Loading…
Loading…
Tender Value
₹7.2 Cr
EMD Value
₹7.2 L
Closing Date
1 Sept 2026, 3:30 pm4d left
SE
ESDC-I 13th Floor, Shakti Bhawan Extn., Lucknow
Construction work of 01No. 220 kv GIS Bay (SKVR Data Centre) at Existing 220 KV GIS Substation Sec-45, Noida
2026_PTRCL_1175175_1
SD-1039
Open Tender
Electrical Works
Turn-key
180 days
Lucknow
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,950
UPPTCL ICICI Ac No. 628105038318 IFSC ICIC0006281
₹7.2 L
6 Aug 2026
6 Aug 2026
2 Sept 2026
6 Aug 2026
1 Sept 2026
6 Aug 2026
Total Price for Supply of Equipments and Material Q -1
Total Price for Handling, Erection, Testing & Commissioning Charges Q -2
Total Price for Electrical works
% Discount, if any on Electrical works
Discount in Rs. on Electrical works
NET Price for Electrical works
Price for Civil Works (Q3)
% Discount , if any on civil works
Discount in Rs. on civil works
NET Price for Civil works
Net Lum Sum Bid Price (Elect+Civil) after Discount
Place :
Designation: ………………………………………………………………………..
Name of Bidder:
SCHEDULE- 1
Schedule for Supply of Equipments for for additional 01 Nos. 220 KV Line Feeder Bay at 220 KV GIS Sub Station Sector-45, Noida alongwith integration with existing GIS(Q1)
245KV GIS Equipments
Feeder Bay Module: 245KV, 1600A, 40KA for 3 sec SF6 gas insulated feeder bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1000-800-500-300/1-1-1-1-1A), having two bus-bar disconnectors (1600A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 1000 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete feeder bay module as per technical specification.
Bus Bar Extension for connecting with existing bus bar : 245kV, 3 single phase (isolated) units, SF6 gas insulated, metal enclosed 2000A bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. As per Technical Specification.
220KV Equipments
245KV CVT
CVT Junction Box
198KV polymer type surge arrestor
245KV Bus post insulator
Simplex control & protction panel as per technical specification of SAS for 220KV feeder
Energy Meters
0.2s accuracy class ABT Energy Meters module as per technical specification.
Metering cubicle for ABT energy meters
Copper Conductor XLPE Power Cable
220KV,1-core 1200 mm2, XLPE copper conductor Power Cable (gantry to GIS, for 220KV feeders)
Cable termination kits
220KV,1-core 1200 mm2, XLPE copper conductor Power Cable (gantry to GIS, for 220KV feeders)
Earthing
40mm MS rod
40mm MS rod electrode 3000mm long
75x10mm MS Flat
50x6mm MS Flat
75x10mm Copper Flat
50x6mm Copper Flat
Structures
Main Structure
Auxilliary Structure
Armoured Aluminium Power Cables
Armoured Copper Control Cables
Conductors
ACSR Zebra
Hardware Fittings for AAC Tarantulla Conductor & ACSR Moose Conductors
70KN Anti fog type Disc Insulator
Single Tension Fittings Suitable for ACSR Zebra
Single Suspension Fittings Suitable for ACSR Zebra
Double Tension Fittings Suitable for ACSR Zebra
Double Suspension Fittings Suitable for ACSR Zebra
PG Clamps suitable for Tarantulla / Zebra
PG Clamps suitable for Zebra / Zebra
Bus Post Clamp suitable for Zebra
Bus Post Clamp suitable for Twin Zebra
Illumination System for complete substation (indoor + outdoor) LED type only
Switchyard/ Street LED Lighting
CABLE TRAY
Pale Fencing
Comunication Equipments
Fiber Optic Terminal Equipment (FOTE) SDH STM-16
Base equipment suitable for 04 directions in subrack fully equipped with all necessary common cards, power supply card, other hardware & acccessories including 10 Nos. optical pathch cords of lengths as per site requirements, DDF etc. with redundant CPU.
Optical Base Card for 04 direction (STM-16), should support STM-1 & STM-4 interfaces.
Short Haul, STM-16 1310nm SFP Transceiver- S-16.1
Long Haul, STM-16 1310nm SFP Transceiver- L-16.1
E1 Interfaces (120Ohm) (32 Interfaces with 2 Cards)
L2Etherner Interfaces 10/100 Base T (16 Interfaces with Minimum 2 Cards)
VOIP Phone
Equipment cabinet for SDH and DTPC 2200mm (h) including 100mm base, wxd should be suitable for 19" or 23" Rack.(Alongwith 220/110V to 48V DC-DC Converter)
MDF (200 Pairs), mounted in cabinet.
04 Command Standalone Digital Tele-protection Couples fully equipped with all necessary common cards, power supply cards, other hardware accessories, connectors, cables, subrack with E1 pathe cord srt of 04 etc.
Total
Seal of Company
Full Signature …………………………………………………………….
Designation ……………………………………………………………….
Name of Bidder:
SCHEDULE- 2
Schedule for Installation of Equipments for additional 01 Nos. 220 KV Line Feeder Bay at 220 KV GIS Sub Station Sector-45, Noida alongwith integration with existing GIS(Q2)
245KV GIS Equipments
Feeder Bay Module: 245KV, 1600A, 40KA for 3 sec SF6 gas insulated feeder bay module each comprising of SF6 gas insulated circuit breaker (1600A), current transformer (1000-800-500-300/1-1-1-1-1A), having two bus-bar disconnectors (1600A) with common grounding switch, line disconnector with safety grounding switches suitable for Main-I & Main-II bus system, Local Control Cubicle, SF6 gas monitoring system for complete bay. Three 1–phase SF6 gas insulated terminal connection for connecting 3 nos of single phase 1000 sq mm XLPE cable with cable termination enclosure, Local Control Cubicle and accessories with GIS etc. to complete feeder bay module as per technical specification.
Bus Bar Extension for connecting with existing bus bar : 245kV, 3 single phase (isolated) units, SF6 gas insulated, metal enclosed 2000A bus bars each enclosed in bus enclosures running along the length of the switchgear to interconnect each of circuit breaker bay module. As per Technical Specification.
220KV Equipments
245KV CVT
CVT Junction Box
198KV polymer type surge arrestor
245KV Bus post insulator
Simplex control & protction panel as per technical specification of SAS for 220KV feeder alongwith integration with existing SCADA
Energy Meters
0.2s accuracy class ABT Energy Meters module as per technical specification.
Metering cubicle for ABT energy meters
Copper Conductor XLPE Power Cable
220KV,1-core 1200 mm2, XLPE copper conductor Power Cable (gantry to GIS, for 220KV feeders)
Cable termination kits
220KV,1-core 1200 mm2, XLPE copper conductor Power Cable (gantry to GIS, for 220KV feeders)
Earthing
40mm MS rod
40mm MS rod electrode 3000mm long
75x10mm MS Flat
50x6mm MS Flat
75x10mm Copper Flat
50x6mm Copper Flat
Structures
Main Structure
Auxilliary Structure
Armoured Aluminium Power Cables alongwith both side termination
Armoured Copper Control Cables alongwith both side termination
Conductors
ACSR Zebra
Hardware Fittings for AAC Tarantulla Conductor & ACSR Moose Conductors
70KN Anti fog type Disc Insulator
Single Tension Fittings Suitable for ACSR Zebra
Single Suspension Fittings Suitable for ACSR Zebra
Double Tension Fittings Suitable for ACSR Zebra
Double Suspension Fittings Suitable for ACSR Zebra
PG Clamps suitable for Tarantulla / Zebra
PG Clamps suitable for Zebra / Zebra
Bus Post Clamp suitable for Zebra
Bus Post Clamp suitable for Twin Zebra
Illumination System for complete substation (indoor + outdoor) LED type only
Switchyard/ Street LED Lighting
CABLE TRAY
Pale Fencing
Comunication Equipments
Fiber Optic Terminal Equipment (FOTE) SDH STM-16
Base equipment suitable for 04 directions in subrack fully equipped with all necessary common cards, power supply card, other hardware & acccessories including 10 Nos. optical pathch cords of lengths as per site requirements, DDF etc. with redundant CPU.
Optical Base Card for 04 direction (STM-16), should support STM-1 & STM-4 interfaces.
Short Haul, STM-16 1310nm SFP Transceiver- S-16.1
Long Haul, STM-16 1310nm SFP Transceiver- L-16.1
E1 Interfaces (120Ohm) (32 Interfaces with 2 Cards)
L2Etherner Interfaces 10/100 Base T (16 Interfaces with Minimum 2 Cards)
VOIP Phone
Equipment cabinet for SDH and DTPC 2200mm (h) including 100mm base, wxd should be suitable for 19" or 23" Rack.(Alongwith 220/110V to 48V DC-DC Converter)
MDF (200 Pairs), mounted in cabinet.
04 Command Standalone Digital Tele-protection Couples fully equipped with all necessary common cards, power supply cards, other hardware accessories, connectors, cables, subrack with E1 pathe cord srt of 04 etc.
Total
Seal of Company
Designation ……………………………………………………………….
Full Signature …………………………………………………………….
Designation ……………………………………………………………….
Name of Bidder:
BILL OF QUANTITY
BOQ FOR Civil Works For Construction of 01 No. 220 KV GIS Bay By UPPTCL At Under Construction 220 KV GIS S/s Sector 45, Noida. (BASED ON SOR 2023-24).
Cement concrete with 2cm gauge approved hard stone ballast, coarse sand and cement in proportion of 3:1.5:1 including supply of all materials, labour,side shuttering if required and T&P etc. required for proper completion of work (CSI No. 5.21)
RCC work with cement, approved coarse sand and 2 cm gauge graded approved hard stone ballast like granite quartzite etc from Dalla, Jhansi or other quarries in proportion 1:1.5:3 in raft foundation and footings , excluding supply of reinforcement & its bending but including its fixing and binding the same with binding wire, including cost of all other materials labour and T&P. (CSI No. 5.27)
RCC work with cement, approved coarse sand and 2 cm gauge graded approved hard stone ballast like granite quartzite etc from Dalla, Jhansi or other quarries in proportion 1:1.5:3 in RCC pile caping, gantry walls/column foundations and RCC pedestals, excluding supply of reinforcement & its bending but including its fixing and binding the same with binding wire, including cost of all other materials labour and T&P. (CSI No. 5.28)
Arranging and spreding 75 mm thick broken grit 20 mm (Granite stone) uniform for turfing over 100mm thick base course of C.C. In 1:4:8 (1cement:4coarse sand: 8, 40mm stone ballast) top finish by brooming of cement mortar 1:4(1cement: 4 Coarse sand) including supply of all materials, labour and tools and plants etc. required for proper completion. (CSI No. 5.31)
First class brick work in 1:4 cement and coarse sand mortar in foundation and plinth including supply of all materials, labour & T&P etc. required for proper completion of work (CSI No. 6.03)
TMT/Tor steel in plain work such as reinforced concrete or reinforced brick work (when not included in an over all rates) wrought to required shape as necessary including bending for proper completion of the work and including supply of steel its wastage, bend, hooks and authorized overlapping shall be measured. (Steel shall be arranged by the contractor) (CSI No. 9.03)
Supply of 28 mm. dia M.S. Anchor bolts (conforming to IS 266) 900 mm. long with base plate (75x75x6mm) welded with anchor bolts including its threading upto a length of 10cm. and also supply of a pair of galvanized standard nuts with threading including supply of 5 mm thick washer and cost of labour, material & T&P for proper completion of work(CSI No. 9.12)
Fixing and grouting 28 mm and above dia bolts in proper alignment level and setout with help of a template complete including supply of all labour & T&P etc. required for proper completion of the work.(labour rates only) . (CSI No. 9.13)
Fixing of template in position level and alignment for grouting of Anchor bolt in main gantry (labour rate only). (CSI No. 9.31)
Fixing of template in position level and alignment for grouting of Anchor bolt in auxiliary structure (labour rate only) (CSI No. 9.32)
Fabrication of template forauxiliary foundationsincluding cost of all labour, and T&P etc. required for proper completion of the work. Steel shall be arranged by contractor free of cost. This template shall be property of contractor.(Labour rate only) (CSI 9.36)
12 mm thick plaster with cement mortar consisting of one part of cement & four part of coarse sand (1:4), minimum thickness not to be less then 10 mm including supply of all material, labour and T&P etc for proper completion of work. (CSI No. 11.07)
Champering the edge of concrete in auxiliary structure, of size 25 mm wide in triangular section including all materials, labour & T&P etc complete. (CSI No.11.18)
Dismantling brick work or stone work in lime or cement mortar and including stacking of materials as directed by the Engineer-in-charge within a distance of 60 metres. (CSI No. 15.01)
Dismantling reinforced cement concrete or reinforced brick work, including stacking of dismantled materials as directed by the Engineer-Incharge within a distance of 60 metres. (CSI No. 15.03)
TOTAL
Special Conditions : -
1. Tenderers are advised to visit the site of work and make themselves acquainted with the site conditions. No claim whatsoever shall be entertained after submission of tender . 2. Tenderer shall quote rates inclusive of all type of taxes (Income Tax, Labour cess, Royalty, No entry zone fees etc.) only GST shall be paid extra. 3. No idling charges shall be paid for contractual period as well as extended period. 4. Rates quoted by Tender will remain firm till completion of scope of work of contract, is any item of work required to complete the scope of work shall be deemed included in the scope of work and rates, if not available in the bill of quantity shall be finalized by SE, ECTC, Noida as per relevant clause. 5. Quantities are approximate and may vary up to any extent on either side as per requirement of the site conditions or may not be executed at all for which no extra claim shall be entertained. 6. All the above work shall be executed as per U.P.P.W.D., U.P.P.T.C.L. specifications or as directed by Engineer- in –charge. 7. The work may be carried in energized S/s area having high voltage installations contractor must employ trained supervisor and labour to work in such electrical hazardous area . All risk to men and material shall be contractor’s responsibility. Insurance of labour & T&P shall be borne by the agency. 8. Contractor shall register his labour engaged in construction work in the office of Dy. Labour Commissioner Only registered Labour in Labour Commissioner office shall be employed. If any labour not registered then it will be registered within 24 hours.
9. MS scrap received against dismantled RCC/RB work will be issued to the contractor@ 30.00/Kg. 10. In dismantling of brick work, 60% bricks, 28% brick bats and 12% debris will be treated as recovered. Bricks shall be issued to contractor @3100/per thousand and Brick Bats @1050/Cum and debris at free of cost. 11. Post concrete testing shall be carried out by department on completion of the work by IIT/ HBTI/ NABL approved laboratory. Final bill shall be prepared, if and only if results will found as per IS standard and all expenditure is the responsibility of the firm. If results are not satisfactory then agency will be recommended for black list and work is dismantled and reconstructed on the expenditure of the firm/ contractor. 12. Contractor has to put up all relevant drawing to SE (Civil) Noida for approval at his own cost the drawing shall be vetted by IIT/Engineering collage nothing shall be paid extra for it. 13. As per G.O. no.622/23-12-2012-2 Audit/08 TC date 08.06.2012, Contractor has to deposit extra security performance guarantee, If the tendered rate are found below to the department rates. 14. As per section 171of CGST Act, 2017 any reduction in rates of Tax of any supply of the goods are service of the benefit of input tax credit shall be passed on to the recipient by the way of commensurate reduction in prices. Hence supplier/Manufacturer to ensure to pass the benefit reduced prices to UPPTCL. Further price quoted by supplier/manufacturer is subject to security under above section 15. A security of 10% of the agreement shall be deducted from running bill of agency. Which shall be released after six months of successful completion of work. 16. The agency shall deposit the proof of GST payment, if not, then their next payment cannot be released by corporation. 17. Receipt for royalty payments for coarse sand and, 20 mm stone blast, earth etc. shall be deposited by agency with each bill, in absence of this, royalty shall be deducted from their bill with penalty, if any. 18. No labour will stay in substation area. 19. All Labour with valid Aadhar card will enter through gate pass in 400/220/132kv sub-station and will leave the sight neat & clean condition in afternoon. No night shift shall be allowed due to hazardous condition.. 20. A COVID help desk shall be maintained by the agency during currency of contract with Mask, Sanitizer, Reporting Register and Thermal Scanner, if disposable Mask is used then it shall be disposed of as per Govt. of India guidelines as time to time . 21. The labours working in the energize switch yard will use Gum Boots , Insulating Gloves, Helmet etc. labours if proper safety measures not followed then the firm will be panelized.
22. If any honey combing appeared in surface then all the grits shall be removed by pointed hammer till the good surface then "Patch fix Concrete" (Make Bostik) shall be used for filling 180 mm depth, for extra deep portion "Patch Fix Concrete" shall be used in layers having depth up to 180mm. 23. Electricity shall be available on payment basis and agency will take the temporary connection from uppcl 24. Water shall be available at one point only and as per time schedule of transmission and firm shall have his own arrangement for storage by tank or any other means. Water charges shall be deducted in any condition. 25. Supply of anchor bolt the factory inspection shall be arrange by the contractor on his own cost & testing of anchor bolt shall be done by IIT/NABL approved laboratory. 26. .Covid-19 Guideline issued by Gov of India shall be applied & binding to the firm. 27. Material for testing like concrete cube, steel, coarse sand, coarse aggregate etc. has to be carried out by the contractor to the division lab at his own cost. 28. Testing of material from NABL approved lab, if required shall be borne by the contractor. Nothing shall be paid extra by the department. 29. Contractor has to made available 6 No. cube at site and will frequently fill the cube at site. Accordingly cube test report will be submitted by contractor at his own cost. Final bill of work will be paid to contractor only after he will submit all satisfactory test result from authorized lab. 30. Site shall be handed over to agency as and where basis no extra claim shall be paid to the contractor for clearing, leveling, dressing etc. 31. Curing of cement work shall be done as per prevailing IS code and if found faulty post concrete testing from IIT shall be done on the cost of firm. 32. The work shall be carried out in energized 220 KV G.I.S. building where opening for two No. 220 KV GIS Module installation shall be done. It is responsibility of firm to take all precautions, so that existing 220 KV G.I.S. module or G.I.S. building will be safe in all respect. Before opening of cut out for new G.I.S. module firm will ensure all safety precautions. The design, drawing and cut out opening procedure shall be submitted to SE, ECTC Jhansi for his approval.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.40 MB
TDSD1039.pdf
Tender Documents • 5.60 MB
BOQSD10392003.xls
Additional Documents • 0.12 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].