| 1 | L1₹9.2 CrAdmitted-Finance I 910 JAHANGIR PURI NEAR BY ANAND MAYA HOSPITAL NORTH WEST DELHI DELHI 110033 UDYAM DL 06 0040830 | NORTH DELHI | DELHI | 110033 | ₹9.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹9.4 CrAdmitted-Finance | ₹9.4 Cr | L2 | Admitted-Finance |
| 3 | L3₹9.8 CrAdmitted-Finance | ₹9.8 Cr | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | JK Electric Engineers Pvt. Ltd. L2 | M/s cee kay Traders L3 | SATISH & CO L1 |
|---|---|---|---|---|---|---|
| 1.0011 KV 1 core 120 mm sqr cable | ||||||
| 1.01 | Supply of 1 core 120 mmsqr XLPE(E) , FRLS, 11kV Aluminium conductor armoured cables suitable for working voltage upto 11000 volts ,stranded,compact circular aluminum conductor, conductor screened with extruded semiconducting compound XLPE insulated, insulation screened with extruded semi conducting compound dry cured(Nitrogen gas cooled) from triple extrusion through common triple cross head (single point triple extrusion) in combination with copper tape cores laid up, Filler inner sheathed, galvanized steel strip armored and overall PVC sheathed black colour cable conforming to IS:7098 (Part II/1985) with latest amendments and as per specification detailed. The cable should satisfactorily operate between the temperature range of Minus 20 Degree Centigrade to 50 Degree Centigrade ( –20 °C to 50 °C ). | 57,680 | RM | 701 ₹4.0 Cr | 1,320 ₹7.6 Cr | 690 ₹4.0 Cr |
| 1.02 | LAYING /testing /commissioning of 11kV POWER CABLES _Main(1 core 120 mm square ) : Laying ,testing and commissioning of under ground cable in cable trenches 900mm below ground level,650 mm wide covered with sand(8 cms below the cable and 10 cms above the cable) Or As directed by the Engineer Incharge , & RC.C covers of 300 mm (Width) X 300 mm (Length) X 60 mm (Thickness)(excluding cost of RCC Cover), for covering under ground cable suitablly as per requirement for mechanical protection to the cable,including necessary connections, digging in extremely rocky soil & refilling with riddled soil,warning tape etc. including primary compaction of trenches for 1 core 120 mmsqr XLPE(E) , FRLS, 11kV Aluminium conductor armoured cables suitable for working voltage upto 11000 volts including proper dressing of the cable in an approved manner complete as required & as per specifications. Complete Job as per IS standards. Four cables to be laid in the cable trench. Trench length is approxiamately 14 Kms.(Interaxial spacing between cables be maintained @150 mm and spacing 150 mm from trench wall as per IS 1255. | 56,140 | RM | 301 ₹1.7 Cr | 40 ₹22.5 L | 300 ₹1.7 Cr |
| 1.03 | 11kV POWER CABLES _ Through HDPE PIPE 90 mm (1 core 120 mm square ) : Laying, testing & commissioning of cable as per item No. 1 including all accessossories required for sucessful installation . Including the cost of HDPE Pipe,collors and other accessories | 1,540 | RM | 1,200 ₹18.5 L | 350 ₹5.4 L | 790 ₹12.2 L |
| 1.04 | Cable Termination _ Indoor/outdoor Type for (1 core 120 mm square ): Supply ,Erection & commissioning of heat shrinkable type indoor termination along with necessary accessories to accommodate 11kV XLPE(E) aluminium cable listed at 1.01 , complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc. in an approved manner complete as required & as per specifications. | 112 | Set | 2,819 ₹3.2 L | 100 ₹11,200 | 3,000 ₹3.4 L |
| 1.05 | Straight Through Joints for 1 core 120 mm square : Supply ,Erection & commissioning of heat shrinkable type suitable for H.T Cable straight through joints along with boots (SILCAB-T) to accommodate following sizes of 11kV XLPE(E) aluminium cable , listed at 1.01 , complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc.in an approved manner complete as required & as per specifications. | 224 | Set | 5,235 ₹11.7 L | 100 ₹22,400 | 5,500 ₹12.3 L |
| 1.06 | Supply,installation,testing and commissioning of Earthing : Earthing with G.I. earth pipe 3 metre long, 40 mm dia through GI strip 25X3 mm . Complete job as per REC/IS standards | 14 | No | 2,409 ₹33,726 | 100 ₹1,400 | 4,000 ₹56,000 |
| 1.07 | Brick Masonary Chamber : Construction of brick masonry chamber 900x900x1050mm. inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover & frame to be not less than 38 kg (weight of cover 23kg & weight of frame 15 kg) & RCC top slab 1:2:4 mix (1 cement :2 coarse sand& : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand& : 10 graded stone aggregate 40 mm nominal size) & inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand&) 12 mm thick, finished with a floating coat of neat cement complete as per standard design with common burnt clay F.P.S. (non modular ) bricks of class designation 7.5 | 28 | No | 75,000 ₹21 L | 1,000 ₹28,000 | 25,000 ₹7 L |
| 1.08 | Supplying & making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand :4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom & 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required. | 140 | No | 1,369 ₹1.9 L | 100 ₹14,000 | 800 ₹1.1 L |
| 1.09 | Supply and fixing of Warning Tape for HT Cable , as per standards | 14 | Km | 28,396 ₹4.0 L | 100 ₹1,400 | 10,000 ₹1.4 L |
Tender Value
₹10.0 Cr
EMD Value
₹19.9 L
Closing Date
26 Dec 2025, 1:00 pmClosed
Superintending Engineer O and M Circle Bijbehara
Superintending Engineer O and M Circle Bijbehara
Construction of Underground Cabling System from Sheeshnag to Panchtarni
2025_PDD_297254_1
SEB/e-tender/ 02 of 2025-26
Open Tender
Electrical Works
180 days
Superintending Engineer O and M Circle Bijbehara
Please refer Tender documents.
7 documents required · 7 mandatory
₹5,000
Superintending Engineer O and M Circle Bijbehara
₹19.9 L
28 Jan 2026
4 Dec 2025
26 Dec 2025
4 Dec 2025
26 Dec 2025
4 Dec 2025
4 Dec 2025 - 20 Dec 2025
11 KV 1 core 120 mm sqr cable
Ring Main Unit(RMU)-4 way Type,2 isolators and 2 Circuit Breakers
Supply of 1 core 120 mmsqr XLPE(E) , FRLS, 11kV Aluminium conductor armoured cables suitable for working voltage upto 11000 volts ,stranded,compact circular aluminum conductor, conductor screened with extruded semiconducting compound XLPE insulated, insulation screened with extruded semi conducting compound dry cured(Nitrogen gas cooled) from triple extrusion through common triple cross head (single point triple extrusion) in combination with copper tape cores laid up, Filler inner sheathed, galvanized steel strip armored and overall PVC sheathed black colour cable conforming to IS:7098 (Part II/1985) with latest amendments and as per specification detailed. The cable should satisfactorily operate between the temperature range of Minus 20 Degree Centigrade to 50 Degree Centigrade ( –20 °C to 50 °C ).
LAYING /testing /commissioning of 11kV POWER CABLES _Main(1 core 120 mm square ) : Laying ,testing and commissioning of under ground cable in cable trenches 900mm below ground level,650 mm wide covered with sand(8 cms below the cable and 10 cms above the cable) Or As directed by the Engineer Incharge , & RC.C covers of 300 mm (Width) X 300 mm (Length) X 60 mm (Thickness)(excluding cost of RCC Cover), for covering under ground cable suitablly as per requirement for mechanical protection to the cable,including necessary connections, digging in extremely rocky soil & refilling with riddled soil,warning tape etc. including primary compaction of trenches for 1 core 120 mmsqr XLPE(E) , FRLS, 11kV Aluminium conductor armoured cables suitable for working voltage upto 11000 volts including proper dressing of the cable in an approved manner complete as required & as per specifications. Complete Job as per IS standards. Four cables to be laid in the cable trench. Trench length is approxiamately 14 Kms.(Interaxial spacing between cables be maintained @150 mm and spacing 150 mm from trench wall as per IS 1255.
11kV POWER CABLES _ Through HDPE PIPE 90 mm (1 core 120 mm square ) : Laying, testing & commissioning of cable as per item No. 1 including all accessossories required for sucessful installation . Including the cost of HDPE Pipe,collors and other accessories
Cable Termination _ Indoor/outdoor Type for (1 core 120 mm square ): Supply ,Erection & commissioning of heat shrinkable type indoor termination along with necessary accessories to accommodate 11kV XLPE(E) aluminium cable listed at 1.01 , complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc. in an approved manner complete as required & as per specifications.
Supply,installation,testing and commissioning of Earthing : Earthing with G.I. earth pipe 3 metre long, 40 mm dia through GI strip 25X3 mm . Complete job as per REC/IS standards
Straight Through Joints for 1 core 120 mm square : Supply ,Erection & commissioning of heat shrinkable type suitable for H.T Cable straight through joints along with boots (SILCAB-T) to accommodate following sizes of 11kV XLPE(E) aluminium cable , listed at 1.01 , complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc.in an approved manner complete as required & as per specifications.
Supplying & making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand :4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom & 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
Brick Masonary Chamber : Construction of brick masonry chamber 900x900x1050mm. inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover & frame to be not less than 38 kg (weight of cover 23kg & weight of frame 15 kg) & RCC top slab 1:2:4 mix (1 cement :2 coarse sand& : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand& : 10 graded stone aggregate 40 mm nominal size) & inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand&) 12 mm thick, finished with a floating coat of neat cement complete as per standard design with common burnt clay F.P.S. (non modular ) bricks of class designation 7.5
RCC protective cover of size 300 mm (width) x 300mm (Length) x 60 mm (Thickness) for underground cables
Reinstatement of roads (100 m x .7 m x 0.2 m thick) = 14 cums
Supply and fixing of Warning Tape for HT Cable , as per standards
Supply of of 120 mm² AB(Aerial Bunched Cable ) (3x120+1x95)mm² XLPE(11 kV, 3C + Earth) (stranded,compacted,circular almunium conductor screened with black extruded semiconducting compound,natural colored,XLPE insulated,Core screened with Black extruded semiconducting compound and one layer of copper tape and covered with black extruded PVC (Core identification by color tape marking Red,Yello
w and Blue with color tape placed longitudinally under the copper tape) and one bare messenger wire shall be stranded non compacted circular almunium alloy conductor. The cable should conform to IS ;8130-1984,IS;398(Part 4)-1994,IS 7098(Part2)-211 and IS 5831-1984 with upto date ammendments) . The cable should satisfactorily operate between the temperature range of Minus 20 Degree Centigrade to 50 Degree Centigrade ( –20 °C to 50 °C ).
Supply and fixing of Galvinized Nuts and Bolts.
Supply and fixing of Suspension/Tension Clamps with eye hook
Supply and fixing of Anticlimbing devices as required
Laying ,Installation ,testing and commissioning of of 120 mm² AB Cable (3x120+1x95)mm² XLPE(11 kV, 3C + Earth) as specified above as per IS/ REC Standard
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Supply and fixing of Heat Shrinkable Termination Kit outdoor Type suitable for 120 mm² AB(Aerial Bunched Cable ) (3x120+1x95)mm² XLPE(11 kV, 3C + Earth)as per REC Standards
Supply , Erection of 7.0 mtr Long GI (65 micron DFT single dip) octogonal poles uniformally tappered with thickness of 3mm with bottom/top Dia of 135 mm x 70mm & base plate of 225x225x12mm/pcd 250 mm provided with proper door opened gear box for connections on the bottom side with G.I. Foundation Bolts (J Type) M25x750 mm long (Set of 4 no.’s per pole , excluding the cost of RCC foundation.
Supply and fixing of Danger Plates with Clamps as per REC Standards
LT FEEDER PILLARS 3 PHASE:-
3 phase, 415V, 1no of 250 Amps incoming 3 TP MCCBs (Breaking 25KA) fitted with outgoing 03 No 100 Amps SP MCCBs, 1No.100Amps 3 pole MCCB for outgoing LT cables, Outdoor Type, Double door, compartmentalised, Distribution feeder Pillar suitable for outdoor installation , made out of CRCA sheet painted through 7-tank process with PU painted Busbars 4P, Aluminium with heat shrinkable sleeves and inter-connection with solid/strandred copper conductor wire/copper strips, gl&s neutral links, name plate & pad locking facility etc. etc., complete as required with detailed specification complete with all accesories 4 way Distribution Feeder Pillar.
Supply and fixing of Support Galvanised angle frame and legs (50mm x 50 mm x 6 mm) for Distribution Feeder Pillar , leg height 1m with 0.3m in soil approx 7m @4.50Kg per mtr
Supply and fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip (25x3 )mm
Cement grouting for support angle legs
LT FEEDER PILLARS SINGLE PHASE:-
1 phase 2 wire, 415V, 1nos of 100 Amps incoming SP MCCBs fitted with outgoing 04 No 32 Amps SP MCBs for Service Connections, Distribution Service Pillar suitable for outdoor installation , made out of CRCA sheet painted through 7-tank process with PU painted Busbars 2P, Aluminium with heat shrinkable sleeves and adequate capacities complete with all accesories 4 way Distribution Service Pillar.
Supply and fixing of Support Galvanised angle frame and legs (40mm x 40 mm x 3 mm) for Distribution Feeder Pillar with leg height 1m with 0.3m in soil approx [email protected] per mtr
Supply and fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip (25x3 )mm
Cement grouting for support angle legs
LV CABLES _Main(2Core 25 Sqmm):
Mid span straight through Jointing kit suitable for 11 KV ABC 120 mm² AB(Aerial Bunched Cable ) (3x120+1x95)mm² XLPE(11 kV, 3C + Earth)
Supply , installation of Galvanised Stay Set with 50x8mm stay clamp, guy insulator(2Nos.), anchor plate (200x 200 x 6 )mm, nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
RCC protective cover of size 300 mm (width) x 300mm (Length) x 60 mm (Thickness) for underground cables
Supply : Supply of (2Core 25 Sqmm)LV (1.1KV) Grade XLPE insulated PVC sheathed, Aluminium conductor, armoured , FRLS, LV Power cable , conforming to to IS:7098 (Part II/1985) with latest amendments and as per specification detailed in SBD,
Supply and fixing of Earthing Complete by GI Pipe 40 mm 3 mtr long through GI Strip (25x3 )mm
Reinstatement of roads (100 m x .7 m x 0.2 m thick) = 14 cums
Supplying & making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand :4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom & 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
Straight Through Joints for 2 core 25mmsqr : Supply ,Erection & commissioning of heat shrinkable type two Core L.T Cable straight through joints along with boots (SILCAB-T) to accommodate following sizes of 1.1kV XLPE(E) aluminium cable complete with all kit contents including earth continuity connection along with 2 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc.in an approved manner complete as required & as per specifications.
Supply and fixing of Warning Tape for LT Cable
Cable Termination _ Indoor/outdoor Type for 2 core 25 mm square : Supply ,Erection & commissioning of heat shrinkable type indoor termination along with necessary accessories to accommodate following sizes of 1.1kV XLPE(E) aluminium cable complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc. in an approved manner complete as required & as per specifications.
25 KVA Distribution Transformer
LV CABLES _Main(2Core 25 Sqmm): Laying , Testing & Commissioning : Laying of (2Core 25 Sqmm):LV (1.1KV) Grade XLPE insulated PVC sheathed, Aluminium conducto, armoured , FRLS, LV Power cable , conforming to to IS:7098 (Part II/1985) with latest amendments and as per specification detailed in SBD, 750mm. below ground level 400mm wide ,covered with sand (80mm below and 100 mm above),R.C.C covers of 300 mm (Width) X 300 mm (Length) X 60 mm (Thickness)(excluding the cost of RCC cover), for covering under ground cable suitablly as per requirement for mechanical protection to the cable,warning tape,including necessary connection, excavation & refilling of trenches for the following sizes as per specification. Two cables to be laid in the cable trench. Trench length is approxiamately 2.5 Kms
Brick Masonary Chamber : Construction of brick masonry chamber 900x900x1050mm. inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover & frame to be not less than 38 kg (weight of cover 23kg & weight of frame 15 kg) & RCC top slab 1:2:4 mix (1 cement :2 coarse sand& : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand& : 10 graded stone aggregate 40 mm nominal size) & inside plastering with cement mortar 1:3 (1 cement : 3 coarse sand&) 12 mm thick, finished with a floating coat of neat cement complete as per standard design with common burnt clay F.P.S. (non modular ) bricks of class designation 7.5
Supply,installation,testing and commissioing of 11/0.433kV, 25 kVA 3-phase Distribution Transformers with Bimetallic Terminal Connectors Energy Level-1 as per latest classification(Previous Level II), Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate with LV Bimetallic terminal connection suitable for vertical take off of cable.
Supply and fixing of 11 kV Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type as per TS given in SBD
Supply and fixing of 35 mm² Single-Core Cable,1.1kV Grade XLPE Insulated Stranded Conductor FRLS type
LV CABLES _Main(2Core 25 Sqmm): _ Through HDPE PIPE 63 mm (2Core 25 Sqmm ) : laying, testing & commissioning of cable as per item No. 4.02 above including all accessossories required for sucessful installation . Including the cost of HDPE Pipe,collors and other accessories
Supply, Installation, testing and commissing of S.T Pole 9mtr Long SP-30, ST-410 with base plate & cap for HT. Strictly as per REC standards
Supply and fixing of LT Shackle with mukhi clamps including nuts & bolts
Supply and fixing of 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply and fixing of 11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Supply and fixing of GI Channel/Angle/Flat of sizes including clamps
Supply and fixing of Galvinized Nuts and Bolts.
Supply ,installation, testing and commissioning of LT Distribution Box for 25 kVA DTR with 40 Amp MCCB 3P 16 kA for incomer & 25 Amp MCCB 3P 16 kA/10 kA 1 No each (=2No.) for Outgoing Circuits .
Cement bottoming 1:2:4 mix as per Standards 0.5cum /pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Painting of poles with one coat of red oxide and two coats of Aluminium paint as per Standards. This also includes numbering of ploes with paint, submission of Pre and Post Execution photographs duly anthenticated by AEE/Incharge Engineer concrened.
Supply and fixing of Danger Plates with Clamps
Supply, Installation, testing and commissing of S.T Pole 8mtr Long SP-13, ST-410 with base plate & cap for HT. Strictly as per REC standards
Supply and fixing of 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type , as per TS given in SBD
Supply, installation,testing and commissioning of 11kV 3 phase indoor terminating kit to be used with cables - 185 sq.mm.
Supply, installation,testing and commissioning of 11kV 3 phase outdoor terminating kit to be used with cables - 185 sq.mm.
Supply and fixing of Cable route Markers.
Excavation in any type of soil including hard laterite soil.
Refilling of excavated soil
Sand for cushioning of the cables in the trench.
Cement Tiles of size 300mm length x250mm width x 37mm thick as a protective cover for underground cables
Earthing of RMU --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 50 mmx6 mm for connection of RMU body as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
Cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded granitic or basaltic stone aggregate 40 m nominal size for foundations)
Centering and shuttering including struttings, propping etc and removal of formwork.
15 mm cement plaster 1:4 (1 - cement: 4 -fine sand) for foundations.
Constructing masonry chamber 600x600x900mm.inside, in brick work in cement mortar 1:4 (1 cement : 4 coarse sand) including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover & frame to be not less than 38 kg (weight of cover 23kg & weight of frame 15 kg) & RCC top slab 1:2:4 mix (1 cement :2 coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine s& : 10 graded stone aggregate 40 mm nominal size) &inside plastering with cement mortar 1:3 (1 cement : 3 coarse s&) 12 mm thick, finished with a floating coat of neat cement complete as per st&ard design with common burnt clay F.P.S. (non modular ) bricks of class designation 7.5
Supply and fixing of Wire mesh fencing around the packaged RMU of size upto 8'x4 ' made out of wire mesh 1"x1" squre including fixing in cement 1:2:4 including welding cutting etc. complete in all respects.
11 KV Isolator
Supply, installation,testing and commissioning of 11kV, three core 120 mm2 Aluminium round wire Armoured XLPE Cable , FRLS (one spare cable)
Supply, installation,testing and commissioning of 11KV Isolators with EB as per IS standard
Supply, installation,testing and commissioning of 11KV Isolators without EB as per IS standard
Design ,fabrication,supply of GI Steel Structure as per requirement(complete job)
Supply, installation,testing and commissioning of Cable Termination Kits (indoor/outdoor) suitable for 120mmsqr 3 core cable
Supply and fixing of Galvinized Nuts and Bolts.
Cement bottoming 1:2:4 mix as per Standards 0.7cum / Block as per requirement
Supply and fixing of Danger Plates with Clamps
Supply, installation,testing and commissioning of 11 kV, 1 core(4 runs) 120sq.mm, Al conductor,XLPE, insulated, armoured cable (from the RMU to the transformer)
Earth work in excavation by mechanical means (hydraulic excavator) in trenches for foundations, drains, pipes, cables etc. (not exceeding 1.5 m in width) and for shafts, wells, cesspits and the like not exceeding 10 sqm on plan, including dressing of sides and ramming of bottoms lift upto 1.5 m, including getting out excavated earth and disposal of surplus excavated earth as directed, within a lead of 50 metres:
P/Laying of Nallah stone soling, handpacked in bed incl. all carriages complete
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering. All work up to plinth level. 1:4:8 (1Cement: 4 fine sand: 8 graded slone aggregate 40mm nominal Size), includi
ng all carriages.
Providing and laying in position cement concrete of specified grade including curing but excluding the cost of centring and shuttering. All work upto plinth level with:1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) including carriage of materials
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level Thermo-Mechanically Treated bars of grade Fe-500D or more.
Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia and length (hold fast lugs or with dash fasteners shall be paidfor separately): imported Wood
Providing and fixing panelled or panelled and glazed shutters for doors, windows and clerestory windows fixing with butt hinges of required size with necessary screws, excluding panelling which will be paid for separately, all complete as per direction of Engineer-in-charge. (Note: -Butt hinges and necessary screws shall be paid separately). imported Wood
Providing and fixing wire gauze shutters using galvanized M.S. wire gauze of average width for aperture 1.4 mm in both directions with wire of dia. 0.63 mm for doors, windows and clerestory windows with ISI marked M.S. pressed butt hinges bright finished of required size with necessary screws as per direction ofEngineer-in charge : imported Wood (same above vide quantity No. 8.07)
Providing & Fixing 12 mm thick pre-laminated particle board (decorative lamination on both sides) grade-1, medium density flat pressed three layer particle board FPT-I or graded wood particle boord FPT-1, IS: 3087 arked, honded with BWP rope synthetic resin adhesive as per IS: 848 and pre aminated conforaing to IS:12823, Grade-1. Type-11 marked
Providing and fixing of 4 mm thick glass panes including Beading & necessary nails, complete job
Providing and fixing of Gi Sheets over Soffit And Exterior Walling Of Gi Sheet 3mm thick of panelling type .
P/F of 12 mm thick plywood ceiling for soffits walls & Ceiling on woodwork in false ceiling, walls over whole area including cost of necessary adhesive &cost of nails etc. complete job
Providing & fixing Hi-rib coated galvalume colour GI sheets 0.50 mm TCT having a erest fasteners height of reputed of 28-32make mm at with 195mm purlinspitch sheet using usingself selfdrilling drillingand andself self tapping tapping 471.38 fasteners (including cost of all material, leads, lifts and carriages etc upto site of work complete) with required head load complete. as approved by Engineer-in-charge
Providing and fixing of plain Gi Sheets In Interior of washroom Without Corrugations 2mm thick
P/Fixing of Havells ventil air DSP 380 mm Exhaust fan including fixing & dismentalling of wall for the fixing of fan if required etc all complete job
Lighting point: One Lighting point shall incl, wiring for lighting points il 1.5 Sq.mm PVC insulated Copper wire & 2.5 Sq.mm PVC Insulate multi-strand Copper wire for lighting Sub- nains, 6 Amp one way swile 2 mm thick PVC conduit/Channel with bends, Junction boxes ele Amp S Pole MCB 10 Amp DP MCB, 2 way DB for Housing MCB an Hyle? Sheet with wooden bas recessed in walls with accessories with 05 No. ceiling lights
One Fan point shall incl, wiring for Lighting points in 1.5 Sqm PVC insulated Multi Strand Copper wire 1200 non ceiling fan/225 mm exhaust fan with ceiling roses & PVC Square block, 350 Watts electronic fan dimmer,2 mm thick PVC conduit/Channel with bends, Junction baxes etc, 6, Amp S Pole MCB, 10 Amp DP MCB, 2 way DB for Housing MCB for lighting circuits and Hylem Sheet with wooden box recessed in walls with accessories
Heating point One Heating point shall incl, wiring for heating points in 2.5 Sq mm PVC insulated Multi-Strand Copper wire & 4 Sq mm PVC insulated multi strand Copper wire fur heating Sub-mains, 16 Amp switch socket combined, 2 mm thick PVC conduit/Channel with hends, Junction boxes ele, 10 Amp S Pole MCB, 2 way DB for Housing MCB and Hylem Sheet with wooden box recessed in walls with accessories
Charger point One Charger point shall incl, wiring in 1.5 Sq mm PVC insulated Multi Strand Copper wire & 2.5 Sq mm PVC insulated multi strand Copper wire fur heating Sub mains, 16 Amp switch socket combined, 2 mm thick PVC conduit/Channel with hends, Junction boxes ele, 10 Amp S Pole MCB, 2 way DB for Housing MCB and Hylem Sheet with wooden box recessed in walls with accessories
Transport for carrying material Mechanically from Baltal To Panjtharni average lead of 20kms
Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid , 10 liter low level white vitreous china flushing cistern and CP flush bend with fittings and C.I. brackets, 40mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required: W.C. pan with ISI marked white solid plastic seat and lid.
Providing fixing testing & commisioning soil, waste and vent pipes IS 13592 & fittings (IS: 14735 ) suitable to rubber ring joints , which includes bends, T-ee, reducers,rubber ring, jointing, junctions, clean out plug , cowls, offsets, collar, M.S holder-bat clamps, access pieces, (P or S) trap of self cleansing design .etc. complete including jointing
110 mm dia. PVC SWR socketed pipe with rubber ring joints as per IS:13592 Type-B
75 mm dia. PVC SWR socketed pipe with rubber ring joints as per IS:13592 Type-B
Providing and Fixing of PVC Floor Traps 110 mm of standard makeand all other fittings required as approved by engineer icharge
75mm Bend
75mm Socket
Proving fixing testing and commissioing of CP Fittings of standard make and as approved by engineer incharg
Providing and fixing 15 mm nominal bore C.P. brass bib cock of approved quality conforming to IS : 8931
Providing and fixing 15 mm nominal boreCP Brass Single lever telephonic wall mixer of approved brand conforming to IS : 8931
Providing and fixing 15 mm nominal bore C.P. Sink Mixer approved quality jaquar conforming to IS : 8931
Providing and fixing 15 mm nominal bore C.P. Washbasin Mixer approved quality jaquar conforming to IS : 8932
15 mm nominal bore C.P. brass angle valve for of approved make conforming to IS : 8931
Two way bib cock & faucet
CP grating rectangular type with open circular lid
Providing and fixing PTMT soap dish holder having length of 125mm, breadth 90 mm, height of 70 mm with concealed fitting arrangements, weighing not less than 96gms.
Providing and fixing PTMT Liquid soap container of 350 ml. capacity with concealed fitting arrangements etc complete job
Providing fixing of CP/ PVC tube connceting pipe with sink/basin/ flushing cistern and all other fitting accessories all complete job as per directions of site incharge
Providing and fixing on wall 50 LTRS Electric
Geyser of approved brand Jaquar with ABS Body. Equivalent as Per Make List with necessary electric fittings & CPconnections etc all complete
Providing and fixing ball valve PPR of approved quality complete
Pilfer resistant 11 Kv metring kisok suitable for Housing Resign CTs,PT and Trivector meter Fabricated out of M.S Sheet of thickness not less than 2mm duly powder coat painted.The foundation base should be of MS Channel not less than 100*50*8.It should have two chambers HV chamber and LV Chamber both having one sided hinged door arrangement .The LV Chamber both having shall be suitable for installation of CT ,PT and termination of 11 Kv cable Kit.It should be possible to take meter reading manually through CMRI and compuer without opening the LV Chamber door ,each panel should contain following items a)Single Phase indoor type resign cast curent Transformer suitable for 11 KV metering having CTR compatable to Distribution Transformers having rating from 25KVA to 63KVa b)11kv/110v,3 phase potential transformer c)Copper bus bar duly insulated with monoplaster tape d)1 lot PVC copeer wire flexible multi-standard of required size for secondary connections . For CT size the minimum wire size should be 4mm Sq (RYB) and for the PT wiring minimum size shall be 2.5mm Sq (RYB). CT and PT wiring routed through separate rigid G.I Conduit. e)Copper Lugs preferably ring type duly crimped for termination of wires and tapes f)Grounding bus of minimum 40mm copper, 25cm long fixed to the unit in HV chamber. The CTs, PT meter and 11kV Cable sheath shall be grounded to the bus through grounding wire (green) of min size 10mm2
DLMS compactable HT, trivector meter 3-phase 4-wire 5amp and 110/63.5 volts.
Pedestal made out of G.I Channel of size 75 x 40 mm or angle iron of size (65 x 65 x 6) mm, duly painted as per site requirement for mounting of metering panel including concrete foundation wherever required including cost of nuts and bolts
3 Core 11 kV Aluminium cable XLPE armoured 50 mm
3 Core 11 kV Aluminium cable XLPE armoured 35 mm2 including cost of clamp for its fixing where ever required.
Heat shirinkable outdoor cable termination kit suitable for 3*35 mm Sq 11kv cable
40 mm Dia G.I pipe or 20 mm G.I Rod , 2.5 meter and 25 *25* mm iron plate as per standards for grounding of metering unit.
Operation & Maintenance Cost for Second & Third Year
Second year(providing of Switch Board Attendents /Operators in Control room/Skilled workers per shift at camping site /Padav for two shifts 2
No. each shift including maintainence charges)
Supply and fixing of 11 kV Horn Gap Fuse Set 3 Phase 200A , as per TS given in SBD
Supply, installation,testing and commissioning of 11 kV, Ring Main Unit ,SF6 Insulated, out-door type, Non-Extensible type,breaking capacity 25 KA for one second with SF6 circuit breaker / VCB self powered with O/C + E/F Relay comprising of a) 11kV 630 Amp Motorised isolators including earthing Switches with making capacity 52kA, having mechanical ON/OFF, earth indications with fault current Indicator. b) 11kV ,200 Amp motorised Spring operated, Circuit breakers with earthing switches, connecting the RMU to Supply transformer. c).Copper Bus Bar of 630 Amp rating. d). 1 No Numerical Aux. Powered relay having non directional O/C and E/F protection (for each ciruit breaker). d). The Circuit Breaker enclosures shall be outfitted with a communicable-type numerical (feeder protection) relay, i.e., one for each circuit breaker. The relay shall also interface via an RS 485 port in order to send, as a minimum, real-time phase current , readings using the MODBUS protocol. e) Incomming Isolator having FPI with electrical reset Contact /facility. f) All necessary Potential free contacts for indications relevent to RMU monitoring and control . g) Capacitor voltage dividers serving Live-Line Cable indicators in each breaker and Isolator.
Supply of 120mmsqr 1 core cable as specified at 1.01
Supply of Cable Termination _ Indoor/outdoor Type for (1 core 120 mm square ) as specified at 1.04
Straight Through Joints for 1 core 120 mm square as specified at 1.05
Supply of of 120 mm² AB(Aerial Bunched Cable ) (3x120+1x95)mm² XLPE(11 kV, 3C + Earth) as specified at 1.12
Supply of Heat Shrinkable Termination Kit outdoor Type suitable for 120 mm² AB(Aerial Bunched Cable ) (3x120+1x95)mm² XLPE(11 kV, 3C + Earth)as per REC Standards
Supply of Mid span straight through Jointing kit suitable for 11 KV ABC 120 mm² AB(Aerial Bunched Cable ) (3x120+1x95)mm² XLPE(11 kV, 3C + Earth)
Supply of (2Core 25 Sqmm)LV (1.1KV) as specified at 4.01
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.25 MB
SBDUGPanjtoShesh.pdf
Tender Documents • 0.83 MB
AnnexureA.pdf
Other Document • 0.30 MB
StandardDrawings.pdf
Other Document • 36.45 MB
TECHNICALSPECIFICATIONSCABLING.pdf
Additional Documents • 7.31 MB
BOQ_963561.xls
BOQ • 0.35 MB
TechnicalSpecificationRingMainUnitFinal.pdf
Additional Documents • 0.79 MB
Download all tender documents and submit your bid