AGE (I) Ayodhya Cantt
Asst Garrison Engineer (I), Military Engineer Services, Ayodhya Cantt PIN-224001
REPAIR/REPLACEMENT AND MAINTENANCE OF STREET LIGHTS SECURITY LIGHTS UNCTION BOX, STREET LIGHT BRACKETS CLAMPS TIMER SWITCHES AND CABLES INCLUDING CONNECTED ITEM OF WORKS OF DRC OTM TRG AREAS MH 146 BDE OTM AREAS AND OTHER OTM AREAS AT AYODHYA CANTT
2026_MES_768568_1
8400/179/E8
Open Tender
Electrical and Maintenance Works
180 days
Ayodhya Cantt
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Ayodhya
₹20,000
Yes
29 May 2026
29 May 2026
22 Jun 2026
29 May 2026
20 Jun 2026
13 Jun 2026
Supply only of Integral LED street light/security lights driver, enclosed with cover frame suitable for existing make/models of LED street light/flood lights of capacity 45 to 50 watt complete all as specified and directed.
All as above item No 2.00 but for capacity 60/65/70/80/90 W complete all as specified and directed.
Supply only of surge protector device for protection upto 10 KV surge voltage suitable for existing make/models of LED street light/flood lights of capacity 30Watt to 100 Watt complete all as specified and directed.
M&L for repair of Street light timer any type including setting/resetting of timing of ON/OFF at dusk & dawn for Street light connected to that Timer including checking of connection of contactor & timer circuits complete all as specified & directed by Engr in charge
S&F in repair of nature timer switch with sensor as per existing capacity and ranges for illumination level for switching ON ≤ 60 Lux and for switching OFF ≥10 Lux alongwith part night operation facility of min 4 hrs to max 12 Hrs complete all as specified & directed including dismantling existing un serviceable from the timer assembly and making reconnection all as specified and directed by Engr-in-charge
S&F in repair contactor rating 40 amp(MNX 40) 2 Pole of existing make/model suitable for street light timer including dismantling existing un serviceable from the timer assembly and making reconnection connection all as specified and directed.
Ditto- as above item No 7 but for capacity 70/63 amp(MNX 63) 3 Pole complete all as specified & directed.
S&f in repairs MCB 63 Amp TPN,415 Volts,50 Hz, C curve all as specified and directed.
S&f in repairs MCB 40 Amp DP,220 Volts,50Hz, C curve all as specified and directed.
S&f in repairs PVC enclosure box with fitting and fixture for fixing up of MCB DP on security lights pole/walls all as specified and directed.
Supply and fix in repairs loop-in loop-out junction box of size 317mmX265mmx160mm made of 1.6mm thick PVC sheet weather proof, dust and vermin proof with hinged door of locking arrangements and slanting cover on top with provision of aluminium busbar of size 25 x 2mm - 4 No (R,Y,B,N) fixed on insulator complete fixed on pole with and including suitable size MS flat iron clamps, nuts, bolts and washers, etc complete all as specified & directed.
S&F in repairs street light bracket made out of 40 mm dia GI pipe medium grade of length upto 1.5 mtr bent to shape required with and including 2 Nos, 40x6 mm MS flat iron clamps with nuts, bolts, washer etc and applying one coat of aluminium paint to clamps including dismantling of old brackets complete all as specified and directed.
S&F in replacement of 1100 Volts grade heavy duty cable one twin core, flat or circular 6 Sqmm PVC insulated aluminium solid conductor served with inner sheathing of PVC tapes and overall PVC sheathed in service connection from pole to Main Switch complete all as specified and directed.
-ditto as above item No 14 but of size 10 Sqmm twin core complete all as specified and directed.
S & F in repair cable twin core PVC insulated and unsheathed solid copper conductor of size 1.50 Sqmm for street light and security light connection complete all as specified and directed.
S & F in repair cable twin core PVC insulated and unsheathed solid aluminium conductor of size 4.00 Sqmm for street light and security light connection complete all as specified and directed.
S& F in repairs PVC Conduit heavy duty 20 mm dia including connected PVC Clamps with nut bolts PVC elbow for service cable encasing along pole ,wall etc from Junction box or DB Box to Lights all as specified and directed.
S&F micro prismatic reflective sheet, min 2.5 cm wide, with self adhesive base for direct fixing on HT/LT steel tubular/PCC pole at suitable height, to glow at night in Red/Yellow colour complete all as directed.
S&f in repairs powder coated pressure die cast aluminium compact LED street light fitting heat resistance with lens on LED diode suitable for 60 Watt with IP 66 protection with inbuilt Surge protection Device (SPD) for protection of surge upto 10 KV, heat resistant IK07 with excellent thermal management including PVC cable connector, LED's should have lens optics and vandal proof prismatic poly carbonate covers for ensuring efficient optics and uniform distribution of light. Fitting should have operating voltage range of 120 - 270 VAC , THD <10% , P.F >.95 complete all as specified.Make- Havells ,Philips, Bajaj, Crompton
S & F in repairs powder coated pressure die cast aluminium compact LED flood light heat resistance suitable for 100 Watt with IP 66 Protection with inbuilt Surge protection Device (SPD) for protection of surge upto 10 KV, heat resistant ,IK07 with excellent thermal management including PVC cable connector, LED's should have lens optics and vandal proof prismatic poly carbonate covers for ensuring efficient optics and uniform distribution of light. Fitting should have operating voltage range of 120 - 270 VAC , THD <10% , P.F >.95 complete all as specified.
S&F in replacement post top energy saving environment friendly long life aesthetically designed with symmetrical light distribution LED Post Top lantern /gate light of capacity 15-20 watt operated on 240 Volts 50 Hz supply with spun aluminium landscape luminaire with high power LED s as light source IP 65 protection complete all as specified & directed.Make- Havells ,Philips, Bajaj, Crompton
Supply and fixing in replacement of ALL-in-One Solar LED street light fitting made up with High Efficiency Mono Crystalline Solar PV Module with suitable Wp, lithium Ferro Phosphate Battery with in built BMS technology , High Efficacy LED, MPPT Solar Charge controller and aluminium Extruded body & is specially programmed to automatically control the dimming and brightness of light , which increases the backup time complete of LED Power light capacity 20/25 Watt IP 66 Protection complete all as specified and as directed. Make- Havells ,Philips, Bajaj, Crompton
S&F and commissioning and testing of Automatic Nature timer switch control of Street Lights complete with MCB, Power and Panel based on lux level of natural light.The sensor (Nature Switch) alongwith and including supply and fix of suitable power contactor of 1 Nos 40 Amps (Two pole ) two Nos MCB 63 Amps (single pole) and support terminals enclosed in pole /wall mountable enclosure of suitable size made out of rust proof electric shock proof termite proof and FR grade special moulding compound sintex make SMC junction box of suitable size confirming to IP54 circuit wiring suitable enough to take load of 8 KW single phase load, with Auto and Manual Mode opeartion facility all as per Kakatiya Energy System Ltd Hydrabad Model SWADEEP Model SWADEEP-02EC 8KW 1P , Healer Enterprises or techno commercially equivalent models in Havells/ L & T complete all as specified and directed. Note :- The contractor shall provide the company warranty certificates of the timer.
M&L for cross arms (any type) supports, brackets, stiffners etc made out of MS channel, angle iron , flat iron of any size including drilling of holes, making clamps, eye hooks, nuts, bolts and washers etc, welding if required including painting with two coats of aluminium paint over a coat of red oxide paint as well as dismantling of existing complete all as specified & directed
M& L for Cleaning and preparation of old painted surface of LT/street light pole by using primer where required complete and painting with one coat of aluminium paint including channels/ brackets, street light brackets, cross arms and making red & white strips or black & white strips as directed with synthetic enameled paint of 30 cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with black synthetic enameled paint and applying white wash on existing PCC coping complete all as specified.
S&F in repairs heat shrinkable 1100 Volts indoor termination LT end joints of size 25 sqmm to 50 sqmm 4 core/3.5 core complete all as specified & directed.
S&f in repairs testing and commissioning of heat shrinkable straight through jointing kit suitable for LT cable of size 70 Sqmm to 150 Sqmm, 3.5 core, XLPE insulated, PVC sheathed armoured 1100 volts grade complete all as specified & directed.
S& F in replacement of Aluminium Lugs/In Line connectors Ferrules of size 16 sqmm complete all as specified & directed.
Ditto as above item 30 but of size 25 sqmm
Ditto as above item 30 but of size 35 sqmm
Ditto as above item 30 but of size 50 sqmm
Supply only of LT PVC tape roll 3/4 inch size ISI marked 25 mtr length complete all as specified & directed.
Supplying, laying,jointing & testing 16 Sqmm 4 core LT underground cable 1100 volts grade, XLPE insulated, PVC sheathed heavy duty, armoured with multi stranded aluminium conductor all as per IS 7098(Part-I) ,laid in trenches, ducts, pipes or on poles etc including cable lugs, jointing, supporting clamp complete etc complete all as specified and directed by Engr-in-Charge.
_Ditto all as above item No 35 here in before but for size 10 Sqmm 2 core complete all as specified and directed.
Excavation in trenches, not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation of poles, stays or for taking out/laying of cables and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in, any type of soil and spreading in layers n. exc 25 Cm thick each layer including watering & well ramming complete all as specified & directed.
Removal of surplus soil to a distance n.exc 50 mtr & depositing where directed at a level n. exc. 1.5mtr above the starting point complete all as specified & directed.
M& L for sub class 'B'bricks locally available best quality laid flat (length of bricks laid across the length of cable) in trenches for protection of U/G cable complete all as specified and directed by Engr-in-Charge.
M&L for sand cushioning with layer of sand 8 cm thick before laying of cable and 15 cm after lying of cable in trenches complete all as specified & directed.Note: Punned thickness of sand will be measured only.
S & F in replacement GI pipe light grade 50mm bore. for cable protection, fixed to pole/ alongwall/ floor/ under road/ across the drain or nallahetc complete all as specified & directed.
Ditto all as per ser item No.42 here-in-before but 40mm bore.
Cutting of floor/wall/footpath for removal of LT U/G cable of any size/description and making good with PCC 1:3 :6 type C-2 the same as per existing specification after relaying the same or new cable and all as specified & directed.
Material and labour for PCC 1:3:6 type C-2,using stone aggregate 40mm graded as in foundation of stays and coping of poles including necessary form work where required and fair finish to the exposed surfaces including demolition of existing damaged PCC all as specified & directed.
Material and labour for PCC 1:4:8 type D-2, using stone aggregate 40mm graded as in foundation for electric poles and making of cable duct including necessary form work where required and fair finish to the exposed surfaces all as specified & directed.
Supply and errect 6 mtr long Hot dip galvanised octagonal pole with 130mm bottom A/F and 70mm top A/F made up of 3mm thick HT steel plate having base plate of 220x220x12mm thick alongwith single arm bracket of 1000 mm length made up of 48.3x3.25mm thick plate, 4 Nos M20 x 700 mm GI 'J' type foundation with door opening 0.90x 350 mm, with bolts,nuts, with template, bakelite sheet box with 01 no 6 A SP MCB and stand type terminal block suitable for 4 core 16 sqmm cable complete.
M&L for RCC foundation of grade M20 (1 cement : 1.5 sand : 3 stone/brick aggregate) of size 550mm x 550mm x 1400mm out of which 1200mm shall be below F.G.L.(Finished Ground Level) using 4 no. 12mm dia steel reinforcement of grade Fe-415 with 50 mm clear cover to reinforcement and rings using 8mm dia steel reinforcement @ 190 C/C using shuttering, along with supply & installation of 2 nos. of 63mm dia PVC pipe for cable entry and cable exit. 4 no. 'J' type foundation bolts shall be anchored in the foundation (PCD of 205 mm) in such a way that 125mm length of bolt is projected above foundation. It includes water curing as required and soil excavation & backfilling. It also includes supply of all material and labour including erection of foundation at Site.
M&L for in replacement of bus bar chamber, size 450mmX300mmX200mm ,fixed on wall, 4 ways, 100 Amps ,415 V powder coated, water & vermin proof , IP-54 protection duly provided with front openable door incl provision of TPN Copper bus bar (ETP grade) with heat shrinkable colored PVC sleeve coated for phases(RYB) and neutral complete all as specified and directed.
S & F in replacement MCCB 415 Volts 4 pole 160 Amps 50 Hz 25 KA alongwith spreader terminal with adjustable thermal setting and Ics=100% ICu including lugs/thimbles of suitable size in existing panels complete all as specified and directed. Note : Necessary addition /alteration required to adjust MCCB in the panel shall be done by the contractor and no extra payment will be made to the contractor.
Ditto all as per ser item No.50 above but of MCCB 125 Amps 4 pole 50 Hz 415 V with rupturing capacity 25 KA and Ics=100% ICu
Ditto all as per ser item No.50 above but of MCCB 100 Amps 4 pole 50 Hz 415 V with rupturing capacity 25 KA and Ics=100% ICu
Ditto all as per ser item No.50 above but of MCCB 63 Amps TPN 50 Hz 415 V with rupturing capacity 16 KA and Ics=100% ICu