Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.8 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹33.7 L+₹2.3 L (7.25%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 3 | L3₹39.4 L+₹8.0 L (25.4%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 4 | L4₹42.2 L+₹10.8 L (34.3%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST BIDDER | |
| 5 | L5₹44.7 L+₹13.3 L (42.4%)Rejected-Finance | L5 | Rejected-Finance OTHER THAN LOWEST BIDDER |
| Sl No | Description | Qty | Unit | niranjan singh and company L1 | DEMROT ELECTRICAL WORKS L3 | Sadhana Enterprises L4 | KIRTIMAN TRADERS L5 | ENGINEER CORPORATION OF INDIA L2 |
|---|---|---|---|---|---|---|---|---|
| 1.00 | Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH (Make-Secure/ L&T/ HPL/ Schneider) and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls :- (Incl Ser No 1.01, 1.02 & 1.03)
Make - L&T/IndoAsian/Havells | 4 | Each Job | 2,25,000 ₹9,00,000 Lowest | 2,50,000 ₹10,00,000 | 4,10,000 ₹16,40,000 | 4,00,000 ₹16,00,000 | 2,82,000 ₹11,28,000 |
| 1.01incl All as per item no 1.00 above (A) OUTER SHELL:- The outer shell shall be made of 3.0 mm thick stainless steel (SS 316) & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. (B) INNER SHELL:- Inner shell made of 2.0 mm thick stainless steel (SS 316) compartmentalized for each control gear, front openable single door system lockable /openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers & air vent gasket for natural flow of air. | ||||||||
| 1.02incl All as per item no 1.01 & 1.02 above 'U' type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer/ outgoing MCCBs and TPN copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB. The TPN bus bar and extension links shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made of nonhygroscopic, noncombustible, track resistant, high strength SMC material at suitable interval through out the length of the TPN bus bar. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided on bus bar chamber. All control wires shall be with not less than 1.5sqmm multi strand copper conductors and shall be properly bunched, tied, ferruled for proper identifications and crimped with adequate size of lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.15mm zinc metal coated should be used at the bottom. Indicating lamps LED type, 230 volts, AC at the incomer of the unit to show three phase availability at the outgoing of incomer. An inspection lamp with I I watt LED shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 & carry the following controls:- | ||||||||
| 1.03incl All as per item no 1.00, 1.01 & 1.02 above 1. Incoming:- One number MCCB 400 Amp, 4 pole, Ics 36 kA, 415 volts, 50 Hz with thermal, magnetic & microprocessor release adjustable between 40% to 100% against overload setting. (Here specify make & Cat ref No. of MCCB) 2. Outgoing:- (a) Six numbers MCCB 63 Amp, 4 pole, Ics 25 kA, 415 Volts, 50 Hz, with microprocessor release adjustable between 40% to 100% against overload setting.(here specify make & Cat ref No.of MCCB). (b) One number MCB double pole 32 amp 'C' series of breraking capacity 10kA, ISI marked. (here specify make & cat ref No. of MCB) (c) One number timer 16amp, 230 volts, Astro type. (Specify make & Cat ref No. of timer) (d) One number contactor 2 pole 40amp with 2 NO contacts. (Specify make & cat ref No. of contractor). (e) 3 way selector switch for manual ON/OFF/AUTO switching of street light fittings. (f) Digital Ammeter flush pattern type square dial 96 x 96 mm alongwith selector switch - 01 No and suitable CT of ratio 0-500 Amps (g) Digital Voltmeter flush pattern type square dial 96 x 96 mm alongwith selector switch - 01 No and suitable PT of ratio 0-500 Volts. (h) Complete control panel wiring with stranded copper conductor of suitable size along with one set indicator lamp for R,Y & B for each incoming and outgoing feeder. | ||||||||
| 2.00 | M&L earthing complete with GI strip as earth lead and MS galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32 x 6 mm with GI pipe, nuts, bolts and washers complete upto and including test point made out of 40 x 3mm GI flat, PCC pit of required size in PCC 1:2:4 type B1 and RCC cover with frame including plastering and white wash, charcoal, common salt 15cm at round the earth plate, watering pipe 20mm med grade/galvanized and 40mm dia GI pipe medium grade for GI strip protection with GI funnel including dismantling old earthing complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2009.
Notes: (i) The unit rate includes for 40mm diam medium grade protection pipe and earth lead upto 7.50 meter.
(ii) Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured & paid seperately separately.
(iii) PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional height of watering pipe, bends, elbow etc shall be deemed to be included in the unit rate. | 10 | Each Job | 3,000 ₹30,000 Lowest | 3,000 ₹30,000 Lowest | 3,000 ₹30,000 Lowest | 3,500 ₹35,000 | 3,400 ₹34,000 |
| 3.00 | Supply and replace 32mm x 6 mm GI strip as in earth continuity conductor fixed to wall or pole or recess or chases or burried in ground or drawn in conduit pipe or any other indicated situation for loop earthing etc as required complete all as specified and directed. | 100 | RM | 200 ₹20,000 | 80 ₹8,000 | 75 ₹7,500 | 70 ₹7,000 | 65 ₹6,500 Lowest |
| 4.00 | Taking out old unservicible cable and Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of Size 16 Sqmm X 4 core, complete all as specified and directed. | 1,000 | RM | 90 ₹90,000 Lowest | 150 ₹1,50,000 | 124 ₹1,24,000 | 160 ₹1,60,000 | 94 ₹94,000 |
| 5.00 | All as per item No. 4.00 but Size 25 Sqmm X 4 core complete all as specified and directed. | 1,000 | RM | 140 ₹1,40,000 | 170 ₹1,70,000 | 163 ₹1,63,000 | 210 ₹2,10,000 | 132 ₹1,32,000 Lowest |
| 6.00 | All as per item No. 4.00 but Size 35 Sqmm X 3.5 core complete all as specified and directed. | 700 | RM | 150 ₹1,05,000 | 210 ₹1,47,000 | 185 ₹1,29,500 | 240 ₹1,68,000 | 145 ₹1,01,500 Lowest |
| 7.00 | All as per item No. 4.00 but Size 70 Sqmm X 3.5 core complete all as specified and directed. | 600 | RM | 320 ₹1,92,000 | 350 ₹2,10,000 | 340 ₹2,04,000 | 440 ₹2,64,000 | 270 ₹1,62,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
13 Aug 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE NASIRABAD
GE Nasirabad Military Engineer Services Pin 305 601 Rajasthan
REPAIR/ REPLACEMENT/ IMPROVEMENT OF LT ELECTRIC OH LINE/MCCBS/ELECTRIC CABLES AND OTHER CONNECTED WORKS NASIRABAD MIL STN GE NASIRABAD
2025_MES_721069_1
8562/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Nasirabad
As per Tender Documents
6 documents required · 6 mandatory
₹500
Yes
GE NASIRABAD
₹80,000
Yes
4 Sept 2025
17 Jul 2025
15 Aug 2025
17 Jul 2025
13 Aug 2025
1 Aug 2025
17 Jul 2025 - 1 Aug 2025
Amount
Supplying, installation, testing & commissioning CPRI pproved outdoor cubical type LT feeder pillar box suitable for 415V, 3 phase, 4 wire 50 Hz, AC supply system fabricated from stainless steel (SS 316) totally enclosed, dust, weather & vermin proof, 3.0 mm thick for outer shell and 2 mm thick for inner shell having TPN copper busbar of rating 1.5 times that of controlling MCCB supported on SMC insulators with short circuit withstand capacity 35 MVA for I second, bottom base channel of MS section not less than 100 mm x 50 mm x 5 mm thick, entire panel shall have a common aluminum earth bar of size 25 mm x 5 mm at the rear with 02 Nos earth stud, solid connections from main bus bar to switch gears with required size pf copper bus bars and control wiring with minimum 1.5sqmm PVC insulated copper conductor cable, cable alleys, cable gland plates in two half including tamper proof digital energy meter to measure voltage, current, PF, KWH, KVAH, KVARH (Make-Secure/ L&T/ HPL/ Schneider) and general construction confirming to IS:8623 / 93 and mounted on suitable PCC foundation with following detailed specifications & controls :- (Incl Ser No 1.01, 1.02 & 1.03) Make - L&T/IndoAsian/Havells
incl All as per item no 1.00 above (A) OUTER SHELL:- The outer shell shall be made of 3.0 mm thick stainless steel (SS 316) & MS angle section 50x50x6 mm frame with front & back openable, single door system lockable/ openable by keys from both sides having flush pattern fancy locks with louvers & air vents gasket for natural flow of air. The bottom of the outer shell contains a detachable plate having provision for entry of armoured cable of adequate size with glands. The dimension of the outer shell should be adequate size with glands. The dimension of the outer shell should be adequate to accommodate inner shell described below giving 50 mm space all around & shall be fabricated in such a way that the complete inner shell alongwith its control gears & accessories could be taken outside without disturbing outer shell. The outer shell shall be mounted on a zinc metal coated stand. Provision of threaded earthing stud at bottom & lifting lugs of suitable size at top to lift the feeder pillar box safely shall be made. Computers cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided. The degree of protection of outer shell shall be IP-54. (B) INNER SHELL:- Inner shell made of 2.0 mm thick stainless steel (SS 316) compartmentalized for each control gear, front openable single door system lockable /openable by keys from both sides having chromium plated fancy locks (2 Nos in each compartment) having louvers & air vent gasket for natural flow of air.
incl All as per item no 1.01 & 1.02 above 'U' type gasket shall be used to make the inner shell completely vermin proof & to accommodate incomer/ outgoing MCCBs and TPN copper bus bar and extension links of rating not less than the 1.5 times the rated capacity of the respective MCCB. The TPN bus bar and extension links shall be insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size 'F' class insulators made of nonhygroscopic, noncombustible, track resistant, high strength SMC material at suitable interval through out the length of the TPN bus bar. Computer cut self adhesive vinyl danger notice plate having conventional symbol of bone & skull be provided on bus bar chamber. All control wires shall be with not less than 1.5sqmm multi strand copper conductors and shall be properly bunched, tied, ferruled for proper identifications and crimped with adequate size of lugs. The cubical shall have a bottom channel of size 75x40 mm duly coated with zinc metal coating. A detachable predrilled gland plate of thickness 3.15mm zinc metal coated should be used at the bottom. Indicating lamps LED type, 230 volts, AC at the incomer of the unit to show three phase availability at the outgoing of incomer. An inspection lamp with I I watt LED shall be fitted on top side of inner shell. The degree of protection for inner shell shall be IP-42 & carry the following controls:-
M&L earthing complete with GI strip as earth lead and MS galvanized steel earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate is not less than 1.5 mtr below normal ground level connected to galvanized iron strips 32 x 6 mm with GI pipe, nuts, bolts and washers complete upto and including test point made out of 40 x 3mm GI flat, PCC pit of required size in PCC 1:2:4 type B1 and RCC cover with frame including plastering and white wash, charcoal, common salt 15cm at round the earth plate, watering pipe 20mm med grade/galvanized and 40mm dia GI pipe medium grade for GI strip protection with GI funnel including dismantling old earthing complete all as specified and directed as shown in electrical plate No 3 of SSR Part-I 2009. Notes: (i) The unit rate includes for 40mm diam medium grade protection pipe and earth lead upto 7.50 meter. (ii) Any variation in length of earth lead and protection pipe beyond 7.5 m shall be measured & paid seperately separately. (iii) PCC pit shall be provided at least 500mm away from the pit and not on the earth pit itself and the extra cost of additional height of watering pipe, bends, elbow etc shall be deemed to be included in the unit rate.
Supply and replace 32mm x 6 mm GI strip as in earth continuity conductor fixed to wall or pole or recess or chases or burried in ground or drawn in conduit pipe or any other indicated situation for loop earthing etc as required complete all as specified and directed.
Taking out old unservicible cable and Supply, laying & testing XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of Size 16 Sqmm X 4 core, complete all as specified and directed.
All as per item No. 4.00 but Size 25 Sqmm X 4 core complete all as specified and directed.
All as per item No. 4.00 but Size 35 Sqmm X 3.5 core complete all as specified and directed.
All as per item No. 4.00 but Size 70 Sqmm X 3.5 core complete all as specified and directed.
All as per item No. 4.00 but Size 120 Sqmm X 3.5 core complete all as specified and directed.
All as per item No. 4.00 but Size 240 Sqmm X 3.5 core complete all as specified and directed.
All as per item No. 4.00 but Size 400 Sqmm X 3.5 core complete all as specified and directed.
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth for pole foundation, cable trench, etc and getting out in any type of soft/hard soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm each complete all as specified and directed.
Removing excavated materials (soil) to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
S & F Double Wall Corrugated(DWC) HDPE Pipe as per new IS-16205 (for electrical cable uses) in protection of UG Cable laid in trenches of following sizes complete all as specified and as directed. Note : Cost of pipe coupler with rubber ring is deemed to be included in the unit Quoted Rate.
All as per item No. 14.00 but 63 mm Outer Dia x 50 mm Inner Dia Pipe
All as per item No. 14.00 but 110 mm Outer Dia x 95 mm Inner Dia Pipe
All as per item No. 14.00 but 250 mm Outer Dia x 215 mm Inner Dia Pipe
S & F in repair MCCB, 415 Volts, 50 Hz, thermal magnetic release type, Ics=100% Icu with adjustable overload setting and adjustable short circuit setting, including spreader terminals and phase barrier fixed in existing panel board by providing suitable nuts, bolts, washers, etc including taking out old unserviceable one for the following capacity complete all as specified and directed :-
All as per item No 15.00 above MCCB, 4 pole, 400 amps having rapturing capacity 36kA all as specified and as directed.
All as per item No 15.00 above MCCB, 4 pole, 250 amps having rapturing capacity 36kA all as specified and as directed.
All as per item No 15.00 above MCCB, 4 pole, 200 amps having rapturing capacity 36kA all as specified and as directed.
All as per item No 15.00 above MCCB, 4 pole, 160 amps having rapturing capacity 36kA all as specified and as directed.
All as per item No 15.00 above MCCB, 4 pole, 100 amps having rapturing capacity 36kA all as specified and as directed.
All as per item No 15.00 above MCCB, 4 pole, 63 amps having rapturing capacity 36kA all as specified and as directed.
M & L boaring holes horizontally under Road by trenchless technology without damaging the surface of road as per given/ directed depth below the road surface with the help of boring machine/ or by manual means and laying of DWC Pipe of any dia for passing of UG cable all as specified and as directed. (Note : DWC pipe laid shall be measured seperately).
Repairing and painting of indoor/outdoor type LT panel board mounted on angle / PCC floor of any size with and including replacement of unserviceable switch/control gears, connector, indicator lamps, panel door lock and other minor repairs including rewiring and extension of incoming and outgoing cables (cable excluded) by opening of loops/making joints and providing cable lugs /thimbles as reqd including repairing rusted part of sheet metal door with existing size MS sheets by necessary arc/gas welding and removing all dirt, dust etc. with air blower and painting complete panel board with two coats of synthetic enamel spray painting over a coat of red oxide primer complete all as specified and directed. Note: (i) Cost of providing aluminium thimbles, earth and neutral link, insulator, hylem sheet, any type of screws or any other minor spares of any type as required at site is deemed to be included in the quoted rate. (ii) MCCB, MCB, aluminium bus bar, indicator lamp, Amp / Volt meter or any other major parts required for relacement shall be measured and paid serately in relevent item.
S & F in replacement LED type indicating Lamp for indication of RYB complete all as specified and directed.
S & F in repair Digital LED Voltmeter range 50-520 V flush type all as specified and as directed.
S & F in repair Digital LED Ammeter range 0-100 Amps, flush type all as specified and as directed.
S & F in repair MCB TPN 63 Amps 440 volts all as specified and as directed.
S & F in repair MCB TPN 40 Amps 440 volts all as specified and as directed.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m including taking out old unserviceable rubber matting and removing from site of work complete all as specified and directed.
Cutting unaxious green growth and wild grass, bushes, shrubs by manual labour or by machine at Electrical Installation Premises, around Pole, Electric LT Panel, Bus Bar Chambers, along the boundary Fencing, removing rubbish from the Site of work and deposting where directed not exc. 100 Metre from the starting point, complete all as specified and as directed. Note : The Item shall be operated maximum 2 times in the entire period of the Contract and the measurement will be taken every time independently for Payment.
M & L in repair for loose filling with broken stone or boulder aggregates of gauge 40 to 80 mm in soakage pits, soakage wells, on open space etc. and taking out old soiled aggregate complete all as specified and as directed.
ENGINEER CORPORATION OF INDIA (BID ID -3385002)
DEMROT ELECTRICAL WORKS (BID ID -3392712)
Sadhana Enterprises (BID ID -3391920)
KIRTIMAN TRADERS (BID ID -3379995)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .