Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.8 LAccepted-Finance 76 1 GURU SADAY DUTTA SARANI NORTH BHARAT NAGAR SILIGUR | L1 | Accepted-Finance LOWEST | |
| 2 | L2₹10.9 L+₹10,615.36 (0.98%)Rejected-Finance 17 1 ABHOY HALDER LANE KOLKATA | KOLKATA | L2 | Rejected-Finance GREATER THAN L1 | |
| 3 | L3₹10.9 L+₹15,955.82 (1.48%)Rejected-Finance 00 DEY ENTERPRISE SODEPUR 9 10 PITS COLLIERY ASANSOL BARDHAMAN WEST BENGAL 713372 | PASCHIM BARDHAMAN | WEST BENGAL | 713372 | L3 | Rejected-Finance GREATER THAN L1 |
Tender Value
₹10.7 L
EMD Value
₹21,996
Closing Date
10 Sept 2024, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE, NMD ,PHE Dte
OFFICE OF THE EXECUTIVE ENGINEER ,NORTHERN MECHANICAL DIVISION ,PHE Dte.SILIGURI SUKANTA SARANI, PARESH NAGAR, SILIGURI, PIN 734001
Restoration of power for starter panel at Sindhap WTP and discharge monitoring syatem for rising main at St.Pauls and Rockvill tank under Darjeeling Water Supply Pumping Scheme
2024_PHED_734446_2
WBPHED/EE/NMD/NIeT- 11 OF 2024-2025
Open Tender
MISC ELECTRICAL WORKS
Item Rate
20 days
Darjeeling
Please refer Tender documents.
5 documents required · 5 mandatory
₹21,996
Yes
20 Sept 2024
14 Aug 2024
12 Sept 2024
16 Aug 2024
10 Sept 2024
16 Aug 2024
Amount
Supply and delivery of following materials at site
240 sqmm 3C XLPE Al Ar 1.1KV Gr as per IS7098 (Part 1)up to latest amendments
MCCB 3 pole DN3 630N 400-500A,415 V, 50Hz,50kA with thermal magnetic release of L&T or same specification of any other approved make
Dismantaling of damaged cable from starter panel and motor by disconnecting of paver block between Sub station and pump house
Laying of two cables 3C 240sqmm in an underground trench in single tier formation (horizontal), the trench size : 680 mm x 760 mm average depth, with brick protection on the top of each cable8 (eight) Nos. bricks per Mtr. and 4 (four) Nos. bricks per Mtr. asseparator between the bricks and cables and also trench to befilled up with shifted soil, levelling up and restoring surface duly rammed
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry ofXLPE/PVC armoured cables 3core 240sqmm.
Finishing the end of following XLPE/PVC armoured cables bycrimping method incl. supplying and fixing solderless socket(Dowels make), tapes, anticorrosive paste & jointing materials 3core 240sqmm.
Dismataling and fitting fixing of damaged MCCB after diconnection of all electrical and mechanical connections with newly supplied one as per instruction of EIC along with repairing of dismanteled paver block , mending good damages.
Supply & delivery of following materials at site:-
Supply and delivery of Electromagnetic Flowmeter for DN200,24 V DC operated,Output 4-20mA/Scalable pulse output,process connection flanges ANSI ASME class 150 rating, process connection flange material carbon steel/stainless steel. Meter tube SS 304/SS316,coil housing SS 304/ Carbon Steel/die cast aluminiumwith buriable design upto 5 mtr depth.Flow sensor shall be IP 68 , flow transmitter shall be IP 67,liner shall be PTFE/hardrubber/EPDM with WRAS approval, accuracy shall be 0.5%, flowmeter shall be supplied with grounding ring/grounding electrode with two nos ASME class 150 rating process counter flanges with each flowmeter. Flow transmitter shall be supplied in a weather proof housing box along with SMPS with internal cabling and cable glands. Interconnection cable between flow sensor and flow transmitter shall not be less than 10m . Test certificate should be submitted at the time of delivery.
Installation,testing and commissioning of above supplied Flowmeter and housing box along with SMPS and internal cabling on rising main of size 200 mm near ST Pauls and Rockvill Tank by cutting the MS pipe , welding of flanges along with power and necessary arrangement for completing the work with all required materials and as per the satisfaction of EIC.
N.B.:MAKE: AS PER PHE APPROVED VENDOR LIST
Add GST @18%
Add Labour Welfare Cess @ 1%
ORIENTAL ENGINEERING CO. (BID ID -5531330)
DEY ENTERPRISE (BID ID -5537922)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .