| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.6 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹16.5 L+₹3.0 L (21.9%)Rejected-Finance RSD STREET HALL BAZAR AMRITSAR 143001 PUNJAB | AMRITSAR | AMRITSAR | PUNJAB | 143001 | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹18.9 L+₹5.3 L (39.0%)Rejected-Finance 1ST FLOOR HRECF OFFICE NEAR JNV SCHOOL MIAN GATE TIA RAY RONG CHOGLAMSAR LEH LADAKH 194101 | LEH LADAKH | LADAKH | 194101 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹21.3 L+₹7.8 L (57.4%)Rejected-Finance 403 GH MANSADEVI COMPLEX PANCHKULA 134109 HARYANA | PANCHKULA | HARYANA | 134109 | L4 | Rejected-Finance Other than L1 |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
3 Jul 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col S S Babu
Headquarters 138 Works Engineers Pin-914138 C/o 56 APO
REPAIR AND MAINT OF HT POLES AND OVER HEAD LINES/HT CABLES WITH CONNECTED ACCESSORIES AT SECTOR A AND B UNDER AGE E/M II OF GE 865 EWS
2021_MES_448820_1
138WE/L-31/2021-22
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE 865 EWS
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE 865 EWS
₹40,000
Yes
13 Jul 2021
5 Jun 2021
5 Jul 2021
5 Jun 2021
3 Jul 2021
19 Jun 2021
60 days
Amount
Excavation in trenches not exc 1.5m wide and not exc 1.5 m in depth, for foundation etc, or for shafts, wells cesspits, manholes, pier holes etc, n exc 10 sqm on plan and n exc 1.5m in depth in hard/dense soil and getting out, complete all as specified and as directed.
Returing, filling in (soil) including spreading, leveling, watering and well ramming in layers not exc, 25cm, complete all as specified and as directed.
Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the strating point, complete all as specified and as directed .
M&L for Sand cushioning to underground cables 8 cm below the cable before laying and 15 cm above the cable after laying, complete all as specified in clause 19.75 of SSR Par-I,complete all as specified and as directed.
M&L for factory made, machine pressed, unreinforced, pre-cast concrete cable cover type-II flat size 300 x 180 x 40mm, complete all as specified and as directed.
M&L for plain cement concrete 1:4:8 type D-2 (using 40mm graded curshd stone aggreegates), as in foundation of poles, complete all as specified and as directed.
M&L for plain cement concrete 1:3:6 type C-2 (using 40mm graded curshd stone aggreegates), as in massconcrete/coping of poles, complete all as specified and as directed.
Taking down old UNSV/Burnt all type of electical cable from exisiting site complete all as directed by Engr-in-Charge.
Supply and laying of 11KV, 95 Sqmm 3 core XLPE insulated, armoured, heavy duty electric cables (heavy duty) with stranded aluminium conductor rating 11000 volts grade of size laid in trences or passing through pipes, ducts or fixed to walls/poles, complete all as specified, (Earth work, cable protection and sand cushioning shall be measured and paid for separately)
Taking down old unserviceable HT End Joint kit Outdoor type 95 Sqmm 3 core complete all as specified and directed by Engr-in-Charge.
M&L for cable joint kit for 11KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm, complete all as directed by Engr-in-Charge.
Dismantling steel poles of any type and size from exisiting site all as directed by Engr-in-Charge.
M&L for steel tubular swaged poles complete with cast iron base plate, finial taper plug, botls, nuts & screws as specified type 410 SP-55 (11.00 metres long), complete all as specified and directed.
Dismantling cross-arms of MS Channel or angle sections etc complete of any size and type from exisiting site all as directed by Engr-in-Charge.
M&L for cross arms bracing supports clamps, back plates fabricated from steel section made out of Fe-0-310/Fe-0-410 including nuts, bolts, and washers welding, drilling hole complete with two coats of aluminium paint over one coat of primer complete all as specified and as directed.
Dismantling of ACSR conductors complete of any size and type from exisiting site complete all as specified and as directed. by Engr-in-Charge.
M&L for ACSR conductor any size drawn straight horizontal on over head lines on existing poles including binding with insulators. Weight of conductor shall be measured straight horizontal distance between centre to centre of two adjacent poles and calculating weight of conductor of size and length by adding 3% extra for sag, jointing jumpers, etc complete all as specified and directed.
Dismantling of stay assembly complete of any size and type from exisiting site all as directed by Engr-in-Charge.
M&L for stay assembly complete with stay plate bow, stay rod of dia 20mm and gavanised iron stay wire stranded of size 7/4mm and accessories as shown in electric plate No 1 of SSR Part-I (loop type insulator, stay clamps, excavation and concrete shall be measured separately) complete all as specified and directed.
Dismantling of earth wire complete of any size and type from exisiting site all as directed by Engr-in-Charge.
M&L for galvanized steel wire 4mm dia for continuous earth wire complete all as specified and as directed.
Dismantling of Unserviceable/HT insulators Pin/shackle/Disc & loop type from existing OH lines, complete all as specified and directed.
S&F shackle type insulators, porcelain, vitreous, brown or green insulator including galvanised mild steel straps, washers, insulators, bolts, washers and nuts, working pressure 11000 votls and size of 150mm in height and 150 mm dia with section of straps 38 x 5mm and dia of bolts 20mm ISI marked complete, all as specified and directed by Engr-in-Charge.
Suplying and fixing Pin type, porcelin, vitreour, white, brown or green insulator, size 150mm height, 150mm dia for 11000 volts grade, including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, conforming to IS: 7321-1931, complete all as specified and as directed by Engr-in-Charge.
M&L for Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green Two-in-series disc assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as spd and as directed by Engineer-in-Charge.
Taking down old unserviceable anti clamping device, complete all as specified and directed.
M&L for Anti climbing devices comprising of 2.24mm dia galvanised steel 2 strand barbed wire with 2.00 mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured or as ordered (clamps measured separately), complete all as specified and directed.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and coventional skull and bones in signal red colour and fixed with MS Clamps, bolts and Nuts of approved size for HT25x20cm size, complete all as specified and as directed.
Taking down old rusted tubes light grade of any size galvanised with all fittings complete from existing site complete all as specified and as directed. by Engr-in-Charge.
Supply and laying of tubes light grade of size 80mm bore galvanised with all fittings and fixed complete to walls and ceiling or laid in floors complete all as specified and as directed..
Disamantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for insulators and operating mechanism for repair/repalcement of broken/worn out components and insulators etc.
Replacement of air break switch gang operated (GOD) triple pole with drop out fuses mechanically operated, mounted on insulators 15 Nos & steel frame with operating mechanism & operating rod of GI pipe 25mm & medium grade with necessary clamps to be operated from ground level 11 KV grade working pressures and current upto 200 Amps complete all as specified and as directed..
Taking down old unserviceable lightning arresters high tension 11000 volts, complete all as specified and directed.
M&L for lighting arresters expulsion type complete with all fitting transmission class discharge capacity 65 Kilo amps 11000 Volts, complete all as specified and directed.
Taking down old unserviceable GI wire Earthing, complete all as specified and directed.
M&L in replacement for earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and including GI strip 4mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in electrical plate No 5 of MES SSR Part-I and testing on completion including excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, MS frame and cover 6 mm thick in cement concrete (1:2:4) type B1 reinforced with welded steel wire fabric or XPM (weight not less than 4 Kg per Sqm) with cast iron frame, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs complete all as specified and directed Note- (i) earth resistance not more than 1.0 OHMS. Writing of details on the surface of the pit with paint. (ii) In case earth resistance more than 1.0 ohms, the contractor will re earthing at no extra cost. (iii) On testing if the earth resistance less than specified is not obtained, earthing will be regenerated at NO EXTRA COST till the desired earth resistance is obtained, complete all as specified and as directed.
M&L for Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to pole or any other indicated situation for loop earthing etc, as required 4mm galvanised iron or steel wire, complete all as specified and directed.
Intrernational Engineers
HIMALAYAN RENEWABLE ENERGY AND CONSTRUCTION FIRM
EESSI
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .