stage
BI-38 10CF12-Q0 Pole Discrepency
BI-39 10CF12-Q0 Local control
BI-40 10CF10+X1 SU-2 Reset
Binary Inputs -A202
BI-1 10CF13-Q1 OFF
BI-2 10CF13-Q1 ON
BI-3 10CF13-Q1 Fault
BI-4 10CF13-Q51 OFF
BI-5 10CF13-Q51 ON
BI-6 10CF13-Q51 Fault
BI-7 10CF13-Q52 OFF
BI-8 10CF13-Q52 ON
BI-9 10CF13-Q52 Fault
BI-10 10CF13-T1 50 ACF trip
BI-11 10CF13-T1 51 ACF trip
BI-12 10CF13-T1 49_59 ACF trip
BI-13 10CF13-T41 51 ACFL trip
BI-14 10CF13-T42 51 ACFR trip
BI-15 10CF13-T41 50 ACFL trip
BI-16 10CF13-T42 50 ACFR trip
BI-17 10R11+R1 power supply fault
BI-18 10R11+R1 test mode
BI-19 10R11+R1-A1 Hardware fault
BI-20 10R11+R1-A1 Simadyn fan fault
BI-21 10R11+R1-A1 Software warning
BI-22 10R11+R1-A1 Software fault
BI-23 10R11+R2B 87ACFB 13 trip
BI-24 10R11+R2B 50BF 13 trip
BI-25 10R11+R2B 86A_86B 13 trip
BI-26 10CF13 TC fault
BI-27 10R11+R2B MCB fault
BI-28 10CF13-Q0 CB point on wave bypass or fault
BI-29 10CF10+S2 ES DS Local control
BI-30 10CF13-Q0 OFF
BI-31 10CF13-Q0 ON
BI-33 10CF13-Q0 Spring unloaded
BI-34 10CF13-Q0 Control voltage fault
BI-35 10CF13-Q0 Motor fault
BI-36 10CF13-Q0 SF6 1st stage
BI-37 10CF13-Q0 SF6 2nd stage
BI-38 10CF13-Q0 Pole Discrepency
BI-39 10CF13-Q0 Local control
BI-40 10CF10+X1 SU-3 Reset
Binary Inputs -A203
BI-1 10CF14-Q1 OFF
BI-2 10CF14-Q1 ON
BI-3 10CF14-Q1 Fault
BI-4 10CF14-Q51 OFF
BI-5 10CF14-Q51 ON
BI-6 10CF14-Q51 Fault
BI-7 10CF14-Q52 OFF
BI-8 10CF14-Q52 ON
BI-9 10CF14-Q52 Fault
BI-10 10CF14-T1 50 CB trip
BI-11 10CF14-T1 51 CB trip
BI-12 10CF14-T1 49_59 CB trip
BI-13 10R11+R1-F11 CPR97 fault
BI-14 10R11+R1-F12 CPR97 fault
BI-15 10R11+R1-F13 CPR97 fault
BI-16 10R11+R1-F21 CPR97 fault
BI-17 10R11+R1-F22 CPR97 fault
BI-18 10R11+R1-F23 CPR97 fault
BI-19 10R11+R1-F31 CPR97 fault
BI-20 10R11+R1-F32 CPR97 fault
BI-21 10R11+R1-F33 CPR97 fault
BI-22 10R11+R1-F41 CPR97 fault
BI-23 10R11+R2B 87ACFB 14 trip
BI-24 10R11+R2B 50BF 14 trip
BI-25 10R11+R2B 86A_86B 14 trip
BI-26 10CF14 TC fault
BI-27 10R11+R2C MCB fault
BI-28 10CF14-Q0 CB point on wave bypass or fault
BI-29 10CF10+S2 ES DS Local control
BI-30 10CF14-Q0 OFF
BI-31 10CF14-Q0 ON
BI-33 10CF14-Q0 Spring unloaded
BI-34 10CF14-Q0 Control voltage fault
BI-35 10CF14-Q0 Motor fault
BI-36 10CF14-Q0 SF6 1st stage
BI-37 10CF14-Q0 SF6 2nd stage
BI-38 10CF14-Q0 Pole Discrepency
BI-39 10CF14-Q0 Local control
BI-40 10CF10+X1 SU-4 Reset
SU200 Signal list 10CF20+X1
AC Station Control interface
Binary Outputs -A200
BO-1 10CF21-Q0 OFF command
BO-2 10CF21-Q0 ON command
BO-3 10CF21-Q1 OFF command
BO-4 10CF21-Q1 ON command
BO-21 10CF20+X1 SU-1 Major
BO-22 10CF20+X1 SU-1 Minor
BO-23 10CF20+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10CF22-Q0 OFF command
BO-2 10CF22-Q0 ON command
BO-3 10CF22-Q1 OFF command
BO-4 10CF22-Q1 ON command
BO-21 10CF20+X1 SU-2 Major
BO-22 10CF20+X1 SU-2 Minor
BO-23 10CF20+X1 SU-2 Warning
Binary Outputs -A202
BO-1 10CF23-Q0 OFF command
BO-2 10CF23-Q0 ON command
BO-3 10CF23-Q1 OFF command
BO-4 10CF23-Q1 ON command
BO-21 10CF20+X1 SU-3 Major
BO-22 10CF20+X1 SU-3 Minor
BO-23 10CF20+X1 SU-3 Warning
Binary Outputs -A203
BO-1 10CF24-Q0 OFF command
BO-2 10CF24-Q0 ON command
BO-3 10CF24-Q1 OFF command
BO-4 10CF24-Q1 ON command
BO-21 10CF20+X1 SU-4 Major
BO-22 10CF20+X1 SU-4 Minor
BO-23 10CF20+X1 SU-4 Warning
Analog Inputs -A200
AI-1 10CF21-T3 Reactive power
Analog Inputs -A201
AI-1 10CF22-T3 Reactive power
Analog Inputs -A202
AI-1 10CF23-T3 Reactive power
Analog Inputs -A203
AI-1 10CF24-T1 Reactive power
Binary Inputs -A200
BI-1 10CF21-Q1 OFF
BI-2 10CF21-Q1 ON
BI-3 10CF21-Q1 Fault
BI-4 10CF21-Q51 OFF
BI-5 10CF21-Q51 ON
BI-6 10CF21-Q51 Fault
BI-7 10CF21-Q52 OFF
BI-8 10CF21-Q52 ON
BI-9 10CF21-Q52 Fault
BI-10 10CF21-Q17 OFF
BI-11 10CF21-Q17 ON
BI-12 10CF21-Q17 fault
BI-13 10CF21-T1 50 ACF trip
BI-14 10CF21-T1 51 ACF trip
BI-15 10CF21-T1 49_59 ACF trip
BI-16 10CF21-T41 51 ACFL trip
BI-17 10CF21-T42 51 ACFR trip
BI-18 10CF21-T41 50 ACFL trip
BI-19 10CF21-T42 50 ACFR trip
BI-20 10R21+R2A 87ACFB 21 trip
BI-21 10R21+R2A 50BF 21 trip
BI-22 10R21+R2A 86A_86B 21 trip
BI-23 10CF21 TC fault
BI-24 10B30+X1 DC supply fault
BI-25 10CF20+S1 VT MCB fault
BI-26 10CF21-Q0 CB point on wave bypass or fault
BI-27 10CF20+S1 AC supply fault
BI-28 10CF20+S1 DC supply fault
BI-29 10CF20+S1 ES DS local control
BI-30 10CF21-Q0 OFF
BI-31 10CF21-Q0 ON
BI-33 10CF21-Q0 Spring unloaded
BI-34 10CF21-Q0 Control voltage fault
BI-35 10CF21-Q0 Motor fault
BI-36 10CF21-Q0 SF6 1st stage
BI-37 10CF21-Q0 SF6 2nd stage
BI-38 10CF21-Q0 Pole Discrepency
BI-39 10CF21-Q0 Local control
BI-40 10CF20+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10CF22-Q1 OFF
BI-2 10CF22-Q1 ON
BI-3 10CF22-Q1 Fault
BI-4 10CF22-Q51 OFF
BI-5 10CF22-Q51 ON
BI-6 10CF22-Q51 Fault
BI-7 10CF22-Q52 OFF
BI-8 10CF22-Q52 ON
BI-9 10CF22-Q52 Fault
BI-10 10CF22-T1 50 ACF trip
BI-11 10CF22-T1 51 ACF trip
BI-12 10CF22-T1 49_59 ACF trip
BI-13 10CF22-T41 51 ACFL trip
BI-14 10CF22-T42 51 ACFR trip
BI-15 10CF22-T41 50 ACFL trip
BI-16 10CF22-T42 50 ACFR trip
BI-17 10R21+R2A 87ACFB 22 trip
BI-18 10R21+R2A 50BF 22 trip
BI-19 10R21+R2A 86A_86B 22 trip
BI-20 10R21+R2C 10CF22 TC fault
BI-21 10R21+R2A 87BBM2 trip
BI-22 10R21+R2A 27_59 trip
BI-23 10R21+R2A 86A_86B_M2 trip
BI-24 10R21+R2A MCB fault
BI-25 10R04+R2 MCB fault
BI-26 10R21+R2 relay 21_22 fault
BI-27 10R21+R2 relay 23 fault
BI-28 10CF22-Q0 CB point on wave bypass or fault
BI-29 10CF20+S1 ES DS local control
BI-30 10CF22-Q0 OFF
BI-31 10CF22-Q0 ON
BI-33 10CF22-Q0 Spring unloaded
BI-34 10CF22-Q0 Control voltage fault
BI-35 10CF22-Q0 Motor fault
BI-36 10CF22-Q0 SF6 1st stage
BI-37 10CF22-Q0 SF6 2nd stage
BI-38 10CF22-Q0 Pole Discrepency
BI-39 10CF22-Q0 Local control
BI-40 10CF20+X1 SU-2 Reset
Binary Inputs -A202
BI-1 10CF23-Q1 OFF
BI-2 10CF23-Q1 ON
BI-3 10CF23-Q1 Fault
BI-4 10CF23-Q51 OFF
BI-5 10CF23-Q51 ON
BI-6 10CF23-Q51 Fault
BI-7 10CF23-Q52 OFF
BI-8 10CF23-Q52 ON
BI-9 10CF23-Q52 Fault
BI-10 10CF23-T1 50 ACF trip
BI-11 10CF23-T1 51 ACF trip
BI-12 10CF23-T1 49_59 ACF trip
BI-13 10CF23-T41 51 ACFL trip
BI-14 10CF23-T42 51 ACFR trip
BI-15 10CF23-T41 50 ACFL trip
BI-16 10CF23-T42 50 ACFR trip
BI-17 10R21+R1 power supply fault
BI-18 10R21+R1 test mode
BI-19 10R21+R1-A1 Hardware fault
BI-20 10R21+R1-A1 Simadyn fan fault
BI-21 10R21+R1-A1 Software warning
BI-22 10R21+R1-A1 Software fault
BI-23 10R21+R2B 87ACFB 23 trip
BI-24 10R21+R2B 50BF 23 trip
BI-25 10R21+R2B 86A_86B 23 trip
BI-26 10CF23 TC fault
BI-27 10R21+R2B MCB fault
BI-28 10CF23-Q0 CB point on wave bypass or fault
BI-29 10CF20+S2 ES DS Local control
BI-30 10CF23-Q0 OFF
BI-31 10CF23-Q0 ON
BI-33 10CF23-Q0 Spring unloaded
BI-34 10CF23-Q0 Control voltage fault
BI-35 10CF23-Q0 Motor fault
BI-36 10CF23-Q0 SF6 1st stage
BI-37 10CF23-Q0 SF6 2nd stage
BI-38 10CF23-Q0 Pole Discrepency
BI-39 10CF23-Q0 Local control
BI-40 10CF20+X1 SU-3 Reset
Binary Inputs -A203
BI-1 10CF24-Q1 OFF
BI-2 10CF24-Q1 ON
BI-3 10CF24-Q1 Fault
BI-4 10CF24-Q51 OFF
BI-5 10CF24-Q51 ON
BI-6 10CF24-Q51 Fault
BI-7 10CF24-Q52 OFF
BI-8 10CF24-Q52 ON
BI-9 10CF24-Q52 Fault
BI-10 10CF24+UT1 WTI
BI-11 10CF24+UT1 OTI
BI-12 10CF24+UT1 Pressure
BI-13 10R21+R1-F11 CPR97 fault
BI-14 10R21+R1-F12 CPR97 fault
BI-15 10R21+R1-F13 CPR97 fault
BI-16 10R21+R1-F21 CPR97 fault
BI-17 10R21+R1-F22 CPR97 fault
BI-18 10R21+R1-F23 CPR97 fault
BI-19 10R21+R1-F31 CPR97 fault
BI-20 10R21+R1-F32 CPR97 fault
BI-21 10R21+R1-F33 CPR97 fault
BI-22 10R04+R2 87L_64_24 trip
BI-23 10R04+R2 50BF 24 trip
BI-24 10R04+R2 50_51L 24 trip
BI-25 10R04+R2 86A_86B 24 trip
BI-26 10CF24 TC fault
BI-27 10R21+R2C MCB fault
BI-28 10CF24+UT1 Buchholz
BI-29 10CF20+S2 ES DS Local control
BI-30 10CF24-Q0 OFF
BI-31 10CF24-Q0 ON
BI-33 10CF24-Q0 Spring unloaded
BI-34 10CF24-Q0 Control voltage fault
BI-35 10CF24-Q0 Motor fault
BI-36 10CF24-Q0 SF6 1st stage
BI-37 10CF24-Q0 SF6 2nd stage
BI-38 10CF24-Q0 Pole Discrepency
BI-39 10CF24-Q0 Local control
BI-40 10CF20+X1 SU-4 Reset
SU200 Signal list 10CF20+X2
AC Station Control interface
Binary Outputs -A200
BO-1 10CF25-Q0 OFF command
BO-2 10CF25-Q0 ON command
BO-3 10CF25-Q1 OFF command
BO-4 10CF25-Q1 ON command
BO-21 10CF20+X2 SU-1 Major
BO-22 10CF20+X2 SU-1 Minor
BO-23 10CF20+X2 SU-1 Warning
Binary Outputs -A201
BO-1 10CF26-Q0 OFF command
BO-2 10CF26-Q0 ON command
BO-3 10CF26-Q1 OFF command
BO-4 10CF26-Q1 ON command
BO-21 10CF20+X2 SU-2 Major
BO-22 10CF20+X2 SU-2 Minor
BO-23 10CF20+X2 SU-2 Warning
Binary Outputs -A202
BO-21 10CF20+X2 SU-3 Major
BO-22 10CF20+X2 SU-3 Minor
BO-23 10CF20+X2 SU-3 Warning
Analog Inputs -A200
AI-1 10CF25-T3 Reactive power
Analog Inputs -A201
AI-1 10CF26-T3 Reactive power
Binary Inputs -A200
BI-1 10CF25-Q1 OFF
BI-2 10CF25-Q1 ON
BI-3 10CF25-Q1 Fault
BI-4 10CF25-Q51 OFF
BI-5 10CF25-Q51 ON
BI-6 10CF25-Q51 Fault
BI-7 10CF25-Q52 OFF
BI-8 10CF25-Q52 ON
BI-9 10CF25-Q52 Fault
BI-10 10CF25-T1 50 ACF trip
BI-11 10CF25-T1 51 ACF trip
BI-12 10CF25-T1 49_59 ACF trip
BI-13 10CF25-T41 51 ACFL trip
BI-14 10CF25-T42 51 ACFR trip
BI-15 10CF25-T41 50 ACFL trip
BI-16 10CF25-T42 50 ACFR trip
BI-17 10R21+R2D 87ACFB 25 trip
BI-18 10R21+R2D 50BF 25 trip
BI-19 10R21+R2D 86A_86B 25 trip
BI-20 10R21+R2E 10CF25 TC fault
BI-24 10R21+R2D MCB fault
BI-25 10CF20+S3 MCB fault
BI-26 10R21+R2D relay 25_26 fault
BI-27 10CF20+S3 DC supply fault
BI-29 10CF25-Q1 local control
BI-30 10CF25-Q0 OFF
BI-31 10CF25-Q0 ON
BI-33 10CF25-Q0 Spring unloaded
BI-34 10CF25-Q0 Control voltage fault
BI-35 10CF25-Q0 Motor fault
BI-36 10CF25-Q0 SF6 1st stage
BI-37 10CF25-Q0 SF6 2nd stage
BI-38 10CF25-Q0 Pole Discrepency
BI-39 10CF25-Q0 Local control
BI-40 10CF20+X2 SU-1 Reset
Binary Inputs -A201
BI-1 10CF26-Q1 OFF
BI-2 10CF26-Q1 ON
BI-3 10CF26-Q1 Fault
BI-4 10CF26-Q51 OFF
BI-5 10CF26-Q51 ON
BI-6 10CF26-Q51 Fault
BI-7 10CF26-Q52 OFF
BI-8 10CF26-Q52 ON
BI-9 10CF26-Q52 Fault
BI-10 10CF26-T1 50 ACF trip
BI-11 10CF26-T1 51 ACF trip
BI-12 10CF26-T1 49_59 ACF trip
BI-13 10CF26-T41 51 ACFL trip
BI-14 10CF26-T42 51 ACFR trip
BI-15 10CF26-T41 50 ACFL trip
BI-16 10CF26-T42 50 ACFR trip
BI-23 10R21+R2D 87ACFB 26 trip
BI-24 10R21+R2D 50BF 26 trip
BI-25 10R21+R2D 86A_86B 26 trip
BI-26 10R21+R2E 10CF26 TC fault
BI-29 10CF26-Q1 local control
BI-30 10CF26-Q0 OFF
BI-31 10CF26-Q0 ON
BI-33 10CF26-Q0 Spring unloaded
BI-34 10CF26-Q0 Control voltage fault
BI-35 10CF26-Q0 Motor fault
BI-36 10CF26-Q0 SF6 1st stage
BI-37 10CF26-Q0 SF6 2nd stage
BI-38 10CF26-Q0 Pole Discrepency
BI-39 10CF26-Q0 Local control
BI-40 10CF20+X2 SU-2 Reset
Binary Inputs -A202
BI-1 10C00+U2 Power supply fault
BI-2 10CF25-Q0 Device OK
BI-3 10CF25-Q0 Sync data error
BI-4 10CF25-Q0 Control switch fault
BI-5 10CF25-Q0 Point on wave bypass or fault
BI-6 10CF25-Q0 Device OK
BI-7 10CF25-Q0 Sync data error
BI-8 10CF25-Q0 Control switch fault
BI-9 10CF25-Q0 Point on wave bypass or fault
BI-17 10R21+R3-F11 CPR04 fault
BI-18 10R21+R3-F12 CPR04 fault
BI-19 10R21+R3-F13 CPR04 fault
BI-20 10R21+R3-F21 CPR04 fault
BI-21 10R21+R3-F22 CPR04 fault
BI-22 10R21+R3-F23 CPR04 fault
BI-30 10R21+R3 power supply fault
BI-31 10R21+R1 Test mode
BI-32 10R21+R3-A1 Simadyn hardware fault
BI-33 10R21+R3-A1 Simadyn fan fault
BI-34 10R21+R3-A1 Software warning
BI-35 10R21+R3-A1 Software fault
BI-40 10CF20+X2 SU-3 Reset
SU200 Signal list 10CF30+X1
AC Station Control interface
Binary Outputs -A200
BO-1 10CF31-Q0 OFF command
BO-2 10CF31-Q0 ON command
BO-3 10CF31-Q1 OFF command
BO-4 10CF31-Q1 ON command
BO-21 10CF30+X1 SU-1 Major
BO-22 10CF30+X1 SU-1 Minor
BO-23 10CF30+X1 SU-1 Warning
Binary Outputs -A201
BO-1 10CF32-Q0 OFF command
BO-2 10CF32-Q0 ON command
BO-3 10CF32-Q1 OFF command
BO-4 10CF32-Q1 ON command
BO-21 10CF30+X1 SU-2 Major
BO-22 10CF30+X1 SU-2 Minor
BO-23 10CF30+X1 SU-2 Warning
Binary Outputs -A202
BO-1 10CF33-Q0 OFF command
BO-2 10CF33-Q0 ON command
BO-3 10CF33-Q1 OFF command
BO-4 10CF33-Q1 ON command
BO-21 10CF30+X1 SU-3 Major
BO-22 10CF30+X1 SU-3 Minor
BO-23 10CF30+X1 SU-3 Warning
Binary Outputs -A203
BO-1 10CF34-Q0 OFF command
BO-2 10CF34-Q0 ON command
BO-3 10CF34-Q1 OFF command
BO-4 10CF34-Q1 ON command
BO-21 10CF30+X1 SU-4 Major
BO-22 10CF30+X1 SU-4 Minor
BO-23 10CF30+X1 SU-4 Warning
Analog Inputs -A200
AI-1 10CF31-T3 Reactive power
Analog Inputs -A201
AI-1 10CF32-T3 Reactive power
Analog Inputs -A202
AI-1 10CF33-T3 Reactive power
Analog Inputs -A203
AI-1 10CF34-T1 Reactive power
Binary Inputs -A200
BI-1 10CF31-Q1 OFF
BI-2 10CF31-Q1 ON
BI-3 10CF31-Q1 Fault
BI-4 10CF31-Q51 OFF
BI-5 10CF31-Q51 ON
BI-6 10CF31-Q51 Fault
BI-7 10CF31-Q52 OFF
BI-8 10CF31-Q52 ON
BI-9 10CF31-Q52 Fault
BI-10 10CF31-Q17 OFF
BI-11 10CF31-Q17 ON
BI-12 10CF31-Q17 fault
BI-13 10CF31-T1 50 ACF trip
BI-14 10CF31-T1 51 ACF trip
BI-15 10CF31-T1 49_59 ACF trip
BI-16 10CF31-T41 51 ACFL trip
BI-17 10CF31-T42 51 ACFR trip
BI-18 10CF31-T41 50 ACFL trip
BI-19 10CF31-T42 50 ACFR trip
BI-20 10R31+R2A 87ACFB 31 trip
BI-21 10R31+R2A 50BF 31 trip
BI-22 10R31+R2A 86A_86B 31 trip
BI-23 10CF31 TC fault
BI-24 10CF20+X1 DC supply fault
BI-25 10CF30+S1 VT MCB fault
BI-26 10CF31-Q0 CB point on wave bypass or fault
BI-27 10CF30+S1 AC supply fault
BI-28 10CF30+S1 DC supply fault
BI-29 10CF30+S1 ES DS local control
BI-30 10CF31-Q0 OFF
BI-31 10CF31-Q0 ON
BI-33 10CF31-Q0 Spring unloaded
BI-34 10CF31-Q0 Control voltage fault
BI-35 10CF31-Q0 Motor fault
BI-36 10CF31-Q0 SF6 1st stage
BI-37 10CF31-Q0 SF6 2nd stage
BI-38 10CF31-Q0 Pole Discrepency
BI-39 10CF31-Q0 Local control
BI-40 10CF30+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10CF32-Q1 OFF
BI-2 10CF32-Q1 ON
BI-3 10CF32-Q1 Fault
BI-4 10CF32-Q51 OFF
BI-5 10CF32-Q51 ON
BI-6 10CF32-Q51 Fault
BI-7 10CF32-Q52 OFF
BI-8 10CF32-Q52 ON
BI-9 10CF32-Q52 Fault
BI-10 10CF32-T1 50 ACF trip
BI-11 10CF32-T1 51 ACF trip
BI-12 10CF32-T1 49_59 ACF trip
BI-13 10CF32-T41 51 ACFL trip
BI-14 10CF32-T42 51 ACFR trip
BI-15 10CF32-T41 50 ACFL trip
BI-16 10CF32-T42 50 ACFR trip
BI-17 10R31+R2A 87ACFB 32 trip
BI-18 10R31+R2A 50BF 32 trip
BI-19 10R31+R2A 86A_86B 32 trip
BI-20 10R31+R2C 10CF32 TC fault
BI-21 10R31+R2A 87BBM2 trip
BI-22 10R31+R2A 27_59 trip
BI-23 10R31+R2A 86A_86B_M2 trip
BI-24 10R31+R2A MCB fault
BI-26 10R31+R2 relay 31_32 fault
BI-27 10R31+R2 relay 33 fault
BI-28 10CF32-Q0 CB point on wave bypass or fault
BI-29 10CF30+S1 ES DS local control
BI-30 10CF32-Q0 OFF
BI-31 10CF32-Q0 ON
BI-33 10CF32-Q0 Spring unloaded
BI-34 10CF32-Q0 Control voltage fault
BI-35 10CF32-Q0 Motor fault
BI-36 10CF32-Q0 SF6 1st stage
BI-37 10CF32-Q0 SF6 2nd stage
BI-38 10CF32-Q0 Pole Discrepency
BI-39 10CF32-Q0 Local control
BI-40 10CF30+X1 SU-2 Reset
Binary Inputs -A202
BI-1 10CF33-Q1 OFF
BI-2 10CF33-Q1 ON
BI-3 10CF33-Q1 Fault
BI-4 10CF33-Q51 OFF
BI-5 10CF33-Q51 ON
BI-6 10CF33-Q51 Fault
BI-7 10CF33-Q52 OFF
BI-8 10CF33-Q52 ON
BI-9 10CF33-Q52 Fault
BI-10 10CF33-T1 50 ACF trip
BI-11 10CF33-T1 51 ACF trip
BI-12 10CF33-T1 49_59 ACF trip
BI-13 10CF33-T41 51 ACFL trip
BI-14 10CF33-T42 51 ACFR trip
BI-15 10CF33-T41 50 ACFL trip
BI-16 10CF33-T42 50 ACFR trip
BI-17 10R31+R1 power supply fault
BI-18 10R31+R1 test mode
BI-19 10R31+R1-A1 Hardware fault
BI-20 10R31+R1-A1 Simadyn fan fault
BI-21 10R31+R1-A1 Software warning
BI-22 10R31+R1-A1 Software fault
BI-23 10R31+R2B 87ACFB 33 trip
BI-24 10R31+R2B 50BF 33 trip
BI-25 10R31+R2B 86A_86B 33 trip
BI-26 10CF33 TC fault
BI-27 10R31+R2B MCB fault
BI-28 10CF33-Q0 CB point on wave bypass or fault
BI-29 10CF30+S2 ES DS Local control
BI-30 10CF33-Q0 OFF
BI-31 10CF33-Q0 ON
BI-33 10CF33-Q0 Spring unloaded
BI-34 10CF33-Q0 Control voltage fault
BI-35 10CF33-Q0 Motor fault
BI-36 10CF33-Q0 SF6 1st stage
BI-37 10CF33-Q0 SF6 2nd stage
BI-38 10CF33-Q0 Pole Discrepency
BI-39 10CF33-Q0 Local control
BI-40 10CF30+X1 SU-3 Reset
Binary Inputs -A203
BI-1 10CF34-Q1 OFF
BI-2 10CF34-Q1 ON
BI-3 10CF34-Q1 Fault
BI-4 10CF34-Q51 OFF
BI-5 10CF34-Q51 ON
BI-6 10CF34-Q51 Fault
BI-7 10CF34-Q52 OFF
BI-8 10CF34-Q52 ON
BI-9 10CF34-Q52 Fault
BI-10 10CF34+UT1 WTI
BI-11 10CF34+UT1 OTI
BI-12 10CF34+UT1 Pressure
BI-13 10R31+R1-F11 CPR97 fault
BI-14 10R31+R1-F12 CPR97 fault
BI-15 10R31+R1-F13 CPR97 fault
BI-16 10R31+R1-F21 CPR97 fault
BI-17 10R31+R1-F22 CPR97 fault
BI-18 10R31+R1-F23 CPR97 fault
BI-19 10R31+R1-F31 CPR97 fault
BI-20 10R31+R1-F32 CPR97 fault
BI-21 10R31+R1-F33 CPR97 fault
BI-22 10R04+R2 87L_64_34 trip
BI-23 10R04+R2 50BF 34 trip
BI-24 10R04+R2 50_51L 34 trip
BI-25 10R04+R2 86A_86B 34 trip
BI-26 10CF34 TC fault
BI-27 10R31+R2C MCB fault
BI-28 10CF34+UT1 Buchholz
BI-29 10CF30+S2 ES DS Local control
BI-30 10CF34-Q0 OFF
BI-31 10CF34-Q0 ON
BI-33 10CF34-Q0 Spring unloaded
BI-34 10CF34-Q0 Control voltage fault
BI-35 10CF34-Q0 Motor fault
BI-36 10CF34-Q0 SF6 1st stage
BI-37 10CF34-Q0 SF6 2nd stage
BI-38 10CF34-Q0 Pole Discrepency
BI-39 10CF34-Q0 Local control
BI-40 10CF30+X1 SU-4 Reset
SU200 Signal list 10XX00+X1
AC Station Service interface
Binary Outputs -A200
BO-21 10XX00+X1 SU-1 Major
BO-22 10XX00+X1 SU-1 Minor
BO-23 10XX00+X1 SU-1 Warning
Binary Outputs -A201
BO-21 10XX00+X1 SU-2 Major
BO-22 10XX00+X1 SU-2 Minor
BO-23 10XX00+X1 SU-2 Warning
Binary Outputs -A202
BO-21 10XX00+X1 SU-3 Major
BO-22 10XX00+X1 SU-3 Minor
BO-23 10XX00+X1 SU-3 Warning
Binary Outputs -A203
BO-21 10XX00+X1 SU-4 Major
BO-22 10XX00+X1 SU-4 Minor
BO-23 10XX00+X1 SU-4 Warning
Analog Inputs -A200
AI-1 10NE01 UL1 SecA Busbar voltage
AI-2 10NE01 UL1 SecB Busbar voltage
AI-3 10NE01 T1 Current
AI-4 10NE01 T2 Current
AI-5 10NE01 T3 Current
Analog Inputs -A201
AI-1 10NE01 T1 Power
AI-2 10NE01 T2 Power
AI-3 10NE01 T3 Power
AI-4 10NE01 T1 Reactive power
AI-5 10NE01 T2 Reactive power
AI-6 10NE01 T3 Reactive power
Analog Inputs -A202
AI-1 11NE01 UL1 voltage
AI-2 11NE02 UL1 voltage
AI-4 12NE01 UL1 voltage
AI-5 12NE02 UL1 voltage
AI-7 11NE01-T1 Current
AI-8 11NE02-T1 Current
Analog Inputs -A203
AI-1 12NE01-T1 Current
AI-2 12NE02-T1 Current
AI-3 11NE01-T2 Current
AI-4 11NE01-T2 Power
AI-5 11NE01-T2 Reactive power
AI-6 12NE01-T2 Current
AI-7 12NE01-T2 Power
AI-8 12NE01-T2 Reactive power
Binary Inputs -A200
BI-1 10NE01-Q01 OFF
BI-2 10NE01-Q01 ON
BI-3 10NE01-Q02 OFF
BI-4 10NE01-Q02 ON
BI-5 10NE01-Q03 OFF
BI-6 10NE01-Q03 ON
BI-7 10NE01-Q04 OFF
BI-8 10NE01-Q04 ON
BI-9 11NE01-Q01 OFF
BI-10 11NE01-Q01 ON
BI-11 11NE01-Q02 OFF
BI-12 11NE01-Q02 ON
BI-13 11NE02-Q01 OFF
BI-14 11NE02-Q01 ON
BI-15 12NE01-Q01 OFF
BI-16 12NE01-Q01 ON
BI-17 12NE01-Q02 OFF
BI-18 12NE01-Q02 ON
BI-19 12NE02-Q01 OFF
BI-20 12NE02-Q01 ON
BI-21 11NE03-Q03 OFF
BI-22 11NE03-Q03 ON
BI-23 11NE01-Q04 OFF
BI-24 11NE01-Q04 ON
BI-27 12NE03-Q03 OFF
BI-28 12NE03-Q03 ON
BI-33 10T11 OTI Alarm
BI-34 10T11 OTI Trip
BI-35 10T12 OTI Alarm
BI-36 10T12 OTI Trip
BI-37 10T12 OTI Alarm
BI-38 10T12 OTI Trip
BI-40 10XX00+X1 SU-1 Reset
Binary Inputs -A201
BI-1 10T11 Buchholz Trip
BI-2 10T11 Buchholz Warning
BI-3 10T11 Winding Trip
BI-4 10T11 Winding Warning
BI-5 10T12 Buchholz Trip
BI-6 10T12 Buchholz Warning
BI-7 10T12 Winding Trip
BI-8 10T12 Winding Warning
BI-9 10T13 Buchholz Trip
BI-10 10T13 Buchholz Warning
BI-11 10T13 Winding Trip
BI-12 10T13 Winding Warning
BI-13 10T11 Differential protection trip
BI-14 10T12 Differential protection trip
BI-15 10T13 Differential protection trip
BI-17 11NE00-G01 Running
BI-18 11NE00-G01 fault
BI-19 11NE00-G01 charger fault
BI-21 11NE00-G01 tank level alarm
BI-22 12NE00-G01 Running
BI-23 12NE00-G01 fault
BI-24 12NE00-G01 charger fault
BI-26 12NE00-G01 tank level alarm
BI-27 10T11 Overcurrent trip K50
BI-28 10T11 Earth fault trip K56
BI-29 10T11 Undervoltage trip K31
BI-30 10T11 External trip spare
BI-31 10T12 Overcurrent trip K50
BI-32 10T12 Earth fault trip K56
BI-33 10T12 Undervoltage trip K31
BI-34 10T12 External trip spare
BI-35 10T13 Overcurrent trip K50
BI-36 10T13 Earth fault trip K56
BI-37 10T13 Undervoltage trip K31
BI-38 10T13 External trip spare
BI-40 10XX00+X1 SU-2 Reset
Binary Inputs -A202
BI-1 10NK11+G11 Charger 1 fault
BI-4 10NK11+G12 Charger 2 fault
BI-7 10NK21+G11 Charger 3 fault
BI-9 10NU11+G11 Charger 1 fault
BI-11 10NU11+G12 Charger 2 fault
BI-13 12NU11+G11 Charger 1 fault
BI-15 12NU11+G12 Charger 2 fault
BI-17 12NU21+G11 Charger 3 fault
BI-25 10NQ11+G11 Charger 1 fault
BI-27 10NQ11+G12 Charger 2 fault
BI-29 10NQ21+G11 Charger 3 fault
BI-33 10NG11+G11 Charger 1 fault
BI-35 10NG21+G11 Charger 2 fault
BI-40 10XX00+X1 SU-3 Reset
Binary Inputs -A203
BI-1 11U61+NG1 Valve Cooling UPS1 Inverter fault
BI-2 11U61+NG2 Valve Cooling UPS2 Inverter fault
BI-3 12U61+NG1 Valve Cooling UPS1 Inverter fault
BI-4 12U61+NG2 Valve Cooling UPS2 Inverter fault
BI-9 10NE01 Power supply fault
BI-10 11NE01 Power supply fault
BI-11 11NE01 Undervoltage
BI-12 11NE02 Power supply fault
BI-13 11NE02 Undervoltage
BI-14 12NE01 Power supply fault
BI-15 12NE01 Undervoltage
BI-16 12NE02 Power supply fault
BI-17 12NE02 Undervoltage
BI-18 10T11-Q1 Line voltage available
BI-19 10T11-Q1 OFF
BI-20 10T11-Q1 ON
BI-21 10T11-Q1 Advance OFF Trip
BI-23 10T12-Q1 Line voltage available
BI-24 10T12-Q1 OFF
BI-25 10T12-Q1 ON
BI-26 10T12-Q1 Advance OFF Trip
BI-28 10T13-Q1 Line voltage available
BI-29 10T13-Q1 OFF
BI-30 10T13-Q1 ON
BI-31 10T13-Q1 Advance OFF Trip
BI-40 10XX00+X1 SU-4 Reset
SU200 Signal list 10XX00+X2
AC Station Owner interface(Installed in NTPC control room)
Binary Outputs -A200
BO-1 10C01A-Q9 Enable interlock
BO-2 10C01C-Q9 Enable interlock
BO-3 10C02A-Q9 Enable interlock
BO-4 10C02C-Q9 Enable interlock
BO-6 11V00+U1-A1 Pole 1 Deblocked
BO-7 11V00+U1-A1 Pole 1 Blocked
BO-8 11V00+U1-A1 DC line fault recovery sequence
BO-10 12V00+U1-A1 Pole 1 Deblocked
BO-11 12V00+U1-A1 Pole 1 Blocked
BO-12 12V00+U1-A1 DC line fault recovery sequence
BO-14 11V00-A1 Pole-1 power Bitcode 1
BO-15 11V00-A1 Pole-1 power Bitcode 2
BO-16 11V00-A1 Pole-1 power Bitcode 3
BO-17 11V00-A1 Pole-1 power Bitcode 4
BO-18 12V00-A1 Pole-2 power Bitcode 1
BO-19 12V00-A1 Pole-2 power Bitcode 2
BO-20 12V00-A1 Pole-2 power Bitcode 3
BO-21 12V00-A1 Pole-2 power Bitcode 4
BO-22 10XJ02 AC Yard SPLIT configuration pole-2
BO-23 10XJ02 AC Yard ISLANDED configuration pole-1+2
Binary Outputs -A201
BO-1 10C01A-Q52 Enable interlock
BO-2 10C01C-Q52 Enable interlock
BO-3 10C02A-Q52 Enable interlock
BO-4 10C02C-Q52 Enable interlock
Analog Inputs -A200
AI-1 10C02C-T1 Power (NTPC-HVDC Feeder 1)
AI-2 10C02C-T1 Reactive power
AI-3 10C02C-T1 Current
AI-4 10C02A-T1 Power (NTPC-HVDC Feeder 2)
AI-5 10C02A-T1 Reactive power
AI-6 10C02A-T1 Current
AI-7 10C01C-T1 Power (NTPC-HVDC Feeder 3)
AI-8 10C01C-T1 Reactive power
Analog Inputs -A201
AI-1 Generator 1 Active power
AI-2 Generator 1 Reactive power
AI-3 Generator 2 Active power
AI-4 Generator 2 Reactive power
AI-5 10C01C-T1 Current (NTPC-HVDC Feeder 3)
AI-6 10C01A-T1 Power (NTPC-HVDC Feeder 4)
AI-7 10C01A-T1 Reactive power
AI-8 10C01A-T1 Current
Analog Inputs -A202
AI-1 Generator 3 Active power
AI-2 Generator 3 Reactive power
AI-3 Generator 4 Active power
AI-4 Generator 4 Reactive power
AI-5 Generator 5 Active power
AI-6 Generator 5 Reactive power
AI-7 Generator 6 Active power
AI-8 Generator 6 Reactive power
Binary Inputs -A200
BI-1 10C02C-Q0 OFF
BI-2 10C02C-Q0 ON
BI-3 10C02C-Q1 OFF
BI-4 10C02C-Q1 ON
BI-5 10C02C-Q9 OFF
BI-6 10C02C-Q9 ON
BI-7 10C02A-Q0 OFF
BI-8 10C02A-Q0 ON
BI-9 10C02A-Q2 OFF
BI-10 10C02A-Q2 ON
BI-11 10C02A-Q9 OFF
BI-12 10C02A-Q9 ON
BI-13 10C01C-Q0 OFF
BI-14 10C01C-Q0 ON
BI-15 10C01C-Q1 OFF
BI-16 10C01C-Q1 ON
BI-17 10C01C-Q9 OFF
BI-18 10C01C-Q9 ON
BI-19 10C01A-Q0 OFF
BI-20 10C01A-Q0 ON
BI-21 10C01A-Q2 OFF
BI-22 10C01A-Q2 ON
BI-23 10C01A-Q9 OFF
BI-24 10C01A-Q9 ON
BI-25 10C02C-Q52 OFF
BI-26 10C02C-Q52 ON
BI-27 10C02A-Q52 OFF
BI-28 10C02A-Q52 ON
BI-29 10C01C-Q52 OFF
BI-30 10C01C-Q52 ON
BI-31 10C01A-Q52 OFF
BI-32 10C01A-Q52 ON
BI-33 10C23-Q01 OFF
BI-34 10C23-Q01 ON
BI-35 10C23-Q02 OFF
BI-36 10C23-Q02 ON
Binary Inputs -A201
BI-1 10C24A OFF
BI-5 10C24B OFF
BI-7 10C24C OFF
BI-9 10C24C-Q9 OFF
BI-10 10C24C-Q9 ON
BI-11 10C25A OFF
BI-12 10C25A ON
BI-13 10C25A-Q9 OFF
BI-14 10C25A-Q9 ON
BI-15 10C25B OFF
BI-16 10C25B ON
BI-17 10C25C OFF
BI-18 10C25C ON
BI-19 10C25C-Q9 OFF
BI-20 10C25C-Q9 ON
BI-21 10C26A OFF
BI-22 10C26A ON
BI-23 10C26A-Q9 OFF
BI-24 10C26A-Q9 ON
BI-27 10C26C OFF
BI-28 10C26C ON
BI-31 10C27A OFF
BI-32 10C27A ON
BI-33 10C27A-Q9 OFF
BI-34 10C27A-Q9 ON
BI-37 10C27C OFF
BI-38 10C27C ON
Binary Inputs -A202
BI-1 10C28A OFF
BI-3 10C28A-Q9 OFF
BI-4 10C28A-Q9 ON
BI-5 10C28B OFF
BI-7 10C28C OFF
BI-9 10C28C-Q9 OFF
BI-10 10C28C-Q9 ON
BI-11 10C29-Q01 OFF
BI-12 10C29-Q01 ON
BI-13 10C29-Q02 OFF
BI-14 10C29-Q02 ON
BI-39 10XX00+X3 DC supply fault
SU200 Signal list 10XX00+X3
AC Station Owner interface(Installed in NTPC control room)
Binary Outputs -A201
BO-1 10T11-Q0 Enable interlock
BO-2 10T12-Q0 Enable interlock
BO-3 10T13-Q0 Enable interlock
Analog Inputs -A200
AI-1 10C24C-T1 Active power (Meramundali 2 Line)
AI-2 10C24C-T1 Reactive power
AI-3 10C13A-T1 Active power (Meramundali 1 Line)
AI-4 10C13A-T1 Reactive power
AI-5 10C13C-T1 Active power (Rengali 2 Line)
AI-6 10C13C-T1 Reactive power
AI-7 10C12A-T1 Active power (Rengali 1 Line)
AI-8 10C12A-T1 Reactive power
Analog Inputs -A201
AI-1 10C12C-T1 Active power (Rourkela 2 Line)
AI-2 10C12C-T1 Reactive power
AI-3 10C11A-T1 Active power (Rourkela 1 Line)
AI-4 10C11A-T1 Reactive power
Binary Inputs -A200
BI-1 10C11A OFF
BI-3 10C11A-Q9 OFF
BI-4 10C11A-Q9 ON
BI-5 10C11B OFF
BI-7 10C11C OFF
BI-9 10C11C-Q9 OFF
BI-10 10C11C-Q9 ON
BI-11 10C12A OFF
BI-12 10C12A ON
BI-13 10C12A-Q9 OFF
BI-14 10C12A-Q9 ON
BI-15 10C12B OFF
BI-16 10C12B ON
BI-17 10C12C OFF
BI-18 10C12C ON
BI-19 10C12C-Q9 OFF
BI-20 10C12C-Q9 ON
BI-21 10C13A OFF
BI-22 10C13A ON
BI-23 10C13A-Q9 OFF
BI-24 10C13A-Q9 ON
BI-25 10C13B OFF
BI-26 10C13B ON
BI-27 10C13C OFF
BI-28 10C13C ON
BI-29 10C13C-Q9 OFF
BI-30 10C13C-Q9 ON
BI-31 10C14A OFF
BI-32 10C14A ON
BI-35 10C14B OFF
BI-36 10C14B ON
BI-37 10C14C OFF
BI-38 10C14C ON
BI-39 10C14C-Q9 OFF
BI-40 10C14C-Q9 ON
Binary Inputs -A201
BI-1 10C15A OFF
BI-7 10C15C OFF
BI-9 10C15C-Q9 OFF
BI-10 10C15C-Q9 ON
BI-11 10C16A OFF
BI-12 10C16A ON
BI-13 10C16A-Q9 OFF
BI-14 10C16A-Q9 ON
BI-17 10C16C OFF
BI-18 10C16C ON
BI-19 10T11-Q0 OFF
BI-20 10T12-Q0 OFF
BI-21 10T13-Q0 OFF
BI-25 10C00+R3 Busbar fault
BI-26 10C00+R3 Busbar MCB fault
BI-35 10XX00+X3 Binary transducer fault
BI-36 10XX00+X3 OLM1 fault
BI-37 10XX00+X3 OLM2 fault
BI-38 10XX00+X3 Time sync fault
BI-39 10XX00+X2 DC supply fault
ATTACHMENTS General guidelines for filling up the Attachments Refurbishment of Talcher-Kolar HVDC REV04
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649
1 Fill up only green shaded cells in the relevent attachments.
2 Attachments 3(QR), 4, 4(A), 5, 5(A), 6, 9, 10, 11, 12, 13, 14, 15, 16, 17, 18, 19 & 21 and Bid Form for 1st Envelope are included here.
3 Attachment 1 Bid Security : Not Applicable
4 Attachment 2 Power of Attorney : No specific format is provided by POWERGRID. Bidder may use their own format.
5 Attachment 8 Manufacturer’s Authorisation Form : To be furnished as per proforma provided in the bidding document, on the letter head of the each Manufactures proposed to supply main items. This attachment is not included here.
6 Attachment 10 Guarantee Declaration: We hereby declare that Attachment-10 (Guarantee Declaration) is provided in our Second Envelope Bid.
6 Attachment 14 Integrity Pact : To be submitted as per ITB Clause No. 9.3(o) and as per remarks in the Attach 14-IP.
7 Attachment 20, 22, 24, 25, 26, 27, 28, 29, 30 & 31: To be submitted as per the provisions of the Bidding Documents (Formats Attached seperately in Volume-III if Bidding Documents.
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 Individual Firm (as per sl. no. 3.1(i) of Annexure-A (BDS))
Individual Firm (as per sl. no. 3.1(ii) of Annexure-A (BDS))
Enter the details of the bidder below: Individual Firm (as per sl. no. 3.2 of Annexure-A (BDS))
Joint Venture Bid (as per sl. no. 5 of Annexure-A (BDS))
Specify type of Bidder [Select from drop down menu] Joint Venture Bid (as per sl. no. 5 of Annexure-A (BDS))
{as per sl. no. 1.1 OR 1.2 OR 1.3 OR 1.4 (as applicable) of Annexure-A (BDS) of Vol-I (Conditions of Contract)} 1
No. of other Partners 1
Whether the bidder is an MSE (Micro & Small Enterprise)
Enter the Name of Registration Authority
Name of the Bidder 1
Address of Registered Office 2 or more
Address of Registered Office
Pick date from here (mm/dd/yyyy):
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-3 (JV) #REF! #REF!
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Joint Venture Agreement and Power of Attorney for Joint Venture*)
Bidder’s Name and Address : To:
0 Contract Services 1 #REF!
Name : 0 Power Grid Corporation of India Ltd., 1
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
The Joint Venture Agreement (as per the proforma attached at no. 15 in Section-VI, Sample Forms and Procedures, Conditions of Contract, Vol.-I of the Bidding Documents) and Power of Attorney for Joint Venture (as per the proforma attached at no. 14 in Section-VI, Sample Forms and Procedures, Conditions of Contract, Vol.-I of the Bidding Documents) are enclosed herewith.
* applicable for Joint Venture
Date : 00-Jan-00 Printed Name : 0 #REF!
Place : 0 Designation : 0 #REF!
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-3 (QR)
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Qualifying Requirement Data)
Bidder’s Name and Address : To:
0 Contract Services
Name: 0 Power Grid Corporation of India Ltd.,
Address: 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
For our Qualification Requirement data, please refer Attachment-QR annexed herewith
In support of the Qualification Requirements (QR) for bidders, stipulated in Annexure-A (BDS) of the Section - III (BDS), Volume-I & Additional Information required as per ITB clause 9.3(c) of the Bidding Documents, we furnish herewith our QR data/details along with other information, as follows herewith our stipulations have been reproduced in italics for ready reference, however, in case of any discrepancy the QR as given in BDS shall prevail).
We have submitted bid as individual firm.
We have submitted bid as joint venture of following firms :
[For details regarding Qualification Requirements of a Joint Venture, please refer para 4.0 below.]
We are furnishing the following details/document in support of Qualifying requirement for the subject package.
A Attached copies of original documents defining :
a) The constitution or legal status;
b) The principal place of business;
c) The place of incorporation (for bidders who are corporations); or the place of registration and the nationality of the Owners (for applicants who are partnerships or individually-owned firms).
B Attached original & copies of the following documents :
a) Written power of attorney of the signatory of the Bid to commit the bidder.
b) Joint Venture Agreement.
C Whether bidder anticipate any change in legal structure/ ownership of their organisation at present. If Yes, please enclose details of same and copy of procedural document(s) with reference to the same/ as required statutorily, as of now
1.0 GENERAL INFORMATION
Bidder is required to provide general information as per the following format.
[Where the Bidder proposes to use named subcontractor(s) for critical components of the works or for work contents in excess of ten (10) percent of the bid price, the following information should also be supplied for the subcontractor(s)].
S No. Particulars Sole Bidder
1 Name of the Firm 0 0 0
2 Head Office/ Registered Office Address 0 0 0
5 Contact Person
6 Place of Incorporation/ Registration
7 Year of Incorporation/ Registration
8 Nationality of
2.0 TECHNICAL REQUIREMENTS {Reference para 1.0 of Annexure-A (BDS)}
TECHNICAL EXPERIENCE
2.1 The Bidder must have designed, manufactured, type tested (as per IEC or equivalent standard), supplied and supervised erection & commissioning of at least two (2) nos. Gas Insulated Switchgear (GIS) circuit breaker bays@ of 345kVor above voltage class in one (1) Substation or Switchyard during the last seven (7) years and these bays must be in satisfactory operation# for at least two (2) years as on the originally scheduled date of bid opening i.e. 15/02/2022
2.2 The Bidder, who has established manufacturing & testing facility in India for 345kV or above voltage level GIS but not meeting the requirement stipulated in para 1.1 above, shall also be considered provided that- a) The Bidder must have manufactured, at least one (1) no. 345kV or above voltage class GIS circuit breaker bays@ based on technological support of the collaborator(s), provided that the collaborator(s) meets the requirement stipulated in para 1.1 above. Further bidder must have either supplied or type tested above CB bay (as per IEC or equivalent standard) as on the originally scheduled date of bid opening mentioned above. b) Further, the bidder shall also submit the following along with the bid: i. A legally enforceable undertaking (jointly with the Collaborator(s) to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s). ii. A confirmation letter from the Collaborator(s) stating that the Collaborator(s) shall furnish performance guarantee for an amount of 3 % of the ex-works cost of such equipment(s). This performance guarantee shall be in addition to Contract Performance Guarantee to be submitted by the bidder. iii. A valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 345kV or above voltage level GIS equipment in India.
2.3 The Bidder, who has established manufacturing & testing facility in India for 345kV or above voltage level GIS as Subsidiary/JVC/Group company by its parent/principal but not meeting the requirement stipulated in para 2.1 above, shall also be considered provided that- a) The Bidder must have manufactured, at least one (1) no. 345kV or above voltage class GIS circuit breaker bays@ based on technological support of the parent/principal, provided that the parent/principal meets the requirement stipulated in para 2.1 above. Further bidder must have either supplied or type tested above CB bay (as per IEC or equivalent standard) as on the originally scheduled date of bid opening mentioned above. b) Further, the bidder shall also submit the following along with the bid: i. A legally enforceable undertaking (jointly with the parent/principal company) to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s). ii. A confirmation letter from the parent/principal company stating that the parent/principal company shall furnish performance guarantee for an amount of 3 % of the ex-works cost of such equipment(s). This performance guarantee shall be in addition to Contract Performance Guarantee to be submitted by the bidder. iii. A valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 345kV or above voltage level GIS equipment in India.
2.4 In case, the bidder is not a GIS manufacturer, he shall also be considered provided: i. The bidder must have erected and commissioned at least two (02) nos. GIS circuit breaker bays of 345kV or above voltage class in one (01) new GIS substation or switchyard during last seven (07) years and these bays must be in satisfactory operation# for at least two (02) years as on the originally scheduled date of bid opening mentioned above. ii. The GIS must be offered from Indian manufacturer, who meets the requirement mentioned at Route-1 or Route-2 or Route-3 above. iii. A legally enforceable undertaking (jointly with the GIS Manufacturer) (as per enclosed format in Section-VI, Volume-I of bidding document) to guarantee quality, timely supply, performance and warranty obligations as specified for the equipment(s) is submitted along with the bid stating that GIS Manufacturer shall furnish performance guarantee for an amount of two (2) % of the total contract price. This performance guarantee shall be in addition to the Contract Performance security to be submitted by the Bidder.
Note :- 1. (#)Satisfactory operation means certificate issued by the Employer certifying the operation without any adverse remark. 2. (@) For the purpose of qualifying requirement, one no. of circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs / Bushing CTs. 3. In case bidder is a holding company, the technical experience referred to in Route-1, 2, 3 & 4 above as the case may be shall be of that holding company only (i.e. excluding its subsidiary/group companies). In case bidder is a subsidiary of a holding company, the technical experience referred to in Route-1, 2, 3 & 4 above as the case may be shall be of that subsidiary company only (i.e. excluding its holding company). 4. In case bidder is qualifying through Route-1, type test reports of Collaborator/ Parent Company/Subsidiary Company/ Group Company shall also be acceptable, for which a confirmation shall be furnished along with the bid as per format attached in the bidding documents.
2.5 Using the following format, each Bidder (individual firms or partners of a joint venture) is requested to list the experience as detailed above, on the basis of which the Bidder wishes to qualify. The information is to be summarised using following format for each experience of the Bidder or of each Partner of a Joint Venture.
(The bidder shall attach documentary evidence, such as copies of utility certificates for completed contracts and copies of award letters etc. for ongoing contracts in support of his experience as listed in the following proforma for each Contract with the help of "Attach" Buttons provided in table given below).
Format for the Bidder/Collaborator/ Parent/Principal/Partner of JV in case of Joint Venture/Indian GIS Mnaufacturer in support of meeting the requirement of para 1.1, Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of Bidder/Collaborator/ Parent/Principal/Partner of a JV/Indian GIS Manufacturer #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the firm/Partner of a JV
4(a)(i) Voltage Level of GIS Substation commissioned under the Contract (Indicate 345kV or above class only)
No. of GIS Circuit Breaker equipped bays under the above contract
(Indicate nos. of GIS Circuit Breaker equipped bays of 345kV or above voltage level where one no. of circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs / Bushing CTs.)
Name of the substation or switchyard
Date of Commissioning
(a)(ii) No. of years, the above Substation have been in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract
(Tick whichever is/are applicable)
NOTE: type test reports of Collaborator/ Parent Company/ Subsidiary Company/ Group Company shall also be acceptable, for which a confirmation shall be furnished along with the bid as per format attached in the bidding documents (Attachment-29 in Volume-III)
of Gas Insulated Switchgear (GIS) circuit breaker bays. of Gas Insulated Switchgear (GIS) circuit breaker bays.
In case of foreign entity, whether bidder have established/ commence the establishment of facility as Indian Subsidiary/ Group Company/ Joint Venture Company for manufacturing & testing of 765kV or above voltage level GIS in India (as per Companies Act 1956 or 2013 of India)
Whether bidder want to propose its above subsidiary/ Group Company/ Joint Venture Company as its associate for executing On-Shore Supply Contract
Foreign Bidder can offer to supply more than one 765kV GIS circuit breaker bay* from India provided his Subsidiary or Group Company or a Joint Venture Company (JVC) must have manufactured at least one (1) number 765kV or above voltage level GIS Circuit Breaker bay* and this bay either should have been supplied or should have been type tested ( as per IEC or equivalent standard) as on the originally scheduled date of bid opening as mentioned above
Whether Undertaking (as per enclosed format in Section-VI, Sample Forms and Procedures of bidding document) for above is enclosed with the bid
Details of documents uploaded in support of the above stated experience
Format for the Indian Associate executing the On-Shore Supply and On-Shore Services Contract for a Foreign Entity submitting its bid as an Individual Firm or in a Joint Venture without any Indian Entity as a Partner, in support of meeting the requirement of para 1.1.1(i) of Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Indian Associate executing the On-Shore Supply and On-Shore Services Contract
1 Name of Contract Undertaken
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the Bidder
4 No. of GIS/AIS Circuit Breaker equipped bays under the contract
(Indicate nos. of Circuit Breaker equipped bays of 345 kV or above voltage level where one no. of circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs / Bushing CTs)
Name of the substation or switchyard
No. of years, the above CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract
(Tick whichever is/are applicable)
Details of documents uploaded in support of the above stated experience
Format-B (Route-2):
Format in support of meeting the requirement of para 1.2 Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
1 Name of the Collaborator
2 Whether bidder have established manufacturing and testing facilities in India for 345kV or above voltage level Gas Insulated Switchgear (GIS)
3 Whether 345kV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bay manufactured by bidder based on technological support of the collaborator have been supplied or Type tested
A if Type tested details of Type test Report
B Details of GIS supplied by them
i Name of Contract Undertaken for manufacturing 345kV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bays
ii Contract Reference No. & Date of Award
iii Name and Address of the Employer/Utility for whom the Contract was executed by the firm/Partner of a JV
iv No. of 345kV Gas Insulated Switchgear (GIS) Circuit Breaker bays manufactured under the contract (Indicate nos. of Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345kV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs. GIS means SF6 Gas insulated Switchgear.)
Name of the substation or switchyard
Whether 345kV or above voltage level Gas Insulated Switchgear (GIS) Circuit breaker bays, as mentioned above, has been manufactured based on technological support of the Collaborator under the Contract.
Date of Type Testing
Scope of work involved under the Contract
Details of documents uploaded in support of the above stated experience
Format in support of meeting the requirement of para 1.2 (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Collaborator (refer para 1.2), if applicable : #REF!
Name of the 345kV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufacturer (refer para 1.2), if applicable : #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
4(a)(i) No. of Circuit Breaker bays under the contract
(Indicate nos. of Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Circuit Breaker bays of 345kV or above)
Name of the substation or switchyard
(a)(ii) No. of years, the above Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract as per IEC
(Tick whichever is/are applicable)
Whether Collaborator(s) meets the technical experience criteria stipulated at 2.1 above, and the details of which is mentioned at Format-A above. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Whether legally enforceable undertaking jointly by Bidder/Manufacturer and the Collaborator(s) (as per enclosed format in Section-VI: Sample Forms and Procedures of bidding document) is furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Confirmation letter from the Collaborator(s) along with the bid stating that Collaborator(s) shall furnish performance guarantee, in addition to contract performance guarantee to be submitted by the bidder, for an amount of 3% of the cost of equipment(s) to be manufactured and supplied from the works in India. (Applicable for the Bidder/Manufacturer wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Whether valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 345kV or above voltage level GIS equipment in India furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-2 of Annexure-A(BDS))
Details of documents uploaded in support of the above stated experience
Format-C: (Route-3)
Format in support of meeting the requirement of para 1.3 Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
1 Name of the Bidder established as Subsidiary/JVC/Group company by its parent/principal Company
2 Name of the parent/principal Company
3 Whether bidder have established manufacturing and testing facilities in India for 345kV or above voltage level Gas Insulated Switchgear (GIS)
4 Whether 345kV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bay manufactured by bidder have been supplied or Type tested based on Technological support of their Parent/ Principal Company
A if Type tested details of Type test Report
B Details of Gas Insulated Switchgear (GIS) Circuit Breaker Bays supplied by them
i Name of Contract Undertaken for manufacturing 345kV or above voltage level Gas Insulated Switchgear (GIS) Circuit Breaker bays
ii Contract Reference No. & Date of Award
iii Name and Address of the Employer/Utility for whom the Contract was executed by the firm/Partner of a JV
iv No. of 345kV Gas Insulated Switchgear (GIS) Circuit Breaker bays manufactured under the contract (Indicate nos. of Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345kV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs. GIS means SF6 Gas insulated Switchgear.)
Name of the substation or switchyard
Whether 345kV or above voltage level Gas Insulated Switchgear (GIS) Circuit breaker bays, as mentioned above, has been manufactured based on technological support of the Parent/Principal Company under the Contract.
Date of Type Testing
Scope of work involved under the Contract
Details of documents uploaded in support of the above stated experience
Format in support of meeting the requirement of para 1.2 (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Collaborator (refer para 1.2), if applicable : #REF!
Name of the 345kV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufacturer (refer para 1.2), if applicable : #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
4(a)(i) No. of Circuit Breaker bays under the contract
(Indicate nos. of Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Circuit Breaker bays of 345kV or above)
Name of the substation or switchyard
(a)(ii) No. of years, the above Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract as per IEC
(Tick whichever is/are applicable)
Whether Parent/Principal Company meets the technical experience criteria stipulated at 2.1 above, and the details of which is mentioned at Format-A above. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Whether legally enforceable undertaking jointly by Bidder/Manufacturer and the Parent/Principal Company (as per enclosed format in Section-VI: Sample Forms and Procedures of bidding document) is furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Confirmation letter from the parent/principal company along with the bid stating that parent/principal company shall furnish performance guarantee, in addition to contract performance guarantee to be submitted by the bidder, for an amount of 3% of the cost of equipment(s) to be manufactured and supplied from the works in India. (Applicable for the Bidder/Manufacturer wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Whether valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 345kV or above voltage level GIS equipment in India furnished along with the bid. (Applicable for the Bidder/Manufacturer(s) wish/proposes to qualify through Route-3 of Annexure-A(BDS))
Name of the substation or switchyard
Whether 345kV or above voltage level Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Circuit breaker bays, as mentioned above, has been manufactured based on technological support of the Parent/ Principal Company under the Contract.
If Yes, indicate the Name of Parent/ Principal Company(s)
No. of years, the above AIS/GIS Subatation(s) are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract for the above 345kV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS bay as per IEC as on the originally scheduled date of bid opening
(Tick whichever is/are applicable)
Details of documents uploaded in support of the above stated experience
Format in support of meeting the requirement of para 1.3 (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Parent Company/ Principal (refer para 1.3), if applicable: #REF!
Name of the 345kV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufacturer (refer para 1.3), if applicable : 0 #REF!
1 Name of Contract Undertaken #REF!
2 Contract Reference No. & Date of Award
4(a)(i) No. of Circuit Breaker bays under the contract
(Indicate nos. of Circuit Breaker bays of 345kV or above)
Name of the substation or switchyard
(a)(ii) No. of years, the above Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS CB bays are in operation as on the originally scheduled date of bid opening.
Scope of work involved under the Contract as per IEC
(Tick whichever is/are applicable)
Whether Joint Deed of Undertaking executed between The Bidder and 345kV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS Equipment Manufaturer has been enclosed with bid ? (in line with para 1.3 (b)(i) of Annexure-A (BDS)
Whether confirmation letter from the parent/principal company stating that the parent/principal company shall furnish performance guarantee for an amount of 10% of the ex-works cost of such equipment(s) has been enclosed with bid? (in line with para 1.3(b)(ii) of Annexure-A (BDS)
Whether valid collaboration agreement for technology transfer / license to design, manufacture, test and supply 345kV Gas Insulated Switchgear (GIS)/ Hybrid GIS /MTS equipment in India has been enclosed with bid ? (in line with para 1.3(b)(iii) of Annexure-A (BDS)
Details of documents uploaded in support of the above stated experience
Format-D: (Route-4)
Format in support of meeting the requirement of para 1.4(Route-4) (as applicable) Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Bidder’s Name :
1 Name of Contract Undertaken
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the firm
4(a)(i) Voltage Level of new GIS Substation or switchyard commissioned under the Contract (Indicate 345kV or above class only)
No. of GIS Circuit Breaker equipped bays under the above contract (Indicate nos. of Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345kV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs. GIS means SF6 Gas insulated Switchgear.)
Name of the New substation or switchyard
Scope of work involved under the Contract (Tick whichever is/are applicable)
No. of years, the above GIS Circuit Breaker equipped bays have been in operation as on the originally scheduled date of bid opening.
Details of documents uploaded in support of the above stated experience
Name of the Proposed Indian GIS Manufacturer (as per the Route-4 of Annexure-A(BDS)
Whether above Indian GIS Manufacturer meets the requirement mentioned at Route-1 or Route-2 or Route-3 above. (If Yes, Please mentioned the details in the Format-A/Format-B/Format-C above)
Whether Undertaking (Jointly with the GIS Manufacturer) (as per enclosed format in Section-VI, Vol-I of bidding document) for above is enclosed with the bid
Details of documents uploaded in support of the above stated experience
3.0 FINANCIAL REQUIREMENTS :
Financial Position {Reference para 2.0 of Annexure-A (BDS)} For the purpose of this particular bid, bidders shall meet the following minimum criteria:
a) Net Worth for last 3 financial years should be positive.
b) Minimum Average Annual Turnover^(MAAT) of the bidder for best three years i.e. 36 months out of last five financial years of the bidder should be Rs. 1563.43 million or equivalent for SS 90 Package
^Note- “Annual gross revenue from operations/gross operating income as incorporated in the profit & loss account excluding other operative income / other income”.
For Bidders to qualify for more than one package, their financial position shall not be less than the sum of the requirement for the packages they propose to qualify for ( strike through if only one package)
c) Bidder shall have Liquid Assets (LA) and/or evidence of access to or availability of credit facilities of not less than Rs. 260.57 million or equivalent for SS-90 Package
Note: (i) In case bidder is a holding company, the Financial Position criteria referred to in para 3.0 above shall be that of holding company only (i.e. excluding its subsidiary / group companies). In case bidder is a subsidiary of a holding company, the Financial Position criteria referred to in para 3.0 above shall be that of subsidiary company only (i.e. excluding its holding company). (ii) In case bidder has established manufacturing facility in India and yet to complete three (3) financial years, the Net Worth and average of the turnover as per financial statement for completed financial years shall be considered for the purpose of compliance to the specified Net Worth and MAAT requirements. (iii) In case of bidder qualifying through Route-3 but not meeting the Financial Position requirement as per note (i) read along with note (ii) above, the following shall be applicable: In case bidder is yet to complete five (5) years from the date of commercial production of such equipment(s) as on the originally scheduled date of bid opening as above, the financial position requirement as per para 3.0 (b) & (c) of parent/principal company providing collaboration for technological support shall be considered. However, once he completes five (5) years from the date of commercial production of such equipment (s) in India as on the originally scheduled date of bid opening as above, the financial position requirements as specified at 3.0 (b) and (c) above shall also be required to be met by such bidder on their own as per note (i) above and not based on their parent/principal company. Further, in case the bidder is yet to complete one (1) financial year, the Net worth requirement as per para 3.0 (a) above of parent/principal shall be considered (iv) Relaxation for Start-Ups^/ MSEs Start-Ups^/ MSEs, meeting the specified requirements at Para 3.0 (a) above in Financial Position shall also be considered qualified if they meet Eighty (80) % of the requirement specified at Para 3.0 (b) & 3.0 (c) above in Financial Position.
^ Start-Ups as defined by DIPP, applicable as on the originally scheduled date of bid opening.
{In support of its ‘Financial Position’, in line with the above, the Bidder (in case of bidding by single firm ) or each of the Partners of a Joint Venture (in case of bidding by a Joint Venture) or Company/Constituents must provide the relevant information in support of the same, along with documentary evidence, in the following format}
2.1 Financial Qualification Data: 0
Details of documentary evidence submitted in support of Qualification Data
Networth (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2020-21 No
B Turnover details:
Details of documentary evidence submitted in support of Qualification Data
Turnover (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
Average Annual Turnover for best Three Years is
C Liquid Assets
LA (in Rs. Million)
Details of evidence of having Liquid assets (LA)
Details of evidence of access to or availability of credit facilities
Details of documentary evidence submitted in support of Qualification Data
Networth (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
B Turnover details:
Details of documentary evidence submitted in support of Qualification Data
Turnover (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
Average Annual Turnover for best Three Years is
C Liquid Assets
LA (in Rs. Million)
Details of evidence of having Liquid assets (LA)
Details of evidence of access to or availability of credit facilities
Details of documentary evidence submitted in support of Qualification Data
Networth (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
B Turnover details:
Details of documentary evidence submitted in support of Qualification Data
Turnover (in Rs. Millions)
Sl No Financial year
Do you have audited results for FY 2016-17 Yes
Do you have audited results for FY 2020-21
Average Annual Turnover for best Three Years is
C Liquid Assets
LA (in Rs. Million)
Details of evidence of having Liquid assets (LA)
Details of evidence of access to or availability of credit facilities
3.0 Joint Venture (JV) Firms {Reference para 3.0 of Annexure-A (BDS)}
JOINT VENTURE BIDS: a) In case a bid is submitted by a Joint Venture (JV) of two or more firms as partners, all the partners of Joint Venture shall meet collectively the complete requirements stipulated at para 2.0 and 3.0 (b) & (c) above. Further, the partner(s) of JV must also meet the following minimum criteria: i. All the partners of the JV shall meet individually the Financial Position criteria given at 3.0 (a) above. ii. The Lead Partner shall meet, not less than 40% of the minimum Financial Position criteria given at para 3.0 (b) & (c) iii. Each of the other partner(s) individually shall meet not less than 25% of the minimum Financial Position criteria given at para 3.0 (b) & (c) above The figure of average annual turnover and liquid assets/credit facilities for each of the partners of the JV shall be added together to determine the JV’s compliance with the minimum qualifying criteria set out in Para 3.0 (b) & (c) above. b) However, for a JV to be qualified, the partners of JV must also meet the following minimum criteria: i. One of the partner(s) of JV must meet the Technical Experience criteria and the requirements stipulated under Route-1 or Route-2 or Route-3 as per para 2.0 above ii. The remaining partner(s) of JV must have erected, tested and commissioned at least two (2) nos. GIS/AIS Circuit Breaker equipped bays@ of 345KV or above voltage level in one (1) substation or switchyard during the last seven (7) years in India and these bays@ must be in satisfactory operation# as on the originally scheduled date of bid opening mentioned above. Note :- (#) Satisfactory operation means certificate issued by the Employer certifying the operation without any adverse remark.
4 The bidder shall furnish documentary evidence in support of the qualifying requirement stipulated as above.
4.1 In accordance with the above, in case of JV bidders, it should be ensured that necessary details including those pertaining to each JV partner are furnished and the documents are submitted alongwith the bid. Further, the JV bidders should also ensure that other requirements are complied with. The lists of documents furnished are to be indicated below :
Format in support of meeting the requirement of para 3.0(b)(ii) of Annexure-A to BDS, Section-III, Volume-I of the Bidding Documents)
Name of the Partner of JV
1 Name of Contract Undertaken
2 Contract Reference No. & Date of Award
3 Name and Address of the Employer/Utility for whom the Contract was executed by the firm
4(a)(i) Voltage Level of AIS/GIS Substation commissioned under the Contract (Indicate 345kV or above class only)
No. of AIS/GIS Circuit Breaker equipped bays under the above contract (Indicate nos. of AIS/Gas Insulated Switchgear (GIS) Circuit Breaker equipped bays of 345kV or above voltage level, where circuit breaker bay shall be considered as a bay used for controlling a line or a transformer or a reactor or a bus section or a bus coupler and comprising of at least one circuit breaker, one disconnector and three nos. of single phase CTs/Bushing CTs.)
Name of the substation or switchyard
Scope of work involved under the Contract (Tick whichever is/are applicable)
No. of years, the above AIS/GIS Circuit Breaker equipped bays have been in operation as on the originally scheduled date of bid opening.
Details of documents uploaded in support of the above stated experience
5.0 The Bidder shall also furnish following documents/details with its bid. {Reference ITB clause 9.3 (c)}
5.1 The complete annual reports together with Audited statement of accounts of the company for last five years of its own (separate) immediately preceding the date of submission of bid.
Note I. In the event the bidder is not able to furnish the information of its own (i.e separate), being a subsidiary company and its accounts are being consolidated with its group/holding/parent company, the bidder should submit the audited balance sheets, income statements, other information pertaining to it only (not of its group/Holding/Parent Company) duly certified by any one of the authority [ (i) Statutory Auditor of the bidder /(ii) Company Secretary of the bidder or (iii) A certified Public Accountant] certifying that such information/documents are based on the audited accounts as the case may be.
II. Similarly, if the bidder happens to be a Group/Holding/Parent Company, the bidder should submit the above documents/information of its own (i.e. exclusive of its subsidiaries) duly certified by any one of the authority mentioned in Note-I above certifying that these information/documents are based on the audited accounts, as the case may be.
5.2 The Bidder should accordingly also provide the following information/documents (In case of JV bidders, information should be provided separately for all the Partners of JV in the given format):
Audited balance sheet and income statements for the last five years as per the following:
Years preceding to the bid opening Audited Balance Sheet and Income Statements enclosed Audited Balance Sheet and Income Statements enclosed
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-4
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Form of Certificate of Origin and Eligibility)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby certify that equipment and materials to be supplied are produced in [Enter the name of country where from equipments & material shall be supplied] eligible source country. Equipments & Materials produced in [Name of countries] Company incorporated & registered in [Name of countries]
We hereby certify that our company is incorporated and registered in [Enter the name of country where from equipments & material shall be supplied] eligible source country.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
country. country. [Enter the name of country where from equipments & material shall be supplied] [Enter the name of country where from equipments & material shall be supplied]
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-4 (A)
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(List of Special Maintenance Tools & Tackles)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We are furnishing below the list of special maintenance tools & tackles for various equipment under the subject package. The prices for these tools & tackles are included in our lumpsum bid price. We further confirm that the list of special maintenance tools & tackles includes all the items specifically identified in your bidding documents as brought out below:
S.No. For Equipment Item Description Unit Quantity
Notwithstanding what is stated above, we further confirm that any additional special maintenance tools and tackles, required for the equipment under this package shall be furnished by us at no extra cost to the employer.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-4 (A)
(List of Special Maintenance Tools & Tackles)
S.No. For Equipment Item Description Unit Quantity
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-5
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Bought-out & Sub-contracted Items)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby furnish the details of the all major items of supply or services i.e. items, whose price is more than 10% of the Bid Price, we propose to buy for the purpose of furnishing and installation of the subject Refurbishment of Talcher-Kolar HVDC :
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Details of the proposed sub-contractor/sub-vendor
Name Nationality
We hereby furnish the details of the items/ sub-assemblies propose to supply from our own works (i.e. as direct transactions) in additiona to the supplies the same from other vendors (i.e. as Bought-out transactions) as detailed in the table given above.
Sl. No. Item Description Quantity proposed to be supplied Details of the plant from where supplies are proposed.
Name of Plant Address
2. We hereby declare that, we would not subcontract the erection portion of the contract without the prior approval of Employer.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-5
(Bought-out & Sub-contracted Items)
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Details of the proposed sub-contractor/sub-vendor
Name Nationality
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-5A
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Items, Components, Raw Material, Services proposed to be sourced from Micro and Small Enterprises)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
1. We hereby furnish the details of the items, components, raw material, services which we propose to buy/avail from Micro and Small Enterprises (MSEs) for the purpose of completion of works under the package. i.e.,Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Name of Micro and Small Enterprises (MSEs)
Name Category (Micro or Small)
We hereby furnish the details of the items/ sub-assemblies propose to supply from our own works (i.e. as direct transactions) in additiona to the supplies the same from other vendors (i.e. as Bought-out transactions) as detailed in the table given above.
Sl. No. Item Description Quantity proposed to be supplied Details of the plant from where supplies are proposed.
Name of Plant Address
2. The above is a list of items we propose to procure from MSEs. However, based on the situations during the execution of the contract, the above list may undergo changes. We hereby confirm that the details regarding actual procurement from MSEs carried out by us, as per the format provided at Section VI, Sample Forms and Procedures (FORMS), Volume-I of bidding documents, shall be submitted along with the bills for payment against supplies made/works done during execution of contract.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-5A
(Items, Components, Raw Material, Services proposed to be sourced from Micro and Small Enterprises)
Sl. No. Item Description Quantity proposed to be bought/sub-contracted Name of Micro and Small Enterprises (MSEs)
Name Category (Micro or Small)
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-6
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Alternative, Deviations and Exceptions to the Provisions)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
The bidder shall itemize any deviation from the Specifications included in his bid. Each item shall be listed (separate sheets may be used and enclosed with this Attachment) with the following information:
Sl. No. Reference clause in the Specifications Deviation Reason for change The change in Bid Prices if the deviation is withdrawn and the Bidder conforms to the Specifications
Any proposed deviation will be applicable only for the bidder whose bid is substantially responsive in accordance with Clause 22, Section ITB, Vol. I of the bidding documents. If a bid is not substantially responsive, it will be rejected and may not subsequently be made responsive by the bidder by correction of the non-conformity.
The above deviations and variations are exhaustive. We confirm that we shall withdraw the deviations proposed by us at the cost of withdrawal indicated in this attachment, failing which our bid may be rejected and Bid Security forfeited.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-6
(Alternative, Deviations and Exceptions to the Provisions)
Sl. No. Reference clause in the Specifications Deviation Cost of withdrawal of the deviation
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 Attachment-7
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Details of Alternative Bid)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
No Alternative Bid
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-9
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Work Completion Schedule)
Bidder’s Name and Address : To
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby declare that the following Work Completion Schedule shall be followed by us in furnishing and installation of the subject package i.e., Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) for the period commencing from the effective date of Contract to us :
Sl. No. Description of Work Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
1 Detailed Engineering and drawing submission a) commencement
2 Procurement of equipment/ components & assembly a) commencement
3 Type Tests a) commencement
4 Manufacturing a) commencement
5 Shipments & Delivery a) commencement
6 Establishment of site office
7 Installation at Site a) commencement
8 Testing & Pre-commissioning a) commencement
9 Trial Operation a) commencement 22
b) completion 20
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation: 0
Note: Bidders to enclose a detailed network covering all the activities to be undertaken for completion of the project indicating key dates for various milestones for each phase constituent-wise
SPEC. NO.: CC/NT/W-HVDC/DOM/A02/26/06464 ATTACHMENT-10
Refurbishment of HVDC Control, Protection, SCADA, Valve Hall Equipment and Valve Cooling System for 1x500 MW Vizag HVDC Back to Back (BTB) Station under Add-Cap.
(Guarantee Declaration)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We confirm that the equipments offered shall have minimum (or a maximum, as the case may be) performance specified in Technical Specifications. We further guarantee the performance/ efficency of the equipments in response to the Technical Specifications
We declare that the ratings, performance figures and availability of the system furnished by us for subject Package covered under this specification are guaranteed by us. In particular, we declare that the 1) 10MVA, (220/V3)/(132/V3) kV, 1-phase Autotransformer; 2) 160MVA, 220/132/33 KV, 3-phase Autotransformer as per scope of package) offered under this package shall meet the maximum loss requirement as stipulated in Technical Specifications
A. For System Performance Guarantee:
We declare that the ratings, performance figures and availability of the system furnished by us for subject Package covered under this specification are guaranteed by us. We further declare that in the event of any deficiencies in meeting the guarantees in respect of the characteristics mentioned below, you may invoke the remedies specified for each of such guarantees, (as the case may be) in line with Technical Specifications.
Sl. No Parameter Guaranteed Values
1 Rated Station capacity a) Pole-1 and Pole-2 individually b) Joint operation of Pole- 1 and Pole-2 a) 1000 MW b) 2000MW.
2 Station Availability Minimum Energy availability requirement for Block-1 ≥ 99.8%
3 Station Reliability Equivalent Outage Frequency (No. of Occurrences Per year) ≤ 2
4a No load losses (in kW) with Converter Transformer set at principal tap* for:
4b Equivalent Load Losses (In kW) (Refer TS Chapter-11, Clause 11.10.1.3 Load Losses)
4c Station load losses (In kW) at different powerlevels of HVDC station as below:
5 Annual Rate of Failure of Thyristor level ≤0.2% per 12 pulse valve group except first unit failure
6 Annual Rate of Failure of Relay Module/C&P Module/Component (Per pole Basis) ≤ 0.5% except first unit failure
7 Shutdown of running system (a) Pole-1 (b) Pole-2 (c) Bipole (a) ≤ 100 days (b) ≤ 100 days (c) ≤ 15 days
* Principal tap is the Tap Position of converter transformer when HVDC converter shall be delivering 1 PU power (1000 MW per pole) at nominal DC voltage at Rectifier (500 kV) keeping ac system voltage 400 KV, 50 Hz at 40 degree Celsius ambient temperature.
# Breakup of Guaranteed Value of No Load Losses for Block-1 is mentioned in Attachment-10b, Table – I.
** Breakup of Station losses for Block-1 at specified power levels are mentioned in Attachment-10(b), Table – II.
The above mentioned guaranteed values shall be applicable for all contractual purpose including evaluation.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A02/26/06464 ATTACHMENT-10
Refurbishment of HVDC Control, Protection, SCADA, Valve Hall Equipment and Valve Cooling System for 1x500 MW Vizag HVDC Back to Back (BTB) Station under Add-Cap.
(Guarantee Declaration)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We confirm that the equipments offered shall have minimum (or a maximum, as the case may be) performance specified in Technical Specifications. We further guarantee the performance/ efficency of the equipments in response to the Technical Specifications
We declare that the ratings, performance figures and availability of the system furnished by us for subject Package covered under this specification are guaranteed by us. In particular, we declare that the 1) 10MVA, (220/V3)/(132/V3) kV, 1-phase Autotransformer; 2) 160MVA, 220/132/33 KV, 3-phase Autotransformer as per scope of package) offered under this package shall meet the maximum loss requirement as stipulated in Technical Specifications
We are furnishing the following details of the No Load Losses and Station Losses for block-1
TABLE – I (No-Load Losses (in kW))
For complete Bipole
(A) Thyristor Valves ; Refer Clause 11.10.2.2 c ^ (B) Thyristor Valves- Cooling Fan & pump, ;Refer Clause 11.10.2.2 c ^
No load Losses (in kW) with Converter Transformer set at principal tap*
* Principal tap is the Tap Position of converter transformer when HVDC converter shall be delivering 1 PU power (1000 MW per pole) at nominal DC voltage at Rectifier (500 kV) keeping ac system voltage 400 KV, 50 Hz at 40 degree Celsius ambient temperature.
^ Refer Chapter -11 of Part-1 of Technical Specification, Volume-II of Bidding Documents.
Note: In case of any discrepancy between Guaranteed Value of No Load Losses for complete bipole, as mentioned at sl. no. 4(a) of Attachment-10, and total calculated from breakup mentioned in this Attachment 10B, Table – I, the Guaranteed Value of No Load Losses as mentioned at sl. no. 4(a) of Attachment-10 shall prevail, and breakup indicated in this Attachment-10B, Table – I shall be adjusted accordingly with mutual agreement between Contractor and Employer.
TABLE – II (Station Losses (in kW))
For complete Bipole
Station operating losses (in kW) at Power Level: (A) Thyristor Valves ; Refer Clause 11.10.2.2 c ^ (B) Thyristor Valves- Cooling Fan & pump;Refer Clause 11.10.2.2 c ^
^ Refer Chapter -11 of Part-1 of Technical Specification, Volume-II of Bidding Documents.
Note: In case of any discrepancy between Total Station Losses for Block-1 at specified power levels , as mentioned at sl. no. 4(b) of Attachment-10, and total calculated from breakup mentioned in this Attachment 10B, Table – II, the Total Station Losses for Block-1 at specified power levels as mentioned at sl. no. 4(b) of Attachment-10 shall prevail, and breakup indicated in this Attachment-10B, Table –II shall be adjusted accordingly with mutual agreement between Contractor and Employer.
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-11
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Information regarding Ex-employees of POWERGRID in our Organisation)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby furnish the details of ex-employees of POWERGRID who had retired/ resigned at the level of General Manager and above from POWERGRID and subsequently have been employed by us:
Sl. No. Name of the person with designation in POWERGRID Date of Retirement/ resignation from POWERGRID Date of joining and designation in our organisation
*In case the date of joining in the bidder’s organization of such ex-employee is within 1 year from the date of retirement/resignation from POWERGRID, No Objection Certificate/ approval from the Competent Authority must be furnished along with the bid or subsequent through clarification pursuant to ITB Clause 21.
In case of non-submission of No Objection Certificate/approval of the Competent Authority, as required, We understand that POWERGRID shall deal with such cases as per its Policy and procedures in vogue, which may also result in rejection of our bid. We also confirm that POWERGRID shall be the sole judge in this regard. We further declare that any misrepresentation or submission of false/forged documents/information in this regard shall be dealt with as per the provisions of the Integrity Pact and/or the Bidding Documents and/or POWERGRID’s policy and procedures.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Note: The information in similar format should be furnished for each partner of joint venture in case of joint venture bid.
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-11
(Information regarding Ex-employees of POWERGRID in our Organisation)
Sl. No. Name of the person with designation in POWERGRID Date of Retirement/ resignation from POWERGRID Date of joining and designation in our organisation
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-11
(Information regarding Ex-employees of POWERGRID in our Organisation)
Sl. No. Name of the person with designation in POWERGRID Date of Retirement/ resignation from POWERGRID Date of joining and designation in our organisation
Date : 00-Jan-00 Printed Name : 0
Place : 00-Jan-00 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-12
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Price Adjustment Data)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No.-2
0 Gurgaon (Haryana) - 122001
We hereby furnish the relevant details pertaining to the price adjustment provisions for equipment as specified in your specifications and documents for the Subject Package. The necessary documentary evidence is enclosed.
A For Equipments (for Ex-works Price component)
Sl. No. Name of Materials/Labour Value of co-efficient Name of the published index Value of index as on thirty (30) days prior to date of opening in line with Appendix-2, Section-VI, Volume-I
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
i) Fixed Portion of the Ex-works Price component of equipment which will not be subject to any adjustment = 0.15
ii) Material Component (Refer Clause Appendix-2 of Conditions of Contract, Vol-I)
I Current Transformer
a) Raw Material
b) Labour l= Indian field labour index – namely All-India Average Consumer Price Index Numbers for Industrial Workers (monthly) (Base 2016=100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in)
The sum of the value of coefficients for raw materials: a+b+c+d=0.55 to 0.65 and sum of all the coefficients including labour shall be a+b+c+d+l=0.85.
Name of Equipment =
The sum of a, b, c, d and e must must be between 0.50 and 0.60
Labour component:
The labour component l is (should be between 0.25 to 0.35) of the equipment component
The value of the above index 30 days prior to the date of opening is
The published index used is
Sl. No. Name of Materials/Labour Value of co-efficient Name of the published index Value of index as on thirty (30) days prior to date of opening in line with Appendix-2, Section-VI, Volume-I
I Installation price component (including Civil works)
i) Labour, l= 0.8 Indian field labour index – namely All India average consumer price index for Industrial Workers (monthly) (Base: 2016= 100), as published by Labour Bureau, Shimla, Government of India (http://labourbureaunew.gov.in).
The Bidders are required to estimate and indicate the values of different coefficients for each of the items in the price variation formulae within the specified range such that their summation is as specified in the Bidding Documents. Where no value or ‘-’ or ‘shall be furnished later’ is specified against the coefficient, the same will be deemed to be zero and the fixed component would be suitably adjusted. If the values of all coefficients in price variation formulae indicated by the Bidder are within the specified range but their sum exceeds the summation specified in the Bidding Documents, the values of the coefficients shall be pro-rata adjusted such that the summation remains as per the provisions of the Bidding Documents. If the values of all coefficients indicated by the Bidder are within the specified range but their summation is less than the value specified in the Bidding Documents, the values of the coefficients as indicated by the Bidder shall be considered as such and the fixed component in the price variation formulae would be suitably adjusted. Further, if any of values of the coefficients indicated by the Bidder is out of the range specified in the Bidding Documents, the lower of the values, as indicated by the Bidder vis-à-vis lower value of the range for that coefficient specified in the Bidding Documents, shall be considered and the fixed component would be suitably adjusted.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-13
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Declaration regarding Social Accountability)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We conform that we stand committed to comply to all requirements of Social Accountability Standards i.e., SA8000 (latest Standard available at www.sa-intl.org) and maintain the necessary records.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-14
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Integrity Pact is annexed herewith this Volume.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Instruction for printing & submitting Integrity Pact
1. The requisite format of Integrity Pact is getting generated automatically and displayed here below.
2. Take print out of first page on a non-judicial stamp paper of Rs. 100/- and other seven pages on plain A4 size paper. Such two sets shall be prepared by the bidder.
3. All the pages of both the copies of the Integrity Pact shall be signed by the authorised representative of the bidder and duly stamped.
4. Both the original copies shall be submitted by the bidder in the form of Hard Copy as part of the first envelope before due date & time of submission of the bid.
5. For further details bidders may please refer ITB Clause 9.3 (o).
Power Grid Corporation of India Limited 0 0
having its Registered Office at B-9, Qutab Institutional Area, Katwaria Sarai, New Delhi – 110016 hereinafter referred to as 0 0
"POWERGRID", 0 0
having its Registered Office at 1 having its Registered Office at ,
hereinafter referred to as
"The Bidder/Contractor"
POWERGRID intends to award, under laid-down organisational procedures, contract(s) for Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap), SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 1 of 8
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap), SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 values full compliance with all relevant laws of the land, rules, regulations, economic use of resources, and of fairness / transparency in its relations with its Bidders/ Contractors.
In order to achieve these goals, POWERGRID and the above named Bidder/Contractor enter into this agreement called 'Integrity Pact' which will form a part of the bid.
It is hereby agreed by and between the parties as under:
Section I - Commitments of POWERGRID
(1) POWERGRID commits itself to take all measures necessary to prevent corruption and to observe the following principles :
a) No employee of POWERGRID, personally or through family members, will in connection with the tender, or the execution of the contract, demand, take a promise for or accept, for him/herself or third person, any material or other benefit which he/she is not legally entitled to.
b) POWERGRID will, during the tender process treat all Bidder(s) with equity, fairness and reason. POWERGRID will in particular, before and during the tender process, provide to all Bidder(s) the same information and will not provide to any Bidder(s) confidential/ additional information through which the Bidder(s) could obtain an advantage in relation to the tender process or the contract execution.
c) POWERGRID will exclude from evaluation of Bids its such employee(s) who has any personnel interest in the Companies/Agencies participating in the Bidding/Tendering process and all known prejudiced persons.
(2) If POWERGRID obtains information on the conduct of any of its employee which is a criminal offence under the IPC / PC Act , or if there be a substantive suspicion in this regard, POWERGRID will inform its Chief Vigilance Officer and in addition disciplinary actions can be initiated under POWERGRID’s Rules.
Section II - Commitments of the Bidder/Contractor
(1) The Bidder/Contractor commits itself to take all measures necessary to prevent corruption. The Bidder/Contractor commits itself to observe the following principles
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 2 of 8
during his participation in the tender process and during the contract execution :
a) The Bidder/Contractor will not, directly or through any other person or firm, offer, promise or give to any of POWERGRID's employees involved in the tender process or the execution of the contract or to any third person any material or other benefit which it is not legally entitled to, in order to obtain in exchange an advantage of any kind whatsoever during the tender process or during the execution of the contract
b) The Bidder/Contractor will not enter into any illegal or undisclosed agreement or understanding, whether formal or informal with other Bidders/Contractors. This applies in particular to prices, specifications, certifications, subsidiary contracts, submission or non-submission of bids or actions to restrict competitiveness or to introduce cartelization in the bidding process.
c) The Bidder/Contractor shall not pass any information provided by POWERGRID as part of business relationship to others and shall not commit any offence under PC / IPC Act.
d) The Bidder/Contractor of foreign origin shall disclose the name and address of the Agents/representatives in India, if any, involved directly or indirectly in the Bidding. Similarly, the Bidder/Contractor of Indian Nationality shall furnish the name and address of the foreign principals, if any, involved directly or indirectly in the Bidding.
e) The Bidder/Contractor will, when presenting his bid, disclose any and all payments made, or committed to or intends to make to agents, brokers or any other intermediaries in connection with the award of the contract and/or with the execution of the contract.
f) The Bidder/Contractor will not misrepresent facts or furnish false/forged documents/information in order to influence the bidding process or the execution of the contract to the detriment of POWERGRID.
g) The Bidder/Contractor shall ensure adoption of Integrity Pact by its Sub-contractors and shall be responsible for the same.
(2) The Bidder/Contractor will not instigate third persons to commit offences outlined above or be an accessory to such offences.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 3 of 8
Section III- Disqualification from tender process and exclusion from future contracts
(1) If the Bidder, before contract award, has committed a transgression through a violation of Section II or in any other form such as to put his reliability or credibility as Bidder into question, POWERGRID may disqualify the Bidder from the tender process or terminate the contract, if already signed, for such reason.
(2) If the Bidder/Contractor has committed a transgression through a violation of Section II such as to put his reliability or credibility into question, POWERGRID may, after following due procedures, ban /blacklist the Bidder/Contractor in line with POWERGRID’s policy for “Black-Listing of Firms / Banning of Business”. The imposition and duration of the ban will be determined by the severity of the transgression. The severity will be determined by the circumstances of the case, in particular the number of transgressions, the position of the transgressors within the company hierarchy of the Bidder/Contractor and the amount of the damage. The ban will be imposed for a maximum of 3 years.
(3) If the Bidder/Contractor can prove that he has restored/recouped the damage caused by him and has installed a suitable corruption prevention system, POWERGRID may revoke the ban prematurely.
Section IV - Liability for violation of Integrity Pact
(1) If POWERGRID has disqualified the Bidder from the tender process prior to the award under Section III, POWERGRID is entitled for forfeiture of the Bid Guarantee under the Bid.
(2) If POWERGRID has terminated the contract under Section III or if POWERGRID is entitled to terminate the contract under Section III, POWERGRID shall be entitled to forfeit the Contract Performance Guarantee of this contract, in full or part thereof as may be decided, besides resorting to other remedies under the contract.
Section V- Previous Transgression
(1) The Bidder shall disclose in its Bid any transgressions occurred in the last 10 years with any other Public Sector Undertaking or Government Department or any other Company, in any country, that may impinge on the Anti-corruption principle.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 4 of 8
(2) If the Bidder makes incorrect statement on this subject, it can be disqualified from the tender process or the contract, if already awarded, can be terminated for such reason and further action can be taken in line with POWERGRID’s policies.
Section VI - Equal treatment to all Bidders / Contractors
(1) POWERGRID will enter into agreements with identical conditions as this one with all Bidders.
(2) POWERGRID will disqualify from the tender process any bidder who does not sign this Pact or violate its provisions.
Section VII - Punitive Action against violating Bidders / Contractors
If POWERGRID obtains knowledge of conduct of a Bidder or a Contractor or his subcontractor or of an employee or a representative or an associate of a Bidder or Contractor or his Subcontractor which constitutes corruption, or if POWERGRID has substantive suspicion in this regard, POWERGRID will inform the Chief Vigilance Officer (CVO).
(*)Section VIII - Independent External Monitor/Monitors
(1) POWERGRID has appointed a panel of Independent External Monitors (IEMs) for this Pact with the approval of Central Vigilance Commission (CVC), Government of India. The names of the IEMs have been indicated in the Bidding Documents.
(2) The panel of IEMs shall review independently and objectively, whether and to what extent the parties comply with the obligations under this agreement. The panel of IEMs has right of access to all project documentation. The panel of IEMs may examine any complaint received by them and submit a report to Chairman-cum-Managing Director, POWERGRID, giving joint findings, at the earliest. The panel of IEMs may also submit a report directly to the CVO and the CVC, in case of suspicion of serious irregularities attracting the provisions of the PC Act.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 5 of 8
(3) The IEM is not subject to instructions by the representatives of the parties and performs his functions neutrally and independently. He / She reports to the Chairman-cum-Managing Director, POWERGRID.
(4) The Bidder(s)/Contractor(s) accepts that the IEM has the right to access without restriction to all documentation of POWERGRID related to this contract including that provided by the Contractor/Bidder. The Bidder/Contractor will also grant the IEM, upon his / her request and demonstration of a valid interest, unrestricted and unconditional access to their documentation. The same is applicable to Subcontractors. The IEM is under contractual obligation to treat the information and documents of the Bidder(s)/Contractor(s)/Subcontractor(s) with confidentiality.
(5) POWERGRID will provide to the IEMs information as sought by him / her which could have an impact on the contractual relations between POWERGRID and the Bidder/Contractor related to this contract. The IEMs shall also sign declaration on ’Non-Disclosure of Confidential Information’ and of ‘Absence of Conflict of Interest’. In case of any conflict of interest arising at a later date, the IEM shall inform Chairman-cum-Managing Director, POWERGRID and recuse himself/herself from that case.
(6) As soon as the IEM notices, or believes to notice, a violation of this agreement, he / she will so inform the Chairman-cum-Managing Director, POWERGRID and request the Chairman-cum-Managing Director, POWERGRID to discontinue or take corrective action, or to take other relevant action. The IEM can in this regard submit non-binding recommendations. Beyond this, the IEM has no right to demand from the parties that they act in a specific manner, refrain from action or tolerate action. However, the IEM shall give an opportunity to POWERGRID and the Bidder/Contractor, as deemed fit, to present its case before making its recommendations to POWERGRID.
(7) The IEM will submit a written report to the Chairman-cum-Managing Director, POWERGRID within 8 to 10 weeks from the date of reference or intimation to him by POWERGRID and, should the occasion arise, submit proposals for correcting problematic situations.
(8) If the IEM has reported to the Chairman-cum-Managing Director, POWERGRID, a substantiated suspicion of an offence under PC / IPC Act, and the Chairman-cum-Managing Director, POWERGRID has not, within the reasonable time taken visible action to proceed against such offence or reported it to the CVO, the Monitor may also transmit this information directly to the CVC, Government of India.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 6 of 8
(9) While representing any matter in relation to the Integrity pact inter-alia including its transgression to the panel of IEMs, POWERGRID and Bidder/Contractor shall not approach the court of law and await the decision of the IEM in the matter.
(10) The word ‘IEM’ would include both singular and plural.
(*) This Section shall be applicable for only those packages wherein the IEMs have been identified in Section – I : Invitation for Bids and/or Clause ITB 9.3 in Section – III: Bid Data Sheets of Conditions of Contract, Volume-I of the Bidding Documents.
Section IX - Pact Duration
This Pact begins when both parties have legally signed it. It expires for the Contractor after the closure of the contract and for all other Bidder's six month after the contract has been awarded.
Section X - Other Provisions
(1) This agreement is subject to Indian Law. Place of performance and jurisdiction is the establishment of POWERGRID. The Arbitration/Conciliation clause provided in the main tender document / contract shall not be applicable for any issue / dispute arising under Integrity Pact.
(2) Changes and supplements as well as termination notices need to be made in writing. Side agreements have not been made.
(3) If the Contractor is a partnership firm or a consortium or Joint Venture, this agreement must be signed by all partners, consortium members and Joint Venture partners.
(4) Nothing in this agreement shall affect the rights of the parties available under the General Conditions of Contract (GCC) and Special Conditions of Contract (SCC).
(5) Issues like Warranty/Guarantees etc. shall be outside the purview of IEMs.
(6) Views expressed or suggestions/submissions made by the parties and the recommendations of the CVO/IEM# in respect of the violation of this agreement, shall not be relied on or introduced as evidence in the arbitral/conciliation or judicial proceedings (arising out of the arbitral/conciliation proceedings) by the parties in connection with the disputes/differences arising out of the subject contract
# CVO shall be applicable for packages wherein IEM are not identified in Section IFB/BDS of Condition of Contract, Volume-I. IEM shall be applicable for packages wherein IEM are identified in Section IFB/BDS of Condition of Contract, Volume-I.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Integrity Pact Page 7 of 8
(7) Should one or several provisions of this agreement turn out to be invalid, the remainder of this agreement remains valid. In this case, the parties will strive to come to an agreement to their original intentions.
Signature Signature
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
(Office Seal) (Office Seal)
Designation : Designation :
Witness 1 : Witness 1 :
Designation : Designation :
Witness 2 : Witness 2 :
Designation : Designation :
Integrity Pact Page 8 of 8
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 Attachment-15(rev) 0
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Option for Initial Advance (either Interest Bearing Initial Advance or No Initial Advance) and Information for E – payment, PF details and declaration for Micro/Small and Medium Enterprise
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
I We have read the provisions in the Bidding Documents regarding furnishing the option for advance payment. Accordingly, as per ITB Clause 9.3 as provided in Section BDS, Section III, Vol.-I of the Bidding Documents, we hereby confirm to opt the following:
A1 Interest Bearing Initial Advance
Supply Portion:
Services Portion:
A2 B. Interest Bearing Interim Advance for Supply Portion :
II We are furnishing the following details of Statutory Registration Numbers and details of Bank for electronic payment.
1. Name of the Supplier/ Contractor in whose favour payment is to be made 0
2. Address with PIN Code and State
Registered Office:
Correspondence Address:
3. (a) Status – Company/others
[Declaration of Micro/ Small/ Medium Enterprise under Micro/ Small & Medium Enterprises Development Act 2006, if applicable]
3. (b) Are you a MSE owned by SC/ST* entrepreneurs in line with Public Procurement Policy for Micro and Small Enterprises (MSEs) order 2012 including subsequent amendment/notification/order (Indicate Yes/No) Note: Documentary evidence is to be attached. Please refer remarks at the end of the attachment. No
3. (c ) If 3(b) is ‘Yes’ please mention whether you are (Proprietary MSE/ Partnership MSE/ Private Limited Company) owned by SC/ST entrepreneurs
3. (d ) Are you a MSE owned by women in line with Public Procurement Policy for Micro and Small Enterprises (MSEs) order 2012, Public Procurement Policy for Micro and Small Enterprises (MSEs) Amendment order 2018 including subsequent amendment/notification/order (Indicate Yes/No) Note: Documentary evidence is to be attached.
4. Permanent Account (PAN) No.
5. GSTIN Numbers
I. GSTIN in the Sates/UT from where the supply of goods take place
Name of the States/UT GSTIN number
II. GSTIN in the States/UT where the supply for services take place (states where sites under the subject package is situated)
Name of the States/UT GSTIN number
6 PF Registration No. of the Company
7 PF Regional Office covered (with Address)
8 Name of Contact Person
9 Contact Details
10 Bank Details for Electronic Payment
Name of the Bank:
Address of Branch:
Type of Account:
Type of Account: Saving Account
11 9 digit MICR code printed at bottom in middle, next to cheque no.
12 IFSC (for RTGS)/NEFT Code (to be obtained from the Bank) Sample Cancelled Cheque to be enclosed
We hereby declare that the above information are true and correct and we agree that the payment on account of this Contract, in the event of award, be made in the above account maintained in the above mentioned Bank.
*The definition of MSEs owned by SC/ST is as given under:
a. In case of proprietary MSE, proprietor(s) shall be SC /ST.
b. In case of partnership MSE, the SC/ST partners shall be holding at least 51% shares in the unit.
c. In case of Private Limited companies, at least 51% share shall be held by SC/ST promoters.
Documentary evidence: Please provide scanned copy(ies) of the SC/ST certificate(s) issued by District Authority as applicable for SC/ST MSE category as per (a), (b) or (c) above.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-16
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Additional Information)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
In support of the additional information required as per ITB Sub-Clause 9.3 (q) of the Bidding Documents, we furnish herewith our data/details/documents etc., alongwith other information, as follows (the stipulations have been reproduced in italics for ready reference):
1.0 The Bidder shall furnish
Certificate from their Banker(s) (as per prescribed formats in Form 16, Section-VI: Sample Forms and Procedures) indicating various fund based/non fund based limits sanctioned to the Bidder and the extent of utilization as on date. Such certificate should have been issued not earlier than three months prior to the date of bid opening. Wherever necessary the Employer may make queries with the Bidders’ Bankers. [Reference ITB clause 9.3(q)(i)]
1.1 In accordance with 1.0, certificate(s) from banker as per requisite format, indicating various fund based/non fund based limits sanctioned to the bidder or each member of the joint venture and the extent of utilization as on date is/are enclosed, as per the following details:
Name of the Bidder : 0 1
Name of the Banker by whom certificate issued 1
Date of certificate (should not be earlier than 3 months prior to date of bid opening)
Whether fund based/non fund based limits are indicated in the certificate
Whether extent of utilization is indicated in the certificate
1.2 The Bidder should accordingly also provide the following information/documents
(i) Details of Banker:
Address of Banker
Contact Name and Title
(ii) As per para 1.0, Authorization Letter(s) from the bidder addressed to the Banker(s), authorizing POWERGRID to seek queries about the bidder with the Banker(s) and advising the Banker(s) to reply the same promptly, is/are enclosed as per following details:
Sl. No. Letter Ref. Date Addressed to (name of the Bank)
2.0 Litigation History
The bidder should provide detailed information on any litigation or arbitration arising out of contracts completed or under execution by it over the last five years. A consistent history of awards involving litigation against the Bidder or any partner of JV may result in rejection of Bid. [Reference ITB clause 9.3(q)(ii)]
2.1 Details of litigation history resulting from Contracts completed or under execution by the bidder over the last five years. A consistent history of awards invlolving litigation against the Bidder or any patner of JV may result in rejection of Bid. [(Refer ITB Clause 9.3 (q)(ii))]
Year Name of client, cause of litigation/arbitration and matter in dispute Details of Contract and date Award for or against the bidder Disputed amount
3.0 Details regarding previous transgressions of Integrity Pact The bidder should provide detailed information on any transgression of Integrity Pact that occurred in the last 10 years with any other Public Sector Undertaking or Government Department or any other Company, in any country
3.1 Details regarding previous transgressions of Integrity Pact that occurred in the last 10 years
Year Name of the Clients Details of Transgression of Integrity Pact by the bidder
4.0 OTHER INFORMATION
4.1 Current Contract Commitments of works in progress
Bidders should provide information on their current commitments on all contracts that have been awarded, or for which a letter of intent or acceptance has been received, or for contracts approaching completion, but for which an unqualified, full completion certificate has yet to be issued.
Details of Contract Value of outstanding work (Rs.) Estimated completion date
4.2 Financial Data:
Figures Rs in Million
Details Actual (Previous five years) Projection for next five years
Total Liability
Current Liability
Profit before taxes
Profit after taxes
4.3 Details of Provident Fund Code Number of the Bidder
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-17
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Declaration for tax exemptions, reductions, allowances or benefits)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Dear Sirs, 1. We confirm that we are solely responsible for obtaining following tax exemptions, reductions, allowances or benefits in respect of supplies under the subject package, in case of award. We further confirm that we have considered the same in our bid thereby passing on the benefit to POWERGRID while quoting our prices. In case of our failure to receive such benefits, partly or fully, for any reason whatsoever, the Employer will not compensate us. 2. We are furnishing the following information required by the Employer for issue of requisite certificate if and as permitted in terms of the applicable Govt. of India policies/procedures (in case of award):
Applicable Act, Notification No. and Clause Ref. No. Sl. No. Description of item on which applicable Country of origin Remarks, if any
(The requirements listed above are as per current Notification of Govt. of India indicated above. These may be modified, if necessary, in terms of the Notifications.)
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Instruction for printing & submitting Safety Pact
1. The requisite format of Safety Pact is getting generated automatically and displayed here below:
2. Take print out of first page on a non-judicial stamp paper of Rs. 100/- and other four pages on plain A4 size paper. Such two sets shall be prepared by the bidder.
3. All the pages of both the copies of the Safety Pact shall be signed by the authorised representative of the bidder and duly stamped.
4. Both the original copies shall be submitted by the bidder in the form of Hard Copy as part of the first envelope before due date & time of submission of the bid.
5. For further details bidders may please refer ITB Clause 9.3 (s).
Power Grid Corporation of India Limited 0 0
having its Registered Office at B-9, Qutab Institutional Area, Katwaria Sarai, New Delhi – 110016 hereinafter referred to as 0 0
"POWERGRID", 0 0
0 1 having its Registered Office at ,
having its Registered Office at, 0, 0, 0 1 AND
hereinafter referred to as
"The Bidder/Contractor"
POWERGRID intends to award, under laid-down organisational procedures, contract(s) for Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649
POWERGRID values full compliance with all relevant laws and regulations and the principles of Safety, Health& Environment in its relations with its Bidders/ Contractors
In order to achieve these goals, POWERGRID and the above named Bidder / Contractor enter into this agreement called “Safety Pact” which will form part of the Bid. It is hereby agreed by and between the parties as under:
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 1 of 5
Section I – Commitments of POWERGRID:
POWERGRID commits itself to take all measures necessary to prevent accidents duringConstruction and Operation of the Transmission Assets and to observe the following:
In order to achieve these goals, POWERGRID and the above named Bidder/Contractor enter into this agreement called 'Safety Pact' which will form a part of the bid.
1 POWERGRID recognizes and accepts its statutory responsibilities for ensuring construction, operation and maintenance of equipments and for the provision of safe methods of work and safe working conditions.
2 POWERGRID recognizes and accepts its statutory responsibilities for ensuring safety of not only its employees but also that of the Contracting Agencies as Principal Employer.
3 POWERGRID shall review the accidents in a structured manner and take necessary actions to ensure that the safety criteria are strengthened for safe construction as well as Operation & Maintenance of the Transmission Assets.
4 POWERGRID shall conduct necessary awareness and training programmes to its Employees to augment the various safety requirements to be followed during Construction and Operation & Maintenance of the Transmission Assets from time to time
5 POWERGRID shall, from time to time, issue necessary guidelines,instructions and deterrents to its employees as well as to the Contracting Agencies, to update them to take necessary preventive measures to avoid repetition of similar accident attributes.
6 POWERGRID shall review and provide necessary guidanceto the Contracting Agencies, as and when, any abnormality / special situations are brought to its notice by the Contracting Agencies during execution of the Transmission Projects being executed by them.
7 POWERGRID shall conduct periodical surveillance site inspections / audits to identify the unsafe conditions and unsafe actions, and bring them to the knowledge of the Contracting Agencies for taking timely corrective actions.
8 POWERGRIDshall investigate all accidents, fatal as well as non-fatal, to identify the lapses, the reason for the accident / incident and suggest measures for prevention of recurrence of such accidents, and fix responsibility for the lapses leading to the accident.
9 POWERGRID shall augment the training to the workers and supervising personnel of the Contracting Agencies, as per schedules, upon nomination by the Contracting Agencies in reasonable time frame.
10 POWERGRID shall exercise the right to claim and recover compensation from the Contracting Agencies in case of any violation of the safety requirements / provisions during execution of the Transmission Projects, as built in the applicable Laws and contractual specifications / guidelines in vogue / issued by POWERGRID from time to time.
11 Section II – Commitments of the Bidder / Contractor:
The Bidder / Contractor commits himself to take all measures necessary to prevent / minimise accidents at their construction / erection sites and to observe the following:
1 The Bidder / Contractor recognizes and acceptsthe statutory and comprehensive responsibility for ensuring safe construction and Testing & Commissioning in the Transmission Projects being executed by thembyproviding safe methods of work, working conditions and Tools & Plants for human safety.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 2 of 5
2 The Bidder / Contractor recognizes and accepts the responsibilities for ensuring safety of not only their employees but also that of the Sub-contractors, Principal Employer and the general public during execution of the Transmission Projects / works.
3 The Bidder / Contractor shall review the accidents in a structured manner and take necessary actions to ensure that the safety criteria are strengthened for safe construction of the Transmission Assets.
4 The Bidder / Contractor shall endeavour continuous development of safe methods of work to ensure that the effect of risks and perils are minimised to the extent possible and implement the same at their worksites.
5 The Bidder / Contractor shall conduct periodical Training to their Employees as well as to that of theirSub-contractors for safety awareness during construction works being executed by them.
6 The Bidder / Contractor shall provide all requisite Tools & Plants required for the work and ensure their healthiness by periodical inspections / testing as required. Unhealthy and sub-standard Tools & Plants will be immediately removed from site as and when they are identified.
7 The Bidder / Contractor shall,at their cost, provide all necessary Personal Protective Equipments such as Double Lanyard Safety Belts, Appropriate Fall Arrest Systems, Safety Helmets, Foot Wear, Hand Gloves, etc., as required for various activities pertaining to execution of the Projects / works, confirming to relevant Indian Standards.
8 The Bidder / Contractor shall ensure that dedicated qualified Safety Officers are posted in the construction projects being executed by them and ensure that the Safety Officer visits each and every gang periodically and conducts audits / inspections to identify the unsafe conditions and unsafe actions, to be rectified by the site supervising personnel promptly.
9 The Bidder / Contractor shall conduct appropriate medical checks-up for the workers before deploying them at their construction sites to ensure that only those who are medically fit are deployed in the Projects / works to be executed by them. The copy of the Medical Reports shall be provided by the Bidder / Contractor to POWERGRID, whenever requested by POWERGRID.
10 The Bidder / Contractor shall screen the workers before deploying them at their construction sites to ensure that only those with the skills, experience and competence to work at heightand also medically fitfor work at height are deployed for work at height in the Projects executed by them.
11 The Bidder / Contractor shall ensure daily before starting the work thattheir site Supervising Personnel / Safety Officer briefs the workers about the work for the day and the safety measures / precautions required to be taken by them.
12 The Bidder / Contractor shall investigate all the accidents at their working sites to ascertain the lapses leading to the incident and the precautionary / corrective measures required to be taken to avoid recurrence of such accidents. These accidents will be reviewed at the Board Management level of the Agencies and the findings / recommendations will be put up to POWERGRID Apex Safety Board within the stipulated period.
13 The Bidder / Contractor shall ensure that all accidents, whether fatal or non-fatal in nature, will be informed to POWERGRID, in writing, immediately on the occurrence of the same,and in any case, within not more than 24 hours of occurrence of the same.
14 The Bidder / Contractor shall ensure that in case of any accident, all necessary medical help / supportshall be provided to the victims / injured till they are completely fit to return to work.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 3 of 5
15 The Bidder / Contractorshall ensure that in case of fatal accidents, all statutory Authorities, including Police, concerned Labour Dept. Officials, concerned Workmen Compensation Commissioner, etc., will be intimated in writing as required by the statutory Law, and followed up for compliance of all statutory obligations. The Bidder / Contractor shall own full responsibility of timely accident reporting to various authorities, including POWERGRID.
16 The Bidder / Contractor shall ensure that in case of fatality or serious injury leading to permanent disablement of the victims, the compensation amount will be deposited with the concerned authorities, as required by the Laws, and followed up for early disbursement to the beneficiaries of the victims.
17 The Bidder / Contractor assures that they shall co-operate to the fullest extent for carrying out any investigation of the accidents at their work sites by POWERGRID to identify the lapses, the reason for the accident / incident and suggest measures for prevention of recurrence of such accidents. All factual details of the occurrence of the accident will be provided to POWERGRID, as and when required.
18 The Bidder / Contractor assures that they take full responsibility of meeting the statutory obligations in case of accidents, and in case of any reference by any Statutory Body at a later date also, they shall provide all information to POWERGRID and meet all the statutory obligations, including payment of additional compensation, if any.
19 The Bidder / Contractor assures that in case of any inspection of their work site or Notice by any Statutory Authority, they shall comply promptly and inform POWERGRID Site Officials of the same, and also provide all necessary information and assistance for smooth compliance of the observations / instructions of such Authorities.
20 The Bidder / Contractor accepts the provisions regarding safety, including payment of any sums to POWERGRID, in case of any violation of the safety requirements / provisions during execution of the Transmission Projects, as built in the Contractual Conditions, Safety Planand the Safety Pact, and confirm to abide by the same.
Section III – Equal treatment to all Bidders / Contractors:
1 POWERGRID will enter into agreements with identical conditions as this one with all Bidders.
2 POWERGRID will disqualify, from the tender process, any bidder/ take punitive actions on the bidder, who does not sign this Pact or violate its provisions.
Section IV – Pact Duration:
This Pact begins when both parties have legally signed it. It expires for the successful Bidder / Contractor after closure of the contract and, for all other Bidders, after the contract has been awarded.
Section V – Other Provisions:
1 This agreement is subject to Indian Law. Place of performance and jurisdiction is the establishment of POWERGRID. The Arbitration/Conciliation clause provided in the main tender document / contract shall not be applicable for any issue / dispute arising under the Safety Pact.
2 Changes and supplements need to be made in writing, which shall come into force only upon mutual agreement / acceptance.
(Signature) (Signature)
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
Safety Pact Page 4 of 5
3 If the Contractor is a partnership firm or consortium of Joint Venture, this agreement must be signed by all partners, consortium members and Joint Venue partners, as applicable as per the Tender Specifications.
4 Nothing in this agreement shall affect the rights of the parties available under General Conditions of Contract (GCC) and Special Conditions of Contract (SCC).
5 Should one or several provisions of this agreement turn out to be invalid, the reminder of this agreement remains valid. In this case, the parties will strive to come to an agreement to their original intentions.
Signature Signature
(For & On behalf of POWERGRID) (For & On behalf of Bidder/ Partner(s) of Joint Venture/ Contractor)
(Office Seal) (Office Seal)
Designation : Designation :
Witness 1 : Witness 1 :
Name & Address: Name & Address:
Witness 2 : Witness 2 :
Name & Address: Name & Address:
Safety Pact Page 5 of 5
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-19
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
Further, we hereby confirm that except as mentioned in the Attachment – 6 (Alternative, Deviations and Exceptions to the Provisions) hereof, forming part of our First Envelope :
(i) there are no discrepancies/inconsistencies and deviations/omissions/ reservations to the Bidding Documents, in the Second Envelope bid;
We also confirm that in case any discrepancies/ inconsistencies and deviations/ omissions/ reservations, as referred to in para (i) and (ii) above, is observed in the Second Envelope, the same shall be deemed as withdrawn/rectified without any financial implication, whatsoever to POWERGRID. However, in case of any arithmetical errors, the same shall be governed as per the provision of ITB Sub-Clause 27.2 read in conjunction with BDS
Date 0-Jan-1900 Printed Name 0
Place 0 Designation 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-23-A
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Declaration by the Bidder in line with Annexure-A (BDS) regarding already having manufacturing & testing facilities for 400kV or above voltage level GIS in India as on the originally scheduled date of bid opening.
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby confirm that we have already incorporated Subsidiary Company */Group Company * /Joint Venture Company * as per Companies Act of India, in line with GCC clause 5.1 to manufacture 400KV or above voltage level GIS in India as on the originally scheduled date of bid opening mentioned in Annexure-A (BDS).
We further confirm that the said Subsidiary Company */Group Company * /Joint Venture Company * has manufacturing & testing facilities for 400kV or above voltage level GIS in India as on the originally scheduled date of bid opening mentioned in Annexure-A (BDS).
Further, we are furnishing the requisite document in support of the above which are attached herewith.
* Stike out which ever is not applicable
Date 0-Jan-1900 Printed Name 0
Place 0 Designation 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-23-B
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Declaration by the Bidder in line with Annexure-A (BDS) regarding commencement of construction activities for establishment of 400kV or above voltage level GIS manufacturing and testing facilities in India as on the originally scheduled date of bid opening.
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We hereby confirm that we have already incorporated Subsidiary Company */Group Company * /Joint Venture Company * as per Companies Act of India, in line with GCC clause 5.1 to manufacture 400KV or above voltage level GIS in India and have commenced the Construction activities for establishment of manufacturing & testing facilities for 400kV or above voltage level GIS in India as on the originally scheduled date of bid opening mentioned in Annexure-A (BDS)
Regarding incorporation of Subsidiary Company */Group Company * /Joint Venture Company * in India and Commencement of Construction activities, we here by declare as under :
a) Our Subsidiary Company */Group Company * /Joint Venture Company * has been incorporated on ___________________ as per Companies Act of India (Documentary Evidence is Attached herewith).
b) Land is in legal and physical possession (Documentary evidence is attached herewith)
c) All Building designs, ordering of civil works have been completed and civil work at site have commenced (Documentary evidence is attached herewith)
d) Purchase order for major long delivery testing equipment have been placed with delivery and commissioning schedule (Documentary evidence is attached herewith)
e) Action plan for availability of trained manpower to take up manufacturing and testing of GIS module is attached herewith.
* Stike out which ever is not applicable
Date 0-Jan-1900 Printed Name 0
Place 0 Designation 0
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 ATTACHMENT-21
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(Declaration regarding Cyber Security requiremen)
Bidder’s Name and Address : To:
0 Contract Services
Name : 0 Power Grid Corporation of India Ltd.,
Address : 0 "Saudamini", Plot No. 2, Sector 29
0 Gurgaon (Haryana) - 122001
We confirm that we shall comply with Cyber Security requirements as specified in the Bidding Documents.
Further, we undertake that in case of award on us, we shall sign the 'Non-Disclosure Agreement' regarding Cyber Security requirements as per the proforma specified in Technical Specifications of the Bidding Documents.
Date : 00-Jan-00 Printed Name : 0
Place : 0 Designation : 0
Before filling up the Bid Form, the Bidder is required to fill up the details as under :
1 Tick whichever is applicable:
1 Enter Details of Amendments:
Amendments to Bidding Documents issued:
6* In case the Bidder is MSE, then insert the Designated Authority under GoI with which they are Registered: ghtg
* applicable for MSE only
SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 Bid Form (First Envelope) 1 st 1 January 1 one
2 nd 2 February 2 two
BID FORM (First Envelope) 3 rd 3 March 3 three
4 th 4 April 4 four
Bid Proposal Ref. No.: 5 th 5 May 5 five
Date : 00-Jan-00 7 th 0 6 June 7 seven
8 th 1 7 July 8 eight
To: 9 th January 8 August 9 nine
Contract Services 10 th 1900 9 September 10 ten
Power Grid Corporation of India Ltd., 11 th 10 October 11 eleven
"Saudamini", Plot No. 2, Sector 29 12 th 11 November 12 twelve
Gurgaon (Haryana) - 122001 13 th 12 December 13 thirteen
14 th Zero 14 fourteen
15 th () 15 fifteen
Name of Contract : Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) SPEC. NO.: CC/NT/W-HVDC/DOM/A10/26/08649 the receipt of which is hereby acknowledged, we the undersigned, offer to design, manufacture, test, deliver, install and commission (including carrying out Trial Operation, Performance & Guarantee Test as per provision of Technical Specification) the Facilities under the above-named package in full conformity with the said Bidding Documents. In accordance with ITB Clause 9.1 of the Bidding Documents, as per which the bid shall be submitted by the bidder under “Single Stage - Two Envelope” procedure of bidding. Accordingly, we hereby submit our Bid, in two envelopes i.e. First Envelope – Techno – Commercial Part & Second Envelope - Price Part (to be opened subsequently).0 16 th 16 sixteen
Dear Ladies and/or Gentlemen, 17 th 17 seventeen
1.0 Having examined the Bidding Documents, including Amendment Nos. dated 00/01/1900, the receipt of which is hereby acknowledged, we the undersigned, offer to design, manufacture, test, deliver, install and commission (including carrying out Trial Operation, Performance & Guarantee Test as per provision of Technical Specification) the Facilities under the above-named package in full conformity with the said Bidding Documents. In accordance with ITB Clause 9.1 of the Bidding Documents, as per which the bid shall be submitted by the bidder under “Single Stage - Two Envelope” procedure of bidding. Accordingly, we hereby submit our Bid, in two envelopes i.e. First Envelope – Techno – Commercial Part & Second Envelope - Price Part (to be opened subsequently). the receipt of which is hereby acknowledged, we the undersigned, offer to design, manufacture, test, deliver, install and commission (including carrying out Trial Operation, Performance & Guarantee Test as per provision of Technical Specification) the Facilities under the above-named package in full conformity with the said Bidding Documents. In accordance with ITB Clause 9.1 of the Bidding Documents, as per which the bid shall be submitted by the bidder under “Single Stage - Two Envelope” procedure of bidding. Accordingly, we hereby submit our Bid, in two envelopes i.e. First Envelope – Techno – Commercial Part & Second Envelope - Price Part (to be opened subsequently). 0 18 th 18 eighteen
1.1 We meet the eligibility requirements and have no conflict of interest in accordance with ITB Clause 2 19 th 19 nineteen
2.0 Attachments to the Bid Form (First Envelope) 20 th 20 twenty
2.1 In line with the requirement of the Bidding Documents, we enclose herewith the following Attachments to the Bid Form : 21 st
(a) Attachment 1: NOT APPLICABLE Bank Draft 22 th
Banks certified Cheque
(b) Attachment 2: Attachment 2: A power of attorney duly authorized by a Notary Public indicating that the person(s) signing the bid have the authority to sign the bid and thus that the bid is binding upon us during the full period of its validity in accordance with the ITB Clause 14. *Further the requisite deed of Joint Undertaking as per stipulated qualification requirement in Annexure-A (BDS) has also been furnished as per your format. * Delete if not applicable A power of attorney duly authorized by a Notary Public indicating that the person(s) signing the bid have the authority to sign the bid and thus that the bid is binding upon us during the full period of its validity in accordance with the ITB Clause 14. Bank Guarantee 23 th
(c) Attachment 3: The documentary evidence that we are eligible to bid in accordance with ITB Clause 2. Further, in terms of ITB Clause 9.3(c) & (e), the qualification data has been furnished as per your format enclosed with the bidding documents [Attachment – 3(QR)]. 24 th
* Further, the required deed of Joint Venture Agreement signed by us and our Partners has also been furnished as per your format [Attachment – 3(JV)].
(d) Attachment 4: The documentary evidence establishing in accordance with ITB Clause 3, Vol.-I of the Bidding Documents that the facility offered by us are eligible facilities and conform to the Bidding Documents has been furnished as Attachment 4 . Moreover, a list of Special Tools & Tackles to be furnished by us, the cost of which is included in our Bid Price, is also enclosed as per your format as Attachment- 4A. 25 th
(e) Attachment 5: The details of all major items of services or supply which we propose subletting in case of award, giving details of the name and nationality of the proposed subcontractor/sub-vendor for each item. 26 th
(f) Attachment 5A: (Items, Components, Raw Material, Services proposed to be sourced from Micro and Small Enterprises): The details of the items, components, raw material, services which is proposed to bought/availed from Micro and Small Enterprises for the purpose of completion of works
(g) Attachment 6: The variation and deviations from the requirements of the Conditions of Contract, Bid Data Sheet and other commercial conditions, Technical Specification and Drawings (excluding critical provisions as mentioned at clause 6.0 below) in your format enclosed with the Bidding Documents, including, inter-alia, the cost of withdrawal of the variations and deviations indicated therein. 27 th
(h) Attachment 7: The details of Alternative Bids made by us indicating the complete Technical Specifications and the deviation to contractual and commercial conditions. [NOT APPLICABLE] 28 th
(i) Attachment 8: Manufacturer’s Authorisation Forms 29 th
(j) Attachment 9: Work Completion Schedule
(k) Attachment 10: Guarantee Declaration
(l) Attachment 11: Information regarding ex-employees of Employer in our firm
(m) Attachment 12: Filled up information regarding Price Adjustment Data as per the format enclosed in the bidding documents
(n) Attachment 13: Declaration regarding Social Accountability
(o) Attachment 14: Integrity Pact, in a separate envelope, duly signed on each page by the person signing the bid.
(p) Attachment 15: Option for Initial Advance (either Interest Bearing Initial Advance or No Initial Advance) and Information for E-payment, PF details and declaration regarding Micro/Small & Medium Enterprises
(q) Attachment 16: Additional information
(r) Attachment 17: Declaration for tax exemptions, reductions, allowances or benefits
(s) Attachment 18: Safety Pact
(t) Attachment 19: Declaration
(u) Attachment 20: Declaration of Key Managerial Person jointly with Power of Attorney holder is attached herewith
(v) Attachment 21: Declaration regarding Cyber Security requirement
(w) Attachment 22: Affidavit of Self certification regarding Minimum Local Content in line with PPP-MII Order and MoP Order, if applicable
(x) Attachment 23: VOID
(y) Attachment 24: Compliance to the process related to the e-RA Terms & Conditions and the Business Rules governing the e-RA
(z) Attachment 25: Declaration by the Bidder regarding events encountered pursuant to ITB Clause 2.1
(aa) Attachment 26: Affidavit of Self certification regarding Domestic Value Addition in Iron &Steel Products in line with DMI&SP policy
(bb) Attachment 27: Certification by the Bidder as per DoE Order in line with ITB Clause 2.1 (In case of a Joint Venture bid, the declaration shall be given by all partners of the Joint Venture)
(cc) Attachment 28: Bid Securing Declaration to be submitted by the Bidder
(dd) Attachment 29: Undertaking regarding submission of original/Hard copy part of the bid
(ee) Attachment 30: Declaration by the bidder for ‘Code of Integrity for Public procurement’
(ff) Attachment 31: Declaration by the bidder for Declaration by the bidder for Acknowledgement and Acceptance of ‘Supplier Code of Conduct’
3.0 We are aware that, in line with Clause No. 27.1 (ITB), our Second Envelope (Price Part) is liable to be rejected in case the same contains any deviation/omission from the contractual and commercial conditions and technical Specifications other than those identified in this First Envelope.
4.0 We confirm that except as otherwise specifically provided our Bid Prices in Second Envelope include all taxes, duties, levies and charges as may be assessed on us, our Sub-Contractor/Sub-Vendor or their employees by all municipal, state or national government authorities in connection with the Facilities, in and outside of India.
4.1 100% of applicable Taxes and Duties i.e. GST which are payable by the Employer under the Contract, shall be reimbursed by the Employer on production of satisfactory documentary evidence by the Contractor in accordance with the provisions of the Bidding Documents.
5.0 Construction of the Contract
, whose capacity, capability and experience are enclosed with our Bid as our Associate(s) for the purpose of executing the ‘Second Contract’ and / or the ‘Third Contract’ and written unequivocal consent of the above mentioned proposed Associate(s) to work as your independent Contractor, on the same terms and conditions as offered by us to you in this bid, is also enclosed with the Bid Form. We shall, however, be overall responsible for the execution of all the three Contracts.
5.1 We declare that we have studied Clause GCC 2.1 relating to mode of contracting for Domestic Bidders and we are making this proposal with a stipulation that you shall award us two separate Contracts viz ‘First Contract’ for ex-works supply of all equipment and materials including mandatory spares and ‘Second Contract’ for providing all the services i.e. inland transportation for delivery at site, In-transit insurance, unloading, handling at site, installation, testing and commissioning including Trial operation in respect of all the equipment supplied under the ‘First Contract’ and other services specified in the Contract Documents. We declare that the award of two contracts, will not, in any way, dilute our responsibility for successful operation of plant/equipment and fulfillment of all obligations as per Bidding Documents and that both the Contracts will have a cross-fall breach clause i.e. a breach in one Contract will automatically be classified as a breach of the other contract which will confer on you the right to terminate the other contract at our risk and cost.
6.0 We have read the provisions of following clauses and confirm that the specified stipulations of these clauses are acceptable to us:
(a) GCC 2.14 Governing Law
(b) GCC 5.1 Contractor’s Responsibilities
(c) GCC 8 Terms of Payment
(d) GCC 9.3 Performance Security
(e) GCC 10 Taxes and Duties
(f) GCC 21.2 Completion Time Guarantee
(g) GCC 22 Defect Liability
(h) GCC 23 Functional Guarantee
(i) GCC 25 Patent Indemnity
(j) GCC 26 Limitation of Liability
(k) GCC 38 Settlement of Disputes
(l) GCC 39 Arbitration
(m) GCC 40 Conciliation
(n) Appendix 2 to Form of Contract Agreement Price Adjustment
Further we understand that deviation taken in any of the above clauses by us shall make our bid non-responsive as per provision of bidding documents and rejected by you.
7.0 We undertake, if our bid is accepted, to commence the work on Facilities immediately upon your Notification of Award to us, and to achieve Completion within the time stated in the Bidding Documents.
8.0 If our bid is accepted, we undertake to provide an Advance Payment Security and Performance Security(ies) in the form and amounts, and within the times specified in the Bidding Documents.
9.0 We agree to abide by this bid for a period of Six (06) months after the date of opening of Techno - Commercial Part i.e. First Envelope as stipulated in the Bidding Documents, and it shall remain binding upon us and may be accepted by you at any time before the expiration of that period.
10.0 Until a formal Contract is prepared and executed between us, this bid, together with your written acceptance thereof in the form of your Notification of Award shall constitute a binding contract between us.
11.0 We understand that you are not bound to accept the lowest or any bid you may receive.
*12.0 (for Joint Venture only) We, the partners of Joint Venture submitting this bid, do agree and confirm that in case of Award of Contract on the Joint Venture, we shall be jointly and severally liable and responsible for the execution of the Contract in accordance with Contract terms and conditions. 1
13.0 We are a Micro and Small Enterprise (MSE) registered with , a designated Authority of GoI under the Public Procurement Policy for MSEs order 2012 Notification dated 01/06/2020 ,26/06/2020 and 19/01/2022 read in conjunction with related notifications issued from time to time for such enterprises. 0 2 2
13.0 We, hereby, declare that only the persons or firms interested in this proposal as principals are named here and that no other persons or firms other than those mentioned herein have any interest in this proposal or in the Contract to be entered into, if the award is made on us, that this proposal is made without any connection with any other person, firm or party likewise submitting a proposal is in all respects for and in good faith, without collusion or fraud.
14.0 We, hereby, declare that we, along with our associate/ collaborators/ sub-contractors/ sub-vendors/consultants/ service providers shall strictly adhere to the POWERGRID Whistle Blower and Fraud Prevention Policy. We, along with our associate / collaborator / subcontractors / sub-vendors / consultants / service providers shall observe the highest standard of ethics and shall not indulge or allow anybody else working in our organization to indulge in fraudulent activities during execution of the contract and would immediately apprise the Employer about any fraud or suspected fraud as soon as it comes to our notice.
Thanking you, we remain
Yours faithfully,
For and on behalf of : 0
Date : 00 January 1900 Printed Name: 0
Place : 00-Jan-00 Designation : 0
Please provide additional information of the Bidder
Business Address :
Country of Incorporation :
(State/Province to be indicated)
Name of Principal Officer :
Address of Principal Officer :
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only EURO Four Thousand Nine Hundred Sixty Only RMB Ten Thousand Three Hundred Fifty Two Only INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
85 Eighty Five 60 Sixty 52 Fifty Two 47 Forty Seven
8 Eight Hundred 9 Nine Hundred 3 Three Hundred 6 Six Hundred
55 Fifty Five Thousand 4 Four Thousand 10 Ten Thousand 91 Ninety One Thousand 0 0 0 0 0 plus
1 One Lac 0 0 6 Six Lac 0 0 0 0 1
1 One 1 One 1 One 1 One 0 0 1 0 1
2 Two 2 Two 2 Two 2 Two 0 0 1 1 0
3 Three 3 Three 3 Three 3 Three 0 0 1 1 1
4 Four 4 Four 4 Four 4 Four 0 1 0 0 0
5 Five 5 Five 5 Five 5 Five 0 1 0 0 1
6 Six 6 Six 6 Six 6 Six 0 1 0 1 0
7 Seven 7 Seven 7 Seven 7 Seven 0 1 0 1 1
8 Eight 8 Eight 8 Eight 8 Eight 0 1 1 0 0
9 Nine 9 Nine 9 Nine 9 Nine 0 1 1 0 1
10 Ten 10 Ten 10 Ten 10 Ten 0 1 1 1 0
11 Eleven 11 Eleven 11 Eleven 11 Eleven 1 1 1 1 1 USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
12 Twelve 12 Twelve 12 Twelve 12 Twelve
13 Thirteen 13 Thirteen 13 Thirteen 13 Thirteen
14 Fourteen 14 Fourteen 14 Fourteen 14 Fourteen
15 Fifteen 15 Fifteen 15 Fifteen 15 Fifteen
16 Sixteen 16 Sixteen 16 Sixteen 16 Sixteen 0 0 0 0 0 +
17 Seventeen 17 Seventeen 17 Seventeen 17 Seventeen 0 0 0 0 1 /- +
18 Eighteen 18 Eighteen 18 Eighteen 18 Eighteen 0 0 0 1 0 /-
19 Nineteen 19 Nineteen 19 Nineteen 19 Nineteen 0 0 0 1 1
20 Twenty 20 Twenty 20 Twenty 20 Twenty 0 0 1 0 0
21 Twenty One 21 Twenty One 21 Twenty One 21 Twenty One 0 0 1 0 1
22 Twenty Two 22 Twenty Two 22 Twenty Two 22 Twenty Two 0 0 1 1 0
23 Twenty Three 23 Twenty Three 23 Twenty Three 23 Twenty Three 0 0 1 1 1
24 Twenty Four 24 Twenty Four 24 Twenty Four 24 Twenty Four 0 1 0 0 0
25 Twenty Five 25 Twenty Five 25 Twenty Five 25 Twenty Five 0 1 0 0 1
26 Twenty Six 26 Twenty Six 26 Twenty Six 26 Twenty Six 0 1 0 1 0
27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 0 1 0 1 1
28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 0 1 1 0 0
29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 0 1 1 0 1
30 Thirty 30 Thirty 30 Thirty 30 Thirty 0 1 1 1 0
31 Thirty One 31 Thirty One 31 Thirty One 31 Thirty One 1 1 1 1 1 USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
32 Thirty Two 32 Thirty Two 32 Thirty Two 32 Thirty Two
33 Thirty Three 33 Thirty Three 33 Thirty Three 33 Thirty Three
34 Thirty Four 34 Thirty Four 34 Thirty Four 34 Thirty Four
35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr
36 Thirty Six 36 Thirty Six 36 Thirty Six 36 Thirty Six
37 Thirty Seven 37 Thirty Seven 37 Thirty Seven 37 Thirty Seven
38 Thirty Eight 38 Thirty Eight 38 Thirty Eight 38 Thirty Eight
39 Thirty Nine 39 Thirty Nine 39 Thirty Nine 39 Thirty Nine
40 Forty 40 Forty 40 Forty 40 Forty
41 Forty One 41 Forty One 41 Forty One 41 Forty One
42 Forty Two 42 Forty Two 42 Forty Two 42 Forty Two
43 Forty Three 43 Forty Three 43 Forty Three 43 Forty Three
44 Forty Four 44 Forty Four 44 Forty Four 44 Forty Four
45 Forty Five 45 Forty Five 45 Forty Five 45 Forty Five
46 Forty Six 46 Forty Six 46 Forty Six 46 Forty Six
47 Forty Seven 47 Forty Seven 47 Forty Seven 47 Forty Seven
48 Forty Eight 48 Forty Eight 48 Forty Eight 48 Forty Eight
49 Forty Nine 49 Forty Nine 49 Forty Nine 49 Forty Nine
50 Fifty 50 Fifty 50 Fifty 50 Fifty
51 Fifty One 51 Fifty One 51 Fifty One 51 Fifty One
52 Fifty Two 52 Fifty Two 52 Fifty Two 52 Fifty Two
53 Fifty Three 53 Fifty Three 53 Fifty Three 53 Fifty Three
54 Fifty Four 54 Fifty Four 54 Fifty Four 54 Fifty Four
55 Fifty Five 55 Fifty Five 55 Fifty Five 55 Fifty Five
56 Fifty Six 56 Fifty Six 56 Fifty Six 56 Fifty Six
57 Fifty Seven 57 Fifty Seven 57 Fifty Seven 57 Fifty Seven
58 Fifty Eight 58 Fifty Eight 58 Fifty Eight 58 Fifty Eight
59 Fifty Nine 59 Fifty Nine 59 Fifty Nine 59 Fifty Nine
60 Sixty 60 Sixty 60 Sixty 60 Sixty
61 Sixty One 61 Sixty One 61 Sixty One 61 Sixty One
62 Sixty Two 62 Sixty Two 62 Sixty Two 62 Sixty Two
63 Sixty Three 63 Sixty Three 63 Sixty Three 63 Sixty Three
64 Sixty Four 64 Sixty Four 64 Sixty Four 64 Sixty Four
65 Sixty Five 65 Sixty Five 65 Sixty Five 65 Sixty Five
66 Sixty Six 66 Sixty Six 66 Sixty Six 66 Sixty Six
67 Sixty Seven 67 Sixty Seven 67 Sixty Seven 67 Sixty Seven
68 Sixty Eight 68 Sixty Eight 68 Sixty Eight 68 Sixty Eight
69 Sixty Nine 69 Sixty Nine 69 Sixty Nine 69 Sixty Nine
70 Seventy 70 Seventy 70 Seventy 70 Seventy
71 Seventy One 71 Seventy One 71 Seventy One 71 Seventy One
72 Seventy Two 72 Seventy Two 72 Seventy Two 72 Seventy Two
73 Seventy Three 73 Seventy Three 73 Seventy Three 73 Seventy Three
74 Seventy Four 74 Seventy Four 74 Seventy Four 74 Seventy Four
75 Seventy Five 75 Seventy Five 75 Seventy Five 75 Seventy Five
76 Seventy Six 76 Seventy Six 76 Seventy Six 76 Seventy Six
77 Seventy Seven 77 Seventy Seven 77 Seventy Seven 77 Seventy Seven
78 Seventy Eight 78 Seventy Eight 78 Seventy Eight 78 Seventy Eight
79 Seventy Nine 79 Seventy Nine 79 Seventy Nine 79 Seventy Nine
80 Eighty 80 Eighty 80 Eighty 80 Eighty
81 Eighty One 81 Eighty One 81 Eighty One 81 Eighty One
82 Eighty Two 82 Eighty Two 82 Eighty Two 82 Eighty Two
83 Eighty Three 83 Eighty Three 83 Eighty Three 83 Eighty Three
84 Eighty Four 84 Eighty Four 84 Eighty Four 84 Eighty Four
85 Eighty Five 85 Eighty Five 85 Eighty Five 85 Eighty Five
86 Eighty Six 86 Eighty Six 86 Eighty Six 86 Eighty Six
87 Eighty Seven 87 Eighty Seven 87 Eighty Seven 87 Eighty Seven
88 Eighty Eight 88 Eighty Eight 88 Eighty Eight 88 Eighty Eight
89 Eighty Nine 89 Eighty Nine 89 Eighty Nine 89 Eighty Nine
90 Ninety 90 Ninety 90 Ninety 90 Ninety
91 Ninety One 91 Ninety One 91 Ninety One 91 Ninety One
92 Ninety Two 92 Ninety Two 92 Ninety Two 92 Ninety Two
93 Ninety Three 93 Ninety Three 93 Ninety Three 93 Ninety Three
94 Ninety Four 94 Ninety Four 94 Ninety Four 94 Ninety Four
95 Ninety Five 95 Ninety Five 95 Ninety Five 95 Ninety Five
96 Ninety Six 96 Ninety Six 96 Ninety Six 96 Ninety Six
97 Ninety Seven 97 Ninety Seven 97 Ninety Seven 97 Ninety Seven
98 Ninety Eight 98 Ninety Eight 98 Ninety Eight 98 Ninety Eight
99 Ninety Nine 99 Ninety Nine 99 Ninety Nine 99 Ninety Nine
100 One Hundred 100 One Hundred 100 One Hundred 100 One Hundred
23 Twenty Three
27 Twenty Seven
28 Twenty Eight
33 Thirty Three
37 Thirty Seven
38 Thirty Eight
73 Seventy Three
74 Seventy Four
75 Seventy Five
77 Seventy Seven
78 Seventy Eight
79 Seventy Nine
83 Eighty Three
87 Eighty Seven
88 Eighty Eight
93 Ninety Three
97 Ninety Seven
98 Ninety Eight
100 One Hundred
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only EURO Four Thousand Nine Hundred Sixty Only RMB Ten Thousand Three Hundred Fifty Two Only INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
85 Eighty Five 60 Sixty 52 Fifty Two 47 Forty Seven
8 Eight Hundred 9 Nine Hundred 3 Three Hundred 6 Six Hundred
55 Fifty Five Thousand 4 Four Thousand 10 Ten Thousand 91 Ninety One Thousand 0 0 0 0 0 plus
1 One Lac 0 0 6 Six Lac 0 0 0 0 1
1 One 1 One 1 One 1 One 0 0 1 0 1
2 Two 2 Two 2 Two 2 Two 0 0 1 1 0
3 Three 3 Three 3 Three 3 Three 0 0 1 1 1
4 Four 4 Four 4 Four 4 Four 0 1 0 0 0
5 Five 5 Five 5 Five 5 Five 0 1 0 0 1
6 Six 6 Six 6 Six 6 Six 0 1 0 1 0
7 Seven 7 Seven 7 Seven 7 Seven 0 1 0 1 1
8 Eight 8 Eight 8 Eight 8 Eight 0 1 1 0 0
9 Nine 9 Nine 9 Nine 9 Nine 0 1 1 0 1
10 Ten 10 Ten 10 Ten 10 Ten 0 1 1 1 0
11 Eleven 11 Eleven 11 Eleven 11 Eleven 1 1 1 1 1 USD One Lac Fifty Five Thousand Eight Hundred Eighty Five Only plus EURO Four Thousand Nine Hundred Sixty Only plus RMB Ten Thousand Three Hundred Fifty Two Only plus INR Six Lac Ninety One Thousand Six Hundred Forty Seven Only
12 Twelve 12 Twelve 12 Twelve 12 Twelve
13 Thirteen 13 Thirteen 13 Thirteen 13 Thirteen
14 Fourteen 14 Fourteen 14 Fourteen 14 Fourteen
15 Fifteen 15 Fifteen 15 Fifteen 15 Fifteen
16 Sixteen 16 Sixteen 16 Sixteen 16 Sixteen 0 0 0 0 0 +
17 Seventeen 17 Seventeen 17 Seventeen 17 Seventeen 0 0 0 0 1 /- +
18 Eighteen 18 Eighteen 18 Eighteen 18 Eighteen 0 0 0 1 0 /-
19 Nineteen 19 Nineteen 19 Nineteen 19 Nineteen 0 0 0 1 1
20 Twenty 20 Twenty 20 Twenty 20 Twenty 0 0 1 0 0
21 Twenty One 21 Twenty One 21 Twenty One 21 Twenty One 0 0 1 0 1
22 Twenty Two 22 Twenty Two 22 Twenty Two 22 Twenty Two 0 0 1 1 0
23 Twenty Three 23 Twenty Three 23 Twenty Three 23 Twenty Three 0 0 1 1 1
24 Twenty Four 24 Twenty Four 24 Twenty Four 24 Twenty Four 0 1 0 0 0
25 Twenty Five 25 Twenty Five 25 Twenty Five 25 Twenty Five 0 1 0 0 1
26 Twenty Six 26 Twenty Six 26 Twenty Six 26 Twenty Six 0 1 0 1 0
27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 27 Twenty Seven 0 1 0 1 1
28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 28 Twenty Eight 0 1 1 0 0
29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 29 Twenty Nine 0 1 1 0 1
30 Thirty 30 Thirty 30 Thirty 30 Thirty 0 1 1 1 0
31 Thirty One 31 Thirty One 31 Thirty One 31 Thirty One 1 1 1 1 1 USD 155885/- + EURO 4960/- + RMB 10352/- + INR 691647/-
32 Thirty Two 32 Thirty Two 32 Thirty Two 32 Thirty Two
33 Thirty Three 33 Thirty Three 33 Thirty Three 33 Thirty Three
34 Thirty Four 34 Thirty Four 34 Thirty Four 34 Thirty Four
35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr 35 Thirty Fivr
36 Thirty Six 36 Thirty Six 36 Thirty Six 36 Thirty Six
37 Thirty Seven 37 Thirty Seven 37 Thirty Seven 37 Thirty Seven
38 Thirty Eight 38 Thirty Eight 38 Thirty Eight 38 Thirty Eight
39 Thirty Nine 39 Thirty Nine 39 Thirty Nine 39 Thirty Nine
40 Forty 40 Forty 40 Forty 40 Forty
41 Forty One 41 Forty One 41 Forty One 41 Forty One
42 Forty Two 42 Forty Two 42 Forty Two 42 Forty Two
43 Forty Three 43 Forty Three 43 Forty Three 43 Forty Three
44 Forty Four 44 Forty Four 44 Forty Four 44 Forty Four
45 Forty Five 45 Forty Five 45 Forty Five 45 Forty Five
46 Forty Six 46 Forty Six 46 Forty Six 46 Forty Six
47 Forty Seven 47 Forty Seven 47 Forty Seven 47 Forty Seven
48 Forty Eight 48 Forty Eight 48 Forty Eight 48 Forty Eight
49 Forty Nine 49 Forty Nine 49 Forty Nine 49 Forty Nine
50 Fifty 50 Fifty 50 Fifty 50 Fifty
51 Fifty One 51 Fifty One 51 Fifty One 51 Fifty One
52 Fifty Two 52 Fifty Two 52 Fifty Two 52 Fifty Two
53 Fifty Three 53 Fifty Three 53 Fifty Three 53 Fifty Three
54 Fifty Four 54 Fifty Four 54 Fifty Four 54 Fifty Four
55 Fifty Five 55 Fifty Five 55 Fifty Five 55 Fifty Five
56 Fifty Six 56 Fifty Six 56 Fifty Six 56 Fifty Six
57 Fifty Seven 57 Fifty Seven 57 Fifty Seven 57 Fifty Seven
58 Fifty Eight 58 Fifty Eight 58 Fifty Eight 58 Fifty Eight
59 Fifty Nine 59 Fifty Nine 59 Fifty Nine 59 Fifty Nine
60 Sixty 60 Sixty 60 Sixty 60 Sixty
61 Sixty One 61 Sixty One 61 Sixty One 61 Sixty One
62 Sixty Two 62 Sixty Two 62 Sixty Two 62 Sixty Two
63 Sixty Three 63 Sixty Three 63 Sixty Three 63 Sixty Three
64 Sixty Four 64 Sixty Four 64 Sixty Four 64 Sixty Four
65 Sixty Five 65 Sixty Five 65 Sixty Five 65 Sixty Five
66 Sixty Six 66 Sixty Six 66 Sixty Six 66 Sixty Six
67 Sixty Seven 67 Sixty Seven 67 Sixty Seven 67 Sixty Seven
68 Sixty Eight 68 Sixty Eight 68 Sixty Eight 68 Sixty Eight
69 Sixty Nine 69 Sixty Nine 69 Sixty Nine 69 Sixty Nine
70 Seventy 70 Seventy 70 Seventy 70 Seventy
71 Seventy One 71 Seventy One 71 Seventy One 71 Seventy One
72 Seventy Two 72 Seventy Two 72 Seventy Two 72 Seventy Two
73 Seventy Three 73 Seventy Three 73 Seventy Three 73 Seventy Three
74 Seventy Four 74 Seventy Four 74 Seventy Four 74 Seventy Four
75 Seventy Five 75 Seventy Five 75 Seventy Five 75 Seventy Five
76 Seventy Six 76 Seventy Six 76 Seventy Six 76 Seventy Six
77 Seventy Seven 77 Seventy Seven 77 Seventy Seven 77 Seventy Seven
78 Seventy Eight 78 Seventy Eight 78 Seventy Eight 78 Seventy Eight
79 Seventy Nine 79 Seventy Nine 79 Seventy Nine 79 Seventy Nine
80 Eighty 80 Eighty 80 Eighty 80 Eighty
81 Eighty One 81 Eighty One 81 Eighty One 81 Eighty One
82 Eighty Two 82 Eighty Two 82 Eighty Two 82 Eighty Two
83 Eighty Three 83 Eighty Three 83 Eighty Three 83 Eighty Three
84 Eighty Four 84 Eighty Four 84 Eighty Four 84 Eighty Four
85 Eighty Five 85 Eighty Five 85 Eighty Five 85 Eighty Five
86 Eighty Six 86 Eighty Six 86 Eighty Six 86 Eighty Six
87 Eighty Seven 87 Eighty Seven 87 Eighty Seven 87 Eighty Seven
88 Eighty Eight 88 Eighty Eight 88 Eighty Eight 88 Eighty Eight
89 Eighty Nine 89 Eighty Nine 89 Eighty Nine 89 Eighty Nine
90 Ninety 90 Ninety 90 Ninety 90 Ninety
91 Ninety One 91 Ninety One 91 Ninety One 91 Ninety One
92 Ninety Two 92 Ninety Two 92 Ninety Two 92 Ninety Two
93 Ninety Three 93 Ninety Three 93 Ninety Three 93 Ninety Three
94 Ninety Four 94 Ninety Four 94 Ninety Four 94 Ninety Four
95 Ninety Five 95 Ninety Five 95 Ninety Five 95 Ninety Five
96 Ninety Six 96 Ninety Six 96 Ninety Six 96 Ninety Six
97 Ninety Seven 97 Ninety Seven 97 Ninety Seven 97 Ninety Seven
98 Ninety Eight 98 Ninety Eight 98 Ninety Eight 98 Ninety Eight
99 Ninety Nine 99 Ninety Nine 99 Ninety Nine 99 Ninety Nine
100 One Hundred 100 One Hundred 100 One Hundred 100 One Hundred
23 Twenty Three
27 Twenty Seven
28 Twenty Eight
33 Thirty Three
37 Thirty Seven
38 Thirty Eight
73 Seventy Three
74 Seventy Four
75 Seventy Five
77 Seventy Seven
78 Seventy Eight
79 Seventy Nine
83 Eighty Three
87 Eighty Seven
88 Eighty Eight
93 Ninety Three
97 Ninety Seven
98 Ninety Eight
100 One Hundred
Package Name Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Package Code Talcher-Kolar HVDC
Specification No. Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649
1 Fill up only green shaded cells in Sch-1, Sch-2, Sch-3, Sch-4, Sch-7 and Bid Form 2nd Envelope.
2 All the cells in Sch-5 & Sch-6 are auto filled, therefore no cell is required to be filled up there.
3 Instructions / error messages, if any, will be displayed automatically after selecting the cell.
4 After filling up all the schedues, save the file, take print out of all the schedules and Bid form and sign & stamp and submit them as hard copy of the 2nd envelope (Price part) of the bid. Also ensure to submit the soft copy of the the same file on CD/ DVD.
पावर ग्रिड कारपोरेशन ऑफ इण्डिया लिमिटेड
(भारत सरकार का उद्यम)
Power Grid Corporation of India Limited
(A Government of India Enterprises)
I While filling up the worksheets following may please be observed :
(i) Fill up only green shaded cells.
(ii) Certain data type entries have been restricted, such as Numeric values or limits of numeric values.
(iii) Select only the options provided in pull down menus.
(iv) Do not link any cell of this work book with any other work book.
(v) Do not use copy & paste or cut & paste options for filling up the data.
(vi) Do not reformat any of the cell of the work book.
II This Workbook consists of following worksheets :
Opening page of the workbook.
Names of Bidder :
● Select Sole Bidder or JV (Joint Venture) from the pull down menu. Do not leave this cell blank.
● Select nos. of the JV Partners other than the Lead Partner from drop down menu.
● In case of JV partners more than 2, enter details of 3rd & more partners along with details of 2nd partner.
● Fill up names and address of the Sole Bidder and /or Joint Venture.
● Fill up date in dd-mmm-yyyy format from drop down menu.
● Click for Sch-1 given at the right top of the worksheet to go to Sch-1.
Sch-1 (Ex-works Prices) :
● Fill up unit rates for all the items in numeric values greater than 0 (zero). If unit rate is left blank, the corresponding item shall be deemed to be included in the total price.
● Corresponding cell for mode of transaction shall be come enable only after filling up the unit rate, therefore first fill up the unit rate and then mode of transaction for the corresponding item.
● Select either Direct or Bought-out from the drop down menu. Do not leave the cell blank the same shall be deemed to be Bought-out if the cell is left blank.
● Total amount shall get calculated automatically.
● Type Test charges shall appear automatically after filling up Sch-7 appropriately.
Sch-2 (Freight & Insurance Charges) :
● Fill up unit rates for all the items in numeric values greater than 0 (zero). If unit rate is left blank, the corresponding item shall be deemed to be included in the total price.
● Total amount shall get calculated automatically.
Sch-3 (Erection Charges) :
● Fill up unit rates for all the items in numeric values greater than 0 (zero). If unit rate is left blank, the corresponding item shall be deemed to be included in the total price.
● Total amount shall get calculated automatically.
Sch-4 (Training Charges) :
● Not applicable, hence no cell is required to be filled up.
Sch-4b (Maintenance Charges during and after Defect Liability Period) :
● Not applicable, hence no cell is required to be filled up.
Sch-5 (Summary of Taxes and Duties applicable on the Goods) :
● No cell is required to be filled in by the bidder in this worksheet.
● Summary of all the Schedules without considering discount (mentioned in the work sheet discount) shall be displayed automatically.
● No cell is required to be filled in by the bidder in this worksheet.
Sch-7 (Type Test Charges) :
● Not applicable, hence no cell is required to be filled up.
Bid from 2nd Envelope :
● Fill up ref. no. as bidder's ref no. of this letter.
● This letter shall consider the net price as per Sch-6 (After Discount).
● Fill up names & Designation of the representatives of other JV partner(s) if the bidder is JV (Joint Venture) .
● Fill up additional information as required.
Happy Bidding !
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Sole Bidder 1 Sole Bidder 1
Joint Venture 2 or More JV (Joint Venture) 2 or More
Enter following details of the bidder
Specify type of Bidder [Select from drop down menu] Sole Bidder Sole Bidder 1 0 Sole Bidder 1 0
Name of Sole Bidder
Address of Sole Bidder
Name of other Partner - 1
Address of other Partner - 1
Name of other Partner - 2 (more, if any) …….. …….. …….. …….. …….. ……..
Address of other Partner - 2 (more, if any) …….. …….. …….. …….. …….. ……..
email ID of Bid Signatory
Mobile No. of Bid Signatory
Tel No. of Bid Signatory
Fax No. of Bid Signatory
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 1 Direct Total 0 Sole Bidder `
BO Total #REF! 0
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(SCHEDULE OF RATES AND PRICES)
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd., , & …….. …….. …….. …….. …….. ……..
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
PLANT AND EQUIPMENT (INCLUDING MANDATORY SPARES PARTS) TO BE SUPPLIED, INCLUDING TYPE TEST CHARGES FOR TESTS TO BE CONDUCTED Direct
All Prices are in Indian Rupees. Bought-Out
SI. No. PR No PR Line Item No Activity Description Material Code HSN Code Whether HSN in column ‘ 6 ’ is confirmed. If not indicate applicable the HSN code * Rate of GST applicable ( in %) Whether rate of GST in column ‘4’ is confirmed. If not indicate applicable rate of GST * Item Description Unit Qty. Unit Ex-works price (excluding GST) Total Ex-works price (excluding GST) GST Tax as confirmed by Bidder
A ADDCAP Talcher-Kolar HVDC Bipole-Talcher
1 10 10 Supply of Equipments at Talcher HVDC 1000052024 85049090 18 THYRISTOR VALVES FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
2 10 20 Supply of Equipments at Talcher HVDC 1000052022 85389000 18 LIGHT GUIDE FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
3 10 30 Supply of Equipments at Talcher HVDC 1000052023 85045090 18 REACTOR MODULES FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
4 10 40 Supply of Equipments at Talcher HVDC 1000052026 73043119 18 WATER TUBES FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
5 10 50 Supply of Equipments at Talcher HVDC 1000044177 85371000 18 HVDC CONTROL SYSTEMS INCLUDING CONVERTER CONTROL , AC FILTER CONTROL &AC & DC STATION CONTROL LS 1 Included 0.00 0 0.00
6 10 60 Supply of Equipments at Talcher HVDC 1000034288 85371000 18 VALVE CONTROL UNIT/VALVE BASE ELECTRONICS SYSTEM LS 1 Included 0.00 0 0.00
7 10 70 Supply of Equipments at Talcher HVDC 1000044178 85371000 18 HVDC PROTECTION SYSTEMS CONSISTING OF CONVERTER, STATION LEVELPROTECTION, AC FILTER PROTECTION, CONVERTER TRANSFORMER PROTECTION, ,SMOOTHING REACTOR PROTECTION AS PER TS LS 1 Included 0.00 0 0.00
8 10 80 Supply of Equipments at Talcher HVDC 1000034287 85371000 18 ANY OTHER PROTECTION (E.G. SUPERVISORY PROTECTION) INCULDINGINTEGRATION WORKS AT HVDC TERMINAL LS 1 Included 0.00 0 0.00
9 10 90 Supply of Equipments at Talcher HVDC 1000034285 85371000 18 STATION CONTROL AND MONITORING (SCADA ) SYSTEMS HARDWARES ANDLICENSED SOFTWARE CONSISTING OF OPERATOR& ENGINEERING WORKSTATIONS,LED DISPLAY SYSTEM, SCM SERVERS, GATEWAY SERVERS, ENGINEER SERVER,FILE SERVER FOR TFR RECORDS, ARCHIVED EVENTS AND ANALOG DATA, DIGITALDOCUMENTATION ETC. SOFTWARE COMPILER;GPS-CLOCKS FOR TIMESYNCHRONIZATION LS 1 Included 0.00 0 0.00
10 10 100 Supply of Equipments at Talcher HVDC 1000034321 90303900 18 TRANSIENT FAULT RECORDER SET 1 Included 0.00 0 0.00
11 10 110 Supply of Equipments at Talcher HVDC 1000072164 85371000 18 AC CONTROL & PROTECTION SYSTEM AS PER TS LOT 1 Included 0.00 0 0.00
12 10 120 Supply of Equipments at Talcher HVDC 1000076707 85389000 18 ON-LINE DC FAULT LOCATOR (IF STAND ALONE)-LCC LOT 1 Included 0.00 0 0.00
13 10 130 Supply of Equipments at Talcher HVDC 1000034277 85371000 18 HVDC ELECTRODE LINE MONITORING SYSTEM SET 1 Included 0.00 0 0.00
14 10 140 Supply of Equipments at Talcher HVDC 1000026582 84814000 18 HVDC Valve Cooling System SET 2 Included 0.00 0 0.00
15 10 150 Supply of Equipments at Talcher HVDC 1000034289 84814000 18 VALVE COOLING CONTROL LS 1 Included 0.00 0 0.00
16 10 160 Supply of Equipments at Talcher HVDC 1000047789 85389000 18 VALVE COOLING UPS (UMD) SYSTEM LOT 1 Included 0.00 0 0.00
17 10 170 Supply of Equipments at Talcher HVDC 1000076716 85045090 18 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included 0.00 0 0.00
18 10 180 Supply of Equipments at Talcher HVDC 1000048366 85371000 18 HVDC CURRENT MESU DEVICE SHUNT RESIST EA 4 Included 0.00 0 0.00
19 10 190 Supply of Equipments at Talcher HVDC 1000028840 85361010 18 DC Voltage Divider Along with Complete with Accessories SET 2 Included 0.00 0 0.00
20 10 200 Supply of Equipments at Talcher HVDC 1000036822 85361010 18 DC VOLTAGE DIVIDER, NEUTRAL EA 2 Included 0.00 0 0.00
21 10 210 Supply of Equipments at Talcher HVDC 1000026952 85389000 18 HVDC Neutral (Wall) Bushings SET 2 Included 0.00 0 0.00
22 10 220 Supply of Equipments at Talcher HVDC 1000041401 85369090 18 DC YARD DISCONNECTORS HVDC SET 1 Included 0.00 0 0.00
23 10 230 Supply of Equipments at Talcher HVDC 1000042198 85389000 18 HVDC GROUNDING SWITCH EA 2 Included 0.00 0 0.00
24 10 240 Supply of Equipments at Talcher HVDC 1000042211 85389000 18 LVDC GROUNDING SWITCH EA 2 Included 0.00 0 0.00
25 10 250 Supply of Equipments at Talcher HVDC 1000076653 85351090 18 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 5 Included 0.00 0 0.00
26 10 260 Supply of Equipments at Talcher HVDC 1000041405 85359090 18 ERECTION HARDWARE ITEMS FOR HVDC(LOT) LOT 1 Included 0.00 0 0.00
27 10 270 Supply of Equipments at Talcher HVDC 1000081233 85369090 18 DC YARD CLAMP AND CONNECTOR SET 1 Included 0.00 0 0.00
28 10 280 Supply of Equipments at Talcher HVDC 1000041428 72125090 18 CONDUCTORS FOR HVDC(LOT) LOT 1 Included 0.00 0 0.00
29 10 290 Supply of Equipments at Talcher HVDC 1000025980 85446020 18 Power and Control Cables LS 1 Included 0.00 0 0.00
30 10 300 Supply of Equipments at Talcher HVDC 1000036829 85030010 18 DIESEL GENERATOR SET SET 2 Included 0.00 0 0.00
31 10 310 Supply of Equipments at Talcher HVDC 1000040813 85079090 18 BATTERY SYSTEM 220V DC LOT 2 Included 0.00 0 0.00
32 10 320 Supply of Equipments at Talcher HVDC 1000040814 85079090 18 BATTERY SYSTEM 48V DC LOT 2 Included 0.00 0 0.00
33 10 330 Supply of Equipments at Talcher HVDC 1000051953 85044030 18 220V BATTERY CHARGERS AS PER TS SET 3 Included 0.00 0 0.00
34 10 340 Supply of Equipments at Talcher HVDC 1000004768 85044030 18 48V Float Cum Boost BatteryCharger as per Technical Specification EA 3 Included 0.00 0 0.00
35 10 350 Supply of Equipments at Talcher HVDC 1000004303 85371000 18 415V AC Distribution Board (ACDB) as per Technical Specification SET 2 Included 0.00 0 0.00
36 10 360 Supply of Equipments at Talcher HVDC 1000001144 85371000 18 220V DCDB SET 2 Included 0.00 0 0.00
37 10 370 Supply of Equipments at Talcher HVDC 1000004754 85371000 18 48V DCDB SET 2 Included 0.00 0 0.00
38 10 380 Supply of Equipments at Talcher HVDC 8000001866 85372000 18 O& M Test Equipment & Tools SET 1 Included 0.00 0 0.00
39 10 390 Supply of Equipments at Talcher HVDC 1000028299 76169990 18 Earthing Material as per TS LOT 2 Included 0.00 0 0.00
40 10 400 Supply of Equipments at Talcher HVDC 1000038259 84289090 18 SCISSOR LIFT EA 1 Included 0.00 0 0.00
41 10 410 Supply of Equipments at Talcher HVDC 1000081999 85371000 18 LOW VOLTAGE DC CURRENT MESURING DEVICE ST 8 Included 0.00 0 0.00
42 10 420 Supply of Equipments at Talcher HVDC 1000081990 85389000 18 HVDC WALL BUSHING ST 2 Included 0.00 0 0.00
43 10 430 Supply of Equipments at Talcher HVDC 1000081993 85351090 18 CONVERTER VALVE SURGE ARRESTERS "V" TYPE INCLUDING COUNTER ST 24 Included 0.00 0 0.00
44 10 440 Supply of Equipments at Talcher HVDC 1000081992 85351090 18 CONVERTER GROUP SURGE ARRESTERS "C" TYPE INCLUDING COUNTER ST 2 Included 0.00 0 0.00
45 10 450 Supply of Equipments at Talcher HVDC 1000081997 85351090 18 DC - HV BUS SURGE ARRESTER "D" TYPE INCLUDING COUNTER ST 4 Included 0.00 0 0.00
46 10 460 Supply of Equipments at Talcher HVDC 1000081994 85351090 18 DC - NEUTRAL BUS SURGE ARRESTER "E" TYPE INCLUDING COUNTER ST 1 Included 0.00 0 0.00
47 10 470 Supply of Equipments at Talcher HVDC 1000081995 85299090 18 DC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included 0.00 0 0.00
48 10 480 Supply of Equipments at Talcher HVDC 1000081998 85323000 18 DC NEUTRAL SURGE CAPACITOR - LVDC YARD ST 2 Included 0.00 0 0.00
49 10 490 Supply of Equipments at Talcher HVDC 1000081991 85299090 18 AC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included 0.00 0 0.00
50 10 500 Supply of Equipments at Talcher HVDC 1000062948 84281019 18 BATTERY OPERATED ARTICULATED BOOM LIFT FOR HVDC VALVE HALL EA 1 Included 0.00 0 0.00
51 10 510 Supply of Equipments at Talcher HVDC 1000081996 85369090 18 DC YARD DISCONNECTOR LVDC LOT 1 Included 0.00 0 0.00
52 10 520 Mandatory Spares at Talcher HVDC 1000072167 85042340 18 SPARES FOR THYRISTOR VALVE AS PER TS SET 1 Included 0.00 0 0.00
53 10 530 Mandatory Spares at Talcher HVDC 1000025982 85049010 18 Spare-Bushings SET 1 Included 0.00 0 0.00
54 10 540 Mandatory Spares at Talcher HVDC 1000076716 85045090 18 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included 0.00 0 0.00
55 10 550 Mandatory Spares at Talcher HVDC 1000044136 85389000 18 COMPLETE DC CURRENT TRANSFORMER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included 0.00 0 0.00
56 10 560 Mandatory Spares at Talcher HVDC 1000044048 85389000 18 DC CURRENT TRANSFORMER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1NO OF EACH TYPE AND FUNCTION] SET 1 Included 0.00 0 0.00
57 10 570 Mandatory Spares at Talcher HVDC 1000044137 85361010 18 COMPLETE DC VOLTAGE DIVIDER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included 0.00 0 0.00
58 10 580 Mandatory Spares at Talcher HVDC 1000044138 85361010 18 DC VOLTAGE DIVIDER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1 NOOF EACH TYPE AND FUNCTION] SET 1 Included 0.00 0 0.00
59 10 590 Mandatory Spares at Talcher HVDC 1000034271 85371000 18 CONTROL & PROTECTION MANDATORY & MAINTENANCE SPARE REQUIRED FOR THENEWLY SUPPLIED SYSTEM AS PER TECHNICAL SPECIFICATIONS LOT 1 Included 0.00 0 0.00
60 10 600 Mandatory Spares at Talcher HVDC 1000030816 84814000 18 VALVE COOLING EQUIPMENT -SPARE LOT 1 Included 0.00 0 0.00
61 10 610 Mandatory Spares at Talcher HVDC 1000019915 85030010 18 Spares for DG set LS 1 Included 0.00 0 0.00
62 10 620 Mandatory Spares at Talcher HVDC 1000025947 85079090 18 SPARE BATTERY AS PER TS SET 1 Included 0.00 0 0.00
63 10 630 Mandatory Spares at Talcher HVDC 1000025948 85049090 18 Spare-Battery Charger SET 1 Included 0.00 0 0.00
64 10 640 Mandatory Spares at Talcher HVDC 1000040847 94051010 18 SPARES FOR STATION UPS, AS PER ANNEXURE SET 1 Included 0.00 0 0.00
65 10 650 Mandatory Spares at Talcher HVDC 1000036865 85446020 18 SPARES FOR CABLE SYSTEM, AS PER ANNEXURE CL OF TS SET 1 Included 0.00 0 0.00
66 10 660 Mandatory Spares at Talcher HVDC 1000030803 85389000 18 ACCESSORIES/COMPONENTS FOR DC HIGH SPEED SWITCHES - SPARE FOR HVDC ASPER TS LOT 1 Included 0.00 0 0.00
67 10 670 Mandatory Spares at Talcher HVDC 1000082001 85369090 18 ACCESSORIES/COMPONENTS FOR DC YARD DISCONNECTORS AS PER TS - SPAREFOR HVDC LOT 1 Included 0.00 0 0.00
68 10 680 Mandatory Spares at Talcher HVDC 1000030818 84814000 18 ACCESSORIES/COMPONENTS FOR VALVE HALL GROUNDING SWITCH {AS PERAS PER TS LOT 1 Included 0.00 0 0.00
69 10 690 Mandatory Spares at Talcher HVDC 1000076049 85369090 18 CLAMPS AND CONNECTORS LOT 1 Included 0.00 0 0.00
70 10 700 Mandatory Spares at Talcher HVDC 1000082000 85299090 18 SPARES FOR AC AND DC PLC FILTERS EQUIPMENT AS PER TS LOT 1 Included 0.00 0 0.00
71 10 710 Mandatory Spares at Talcher HVDC 1000082002 82057000 18 SPARE - ERECTION HARDWARES - CONDUCTING LEADS & LUGS FOR CAPACITORS(10 SETS) AND 5% SPARES OF THE ACTUAL QUANTITY FOR INSULATOR STRING &HARDWARE, CLAMPS & CONNECTORS, SPACERS ETC. LOT 1 Included 0.00 0 0.00
72 10 720 Mandatory Spares at Talcher HVDC 1000082003 85311020 18 SPARES FOR VESDA / ARC / UV DETECTION AS PER TS LOT 1 Included 0.00 0 0.00
73 10 730 Mandatory Spares at Talcher HVDC 1000076653 85351090 18 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 1 Included 0.00 0 0.00
74 10 740 Mandatory Spares at Talcher HVDC 1000041401 85369090 18 DC YARD DISCONNECTORS HVDC SET 1 Included 0.00 0 0.00
75 10 750 Mandatory Spares at Talcher HVDC 1000042198 85389000 18 HVDC GROUNDING SWITCH EA 1 Included 0.00 0 0.00
76 10 760 Mandatory Spares at Talcher HVDC 1000042211 85389000 18 LVDC GROUNDING SWITCH EA 1 Included 0.00 0 0.00
77 10 770 Mandatory Spares at Talcher HVDC 1000036860 85354010 18 AC & DC SURGE ARRESTERS. [SET CONSISTS OF 3 NUMBERS OF EACH TYPE ANDRATING. FOR ARRESTERS WHERE MAIN QUANTITY IS LESS THAN OR EQUAL TO 2,1NO ARRESTOR OF EACH TYPE AND RATING SHALL BE SUPPLIED.] SET 1 Included 0.00 0 0.00
78 10 780 Mandatory Spares at Talcher HVDC 1000020440 85359090 18 Surge monitor (1-Phase) EA 5 Included 0.00 0 0.00
79 10 790 Mandatory Spares at Talcher HVDC 1000081996 85369090 18 DC YARD DISCONNECTOR LVDC LOT 1 Included 0.00 0 0.00
B ADDCAP Talcher-Kolar HVDC Bipole-Kolar 0.00 0 0.00
80 20 10 Supply of Equipment at Kolar HVDC 1000052024 85049090 18 THYRISTOR VALVES FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
81 20 20 Supply of Equipment at Kolar HVDC 1000052022 85389000 18 LIGHT GUIDE FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
82 20 30 Supply of Equipment at Kolar HVDC 1000052023 85045090 18 REACTOR MODULES FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
83 20 40 Supply of Equipment at Kolar HVDC 1000052026 73043119 18 WATER TUBES FOR QUADRIVALVE SET 6 Included 0.00 0 0.00
84 20 50 Supply of Equipment at Kolar HVDC 1000044177 85371000 18 HVDC CONTROL SYSTEMS INCLUDING CONVERTER CONTROL , AC FILTER CONTROL &AC & DC STATION CONTROL LS 1 Included 0.00 0 0.00
85 20 60 Supply of Equipment at Kolar HVDC 1000034288 85371000 18 VALVE CONTROL UNIT/VALVE BASE ELECTRONICS SYSTEM LS 1 Included 0.00 0 0.00
86 20 70 Supply of Equipment at Kolar HVDC 1000044178 85371000 18 HVDC PROTECTION SYSTEMS CONSISTING OF CONVERTER, STATION LEVELPROTECTION, AC FILTER PROTECTION, CONVERTER TRANSFORMER PROTECTION, ,SMOOTHING REACTOR PROTECTION AS PER TS LS 1 Included 0.00 0 0.00
87 20 80 Supply of Equipment at Kolar HVDC 1000034287 85371000 18 ANY OTHER PROTECTION (E.G. SUPERVISORY PROTECTION) INCULDINGINTEGRATION WORKS AT HVDC TERMINAL LS 1 Included 0.00 0 0.00
88 20 90 Supply of Equipment at Kolar HVDC 1000034285 85371000 18 STATION CONTROL AND MONITORING (SCADA ) SYSTEMS HARDWARES ANDLICENSED SOFTWARE CONSISTING OF OPERATOR& ENGINEERING WORKSTATIONS,LED DISPLAY SYSTEM, SCM SERVERS, GATEWAY SERVERS, ENGINEER SERVER,FILE SERVER FOR TFR RECORDS, ARCHIVED EVENTS AND ANALOG DATA, DIGITALDOCUMENTATION ETC. SOFTWARE COMPILER;GPS-CLOCKS FOR TIMESYNCHRONIZATION LS 1 Included 0.00 0 0.00
89 20 100 Supply of Equipment at Kolar HVDC 1000034321 90303900 18 TRANSIENT FAULT RECORDER SET 1 Included 0.00 0 0.00
90 20 110 Supply of Equipment at Kolar HVDC 1000072164 85371000 18 AC CONTROL & PROTECTION SYSTEM AS PER TS LOT 1 Included 0.00 0 0.00
91 20 120 Supply of Equipment at Kolar HVDC 1000076707 85389000 18 ON-LINE DC FAULT LOCATOR (IF STAND ALONE)-LCC LOT 1 Included 0.00 0 0.00
92 20 130 Supply of Equipment at Kolar HVDC 1000034277 85371000 18 HVDC ELECTRODE LINE MONITORING SYSTEM SET 1 Included 0.00 0 0.00
93 20 140 Supply of Equipment at Kolar HVDC 1000026582 84814000 18 HVDC Valve Cooling System SET 2 Included 0.00 0 0.00
94 20 150 Supply of Equipment at Kolar HVDC 1000034289 84814000 18 VALVE COOLING CONTROL LS 1 Included 0.00 0 0.00
95 20 160 Supply of Equipment at Kolar HVDC 1000047789 85389000 18 VALVE COOLING UPS (UMD) SYSTEM LOT 1 Included 0.00 0 0.00
96 20 170 Supply of Equipment at Kolar HVDC 1000076716 85045090 18 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included 0.00 0 0.00
97 20 180 Supply of Equipment at Kolar HVDC 1000048366 85371000 18 HVDC CURRENT MESU DEVICE SHUNT RESIST EA 4 Included 0.00 0 0.00
98 20 190 Supply of Equipment at Kolar HVDC 1000028840 85361010 18 DC Voltage Divider Along with Complete with Accessories SET 2 Included 0.00 0 0.00
99 20 200 Supply of Equipment at Kolar HVDC 1000036822 85361010 18 DC VOLTAGE DIVIDER, NEUTRAL EA 2 Included 0.00 0 0.00
100 20 210 Supply of Equipment at Kolar HVDC 1000026952 85389000 18 HVDC Neutral (Wall) Bushings SET 2 Included 0.00 0 0.00
101 20 220 Supply of Equipment at Kolar HVDC 1000041401 85369090 18 DC YARD DISCONNECTORS HVDC SET 1 Included 0.00 0 0.00
102 20 230 Supply of Equipment at Kolar HVDC 1000042198 85389000 18 HVDC GROUNDING SWITCH EA 2 Included 0.00 0 0.00
103 20 240 Supply of Equipment at Kolar HVDC 1000042211 85389000 18 LVDC GROUNDING SWITCH EA 2 Included 0.00 0 0.00
104 20 250 Supply of Equipment at Kolar HVDC 1000076653 85351090 18 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 5 Included 0.00 0 0.00
105 20 260 Supply of Equipment at Kolar HVDC 1000041405 85359090 18 ERECTION HARDWARE ITEMS FOR HVDC(LOT) LOT 1 Included 0.00 0 0.00
106 20 270 Supply of Equipment at Kolar HVDC 1000081233 85369090 18 DC YARD CLAMP AND CONNECTOR SET 1 Included 0.00 0 0.00
107 20 280 Supply of Equipment at Kolar HVDC 1000041428 72125090 18 CONDUCTORS FOR HVDC(LOT) LOT 1 Included 0.00 0 0.00
108 20 290 Supply of Equipment at Kolar HVDC 1000025980 85446020 18 Power and Control Cables LS 1 Included 0.00 0 0.00
109 20 300 Supply of Equipment at Kolar HVDC 1000036829 85030010 18 DIESEL GENERATOR SET SET 2 Included 0.00 0 0.00
110 20 310 Supply of Equipment at Kolar HVDC 1000040813 85079090 18 BATTERY SYSTEM 220V DC LOT 2 Included 0.00 0 0.00
111 20 320 Supply of Equipment at Kolar HVDC 1000040814 85079090 18 BATTERY SYSTEM 48V DC LOT 2 Included 0.00 0 0.00
112 20 330 Supply of Equipment at Kolar HVDC 1000051953 85044030 18 220V BATTERY CHARGERS AS PER TS SET 3 Included 0.00 0 0.00
113 20 340 Supply of Equipment at Kolar HVDC 1000004768 85044030 18 48V Float Cum Boost BatteryCharger as per Technical Specification EA 3 Included 0.00 0 0.00
114 20 350 Supply of Equipment at Kolar HVDC 1000004303 85371000 18 415V AC Distribution Board (ACDB) as per Technical Specification SET 2 Included 0.00 0 0.00
115 20 360 Supply of Equipment at Kolar HVDC 1000001144 85371000 18 220V DCDB SET 2 Included 0.00 0 0.00
116 20 370 Supply of Equipment at Kolar HVDC 1000004754 85371000 18 48V DCDB SET 2 Included 0.00 0 0.00
117 20 380 Supply of Equipment at Kolar HVDC 8000001866 85372000 18 O& M Test Equipment & Tools SET 1 Included 0.00 0 0.00
118 20 390 Supply of Equipment at Kolar HVDC 1000028299 76169990 18 Earthing Material as per TS LOT 2 Included 0.00 0 0.00
119 20 400 Supply of Equipment at Kolar HVDC 1000038259 84289090 18 SCISSOR LIFT EA 1 Included 0.00 0 0.00
120 20 410 Supply of Equipment at Kolar HVDC 1000081999 85371000 18 LOW VOLTAGE DC CURRENT MESURING DEVICE ST 8 Included 0.00 0 0.00
121 20 420 Supply of Equipment at Kolar HVDC 1000081990 85389000 18 HVDC WALL BUSHING ST 2 Included 0.00 0 0.00
122 20 430 Supply of Equipment at Kolar HVDC 1000081993 85351090 18 CONVERTER VALVE SURGE ARRESTERS "V" TYPE INCLUDING COUNTER ST 24 Included 0.00 0 0.00
123 20 440 Supply of Equipment at Kolar HVDC 1000081992 85351090 18 CONVERTER GROUP SURGE ARRESTERS "C" TYPE INCLUDING COUNTER ST 2 Included 0.00 0 0.00
124 20 450 Supply of Equipment at Kolar HVDC 1000081997 85351090 18 DC - HV BUS SURGE ARRESTER "D" TYPE INCLUDING COUNTER ST 4 Included 0.00 0 0.00
125 20 460 Supply of Equipment at Kolar HVDC 1000081994 85351090 18 DC - NEUTRAL BUS SURGE ARRESTER "E" TYPE INCLUDING COUNTER ST 1 Included 0.00 0 0.00
126 20 470 Supply of Equipment at Kolar HVDC 1000081995 85299090 18 DC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included 0.00 0 0.00
127 20 480 Supply of Equipment at Kolar HVDC 1000081998 85323000 18 DC NEUTRAL SURGE CAPACITOR - LVDC YARD ST 2 Included 0.00 0 0.00
128 20 490 Supply of Equipment at Kolar HVDC 1000081991 85299090 18 AC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included 0.00 0 0.00
129 20 500 Supply of Equipment at Kolar HVDC 1000062948 84281019 18 BATTERY OPERATED ARTICULATED BOOM LIFT FOR HVDC VALVE HALL EA 1 Included 0.00 0 0.00
130 20 510 Supply of Equipment at Kolar HVDC 1000081996 85369090 18 DC YARD DISCONNECTOR LVDC LOT 1 Included 0.00 0 0.00
131 20 520 Mandatory Spares at Kolar HVDC 1000072167 85042340 18 SPARES FOR THYRISTOR VALVE AS PER TS SET 1 Included 0.00 0 0.00
132 20 530 Mandatory Spares at Kolar HVDC 1000025982 85049010 18 Spare-Bushings SET 1 Included 0.00 0 0.00
133 20 540 Mandatory Spares at Kolar HVDC 1000076716 85045090 18 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included 0.00 0 0.00
134 20 550 Mandatory Spares at Kolar HVDC 1000044136 85389000 18 COMPLETE DC CURRENT TRANSFORMER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included 0.00 0 0.00
135 20 560 Mandatory Spares at Kolar HVDC 1000044048 85389000 18 DC CURRENT TRANSFORMER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1NO OF EACH TYPE AND FUNCTION] SET 1 Included 0.00 0 0.00
136 20 570 Mandatory Spares at Kolar HVDC 1000044137 85361010 18 COMPLETE DC VOLTAGE DIVIDER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included 0.00 0 0.00
137 20 580 Mandatory Spares at Kolar HVDC 1000044138 85361010 18 DC VOLTAGE DIVIDER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1 NOOF EACH TYPE AND FUNCTION] SET 1 Included 0.00 0 0.00
138 20 590 Mandatory Spares at Kolar HVDC 1000034271 85371000 18 CONTROL & PROTECTION MANDATORY & MAINTENANCE SPARE REQUIRED FOR THENEWLY SUPPLIED SYSTEM AS PER TECHNICAL SPECIFICATIONS LOT 1 Included 0.00 0 0.00
139 20 600 Mandatory Spares at Kolar HVDC 1000030816 84814000 18 VALVE COOLING EQUIPMENT -SPARE LOT 1 Included 0.00 0 0.00
140 20 610 Mandatory Spares at Kolar HVDC 1000019915 85030010 18 Spares for DG set LS 1 Included 0.00 0 0.00
141 20 620 Mandatory Spares at Kolar HVDC 1000025947 85079090 18 SPARE BATTERY AS PER TS SET 1 Included 0.00 0 0.00
142 20 630 Mandatory Spares at Kolar HVDC 1000025948 85049090 18 Spare-Battery Charger SET 1 Included 0.00 0 0.00
143 20 640 Mandatory Spares at Kolar HVDC 1000040847 94051010 18 SPARES FOR STATION UPS, AS PER ANNEXURE SET 1 Included 0.00 0 0.00
144 20 650 Mandatory Spares at Kolar HVDC 1000036865 85446020 18 SPARES FOR CABLE SYSTEM, AS PER ANNEXURE CL OF TS SET 1 Included 0.00 0 0.00
145 20 660 Mandatory Spares at Kolar HVDC 1000030803 85389000 18 ACCESSORIES/COMPONENTS FOR DC HIGH SPEED SWITCHES - SPARE FOR HVDC ASPER TS LOT 1 Included 0.00 0 0.00
146 20 670 Mandatory Spares at Kolar HVDC 1000082001 85369090 18 ACCESSORIES/COMPONENTS FOR DC YARD DISCONNECTORS AS PER TS - SPAREFOR HVDC LOT 1 Included 0.00 0 0.00
147 20 680 Mandatory Spares at Kolar HVDC 1000030818 84814000 18 ACCESSORIES/COMPONENTS FOR VALVE HALL GROUNDING SWITCH {AS PERAS PER TS LOT 1 Included 0.00 0 0.00
148 20 690 Mandatory Spares at Kolar HVDC 1000076049 85369090 18 CLAMPS AND CONNECTORS LOT 1 Included 0.00 0 0.00
149 20 700 Mandatory Spares at Kolar HVDC 1000082000 85299090 18 SPARES FOR AC AND DC PLC FILTERS EQUIPMENT AS PER TS LOT 1 Included 0.00 0 0.00
150 20 710 Mandatory Spares at Kolar HVDC 1000082002 82057000 18 SPARE - ERECTION HARDWARES - CONDUCTING LEADS & LUGS FOR CAPACITORS(10 SETS) AND 5% SPARES OF THE ACTUAL QUANTITY FOR INSULATOR STRING &HARDWARE, CLAMPS & CONNECTORS, SPACERS ETC. LOT 1 Included 0.00 0 0.00
151 20 720 Mandatory Spares at Kolar HVDC 1000082003 85311020 18 SPARES FOR VESDA / ARC / UV DETECTION AS PER TS LOT 1 Included 0.00 0 0.00
152 20 730 Mandatory Spares at Kolar HVDC 1000076653 85351090 18 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 1 Included 0.00 0 0.00
153 20 740 Mandatory Spares at Kolar HVDC 1000041401 85369090 18 DC YARD DISCONNECTORS HVDC SET 1 Included 0.00 0 0.00
154 20 750 Mandatory Spares at Kolar HVDC 1000042198 85389000 18 HVDC GROUNDING SWITCH EA 2 Included 0.00 0 0.00
155 20 760 Mandatory Spares at Kolar HVDC 1000042211 85389000 18 LVDC GROUNDING SWITCH EA 2 Included 0.00 0 0.00
156 20 770 Mandatory Spares at Kolar HVDC 1000036860 85354010 18 AC & DC SURGE ARRESTERS. [SET CONSISTS OF 3 NUMBERS OF EACH TYPE ANDRATING. FOR ARRESTERS WHERE MAIN QUANTITY IS LESS THAN OR EQUAL TO 2,1NO ARRESTOR OF EACH TYPE AND RATING SHALL BE SUPPLIED.] SET 1 Included 0.00 0 0.00
157 20 780 Mandatory Spares at Kolar HVDC 1000020440 85359090 18 Surge monitor (1-Phase) EA 5 Included 0.00 0 0.00
158 20 790 Mandatory Spares at Kolar HVDC 1000082000 85299090 18 SPARES FOR AC AND DC PLC FILTERS EQUIPMENT AS PER TS LOT 1 Included 0.00 0 0.00
159 20 800 Mandatory Spares at Kolar HVDC 1000081996 85369090 18 DC YARD DISCONNECTOR LVDC LOT 1 Included 0.00 0 0.00
Total Ex-works Price 0.00 0.00
Total Type Test charges as per Schedule-7 0.00
Total Ex-works Price including Type Test charges 0.00
Total GST Tax as confirmed by Bidder 0.00
Note : Specify amount of GST on the transaction between the Contractor and the Employer.
* In case the bidder leaves the cell for confirmation of the HSN code and/or GST rate “blank”, the HSN code and corresponding GST rate indicated by the Employer shall be deemed to be the one confirmed by the Bidder.
Place : Printed Name :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 1 Direct Total 0 Sole Bidder `
BO Total #REF! 0
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(SCHEDULE OF RATES AND PRICES : EX-WORKS PRICES)
Bidder’s Name and Address (Sole Bidder) : To:
Contract Services
Name : Power Grid Corporation of India Ltd., , & …….. …….. …….. …….. …….. ……..
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
Plant and Equipment (including Mandatory Spares Parts) to be supplied, including Type Test Charges for Tests to be conducted. Direct
All Prices are in Indian Rupees. Bought-Out
SI. No. Item Description Unit Qty. Unit Ex-works price Total Ex-works price Mode of Transaction (Direct / Bought-out)
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
Total Ex-Works Price Direct 0.00 Direct
Total Ex-Works Price Bought Out 0.00
Total Ex-Works Price 0.00
Total Type Test charges as per Schedule-7 #REF! #REF! #REF!
Total Ex-works Price including Type Test charges #REF! #REF! #REF!
Discount Sch-1 #REF! MPD Sch-1 #REF!
Dis Alert #REF!
Note : Specify amount of Excise Duty, Sales Tax/'VAT and other taxes payable on the transaction between the Contractor and the Employer and octroi/entry tax as applicable for destination site/state on all items of supply including bought-out finished items (to be identified in the Contract), which shall be dispatched directly from the sub-vendor’s works to the Employer’s site (sale-in-transit), separately in Schedule-5. Excise Duty, Sales tax and other levies for all the bought-out items are to be included in the EXW Price (Col. No. 5) only and not to be indicated in Schedule-5.
Place : Printed Name :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 2
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(SCHEDULE OF RATES AND PRICES)
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
LOCAL TRANSPORTATION, IN-TRANSIT INSURANCE, LOADING AND UNLOADING
All Prices are in Indian Rupees.
SI. No. PR No PR Line Item No Activity Description Material Code Description Unit Quantity Unit Freight, In-transit Insurance, loading & unloading Charges Total Freight, In-transit Insurance, loading & unloading Charges
PART A (Substation Portion)
A ADDCAP Talcher-Kolar HVDC Bipole-Talcher
1 10 10 Supply of Equipments at Talcher HVDC 1000052024 THYRISTOR VALVES FOR QUADRIVALVE SET 6 Included
2 10 20 Supply of Equipments at Talcher HVDC 1000052022 LIGHT GUIDE FOR QUADRIVALVE SET 6 Included
3 10 30 Supply of Equipments at Talcher HVDC 1000052023 REACTOR MODULES FOR QUADRIVALVE SET 6 Included
4 10 40 Supply of Equipments at Talcher HVDC 1000052026 WATER TUBES FOR QUADRIVALVE SET 6 Included
5 10 50 Supply of Equipments at Talcher HVDC 1000044177 HVDC CONTROL SYSTEMS INCLUDING CONVERTER CONTROL , AC FILTER CONTROL &AC & DC STATION CONTROL LS 1 Included
6 10 60 Supply of Equipments at Talcher HVDC 1000034288 VALVE CONTROL UNIT/VALVE BASE ELECTRONICS SYSTEM LS 1 Included
7 10 70 Supply of Equipments at Talcher HVDC 1000044178 HVDC PROTECTION SYSTEMS CONSISTING OF CONVERTER, STATION LEVELPROTECTION, AC FILTER PROTECTION, CONVERTER TRANSFORMER PROTECTION, ,SMOOTHING REACTOR PROTECTION AS PER TS LS 1 Included
8 10 80 Supply of Equipments at Talcher HVDC 1000034287 ANY OTHER PROTECTION (E.G. SUPERVISORY PROTECTION) INCULDINGINTEGRATION WORKS AT HVDC TERMINAL LS 1 Included
9 10 90 Supply of Equipments at Talcher HVDC 1000034285 STATION CONTROL AND MONITORING (SCADA ) SYSTEMS HARDWARES ANDLICENSED SOFTWARE CONSISTING OF OPERATOR& ENGINEERING WORKSTATIONS,LED DISPLAY SYSTEM, SCM SERVERS, GATEWAY SERVERS, ENGINEER SERVER,FILE SERVER FOR TFR RECORDS, ARCHIVED EVENTS AND ANALOG DATA, DIGITALDOCUMENTATION ETC. SOFTWARE COMPILER;GPS-CLOCKS FOR TIMESYNCHRONIZATION LS 1 Included
10 10 100 Supply of Equipments at Talcher HVDC 1000034321 TRANSIENT FAULT RECORDER SET 1 Included
11 10 110 Supply of Equipments at Talcher HVDC 1000072164 AC CONTROL & PROTECTION SYSTEM AS PER TS LOT 1 Included
12 10 120 Supply of Equipments at Talcher HVDC 1000076707 ON-LINE DC FAULT LOCATOR (IF STAND ALONE)-LCC LOT 1 Included
13 10 130 Supply of Equipments at Talcher HVDC 1000034277 HVDC ELECTRODE LINE MONITORING SYSTEM SET 1 Included
14 10 140 Supply of Equipments at Talcher HVDC 1000026582 HVDC Valve Cooling System SET 2 Included
15 10 150 Supply of Equipments at Talcher HVDC 1000034289 VALVE COOLING CONTROL LS 1 Included
16 10 160 Supply of Equipments at Talcher HVDC 1000047789 VALVE COOLING UPS (UMD) SYSTEM LOT 1 Included
17 10 170 Supply of Equipments at Talcher HVDC 1000076716 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included
18 10 180 Supply of Equipments at Talcher HVDC 1000048366 HVDC CURRENT MESU DEVICE SHUNT RESIST EA 4 Included
19 10 190 Supply of Equipments at Talcher HVDC 1000028840 DC Voltage Divider Along with Complete with Accessories SET 2 Included
20 10 200 Supply of Equipments at Talcher HVDC 1000036822 DC VOLTAGE DIVIDER, NEUTRAL EA 2 Included
21 10 210 Supply of Equipments at Talcher HVDC 1000026952 HVDC Neutral (Wall) Bushings SET 2 Included
22 10 220 Supply of Equipments at Talcher HVDC 1000041401 DC YARD DISCONNECTORS HVDC SET 1 Included
23 10 230 Supply of Equipments at Talcher HVDC 1000042198 HVDC GROUNDING SWITCH EA 2 Included
24 10 240 Supply of Equipments at Talcher HVDC 1000042211 LVDC GROUNDING SWITCH EA 2 Included
25 10 250 Supply of Equipments at Talcher HVDC 1000076653 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 5 Included
26 10 260 Supply of Equipments at Talcher HVDC 1000041405 ERECTION HARDWARE ITEMS FOR HVDC(LOT) LOT 1 Included
27 10 270 Supply of Equipments at Talcher HVDC 1000081233 DC YARD CLAMP AND CONNECTOR SET 1 Included
28 10 280 Supply of Equipments at Talcher HVDC 1000041428 CONDUCTORS FOR HVDC(LOT) LOT 1 Included
29 10 290 Supply of Equipments at Talcher HVDC 1000025980 Power and Control Cables LS 1 Included
30 10 300 Supply of Equipments at Talcher HVDC 1000036829 DIESEL GENERATOR SET SET 2 Included
31 10 310 Supply of Equipments at Talcher HVDC 1000040813 BATTERY SYSTEM 220V DC LOT 2 Included
32 10 320 Supply of Equipments at Talcher HVDC 1000040814 BATTERY SYSTEM 48V DC LOT 2 Included
33 10 330 Supply of Equipments at Talcher HVDC 1000051953 220V BATTERY CHARGERS AS PER TS SET 3 Included
34 10 340 Supply of Equipments at Talcher HVDC 1000004768 48V Float Cum Boost BatteryCharger as per Technical Specification EA 3 Included
35 10 350 Supply of Equipments at Talcher HVDC 1000004303 415V AC Distribution Board (ACDB) as per Technical Specification SET 2 Included
36 10 360 Supply of Equipments at Talcher HVDC 1000001144 220V DCDB SET 2 Included
37 10 370 Supply of Equipments at Talcher HVDC 1000004754 48V DCDB SET 2 Included
38 10 380 Supply of Equipments at Talcher HVDC 8000001866 O& M Test Equipment & Tools SET 1 Included
39 10 390 Supply of Equipments at Talcher HVDC 1000028299 Earthing Material as per TS LOT 2 Included
40 10 400 Supply of Equipments at Talcher HVDC 1000038259 SCISSOR LIFT EA 1 Included
41 10 410 Supply of Equipments at Talcher HVDC 1000081999 LOW VOLTAGE DC CURRENT MESURING DEVICE ST 8 Included
42 10 420 Supply of Equipments at Talcher HVDC 1000081990 HVDC WALL BUSHING ST 2 Included
43 10 430 Supply of Equipments at Talcher HVDC 1000081993 CONVERTER VALVE SURGE ARRESTERS "V" TYPE INCLUDING COUNTER ST 24 Included
44 10 440 Supply of Equipments at Talcher HVDC 1000081992 CONVERTER GROUP SURGE ARRESTERS "C" TYPE INCLUDING COUNTER ST 2 Included
45 10 450 Supply of Equipments at Talcher HVDC 1000081997 DC - HV BUS SURGE ARRESTER "D" TYPE INCLUDING COUNTER ST 4 Included
46 10 460 Supply of Equipments at Talcher HVDC 1000081994 DC - NEUTRAL BUS SURGE ARRESTER "E" TYPE INCLUDING COUNTER ST 1 Included
47 10 470 Supply of Equipments at Talcher HVDC 1000081995 DC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included
48 10 480 Supply of Equipments at Talcher HVDC 1000081998 DC NEUTRAL SURGE CAPACITOR - LVDC YARD ST 2 Included
49 10 490 Supply of Equipments at Talcher HVDC 1000081991 AC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included
50 10 500 Supply of Equipments at Talcher HVDC 1000062948 BATTERY OPERATED ARTICULATED BOOM LIFT FOR HVDC VALVE HALL EA 1 Included
51 10 510 Supply of Equipments at Talcher HVDC 1000081996 DC YARD DISCONNECTOR LVDC LOT 1 Included
52 10 520 Mandatory Spares at Talcher HVDC 1000072167 SPARES FOR THYRISTOR VALVE AS PER TS SET 1 Included
53 10 530 Mandatory Spares at Talcher HVDC 1000025982 Spare-Bushings SET 1 Included
54 10 540 Mandatory Spares at Talcher HVDC 1000076716 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included
55 10 550 Mandatory Spares at Talcher HVDC 1000044136 COMPLETE DC CURRENT TRANSFORMER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included
56 10 560 Mandatory Spares at Talcher HVDC 1000044048 DC CURRENT TRANSFORMER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1NO OF EACH TYPE AND FUNCTION] SET 1 Included
57 10 570 Mandatory Spares at Talcher HVDC 1000044137 COMPLETE DC VOLTAGE DIVIDER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included
58 10 580 Mandatory Spares at Talcher HVDC 1000044138 DC VOLTAGE DIVIDER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1 NOOF EACH TYPE AND FUNCTION] SET 1 Included
59 10 590 Mandatory Spares at Talcher HVDC 1000034271 CONTROL & PROTECTION MANDATORY & MAINTENANCE SPARE REQUIRED FOR THENEWLY SUPPLIED SYSTEM AS PER TECHNICAL SPECIFICATIONS LOT 1 Included
60 10 600 Mandatory Spares at Talcher HVDC 1000030816 VALVE COOLING EQUIPMENT -SPARE LOT 1 Included
61 10 610 Mandatory Spares at Talcher HVDC 1000019915 Spares for DG set LS 1 Included
62 10 620 Mandatory Spares at Talcher HVDC 1000025947 SPARE BATTERY AS PER TS SET 1 Included
63 10 630 Mandatory Spares at Talcher HVDC 1000025948 Spare-Battery Charger SET 1 Included
64 10 640 Mandatory Spares at Talcher HVDC 1000040847 SPARES FOR STATION UPS, AS PER ANNEXURE SET 1 Included
65 10 650 Mandatory Spares at Talcher HVDC 1000036865 SPARES FOR CABLE SYSTEM, AS PER ANNEXURE CL OF TS SET 1 Included
66 10 660 Mandatory Spares at Talcher HVDC 1000030803 ACCESSORIES/COMPONENTS FOR DC HIGH SPEED SWITCHES - SPARE FOR HVDC ASPER TS LOT 1 Included
67 10 670 Mandatory Spares at Talcher HVDC 1000082001 ACCESSORIES/COMPONENTS FOR DC YARD DISCONNECTORS AS PER TS - SPAREFOR HVDC LOT 1 Included
68 10 680 Mandatory Spares at Talcher HVDC 1000030818 ACCESSORIES/COMPONENTS FOR VALVE HALL GROUNDING SWITCH {AS PERAS PER TS LOT 1 Included
69 10 690 Mandatory Spares at Talcher HVDC 1000076049 CLAMPS AND CONNECTORS LOT 1 Included
70 10 700 Mandatory Spares at Talcher HVDC 1000082000 SPARES FOR AC AND DC PLC FILTERS EQUIPMENT AS PER TS LOT 1 Included
71 10 710 Mandatory Spares at Talcher HVDC 1000082002 SPARE - ERECTION HARDWARES - CONDUCTING LEADS & LUGS FOR CAPACITORS(10 SETS) AND 5% SPARES OF THE ACTUAL QUANTITY FOR INSULATOR STRING &HARDWARE, CLAMPS & CONNECTORS, SPACERS ETC. LOT 1 Included
72 10 720 Mandatory Spares at Talcher HVDC 1000082003 SPARES FOR VESDA / ARC / UV DETECTION AS PER TS LOT 1 Included
73 10 730 Mandatory Spares at Talcher HVDC 1000076653 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 1 Included
74 10 740 Mandatory Spares at Talcher HVDC 1000041401 DC YARD DISCONNECTORS HVDC SET 1 Included
75 10 750 Mandatory Spares at Talcher HVDC 1000042198 HVDC GROUNDING SWITCH EA 1 Included
76 10 760 Mandatory Spares at Talcher HVDC 1000042211 LVDC GROUNDING SWITCH EA 1 Included
77 10 770 Mandatory Spares at Talcher HVDC 1000036860 AC & DC SURGE ARRESTERS. [SET CONSISTS OF 3 NUMBERS OF EACH TYPE ANDRATING. FOR ARRESTERS WHERE MAIN QUANTITY IS LESS THAN OR EQUAL TO 2,1NO ARRESTOR OF EACH TYPE AND RATING SHALL BE SUPPLIED.] SET 1 Included
78 10 780 Mandatory Spares at Talcher HVDC 1000020440 Surge monitor (1-Phase) EA 5 Included
79 10 790 Mandatory Spares at Talcher HVDC 1000081996 DC YARD DISCONNECTOR LVDC LOT 1 Included
B ADDCAP Talcher-Kolar HVDC Bipole-Kolar
80 20 10 Supply of Equipment at Kolar HVDC 1000052024 THYRISTOR VALVES FOR QUADRIVALVE SET 6 Included
81 20 20 Supply of Equipment at Kolar HVDC 1000052022 LIGHT GUIDE FOR QUADRIVALVE SET 6 Included
82 20 30 Supply of Equipment at Kolar HVDC 1000052023 REACTOR MODULES FOR QUADRIVALVE SET 6 Included
83 20 40 Supply of Equipment at Kolar HVDC 1000052026 WATER TUBES FOR QUADRIVALVE SET 6 Included
84 20 50 Supply of Equipment at Kolar HVDC 1000044177 HVDC CONTROL SYSTEMS INCLUDING CONVERTER CONTROL , AC FILTER CONTROL &AC & DC STATION CONTROL LS 1 Included
85 20 60 Supply of Equipment at Kolar HVDC 1000034288 VALVE CONTROL UNIT/VALVE BASE ELECTRONICS SYSTEM LS 1 Included
86 20 70 Supply of Equipment at Kolar HVDC 1000044178 HVDC PROTECTION SYSTEMS CONSISTING OF CONVERTER, STATION LEVELPROTECTION, AC FILTER PROTECTION, CONVERTER TRANSFORMER PROTECTION, ,SMOOTHING REACTOR PROTECTION AS PER TS LS 1 Included
87 20 80 Supply of Equipment at Kolar HVDC 1000034287 ANY OTHER PROTECTION (E.G. SUPERVISORY PROTECTION) INCULDINGINTEGRATION WORKS AT HVDC TERMINAL LS 1 Included
88 20 90 Supply of Equipment at Kolar HVDC 1000034285 STATION CONTROL AND MONITORING (SCADA ) SYSTEMS HARDWARES ANDLICENSED SOFTWARE CONSISTING OF OPERATOR& ENGINEERING WORKSTATIONS,LED DISPLAY SYSTEM, SCM SERVERS, GATEWAY SERVERS, ENGINEER SERVER,FILE SERVER FOR TFR RECORDS, ARCHIVED EVENTS AND ANALOG DATA, DIGITALDOCUMENTATION ETC. SOFTWARE COMPILER;GPS-CLOCKS FOR TIMESYNCHRONIZATION LS 1 Included
89 20 100 Supply of Equipment at Kolar HVDC 1000034321 TRANSIENT FAULT RECORDER SET 1 Included
90 20 110 Supply of Equipment at Kolar HVDC 1000072164 AC CONTROL & PROTECTION SYSTEM AS PER TS LOT 1 Included
91 20 120 Supply of Equipment at Kolar HVDC 1000076707 ON-LINE DC FAULT LOCATOR (IF STAND ALONE)-LCC LOT 1 Included
92 20 130 Supply of Equipment at Kolar HVDC 1000034277 HVDC ELECTRODE LINE MONITORING SYSTEM SET 1 Included
93 20 140 Supply of Equipment at Kolar HVDC 1000026582 HVDC Valve Cooling System SET 2 Included
94 20 150 Supply of Equipment at Kolar HVDC 1000034289 VALVE COOLING CONTROL LS 1 Included
95 20 160 Supply of Equipment at Kolar HVDC 1000047789 VALVE COOLING UPS (UMD) SYSTEM LOT 1 Included
96 20 170 Supply of Equipment at Kolar HVDC 1000076716 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included
97 20 180 Supply of Equipment at Kolar HVDC 1000048366 HVDC CURRENT MESU DEVICE SHUNT RESIST EA 4 Included
98 20 190 Supply of Equipment at Kolar HVDC 1000028840 DC Voltage Divider Along with Complete with Accessories SET 2 Included
99 20 200 Supply of Equipment at Kolar HVDC 1000036822 DC VOLTAGE DIVIDER, NEUTRAL EA 2 Included
100 20 210 Supply of Equipment at Kolar HVDC 1000026952 HVDC Neutral (Wall) Bushings SET 2 Included
101 20 220 Supply of Equipment at Kolar HVDC 1000041401 DC YARD DISCONNECTORS HVDC SET 1 Included
102 20 230 Supply of Equipment at Kolar HVDC 1000042198 HVDC GROUNDING SWITCH EA 2 Included
103 20 240 Supply of Equipment at Kolar HVDC 1000042211 LVDC GROUNDING SWITCH EA 2 Included
104 20 250 Supply of Equipment at Kolar HVDC 1000076653 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 5 Included
105 20 260 Supply of Equipment at Kolar HVDC 1000041405 ERECTION HARDWARE ITEMS FOR HVDC(LOT) LOT 1 Included
106 20 270 Supply of Equipment at Kolar HVDC 1000081233 DC YARD CLAMP AND CONNECTOR SET 1 Included
107 20 280 Supply of Equipment at Kolar HVDC 1000041428 CONDUCTORS FOR HVDC(LOT) LOT 1 Included
108 20 290 Supply of Equipment at Kolar HVDC 1000025980 Power and Control Cables LS 1 Included
109 20 300 Supply of Equipment at Kolar HVDC 1000036829 DIESEL GENERATOR SET SET 2 Included
110 20 310 Supply of Equipment at Kolar HVDC 1000040813 BATTERY SYSTEM 220V DC LOT 2 Included
111 20 320 Supply of Equipment at Kolar HVDC 1000040814 BATTERY SYSTEM 48V DC LOT 2 Included
112 20 330 Supply of Equipment at Kolar HVDC 1000051953 220V BATTERY CHARGERS AS PER TS SET 3 Included
113 20 340 Supply of Equipment at Kolar HVDC 1000004768 48V Float Cum Boost BatteryCharger as per Technical Specification EA 3 Included
114 20 350 Supply of Equipment at Kolar HVDC 1000004303 415V AC Distribution Board (ACDB) as per Technical Specification SET 2 Included
115 20 360 Supply of Equipment at Kolar HVDC 1000001144 220V DCDB SET 2 Included
116 20 370 Supply of Equipment at Kolar HVDC 1000004754 48V DCDB SET 2 Included
117 20 380 Supply of Equipment at Kolar HVDC 8000001866 O& M Test Equipment & Tools SET 1 Included
118 20 390 Supply of Equipment at Kolar HVDC 1000028299 Earthing Material as per TS LOT 2 Included
119 20 400 Supply of Equipment at Kolar HVDC 1000038259 SCISSOR LIFT EA 1 Included
120 20 410 Supply of Equipment at Kolar HVDC 1000081999 LOW VOLTAGE DC CURRENT MESURING DEVICE ST 8 Included
121 20 420 Supply of Equipment at Kolar HVDC 1000081990 HVDC WALL BUSHING ST 2 Included
122 20 430 Supply of Equipment at Kolar HVDC 1000081993 CONVERTER VALVE SURGE ARRESTERS "V" TYPE INCLUDING COUNTER ST 24 Included
123 20 440 Supply of Equipment at Kolar HVDC 1000081992 CONVERTER GROUP SURGE ARRESTERS "C" TYPE INCLUDING COUNTER ST 2 Included
124 20 450 Supply of Equipment at Kolar HVDC 1000081997 DC - HV BUS SURGE ARRESTER "D" TYPE INCLUDING COUNTER ST 4 Included
125 20 460 Supply of Equipment at Kolar HVDC 1000081994 DC - NEUTRAL BUS SURGE ARRESTER "E" TYPE INCLUDING COUNTER ST 1 Included
126 20 470 Supply of Equipment at Kolar HVDC 1000081995 DC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included
127 20 480 Supply of Equipment at Kolar HVDC 1000081998 DC NEUTRAL SURGE CAPACITOR - LVDC YARD ST 2 Included
128 20 490 Supply of Equipment at Kolar HVDC 1000081991 AC PLC FILTERS EQUIPMENT INCLUDING FILTER CAPACITOR, FILTER REACTOR,TUNIG DEVICE, SUPPORT INSULATORS ETC. ST 2 Included
129 20 500 Supply of Equipment at Kolar HVDC 1000062948 BATTERY OPERATED ARTICULATED BOOM LIFT FOR HVDC VALVE HALL EA 1 Included
130 20 510 Supply of Equipment at Kolar HVDC 1000081996 DC YARD DISCONNECTOR LVDC LOT 1 Included
131 20 520 Mandatory Spares at Kolar HVDC 1000072167 SPARES FOR THYRISTOR VALVE AS PER TS SET 1 Included
132 20 530 Mandatory Spares at Kolar HVDC 1000025982 Spare-Bushings SET 1 Included
133 20 540 Mandatory Spares at Kolar HVDC 1000076716 POLE BUS SMOOTHING REACTOR ALONG WITH INSULATORS, ACCESSORIES,COMPLETE IN ALL RESPECT (LOT) LOT 1 Included
134 20 550 Mandatory Spares at Kolar HVDC 1000044136 COMPLETE DC CURRENT TRANSFORMER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included
135 20 560 Mandatory Spares at Kolar HVDC 1000044048 DC CURRENT TRANSFORMER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1NO OF EACH TYPE AND FUNCTION] SET 1 Included
136 20 570 Mandatory Spares at Kolar HVDC 1000044137 COMPLETE DC VOLTAGE DIVIDER ALONG WITH ALL ACCESSORIES INCLUDINGELECTRONICS [SET CONSISTS OF 1 COMPLETE SET OF UNITS TO MAKE ONE NO.OF EACH TYPE AND RATING] SET 1 Included
137 20 580 Mandatory Spares at Kolar HVDC 1000044138 DC VOLTAGE DIVIDER ACCESSORIES & ELECTRONICS [SET CONSISTS OF 1 NOOF EACH TYPE AND FUNCTION] SET 1 Included
138 20 590 Mandatory Spares at Kolar HVDC 1000034271 CONTROL & PROTECTION MANDATORY & MAINTENANCE SPARE REQUIRED FOR THENEWLY SUPPLIED SYSTEM AS PER TECHNICAL SPECIFICATIONS LOT 1 Included
139 20 600 Mandatory Spares at Kolar HVDC 1000030816 VALVE COOLING EQUIPMENT -SPARE LOT 1 Included
140 20 610 Mandatory Spares at Kolar HVDC 1000019915 Spares for DG set LS 1 Included
141 20 620 Mandatory Spares at Kolar HVDC 1000025947 SPARE BATTERY AS PER TS SET 1 Included
142 20 630 Mandatory Spares at Kolar HVDC 1000025948 Spare-Battery Charger SET 1 Included
143 20 640 Mandatory Spares at Kolar HVDC 1000040847 SPARES FOR STATION UPS, AS PER ANNEXURE SET 1 Included
144 20 650 Mandatory Spares at Kolar HVDC 1000036865 SPARES FOR CABLE SYSTEM, AS PER ANNEXURE CL OF TS SET 1 Included
145 20 660 Mandatory Spares at Kolar HVDC 1000030803 ACCESSORIES/COMPONENTS FOR DC HIGH SPEED SWITCHES - SPARE FOR HVDC ASPER TS LOT 1 Included
146 20 670 Mandatory Spares at Kolar HVDC 1000082001 ACCESSORIES/COMPONENTS FOR DC YARD DISCONNECTORS AS PER TS - SPAREFOR HVDC LOT 1 Included
147 20 680 Mandatory Spares at Kolar HVDC 1000030818 ACCESSORIES/COMPONENTS FOR VALVE HALL GROUNDING SWITCH {AS PERAS PER TS LOT 1 Included
148 20 690 Mandatory Spares at Kolar HVDC 1000076049 CLAMPS AND CONNECTORS LOT 1 Included
149 20 700 Mandatory Spares at Kolar HVDC 1000082000 SPARES FOR AC AND DC PLC FILTERS EQUIPMENT AS PER TS LOT 1 Included
150 20 710 Mandatory Spares at Kolar HVDC 1000082002 SPARE - ERECTION HARDWARES - CONDUCTING LEADS & LUGS FOR CAPACITORS(10 SETS) AND 5% SPARES OF THE ACTUAL QUANTITY FOR INSULATOR STRING &HARDWARE, CLAMPS & CONNECTORS, SPACERS ETC. LOT 1 Included
151 20 720 Mandatory Spares at Kolar HVDC 1000082003 SPARES FOR VESDA / ARC / UV DETECTION AS PER TS LOT 1 Included
152 20 730 Mandatory Spares at Kolar HVDC 1000076653 DC POLE HIGH SPEED SWITCH ALONG WITH ALL ACCESSORIES COMPLETE IN ALLRESPECT SET 1 Included
153 20 740 Mandatory Spares at Kolar HVDC 1000041401 DC YARD DISCONNECTORS HVDC SET 1 Included
154 20 750 Mandatory Spares at Kolar HVDC 1000042198 HVDC GROUNDING SWITCH EA 2 Included
155 20 760 Mandatory Spares at Kolar HVDC 1000042211 LVDC GROUNDING SWITCH EA 2 Included
156 20 770 Mandatory Spares at Kolar HVDC 1000036860 AC & DC SURGE ARRESTERS. [SET CONSISTS OF 3 NUMBERS OF EACH TYPE ANDRATING. FOR ARRESTERS WHERE MAIN QUANTITY IS LESS THAN OR EQUAL TO 2,1NO ARRESTOR OF EACH TYPE AND RATING SHALL BE SUPPLIED.] SET 1 Included
157 20 780 Mandatory Spares at Kolar HVDC 1000020440 Surge monitor (1-Phase) EA 5 Included
158 20 790 Mandatory Spares at Kolar HVDC 1000082000 SPARES FOR AC AND DC PLC FILTERS EQUIPMENT AS PER TS LOT 1 Included
159 20 800 Mandatory Spares at Kolar HVDC 1000081996 DC YARD DISCONNECTOR LVDC LOT 1 Included
Total F&I Price 0.00
Date: -- Printed Name :
Place: Designation :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 2 Dis
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) As per Lum-sum 0
(SCHEDULE OF RATES AND PRICES : FREIGHT & INSURANCE CHARGES) AS per Percent #REF!
As per lum-sum on Sch-2 0.00%
Bidder’s Name and Address (Sole Bidder) : To: As per Percent on Sch-2 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Sector-29, Multipackage Discount 0.00%
Gurgaon (Haryana) - 122001
All Prices are in Indian Rupees. Amount after Discount (Rs.) Dis Alert Amount after MPD (Rs.)
SI. No. Description Unit Quantity Unit Freight & Insurance Charges Total Freight & Insurance Charges Unit Freight & Insurance Charges Total Freight & Insurance Charges Unit Freight & Insurance Charges Total Freight & Insurance Charges
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
Total F&I Price #REF!
Place : Printed Name :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 3
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES ) AS per Percent #REF!
As per lum-sum on Sch-3 0.00%
Bidder’s Name and Address (Sole Bidder) : To: As per Percent on Sch-3 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Sector-29, Multipackage lum-sum 0.00%
Gurgaon (Haryana) - 122001
INSTALLATION CHARGES Amount after Discount (Rs.) Dis Alert Amount after MPD (Rs.)
All Prices are in Indian Rupees.
SI. No. PR No PR Line Item No Activity Header PR Activity No Activity Description Service Code SAC (Service Accounting Codes) Whether SAC in column '8’ is confirmed. If not indicate applicable the SAC * Rate of GST applicable ( in %) Whether rate of GST in column ‘4’ is confirmed. If not indicate applicable rate of GST * Description Unit Quantity Unit Erection Charges Total Erection Charges Total GST as confirmed by Bidder Unit Erection Charges Total Erection Charges Unit Erection Charges Total Erection Charges
A ADDCAP Talcher-Kolar HVDC Bipole-Talcher Revaluation of J column Tax Calculation
1 10 10 30 10 Service- Dismantling and re-erection 100012399 995431 18 Dismantling of Quadrivalve SET 1 Included 0.00 0 0
2 10 20 30 20 Service- Dismantling and re-erection 100012833 995431 18 Erection of Quadrivalve as per TS SET 1 Included 0.00 0 0
3 10 30 30 30 Service- Dismantling and re-erection 100012400 995429 18 Dismantling & Removal of Existing Control, Protection and SCADA System . LS 1 Included 0.00 0 0
4 10 40 30 40 Service- Dismantling and re-erection 100048649 995461 18 HVDC CONTROL SYSTEM AS PER TECHNICAL SPECIFICATION LS 1 Included 0.00 0 0
5 10 50 30 50 Service- Dismantling and re-erection 100048650 995461 18 HVDC PROTECTION SYSTEM AS PER TECHNICAL SPECIFICATION LS 1 Included 0.00 0 0
6 10 60 30 60 Service- Dismantling and re-erection 100004381 995461 18 Station Control and Monitoring (SCADA ) Systems Hardwares and Licensed Software consisting of Operator& Engineering Workstations,LED Display System, SCM Servers, Gateway Servers, Engineer Server, file server for TFR records, archived events and analog data,digital documentation etc. software compiler;GPS-clocks for time synchronization LS 1 Included 0.00 0 0
7 10 70 30 70 Service- Dismantling and re-erection 100004383 995461 18 Valve Control Unit/Valve Base Electronics System LS 1 Included 0.00 0 0
8 10 80 30 80 Service- Dismantling and re-erection 100012398 995429 18 Valve Control Unit/Valve Base Electronics System LS 1 Included 0.00 0 0
9 10 90 30 90 Service- Dismantling and re-erection 100004382 995461 18 Any Other Protection (e.g. Supervisory protection) inculding integration works at HVDC Terminal LS 1 Included 0.00 0 0
10 10 100 30 100 Service- Dismantling and re-erection 100004385 995461 18 Transient Fault Recorder SET 1 Included 0.00 0 0
11 10 110 30 110 Service- Dismantling and re-erection 100006676 995461 18 DISMANTLING - VALVE COOLING SYSTEM . SET 1 Included 0.00 0 0
12 10 120 30 120 Service- Dismantling and re-erection 100004441 995461 18 HVDC VALVE COOLING SYSTEM SET 1 Included 0.00 0 0
13 10 130 30 130 Service- Dismantling and re-erection 100012832 995431 18 Dismantling of Valve Cooling Control LS 1 Included 0.00 0 0
14 10 140 30 140 Service- Dismantling and re-erection 100004384 995461 18 Valve Cooling Control LS 1 Included 0.00 0 0
15 10 150 30 150 Service- Dismantling and re-erection 100006638 995461 18 DISMANTLING - DCCT . EA 1 Included 0.00 0 0
16 10 160 30 160 Service- Dismantling and re-erection 100006636 995461 18 DC CURRENT TRANSFORMERS . EA 1 Included 0.00 0 0
17 10 170 30 170 Service- Dismantling and re-erection 100006639 995461 18 DISMANTLING - DCVD . EA 1 Included 0.00 0 0
18 10 180 30 180 Service- Dismantling and re-erection 100006637 995461 18 DC VOLTAGE DIVIDER . EA 1 Included 0.00 0 0
19 10 190 30 190 Service- Dismantling and re-erection 100048618 995429 18 Dismantling of PLC Filter and Capacitive Voltage Divider (CVD) LS 2 Included 0.00 0 0
20 10 200 30 200 Service- Dismantling and re-erection 100012834 995431 18 Erection of AC PLC Filter including Capacitive Voltage Divider (CVD) as per TS SET 1 Included 0.00 0 0
21 10 210 30 210 Service- Dismantling and re-erection 100006670 995461 18 ERECTION HARDWARE - AS PER PROVISIONS OF LOA SET 1 Included 0.00 0 0
22 10 220 30 220 Service- Dismantling and re-erection 100006671 995461 18 CONDUCTORS . LS 1 Included 0.00 0 0
23 10 230 30 230 Service- Dismantling and re-erection 100012366 998731 18 Bus Work LS 1 Included 0.00 0 0
24 10 240 30 240 Service- Dismantling and re-erection 100002353 998736 18 Power and control cables as per Technical Specification LS 1 Included 0.00 0 0
25 10 250 30 250 Service- Dismantling and re-erection 100004966 995429 18 Dismantling of existing power & control cables as per TS LS 1 Included 0.00 0 0
26 10 260 30 260 Service- Dismantling and re-erection 100003231 998731 18 DG Set SET 2 Included 0.00 0 0
27 10 270 30 270 Service- Dismantling and re-erection 100012830 998736 18 Dismantling of 48V Battery Chargers as per TS LS 1 Included 0.00 0 0
28 10 280 30 280 Service- Dismantling and re-erection 100012369 998736 18 Erection of 48V Battery Chargers as per TS LS 1 Included 0.00 0 0
29 10 290 30 290 Service- Dismantling and re-erection 100012831 998736 18 Dismantling of 220V Battery chargers As per TS LS 1 Included 0.00 0 0
30 10 300 30 300 Service- Dismantling and re-erection 100006970 998736 18 220V Float cum Boost battery Charger . EA 5 Included 0.00 0 0
31 10 310 30 310 Service- Dismantling and re-erection 100048619 998736 18 DISMANTLING OF 220 V BATTERY SYSTEM AS PER TS LS 1 Included 0.00 0 0
32 10 320 30 320 Service- Dismantling and re-erection 100057285 998736 18 220V Battery system SET 2 Included 0.00 0 0
33 10 330 30 330 Service- Dismantling and re-erection 100048630 998736 18 DISMANTLING OF 48 V BATTERY SYSTEM AS PER TS LS 1 Included 0.00 0 0
34 10 340 30 340 Service- Dismantling and re-erection 150000051 998739 18 Installation, Testing & Commissioning(floor/wall mounted including supply ofall material required for installation)of 415V AC Distribution Board/Panelalongwith supply & installation of allaccessories to complete auxiliary ACpower supply system as per TS EA 2 Included 0.00 0 0
35 10 350 30 350 Service- Dismantling and re-erection 100000902 998736 18 220V DCDB SET 2 Included 0.00 0 0
36 10 360 30 360 Service- Dismantling and re-erection 100000905 998736 18 48V DCDB SET 2 Included 0.00 0 0
37 10 370 30 370 Service- Dismantling and re-erection 100004388 995461 18 Earthing materials as required as per TS LOT 1 Included 0.00 0 0
38 10 380 30 380 Service- Dismantling and re-erection 100059226 995429 18 Dismantling Smoothing Reactor (DC Side) as per TS - HVDC PC 4 Included 0.00 0 0
39 10 390 30 390 Service- Dismantling and re-erection 100059215 995421 18 Erection and Comissioning Smoothing Reactor (DC Side) as per TS- HVDC PC 4 Included 0.00 0 0
40 10 400 30 400 Service- Dismantling and re-erection 100059227 995429 18 Dismantling HVDC/LVDC Wall bushing as per TS - HVDC PC 2 Included 0.00 0 0
41 10 410 30 410 Service- Dismantling and re-erection 100059216 995421 18 Erection and Comissioning of HVDC/LVDC Wall bushing as per TS - HVDC PC 2 Included 0.00 0 0
42 10 420 30 420 Service- Dismantling and re-erection 100059223 995429 18 Dismantling DC Disconnector as per TS LOT 1 Included 0.00 0 0
43 10 430 30 430 Service- Dismantling and re-erection 100059212 995421 18 Erection and Commissioning of DC Disconnector with or without Grounding Switches as per TS LOT 1 Included 0.00 0 0
44 10 440 30 440 Service- Dismantling and re-erection 100059224 995429 18 Dismantling HVDC/LVDC Grounding Switches as per TS LOT 1 Included 0.00 0 0
45 10 450 30 450 Service- Dismantling and re-erection 100059213 995421 18 Erection and Commissioning of HVDC/LVDC Grounding Switches as per TS LS 1 Included 0.00 0 0
46 10 460 30 460 Service- Dismantling and re-erection 100002335 995429 18 Dismantling of Surge Arrester of various ratings as per technical specification EA 1 Included 0.00 0 0
47 10 470 30 470 Service- Dismantling and re-erection 100059211 995421 18 Erection and Commissioning of Surge Arresters incl. counter as per TS LOT 1 Included 0.00 0 0
48 10 480 30 480 Service- Dismantling and re-erection 100059229 995429 18 Dismantling of DC High Speed Switch as per TS PC 5 Included 0.00 0 0
49 10 490 30 490 Service- Dismantling and re-erection 100059218 995421 18 Erection and Commissioning of DC High Speed Switch as per TS PC 5 Included 0.00 0 0
50 10 500 30 500 Service- Dismantling and re-erection 100059225 995429 18 Dismantling of DC PLC Filters equipment as per TS LOT 1 Included 0.00 0 0
51 10 510 30 510 Service- Dismantling and re-erection 100059214 995421 18 Erection and Commissioning of DC PLC Filter equipment as per TS LOT 1 Included 0.00 0 0
52 10 520 30 520 Service- Dismantling and re-erection 100059228 995429 18 Dismantling of Neutral surge capacitor as per TS PC 2 Included 0.00 0 0
53 10 530 30 530 Service- Dismantling and re-erection 100059217 995421 18 Erection and Commissioning of Neutral surge capacitor as per TS PC 2 Included 0.00 0 0
54 10 540 30 540 Service- Dismantling and re-erection 100059230 995429 18 Dismantling of existing AC and DC Bus Bar in complete sense as per TS LOT 1 Included 0.00 0 0
55 10 550 30 550 Service- Dismantling and re-erection 100059219 995429 18 Dismanltling of DG Set as per TS SET 2 Included 0.00 0 0
56 10 560 30 560 Service- Dismantling and re-erection 100059222 995429 18 Dismantling of 48V DC Distribution Board (DCDB) as per TS LOT 1 Included 0.00 0 0
57 10 570 30 570 Service- Dismantling and re-erection 100059220 995429 18 Dismantling of 415V AC Distribution Board (ACDB) as per TS LOT 1 Included 0.00 0 0
58 10 580 30 580 Service- Dismantling and re-erection 100059221 995429 18 Dismantling of 220V DC Distribution Board (DCDB) as per TS LOT 1 Included 0.00 0 0
59 10 590 30 590 Service- Dismantling and re-erection 100059279 998736 18 48 V BATTERY SYS AS PER TS LS 2 Included 0.00 0 0
60 10 600 30 600 Service- Dismantling and re-erection 100005128 995428 18 CIVIL WORKS AS PER TS - HVDC LS 1 Included 0.00 0 0
B ADDCAP Talcher-Kolar HVDC Bipole-Kolar 0.00 0 0
61 20 10 30 10 Service- Dismantling and re-erection 100012399 995431 18 Dismantling of Quadrivalve SET 1 Included 0.00 0 0
62 20 20 30 20 Service- Dismantling and re-erection 100012833 995431 18 Erection of Quadrivalve as per TS SET 1 Included 0.00 0 0
63 20 30 30 30 Service- Dismantling and re-erection 100012400 995429 18 Dismantling & Removal of Existing Control, Protection and SCADA System . LS 1 Included 0.00 0 0
64 20 40 30 40 Service- Dismantling and re-erection 100048649 995461 18 HVDC CONTROL SYSTEM AS PER TECHNICAL SPECIFICATION LS 1 Included 0.00 0 0
65 20 50 30 50 Service- Dismantling and re-erection 100048650 995461 18 HVDC PROTECTION SYSTEM AS PER TECHNICAL SPECIFICATION LS 1 Included 0.00 0 0
66 20 60 30 60 Service- Dismantling and re-erection 100004381 995461 18 Station Control and Monitoring (SCADA ) Systems Hardwares and Licensed Software consisting of Operator& Engineering Workstations,LED Display System, SCM Servers, Gateway Servers, Engineer Server, file server for TFR records, archived events and analog data,digital documentation etc. software compiler;GPS-clocks for time synchronization LS 1 Included 0.00 0 0
67 20 70 30 70 Service- Dismantling and re-erection 100004383 995461 18 Valve Control Unit/Valve Base Electronics System LS 1 Included 0.00 0 0
68 20 80 30 80 Service- Dismantling and re-erection 100012398 995429 18 Valve Control Unit/Valve Base Electronics System LS 1 Included 0.00 0 0
69 20 90 30 90 Service- Dismantling and re-erection 100004382 995461 18 Any Other Protection (e.g. Supervisory protection) inculding integration works at HVDC Terminal LS 1 Included 0.00 0 0
70 20 100 30 100 Service- Dismantling and re-erection 100004385 995461 18 Transient Fault Recorder SET 1 Included 0.00 0 0
71 20 110 30 110 Service- Dismantling and re-erection 100006676 995461 18 DISMANTLING - VALVE COOLING SYSTEM . SET 1 Included 0.00 0 0
72 20 120 30 120 Service- Dismantling and re-erection 100004441 995461 18 HVDC VALVE COOLING SYSTEM SET 1 Included 0.00 0 0
73 20 130 30 130 Service- Dismantling and re-erection 100012832 995431 18 Dismantling of Valve Cooling Control LS 1 Included 0.00 0 0
74 20 140 30 140 Service- Dismantling and re-erection 100004384 995461 18 Valve Cooling Control LS 1 Included 0.00 0 0
75 20 150 30 150 Service- Dismantling and re-erection 100006638 995461 18 DISMANTLING - DCCT . EA 1 Included 0.00 0 0
76 20 160 30 160 Service- Dismantling and re-erection 100006636 995461 18 DC CURRENT TRANSFORMERS . EA 1 Included 0.00 0 0
77 20 170 30 170 Service- Dismantling and re-erection 100006639 995461 18 DISMANTLING - DCVD . EA 1 Included 0.00 0 0
78 20 180 30 180 Service- Dismantling and re-erection 100006637 995461 18 DC VOLTAGE DIVIDER . EA 1 Included 0.00 0 0
79 20 190 30 190 Service- Dismantling and re-erection 100002335 995429 18 Dismantling of Surge Arrester of various ratings as per technical specification EA 1 Included 0.00 0 0
80 20 200 30 200 Service- Dismantling and re-erection 100048618 995429 18 Dismantling of PLC Filter and Capacitive Voltage Divider (CVD) LS 1 Included 0.00 0 0
81 20 210 30 210 Service- Dismantling and re-erection 100012834 995431 18 Erection of AC PLC Filter including Capacitive Voltage Divider (CVD) as per TS SET 1 Included 0.00 0 0
82 20 220 30 220 Service- Dismantling and re-erection 100006670 995461 18 ERECTION HARDWARE - AS PER PROVISIONS OF LOA SET 1 Included 0.00 0 0
83 20 230 30 230 Service- Dismantling and re-erection 100006671 995461 18 CONDUCTORS . LS 1 Included 0.00 0 0
84 20 240 30 240 Service- Dismantling and re-erection 100012366 998731 18 Bus Work LS 1 Included 0.00 0 0
85 20 250 30 250 Service- Dismantling and re-erection 100002353 998736 18 Power and control cables as per Technical Specification LS 1 Included 0.00 0 0
86 20 260 30 260 Service- Dismantling and re-erection 100004966 995429 18 Dismantling of existing power & control cables as per TS LS 1 Included 0.00 0 0
87 20 270 30 270 Service- Dismantling and re-erection 100003231 998731 18 DG Set SET 2 Included 0.00 0 0
88 20 280 30 280 Service- Dismantling and re-erection 100012830 998736 18 Dismantling of 48V Battery Chargers as per TS LS 1 Included 0.00 0 0
89 20 290 30 290 Service- Dismantling and re-erection 100012369 998736 18 Erection of 48V Battery Chargers as per TS LS 1 Included 0.00 0 0
90 20 300 30 300 Service- Dismantling and re-erection 100012831 998736 18 Dismantling of 220V Battery chargers As per TS LS 1 Included 0.00 0 0
91 20 310 30 310 Service- Dismantling and re-erection 100006970 998736 18 220V Float cum Boost battery Charger . EA 5 Included 0.00 0 0
92 20 320 30 320 Service- Dismantling and re-erection 100048619 998736 18 DISMANTLING OF 220 V BATTERY SYSTEM AS PER TS LS 1 Included 0.00 0 0
93 20 330 30 330 Service- Dismantling and re-erection 100057285 998736 18 220V Battery system SET 2 Included 0.00 0 0
94 20 340 30 340 Service- Dismantling and re-erection 100048630 998736 18 DISMANTLING OF 48 V BATTERY SYSTEM AS PER TS LS 1 Included 0.00 0 0
95 20 350 30 350 Service- Dismantling and re-erection 150000051 998739 18 Installation, Testing & Commissioning(floor/wall mounted including supply ofall material required for installation)of 415V AC Distribution Board/Panelalongwith supply & installation of allaccessories to complete auxiliary ACpower supply system as per TS EA 2 Included 0.00 0 0
96 20 360 30 360 Service- Dismantling and re-erection 100000902 998736 18 220V DCDB SET 2 Included 0.00 0 0
97 20 370 30 370 Service- Dismantling and re-erection 100000905 998736 18 48V DCDB SET 2 Included 0.00 0 0
98 20 380 30 380 Service- Dismantling and re-erection 100004388 995461 18 Earthing materials as required as per TS LOT 1 Included 0.00 0 0
99 20 390 30 390 Service- Dismantling and re-erection 100059226 995429 18 Dismantling Smoothing Reactor (DC Side) as per TS - HVDC PC 4 Included 0.00 0 0
100 20 400 30 400 Service- Dismantling and re-erection 100059215 995421 18 Erection and Comissioning Smoothing Reactor (DC Side) as per TS- HVDC PC 4 Included 0.00 0 0
101 20 410 30 410 Service- Dismantling and re-erection 100059227 995429 18 Dismantling HVDC/LVDC Wall bushing as per TS - HVDC PC 2 Included 0.00 0 0
102 20 420 30 420 Service- Dismantling and re-erection 100059216 995421 18 Erection and Comissioning of HVDC/LVDC Wall bushing as per TS - HVDC PC 2 Included 0.00 0 0
103 20 430 30 430 Service- Dismantling and re-erection 100059223 995429 18 Dismantling DC Disconnector as per TS LOT 1 Included 0.00 0 0
104 20 440 30 440 Service- Dismantling and re-erection 100059212 995421 18 Erection and Commissioning of DC Disconnector with or without Grounding Switches as per TS LOT 1 Included 0.00 0 0
105 20 450 30 450 Service- Dismantling and re-erection 100059224 995429 18 Dismantling HVDC/LVDC Grounding Switches as per TS LOT 1 Included 0.00 0 0
106 20 460 30 460 Service- Dismantling and re-erection 100059213 995421 18 Erection and Commissioning of HVDC/LVDC Grounding Switches as per TS LS 2 Included 0.00 0 0
107 20 470 30 470 Service- Dismantling and re-erection 100059211 995421 18 Erection and Commissioning of Surge Arresters incl. counter as per TS LOT 1 Included 0.00 0 0
108 20 480 30 480 Service- Dismantling and re-erection 100059229 995429 18 Dismantling of DC High Speed Switch as per TS PC 5 Included 0.00 0 0
109 20 490 30 490 Service- Dismantling and re-erection 100059218 995421 18 Erection and Commissioning of DC High Speed Switch as per TS PC 5 Included 0.00 0 0
110 20 500 30 500 Service- Dismantling and re-erection 100059225 995429 18 Dismantling of DC PLC Filters equipment as per TS LOT 1 Included 0.00 0 0
111 20 510 30 510 Service- Dismantling and re-erection 100059214 995421 18 Erection and Commissioning of DC PLC Filter equipment as per TS LOT 1 Included 0.00 0 0
112 20 520 30 520 Service- Dismantling and re-erection 100059228 995429 18 Dismantling of Neutral surge capacitor as per TS PC 2 Included 0.00 0 0
113 20 530 30 530 Service- Dismantling and re-erection 100059217 995421 18 Erection and Commissioning of Neutral surge capacitor as per TS PC 2 Included 0.00 0 0
114 20 540 30 540 Service- Dismantling and re-erection 100059230 995429 18 Dismantling of existing AC and DC Bus Bar in complete sense as per TS LOT 1 Included 0.00 0 0
115 20 550 30 550 Service- Dismantling and re-erection 100059219 995429 18 Dismanltling of DG Set as per TS SET 2 Included 0.00 0 0
116 20 560 30 560 Service- Dismantling and re-erection 100059220 995429 18 Dismantling of 415V AC Distribution Board (ACDB) as per TS LOT 1 Included 0.00 0 0
117 20 570 30 570 Service- Dismantling and re-erection 100059221 995429 18 Dismantling of 220V DC Distribution Board (DCDB) as per TS LOT 2 Included 0.00 0 0
118 20 580 30 580 Service- Dismantling and re-erection 100059222 995429 18 Dismantling of 48V DC Distribution Board (DCDB) as per TS LOT 2 Included 0.00 0 0
119 20 590 30 590 Service- Dismantling and re-erection 100059279 998736 18 48 V BATTERY SYS AS PER TS LS 2 Included 0.00 0 0
120 20 600 30 600 Service- Dismantling and re-erection 100005128 995428 18 CIVIL WORKS AS PER TS - HVDC LS 1 Included 0.00 0 0
Total Installation Charges 0.00 0
Total GST as confirmed by Bidder 0.00
* In case the bidder leaves the cell for confirmation of the SAC and/or GST rate “blank”, the SAC and corresponding GST rate indicated by the Employer shall be deemed to be the one confirmed by the Bidder.
Place : Printed Name :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 3
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES : ERECTION CHARGES) AS per Percent #REF!
As per lum-sum on Sch-3 0.00%
Bidder’s Name and Address (Sole Bidder) : To: As per Percent on Sch-3 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Sector-29, Multipackage lum-sum 0.00%
Gurgaon (Haryana) - 122001
All Prices are in Indian Rupees. Amount after Discount (Rs.) Dis Alert Amount after MPD (Rs.)
SI. No. Description Unit Quantity Unit Erection Charges Total Erection Charges Unit Erection Charges Total Erection Charges Unit Erection Charges Total Erection Charges
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! (a) Detailed Soil Investigation
#REF! #REF! #REF! #REF! #REF! (b) All kinds of soil except fissured rock & hard rock
#REF! #REF! #REF! #REF! #REF! (e) River Crossing Location
#REF! #REF! #REF! #REF! #REF! (f)
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF! #REF!
#REF! #REF! #REF! #REF! #REF!
Total Erection Price (A+B) #REF!
Place : Printed Name :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 4
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(SCHEDULE OF RATES AND PRICES )
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
Training Charges for Training to be imparted
SI. No. PR No PR Line Item No Activity Header PR Activity No Activity Description Service Code SAC (Service Accounting Codes) Whether SAC in column '8’ is confirmed. If not indicate applicable the SAC * Rate of GST applicable ( in %) Whether rate of GST in column ‘4’ is confirmed. If not indicate applicable rate of GST * Description Unit Quantity Unit Training Charges excluding GST Total Training Charges excluding GST Total GST as confirmed by Bidder
Revaluation of J column Tax Calculation
NOT APPLICABLE Revaluation of J column Tax Calculation
Included 0.00 0 0
Total Training Charges 0.00 0
Total GST as confirmed by Bidder 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 4b
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(SCHEDULE OF RATES AND PRICES )
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
Maintenance Charges during & after Defect Laibility Period
SI. No. PR No PR Line Item No Activity Header PR Activity No Activity Description Service Code SAC (Service Accounting Codes) Whether SAC in column '8’ is confirmed. If not indicate applicable the SAC * Rate of GST applicable ( in %) Whether rate of GST in column ‘4’ is confirmed. If not indicate applicable rate of GST * Description Unit Quantity Unit Maintenance Charges excluding GST Total Maintenance Charges excluding GST Total GST as confirmed by Bidder
0 Revaluation of P column Tax Calculation
A. #REF! Revaluation of P column Tax Calculation
1 Included 0.00 0 0
2 Included 0.00 0 0
3 Included 0.00 0 0
4 Included 0.00 0 0
B. #REF! Revaluation of P column Tax Calculation
1 Included 0.00 0 0
2 Included 0.00 0 0
3 Included 0.00 0 0
4 Included 0.00 0 0
Total Maintenance Charges during and after Defect Liabilty Period 0.00 0
Total GST as confirmed by Bidder 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 5
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(SUMMARY OF TAXES & DUTIES APPLICABLE ON PLANT & EQUIPMENT)
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
Sl. No. Item Nos. Total Price (INR) After Discount After MPDiscount
1 TOTAL GST ON GOODS Excise Duty #REF! Excise Duty #REF!
Total GST for Supply of Goods (inter-alia including Type Test Charges) between the Contractor and the Employer (identified in Schedule 1') which are not included in the Ex-works price as per the provision of the Bidding Documents, as applicable. 0.00
2 TOTAL GST ON SERVICES Sales Tax 0.00 Sales Tax 0.00
Total GST on Installation Services (Schedule-3), Training to be imparted in India (Schedule-4) 0.00 #REF! 0 #REF! 0
GRAND TOTAL [1+2] 0.00 Grand Total after Discount #REF! Grand Total after MPD #REF!
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 5
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
SUMMARY OF TAXES & DUTIES APPLICABLE ON GOODS
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
Sl. No. Item Nos. Total Price (INR)
1 TOTAL GST ON GOODS 0.00
Total GST for Supply of Goods (inter-alia including Type Test Charges) between the Contractor and the Employer (identified in Schedule 1') which are not included in the Ex-works price as per the provision of the Bidding Documents, as applicable.
2 TOTAL GST ON SERVICES 0.00
Total GST on Installation Services (Schedule-3), Training to be imparted in India (Schedule-4a) and Maintenance Charges during and after Defect Liabilty Period (Schedule-4b)
GRAND TOTAL [1+2] 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 6
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(GRAND SUMMARY)
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
Sl. No. Description Total Price (INR)
1 TOTAL SCHEDULE NO. 1 0.00
Ex-works price of Plant and Equipment including Type Test Charges
2 TOTAL SCHEDULE NO. 2 0.00
Local Transportation, In-transit Insurance, loading & unloading
3 TOTAL SCHEDULE NO. 3 0.00
Installation Charges
4 TOTAL SCHEDULE NO. 4 0.00
Training Charges
4b TOTAL SCHEDULE NO. 4b 0.00
Maintenance Charges during & after Defect Laibility Period
5 TOTAL SCHEDULE NO. 5 0.00
Taxes and Duties
6 TOTAL SCHEDULE NO. 7 0.00
Type Test Charges [Total of this Schedule is included in Schedule - 1 above.]
GRAND TOTAL [1+2+3+4+5] 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule - 6 After Discount
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
(GRAND SUMMARY)
Bidder’s Name and Address (Sole Bidder) : To:
Contracts Services, 3rd Floor
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Gurgaon (Haryana) - 122001
Sl. No. Description Total Price (INR)
1 TOTAL SCHEDULE NO. 1 0.00
Ex-works price of Plant and Equipment including Type Test Charges
2 TOTAL SCHEDULE NO. 2 0.00
Local Transportation, In-transit Insurance, loading & unloading
3 TOTAL SCHEDULE NO. 3 0.00
Installation Charges
4 TOTAL SCHEDULE NO. 4 0.00
Training Charges
4b TOTAL SCHEDULE NO. 4b 0.00
Maintenance Charges during & after Defect Laibility Period
5 TOTAL SCHEDULE NO. 5 0.00
Taxes and Duties
6 TOTAL SCHEDULE NO. 7 0.00
Type Test Charges [Total of this Schedule is included in Schedule - 1 above.]
GRAND TOTAL [1+2+3+4+5] 0.00
Date : -- Printed Name :
Place : Designation :
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Schedule 7
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES ) AS per Percent #REF!
As per lum-sum on Sch-7 0.00%
Bidder’s Name and Address (Sole Bidder) : To: As per Percent on Sch-7 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Sector-29, Multipackage Discount 0.0000%
Gurgaon (Haryana) - 122001
Type tests on Earthwire, Hardwar Fittings & accessories of conductor & earthwire:
SL. NO. PR No Line Item No Code HSN Code Whether HSN in column ‘2’ is confirmed. If not indicate applicable the HSN code * Rate of GST applicable ( in %) Whether rate of GST in column ‘4’ is confirmed. If not indicate applicable rate of GST * Description of Test Unit Quantity Unit Test Charge Total Test Charges (Rs.) Total GST as confirmed by Bidder Revaluation of M column Tax Calculation Total Test Charges After Discount (Rs.) Dis Alert Total Test Charges After MPD (Rs.)
1 Included 0.00 0 0.00
2 Included 0.00 0 0.00
TOTAL TYPE TEST CHARGES 0.00
Total GST as confirmed by Bidder 0.00
Date : -- Printed Name :
Place : Designation :
Note : Bidder should indicate the name of test laboratories where type tests are proposed to be conducted
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) 0 0
(SCHEDULE OF RATES AND PRICES ) 0 0
Bidder’s Name and Address (Sole Bidder) :
SL. NO. Description of Test #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) As per Lum-sum 0.00%
(SCHEDULE OF RATES AND PRICES : TYPE TEST CHARGES) AS per Percent #REF!
As per lum-sum on Sch-7 0.00%
Bidder’s Name and Address (Sole Bidder) : To: As per Percent on Sch-7 #REF!
Contracts Services, 3rd Floor Total Discount #REF!
Name : Power Grid Corporation of India Ltd.,
Address : "Saudamini", Plot No.-2
Sector-29, Multipackage Discount 0.0000%
Gurgaon (Haryana) - 122001
Type Tests on Earthwire
SL. NO. Description of Test Unit Quantity Unit Test Charge Total Test Charges (Rs.) Total Test Charges After Discount (Rs.) Dis Alert Total Test Charges After MPD (Rs.)
(a) #REF! #REF! #REF! #REF! #REF!
(b) #REF! #REF! #REF! #REF! #REF!
Sub-Total (I) #REF!
TOTAL TEST CHARGES (I) #REF!
Discount Sche-7 #REF! MPD Sche-7 #REF!
Dis Alert #REF!
Date : -- Printed Name :
Place : Designation :
Note : Bidder should indicate the name of test laboratories where type tests are proposed to be conducted
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) 0 0 0
(SCHEDULE OF RATES AND PRICES : TYPE TEST CHARGES) 0 0 0
Bidder’s Name and Address (Sole Bidder) : 0
SL. NO. Description of Test 0
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
#REF! #REF! #REF!
This letter of discount is optional. Bidder may / may not offer any discount.
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Letter of Discount
LETTER OF DISCOUNT
Contract Services
Power Grid Corporation of India Ltd.,
"Saudamini", Plot No.-2
Sector-29, (near IFFCO Chowk)
Gurgaon (Haryana) - 122001
Subject : Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap)
With reference to the subject tender, we hereby offer unconditional discount on the prices quoted by us as per details given here below : Eq Weightage of Rs/ % Final Discount Factor
1 Discount on lum-sum basis on total price quoted by us without Taxes & Duties. [The discount shall be proportionately applicable on all the items of all the Schdules i.e. Sch-1 (without type test charges), Sch-2, Sch-3, Sch-4a, Sch-4b & Sch-7] In Rs. 0.00 0.0000000000%
2 Discount on percent basis on total price quoted by us without Taxes & Duties. [The discount shall be proportionately applicable on all the items of all the Schdules i.e. Sch-1 (without type test charges), Sch-2 , Sch-3, Sch-4a, Sch-4b & Sch-7] In Percent (%) 0.00 0.00%
3 Discount on lum-sum basis on the Schedules as given below : [The discount shall be proportionately applicable on all the relevent items of the respective Schdules.] In Rs.
Schedule-1 : Ex works prices In Rs. 0.00 0.0000000000% Schedule-1 : Ex-Works Price 0.0000000000%
Schedule-2 : Freight & Insurance In Rs. 0.00 0.0000000000% Schedule-2 : Freight & Insurance 0.0000000000%
Schedule-3 : Erection Charges In Rs. 0.00 0.0000000000% Schedule-3 : Erection Charges 0.0000000000%
Schedule-4a : Training Charges In Rs. 0.00 0.0000000000% Schedule-4a : Training Charges 0.0000000000%
Schedule-4b : Maintenance Charges during and after DLP In Rs. 0.00 0.0000000000% Schedule-4b : Maintenance Charges 0.0000000000%
Schedule-7 : Type Test Charges In Rs. 0.00 0.0000000000% Schedule-7 : Type Test Charges 0.0000000000%
4 Discount on percent basis on the Schedules as given below : [The discount shall be proportionately applicable on all the relevent items of the respective Schdules.] In Percent (%)
Schedule-1 : Ex works prices In Percent (%) 0.00 0.00%
Schedule-2 : Freight & Insurance In Percent (%) 0.00 0.00%
Schedule-3 : Erection Charges In Percent (%) 0.00 0.00%
Schedule-4a : Training Charges In Percent (%) 0.00 0.00%
Schedule-4b : Maintenance Charges during and after DLP In Percent (%) 0.00 0.00%
Schedule-7 : Type Test Charges In Percent (%) 0.00 0.00%
Discount(s) offered at sl. No. 1 to 4 will get displayed and accounted for automatically in the respective items of the Schedules.
5 We hereby offer Multi-package discount as given below:
Multi-Package Discount(s) offered at sl. No. 5 will not get automatically accounted for in the respective items of the Schedules. The same shall be worked out saparately for evaluation.
Please consider this letter of discount as the integral part of our price bid.
Thanking you, we remain,
Yours faithfully,
For and on behalf of
Date : -- Printed Name :
Place : Designation :
Details of Octroi
Sl No. Description of Items Amount on which Octroi is applicable Rate of Octroi Octroi
Details of Entry Tax
Sl No. Description of Items Amount on which Entry Tax is applicable Rate of Entry Tax Entry Tax
Details of Other Taxes & Duties
Sl No. Description of Items Amount on which Other Taxes & Duties are applicable Description of Taxes & Duties Rate of Taxes & Duties Amount of Taxes & Duties
Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649 Bid Form 2nd Envelope Sole Bidder 1 st 1 January
0 2 nd 2 February
BID FORM (Second Envelope) 3 rd 3 March
Bid Proposal Ref. No. 5 th 5 May
Date : -- 6 th #VALUE! 6 June
7 th #VALUE! 7 July
To: 8 th #VALUE! 8 August
Contracts Services, 3rd Floor 9 th #VALUE! 9 September
Power Grid Corporation of India Ltd., 10 th 10 October
"Saudamini", Plot No.-2 11 th 11 November
Sector-29, 12 th 12 December
Gurgaon (Haryana) - 122001 13 th
Name of Contract : Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) 15 th
Dear Ladies and/or Gentlemen, 16 th
Schedule 1 Plant and Equipment (Including Mandatory Spare Parts) to be supplied, including Type Test Charges. 21 st
Schedule 2 Local Transportation, In-transit Insurance, loading and unloading 22 th
Schedule 3 Installation Charges. 23 th
Schedule 4 Training charges for training to be imparted. 24 th
Schedule 4b Maintenance Charges during & after Defect Laibility Period.
Schedule 5 Taxes and Duties not included in Schedule 1 25 th
Schedule 6 Grand Summary [Schedule 1to 5] 26 th
Schedule 7 Break-up of Type Test Charges for Type Tests to be conducted 27 th
2.5 We declare that items left blank in the Schedules will be deemed to have been included in other items. The TOTAL for each Schedule and the TOTAL of Grand Summary shall be deemed to be the total price for executing the Facilities and sections thereof in complete accordance with the Contract, whether or not each individual item has been priced. 31 st
3.0 We confirm that except as otherwise specifically provided our Bid Prices in this Second Envelope include all taxes, duties, levies and charges as may be assessed on us/our Associate (applicable for Foreign Bidder), our Sub-Contractor/Sub-Vendor or their employees by all municipal, state or national government authorities in connection with the Facilities, in and outside of India.
3.1 100% of applicable Taxes and Duties i.e GST which are payable by the Employer under the Contract, shall be reimbursed by the Employer on production of satisfactory documentary evidence by the Contractor in accordance with the provisions of the Bidding Documents.
3.3 We confirm that we have also registered/we shall also get registered in the GST Network with a GSTIN, in all the states where the project is located and the states from which we shall make our supply of goods.
4.0 # (For Joint Venture only) We, the partners of Joint Venture submitting this bid, do agree and confirm that in case of Award of Contract on the Joint Venture, we shall be jointly and severally liable and responsible for the execution of the Contract in accordance with Contract terms and conditions. 1
5.0 We, hereby, declare that only the persons or firms interested in this proposal as principals are named here and that no other persons or firms other than those mentioned herein have any interest in this proposal or in the Contract to be entered into, if the award is made on us, that this proposal is made without any connection with any other person, firm or party likewise submitting a proposal is in all respects for and in good faith, without collusion or fraud.
Thanking you, we remain,
Yours faithfully,
For and on behalf of
Date : -- Printed Name :
Place : Designation :
In case of bid from a Joint Venture, name & designation of representative of JV partner is to be provided and Bid Form is also to be signed by him.
Please provide additional information of the Bidder
Business Address :
Country of Incorporation :
State/Province to be indicated :
Name of Principal Officer :
Address of Principal Officer :
Note: Bidders may note that no prescribed proforma has been enclosed for Attachment 2 : Power of Attorney. Bidders may use their own proforma for furnishing the required information with the bid.
STATEMENT OF QUOTED / CORRECTED PRICES
All Figures are in Rupees
Sl. No. Price Component Quoted Price Corrected Price
1 TOTAL SCHEDULE NO. 1:Ex-Works Price of Plant and Equipment including Type Test Charges 0.00 0.00
2 TOTAL SCHEDULE NO.2: Local Transportation, Insurance and other Incidental Services. 0.00 0.00
3 TOTAL SCHEDULE NO.3: Installation Charges 0.00 0.00
4 TOTAL SCHEDULE NO.4: Training Charges Not Applicable Not Applicable
5 TOTAL BID PRICE: (Excluding Taxes & Duties) 0.00 0.00
6 DISCOUNT #REF! #REF! #REF!
7 NET BID PRICE (Excluding Taxes & Duties) #REF! #REF!
8 TAXES & DUTIES PAYABLE ADDITIONALLY
A) EXCISE DUTY 0 0.00
B) CENTRAL SALES TAX 0 0.00
C) VAT #REF! 0.00
D) ENTRY TAX / OCTROI #REF! 0.00
F) TOTAL TAXES & DUTIES #REF! 0.00
8 TOTAL BID PRICE (INCLUDING TAXES & DUTIES) #REF! 0.00
9 TOTAL SCHEDULE NO.7: Type Test Charges [Total of this Schedule is included in Schedule-1 above] 0.00 0.00
I) Bidder has indicated the following taxes and duties additionally applicable for their bid:
Excise Duty % as Excise Duty
#REF! VAT #REF! #REF!
#REF! Entry Tax/ Octroi #REF! #REF!
Others as Others
II) With regard to Entry Tax, it may be mentioned that the substations covered under the subject pacakge falls in State of MP, where an entry tax @ 2% of Purchase Price is applicable. In view of the above, the taxes and duties inter-alia including entry tax applicable for the bids are calculated :
a) Ex-Works Price of Direct Supplies (after discount, if any) Rs. 0
b) Excise Duty, as applicable on (a) above at the rate : 10.00% Rs. 0
c) Amount on which Sales Tax is applicable 0.00 0
d) CST, as applicable on (a) + ED (b) above at the rate : 2.00% Rs. 0
e) VAT, as applicable on (a) + ED (b) above at the rate : 1.00% 0
g) Purchase Price for Entry Tax (Total Ex-Works+F&I+ED+CST+Others) Rs. 0
h) Entry Tax, as applicable on (e) above at the rate : Rs. 0.00
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) Statement of Quoted / Corrected Prices Page
Spec. No. Specification No.: CC/NT/W-HVDC/DOM/A10/26/08649
STATEMENT OF QUOTED / CORRECTED PRICES
All Figures are in Rupees
Sl. No. Price Component Quoted Price Corrected Price
1 TOTAL SCHEDULE NO. 1:Ex-Works Price of Plant and Equipment including Type Test Charges 0.00 0.00
2 TOTAL SCHEDULE NO.2: Local Transportation, Insurance and other Incidental Services. 0.00 0.00
3 TOTAL SCHEDULE NO.3: Installation Charges 0.00 0.00
4 TOTAL SCHEDULE NO.4: Training Charges Not Applicable Not Applicable
5 TOTAL BID PRICE: (Excluding Taxes & Duties) 0.00 0.00
6 DISCOUNT #REF! #REF!
7 NET BID PRICE (Excluding Taxes & Duties) #REF! #REF!
8 TAXES & DUTIES PAYABLE ADDITIONALLY
A) EXCISE DUTY #REF! 0.00
B) CENTRAL SALES TAX /VAT #REF! #REF!
C) ENTRY TAX / OCTROI #REF! #REF!
D) OTHERS #REF! 0.00
E) TOTAL TAXES & DUTIES #REF! #REF!
8 TOTAL BID PRICE (INCLUDING TAXES & DUTIES) #REF! #REF!
9 TOTAL SCHEDULE NO.7: Type Test Charges [Total of this Schedule is included in Schedule-1 above] 0.00 0.00
I) Bidder has indicated the following taxes and duties additionally applicable for their bid:
a) Excise Duty Rs. #REF!
b) CST /VAT Rs. #REF!
c) Entry Tax / Octroi Rs. #REF!
d) Others Rs. #REF!
II) Bidder has offered following discount(s)
III) With regard to Entry Tax, it may be mentioned that the substations covered under the subject pacakge falls in State of MP, where an entry tax @ 1% of Purchase Price is applicable. In view of the above, the taxes and duties inter-alia including entry tax applicable for the bids are calculated : Details of dicounts
a) Ex-Works Price of Direct Supplies (after discount, if any) Rs. 0 Gross LS #REF! #REF! #REF! Gross % #REF! #REF! #REF!
b) Excise Duty @ 10.3% of (a) above Rs. 0 #REF! #REF!
c) CST / VAT @ 2% of Ex-Works of Direct Supplies (a) + ED (b) above Rs. #REF! Sch-1 Direct LS #REF! #REF! #REF! Sch-1 Direct % #REF! #REF! #REF!
d) Others Rs. Sch-1 BO LS #REF! #REF! #REF! Sch-1 BO % #REF! #REF! #REF!
e) Purchase Price for Entry Tax (Total Ex-Works+F&I+ED+CST+Others) Rs. #REF! Sch-2 LS #REF! #REF! #REF! Sch-2 % #REF! #REF! #REF!
f) Entry Tax @ 1% of (e) above Rs. #REF! Sch-3 LS #REF! #REF! #REF! Sch-3 % #REF! #REF! #REF!
Sch-7 LS #REF! #REF! #REF! Sch-7 % #REF! #REF! #REF!
Refurbishment of ± 500 KV, 2000 MW Talcher-Kolar HVDC Bipole System under Additional Capital expenditure (Add Cap) Statement of Quoted / Corrected Prices Page Different Manner #REF!
Text for Discount #REF!
23 Twenty Three
27 Twenty Seven
28 Twenty Eight
33 Thirty Three
37 Thirty Seven
38 Thirty Eight
73 Seventy Three
74 Seventy Four
75 Seventy Five
77 Seventy Seven
78 Seventy Eight
79 Seventy Nine
83 Eighty Three
87 Eighty Seven
88 Eighty Eight
93 Ninety Three
97 Ninety Seven
98 Ninety Eight
100 One Hundred
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html
Annxure-Test Eqpts.pdf
pdf • 3.68 MB
Annexure N1 - Copy.pdf
pdf • 0.24 MB
Annexure_AC FOR SPR.pdf
pdf • 0.09 MB
Annexure_CCTV.pdf
pdf • 0.22 MB
Annexure_VH Environment Control.pdf
pdf • 0.85 MB
Annexure-I _UPS_TS.pdf
pdf • 0.26 MB
Annexure-N-VESDA.pdf
pdf • 0.54 MB
Annexure-Ventilation.pdf
pdf • 0.17 MB
Section_Switchyard Erection_Rev_10.pdf
pdf • 5.99 MB
Section-Switchgear-CB_Rev12.pdf
pdf • 1.73 MB
Section-Switchgear-INST_rev12.pdf
pdf • 0.86 MB
Section-Switchgear-SA_Rev13.pdf
pdf • 0.87 MB
annex Z.pdf
pdf • 0.29 MB
Annexure I (Revised) ups.pdf
pdf • 2.91 MB
Annexure -Power and Control cables scope.pdf
pdf • 0.02 MB
Annexure-Lighting System_Rev07.pdf
pdf • 4.29 MB
Power & Control Cable Rev R6.pdf
pdf • 0.26 MB
Annexure_AC Harmonic Filters.pdf
pdf • 0.59 MB
Annexure-Swichyard Erection_Rev 09.pdf
pdf • 3.73 MB
Figure 5.2.1 (SLD_Talcher).pdf
pdf • 0.34 MB
Figure 5.2.2 (SLD_Kolar).pdf
pdf • 0.42 MB
Remote operation from NTAMC 27-05-2026.docx
docx • 0.45 MB
Remote operation from NTAMC.pdf
pdf • 0.48 MB
Annexure_Filter Data.pdf
pdf • 0.53 MB
Annexure_Overload.pdf
pdf • 0.01 MB
Annexure_T-K MCP.pdf
pdf • 0.02 MB
Station UPS.pdf
pdf • 6.46 MB
Control Room layout Kolar.PDF
pdf • 7.98 MB
DC Arrester Details_Kolar.PDF
pdf • 1.44 MB
EC1.801.2.K-D.pdf
pdf • 0.36 MB
Aux Supply_Kolar.pdf
pdf • 0.04 MB
Battery Charger.pdf
pdf • 8.28 MB
DC Line Data.pdf
pdf • 0.07 MB
Signal List_Kolar HVDC.xlsx
xlsx • 0.16 MB
AC Arrester Details_Kolar.PDF
pdf • 1.96 MB
AC PLC NOISE FILTER LINE TRAP.PDF
pdf • 0.69 MB
Annexure_Bushing Details.PDF
pdf • 0.99 MB
Annexure_Reactive Power.pdf
pdf • 0.54 MB
Battery.pdf
pdf • 2.40 MB
Forced SMR Cooling_Kolar.pdf
pdf • 2.15 MB
SLD_Kolar.pdf
pdf • 0.42 MB
Smoothing Reactor Details_Kolar.PDF
pdf • 0.47 MB
Vale Timing PT.PDF
pdf • 0.37 MB
Battery Charger_1.pdf
pdf • 0.53 MB
Fig 5.2.1_SLD_Talcher.pdf
pdf • 0.34 MB
Signal list_HVDC Talcher.xlsx
xlsx • 0.09 MB
SLD_Talcher Marked.pdf
pdf • 0.56 MB
UPS Talcher.pdf
pdf • 0.45 MB
Battery_1.pdf
pdf • 4.00 MB
Control Room layout Talcher.pdf
pdf • 5.11 MB
AC Circuit Breaker Data.pdf
pdf • 0.29 MB
GENERAL LAYOUT PLAN VIEW KOLAR SUBSTATION.pdf
pdf • 0.39 MB
KOLAR -G.A. AND DETAILS OF FOUNDATIONS VALVE HALL-POLE I& II AND CONTROL BLDG. LAYOUT OF FOOTINGS & COLUMNS.pdf
pdf • 0.82 MB
KOLAR GENERAL LAYOUT.pdf
pdf • 0.53 MB
KOLAR TERMINAL G.A. & DETAILS OF INTERMEDIATE FLOOR POLE I & POLE II.pdf
pdf • 0.46 MB
KOLAR TERMINAL VALVE HALL POLE-I ARCHTECTURAL PLAN AT ROOF LEVEL.pdf
pdf • 0.21 MB
KOLAR TERMINAL VALVE HALL POLE-II ARCHTECTURAL PLAN AT GROUND floor (SHEET 1 OF 2).pdf
pdf • 0.50 MB
KOLAR TERMINAL VALVE HALL-POLE I & POLE II ARCH. ELEVATION A-1,A1-A1,B-B,B1-B1 & D1-D1.pdf
pdf • 0.34 MB
KOLAR TERMINAL VALVE HALL-POLE I & POLE II ARCH. ELEVATION C-C,C1-C1, & D-D.pdf
pdf • 0.31 MB
KOLAR TERMINAL VALVE HALL-POLE I & POLE II ARCH. SECTION B-B,B1-B1,E-E,E1-E1,F-F,F1-F1.pdf
pdf • 0.43 MB
Transformer Data Sheet.pdf
pdf • 0.50 MB
VALVE HALL - ELEVATION OF TRUSS FOR POLE I AND POLE II.pdf
pdf • 0.39 MB
VALVE HALL- LAYOUT OF BEAMS SUPPORTING VALVE BANKS FOR POLE-I.pdf
pdf • 0.50 MB
VALVE HALL- LAYOUT OF BEAMS SUPPORTING VALVE BANKS FOR POLE-II.pdf
pdf • 0.56 MB
VALVE HALL POLE I & II R.C. DETAILS OF ROOF SLAB.pdf
pdf • 0.29 MB
VALVE HALL(POLE-I) STRU. G.A.-LAYOUT AND DETAILS OF TOP CHORD, BRACING AND PURLIN.pdf
pdf • 0.57 MB
VALVE HALL(POLE-II) STRU. G.A.-LAYOUT AND DETAILS OF TOP CHORD, BRACING AND PURLIN.pdf
pdf • 0.54 MB
scan0006.pdf
pdf • 0.49 MB
scan0007.pdf
pdf • 0.41 MB
scan0008.pdf
pdf • 0.65 MB
scan0009.pdf
pdf • 0.56 MB
scan0010.pdf
pdf • 0.49 MB
scan0011.pdf
pdf • 0.58 MB
scan0012.pdf
pdf • 0.32 MB
scan0017.pdf
pdf • 0.56 MB
TALCHER GENERAL LAYOUT.pdf
pdf • 0.50 MB
Control Room Aux Changeover Panel_3.pdf
pdf • 8.38 MB
Control Room Aux Changeover Panel_2.pdf
pdf • 8.68 MB
Control Room Aux Changeover Panel_1.pdf
pdf • 8.46 MB
415V ACDB_2.pdf
pdf • 5.86 MB
415V ACDB_1.pdf
pdf • 5.51 MB
230V ACDB_2.pdf
pdf • 4.95 MB
230V ACDB_1.pdf
pdf • 7.04 MB
220V,48V,24V DCDB_5.pdf
pdf • 8.28 MB
220V,48V,24V DCDB_4.pdf
pdf • 8.88 MB
220V,48V,24V DCDB_3.pdf
pdf • 9.04 MB
220V,48V,24V DCDB_2.pdf
pdf • 9.22 MB
220V,48V,24V DCDB_1.pdf
pdf • 7.35 MB
ACF Main AC DC Supply.pdf
pdf • 2.41 MB
ACF New (26,27) AC DC Supply.pdf
pdf • 2.85 MB
ACF New (36) AC DC Supply.pdf
pdf • 1.24 MB
Point wave AC DC Supply.pdf
pdf • 1.29 MB
220V DC SLD Drawing.pptx
pptx • 0.06 MB
48V DC SLD Drawing.pptx
pptx • 0.06 MB
ACDB Details.pdf
pdf • 8.24 MB
HVAC AUX SLD.pdf
pdf • 0.01 MB
HVDC AUX SLD_1.pdf
pdf • 0.37 MB
HVDC AUX SLD_2.pdf
pdf • 0.38 MB
P1 24V DC SLD Drawing.pptx
pptx • 0.06 MB
P2 24V DC SLD Drawing.pptx
pptx • 0.06 MB
AC Arrester Details_Kolar_1.PDF
pdf • 1.96 MB
Converter transformer Surge Arresters.pdf
pdf • 0.23 MB
EC1.515.AA.T-A.pdf
pdf • 0.24 MB
EC1.515.Fac1.1.T-A.pdf
pdf • 0.22 MB
EC1.515.Fac1.2.T-A.pdf
pdf • 0.21 MB
EC1.515.Fac2.1.T-A.pdf
pdf • 0.22 MB
EC1.515.Fac2.2.T-A.pdf
pdf • 0.21 MB
EC1.515.SR.T-0.pdf
pdf • 0.08 MB
EC1.515.ST.T-0.pdf
pdf • 0.15 MB
Filter Data.pdf
pdf • 0.54 MB
KOLAR GENERAL LAYOUT_1.pdf
pdf • 0.53 MB
TALCHER GENERAL LAYOUT_1.pdf
pdf • 0.50 MB
T-K MCP.pdf
pdf • 0.72 MB
Transformer Data Sheet_1.pdf
pdf • 0.50 MB
Valve Cooling Layout P-1.pdf
pdf • 0.45 MB
Valve Cooling Layout P-2.pdf
pdf • 0.44 MB
1.Annexure C&P dated 27-05-2026.pdf
pdf • 0.13 MB
10.Annexure Discon.pdf
pdf • 0.16 MB
12.Annexure GS.pdf
pdf • 0.15 MB
13.Annexure_VC.pdf
pdf • 0.27 MB
17.Annexure BT.pdf
pdf • 0.01 MB
18.Annexure DCHS.pdf
pdf • 0.04 MB
19.Annexure UPS dated 27-05-2026.pdf
pdf • 0.16 MB
21.Annexure CL dated 27-05-2026.pdf
pdf • 0.10 MB
22.Annexure DG - Copy.pdf
pdf • 0.08 MB
Annexure K1 27-05-2026.pdf
pdf • 0.16 MB
Annexure Communication.pdf
pdf • 0.03 MB
Annexure Outage Schedule.pdf
pdf • 0.28 MB
Annexure -Power and Control cables scope_1.pdf
pdf • 0.04 MB
Annexure Store area.pdf
pdf • 1.02 MB
Annexure-I.pdf
pdf • 0.32 MB
Annexure-JDU.pdf
pdf • 0.07 MB
Annexure-S12, S13, S14.pdf
pdf • 0.34 MB
Final_Type_Test_Guidelines_2026.pdf
pdf • 0.82 MB
Remote operation from NTAMC_1.pdf
pdf • 0.48 MB
TK_Chapter-01_Rev001.pdf
pdf • 0.46 MB
TK_Chapter-02_Rev002.pdf
pdf • 0.25 MB
TK_Chapter-03_Rev000.pdf
pdf • 0.51 MB
TK_Chapter-04 (Part-1)_Rev001.pdf
pdf • 3.73 MB
TK_Chapter-04 (Part-2)_Rev002.pdf
pdf • 0.78 MB
TK_Chapter-05_Rev000.pdf
pdf • 0.27 MB
TK_Chapter-06_Rev001.pdf
pdf • 1.40 MB
TK_Chapter-07_Rev001.pdf
pdf • 0.26 MB
TK_Chapter-08_Rev 001.pdf
pdf • 0.65 MB
TK_Chapter-09_Rev001.pdf
pdf • 0.34 MB
TK_Chapter-10_Rev001.pdf
pdf • 0.19 MB
TK_Chapter-11_Rev001.pdf
pdf • 0.32 MB
01_Attachment-8_Manufacturer Authorization Form.docx
docx • 0.03 MB
02_Attachment-20_KMP Declaration.doc
doc • 0.03 MB
03_Attachment_22_Affidavit for Self-Certification_PPP-MII.DOCX
docx • 0.02 MB
05_Attachment-24_Compliance_process related to the e-RA.docx
docx • 0.02 MB
06_Attachment-25_Declaration_events encountered.docx
docx • 0.03 MB
07_Attachment-26_Affidavit of Self certification regarding Domestic Value Addition in Iron &Steel Produc.docx
docx • 0.02 MB
08_Attachment 27_Certificate by bidder.docx
docx • 0.02 MB
09_Attachment-28_Bid Securing Declaration.docx
docx • 0.02 MB
10_Attachment-29_Undertaking_Hard copy bid.docx
docx • 0.02 MB
11_Attachment-30_Declaration_Code of Integrity for Public procurement.docx
docx • 0.02 MB
12_Attachment-31.docx
docx • 0.02 MB
13_Legends for Units.pdf
pdf • 0.03 MB
Attachment 3(QR).docx
docx • 0.07 MB
First Envelope and Bid Forms.xlsx
xlsx • 0.57 MB
Price_Schedule.xlsx
xlsx • 1.56 MB
01_Main Index_Vol-I.doc
doc • 0.02 MB
02-Section - I IFB SSTE_Vol-I.docx
docx • 0.04 MB
03_ Section - II ITB SSTE S&I DCB-PRANIT_Vol-I.docx
docx • 0.10 MB
04- Section-III-BDS.docx
docx • 0.08 MB
04-Annexure-A (BDS).doc
doc • 0.07 MB
04-Annexure-B to BDS.docx
docx • 0.02 MB
04-Annexure-C (BDS) - MJunction.docx
docx • 0.03 MB
04-Annexure-C (BDS) - PRANIT.docx
docx • 0.03 MB
05-Section - IV GCC -S&I Rev 3-DCB.pdf
pdf • 1.93 MB
06- Section-V-SCC.docx
docx • 0.10 MB
07- Appendix-I to SCC.docx
docx • 0.03 MB
07- Appendix-II to SCC.docx
docx • 0.03 MB
07-Appendix-III to SCC.pdf
pdf • 0.62 MB
08-Section - VI Forms and Proceedures.doc
doc • 0.59 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].