Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.7 LAccepted-AOC 24 25 MANGAL ARCADE TELCO ROAD OPP HOTEL DOUBLE TREE MOHAN NAGAR CHINCHWAD PUNE 411019 | PUNE | MAHARASHTRA | 411019 | L1 | Accepted-AOC Lowest quoted amount overall reasonable | |
| 2 | L2₹24.3 L+₹2.2 L (9.84%)Rejected-AOC | L2 | Rejected-AOC 2nd lowest hence rejected | |
| 3 | L3₹25.0 L+₹2.9 L (13.1%)Rejected-AOC | L3 | Rejected-AOC 3rd lowest hence rejected | |
| 4 | L4₹25.9 L+₹3.8 L (17.3%)Rejected-AOC | L4 | Rejected-AOC 4th lowest hence rejected | |
| 5 | L5₹26.9 L+₹4.8 L (21.7%)Rejected-AOC | L5 | Rejected-AOC 5th lowest hence rejected |
Tender Value
Refer Docs
EMD Value
₹70,000
Closing Date
23 Jan 2021, 6:00 pmClosed
Garrison Engineer Belgaum
Garrison Engineer Belgaum Laxmitek Camp Belgaum 590009 KArnataka
REPLACEMENT OF MCCBs, MCBs, DISTRIBUTION BOARDS, MAIN SWITCH BOARDS, EARTHING AND CERTAIN OTHER CONNECTED WORKS IN OTM AND MD ACCN UNDER GE BELGAUM
2021_MES_408852_1
GE/ BEL/ OF 2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Belgaum
As per tender documents
8 documents required · 8 mandatory
₹500
Yes
Garrison Engineer Belgaum
₹70,000
Yes
13 Feb 2021
1 Jan 2021
25 Jan 2021
2 Jan 2021
23 Jan 2021
2 Jan 2021
Amount
Excavating in trenches n exc 1.5m wide and n exc 1.5m depth and getting out in hard/ dense soil for cable/ pipe trenches, etc. all as specified and directed.
Returning filling in including spreading leveling, watering and well ramming in layers n.exc 25cm thick all as specified and directed.
Removing excavated materials to a distance n exc 50m and depositing where directed at a level n.exc 1.5m above the starting point all as specified and directed.
Taking up/ down existing serviceable XLPE insulated, armoured, heavy duty electric LT UG cables of any description and size after disconnecting the connections and relaying the same in trenches/ passing through pipe/ duct or fixed to wall after making LT cable straight through joints, connecting up, testing and commissioning complete all as specified and as directed. Note: LT cable jointing kit, excavation, earth work, cable protection shall be measured and paid separately under relevant items of this schedule.
M&L for double wall corrugated HDPE pipes, conforming to IS 14930-2001, ISI marked, 110mm outer dia, as in cable protection, fixed to poles/ walls with necessary MS clamps, bolts, nuts, washers or laid in trenches/ under roads/ crossing etc. all as specified and as directed.
M&L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size, fixed in repairs, including painting two coats with aluminium paint over one coat of primer all as specified and as directed
M&L for plain Cement concrete 1:4:8 type D2 using 40 mm graded stone aggregate for foundation, filling and mass concrete complete all as specified and directed
M&L for straight through cable jointing kit, heat shrinkable type, with all jointing materials, suitable for XLPE insulated LT UG cable with multi-stranded aluminium conductor, 1100 Volts grade, cross sectional area 240 to 300 sqmm x 3.5 core, fixed in repairs, including testing and commissioning complete all as specified and as directed.
All as described in item No. 08 but suitable for LT UG cable of size 120 to 185 Sqmm x 3.5 core
All as described in item No. 08 but suitable for LT UG cable of size 50 to 95 Sqmm x 3.5 core
All as described in item No. 08 but suitable for LT UG cable of size 25 to 35 Sqmm x 3.5 core
All as described in item No. 08 but suitable for LT UG cable of size 6 to 16 Sqmm x 3.5/ 4 core
S&F in repairs Digital MCCB, 4 Pole, 415 V, 50KA breaking capacity, 630 Amps rating, with adjustable micrprocessor release all as specified and as directed. Make: Cat No. ISLLNFEF0630 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 3 Pole, 415 V, 36KA breaking capacity, 630 Amps rating, with adjustable micrprocessor release all as specified and as directed. Make: Cat No. ISLLSEET0630 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 4 Pole, 415 V, 36KA breaking capacity, 400 Amps rating, with adjustable micrprocessor release all as specified and as directed. Make: Cat No. ISLLSEEF0400 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 3 Pole, 415 V, 36KA breaking capacity, 400 Amps rating, with adjustable micrprocessor release all as specified and as directed. Make: Cat No. ISLLSEET0400 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 4 Pole, 415 V, 36KA breaking capacity, 320 Amps rating, with adjustable micrprocessor release all as specified and as directed. Make: Cat No. ISLLSEEF0320 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 3 Pole, 415 V, 36KA breaking capacity, 320 Amps rating, with adjustable micrprocessor release all as specified and as directed. Make: Cat No. ISLLSEET0320 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 4 Pole, 415 V, 36KA breaking capacity, 250 Amps rating, with adjustable micrprocessor release all as specified and as directed. Make: Cat No. ISLFENF0250 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 3 Pole, 415 V, 36KA breaking capacity, 250 Amps rating, with adjustable microprocessor release all as specified and as directed. Make: Cat No. ISLFENT0250 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 3 Pole, 415 V, 36KA breaking capacity, 250 Amps rating, with adjustable thermal and adjustable magnetic setting all as specified and as directed. Make: Cat No. ISLLSECT0250 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 4 Pole, 415 V, 25KA breaking capacity, 200 Amps rating, with adjustable thermal and fixed magnetic setting all as specified and as directed. Make: Cat No. ISLANF0200 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 3 Pole, 415 V, 25KA breaking capacity, 200 Amps rating, with adjustable thermal and fixed magnetic setting all as specified and as directed. Make: Cat No. ISLANT0200 of Havells or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 4 Pole, 415 V, 35KA breaking capacity, 160 Amps rating, with adjustable thermal and adjustable magnetic setting all as specified and as directed. Make: Cat No. ISLCNF0160 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 3 Pole, 415 V, 35KA breaking capacity, 160 Amps rating, with adjustable thermal and adjustable magnetic setting all as specified and as directed. Make: Cat No. ISLCNT0160 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 4 Pole, 415 V, 35KA breaking capacity, 125 Amps rating, with adjustable microprocessor release all as specified and as directed. Make: Cat No. ISLFENF0125 of Standard or equivalent makes as specified in particular specifications
S&F in repairs Digital MCCB, 3 Pole, 415 V, 35KA breaking capacity, 125 Amps rating, with adjustable microprocessor release all as specified and as directed. Make: Cat No. ISLFENT0125 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 4 Pole, 415 V, 25KA breaking capacity, 100 Amps rating, with fixed thermal and fixed magnetic setting all as specified and as directed. Make: Cat No. ISLGHF0100 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 3 Pole, 415 V, 25KA breaking capacity, 100 Amps rating, with fixed thermal and fixed magnetic setting all as specified and as directed. Make: Cat No. ISLGHT0100 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 4 Pole, 415 V, 25KA breaking capacity, 63 Amps rating, with fixed thermal and fixed magnetic setting all as specified and as directed. Make: Cat No. ISLGHF0063 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 3 Pole, 415 V, 25KA breaking capacity, 100 Amps rating, with fixed thermal and fixed magnetic setting all as specified and as directed. Make: Cat No. ISLGHT0063 of Standard or equivalent makes as specified in particular specifications
S&F in repairs MCCB, 3 Pole, 415 V, 25KA breaking capacity, 32 Amps rating, with fixed thermal and fixed magnetic setting all as specified and as directed. Make: Cat No. ISLGHT0032 of Standard or equivalent makes as specified in particular specifications
S&F in repairs powerline vertical MCCB DB TPN 8 Way suitable for MCCB as incommer, 415 volts, 200 Amps rated bus bar, double door type including provision of 2nd class hard wood board with sunmica top of suitable size fixed to wall and fixing of the MCCB DB on board complete all as specified and directed. Make: Cat No. DSDLVDRBAOF008 of Standard or equivalent makes as specified in particular specifications
S&F in repairs powerline vertical MCCB DB TPN 4 Way suitable for MCCB as incommer, 415 volts, 200 Amps rated bus bar, double door type including provision of 2nd class hard wood board with sunmica top of suitable size fixed to wall and fixing of the MCCB DB on board complete all as specified and directed. Make: Cat No. DSDLVDRBAOF004 of Standard or equivalent makes as specified in particular specifications
S&F in repairs, MCB DB TPN 4 Way with 200 Amps rated bus bars double door type and including provision of 2nd class hard wood board 40mm deep with sunmica top of suitable size fixed to wall and fixing of the MCB DB on board complete all as specified and directed.
S&F in repairs, MCB DB SPN 12 Way with 100 Amps rated bus bars double door type and including provision of 2nd class hard wood board 40mm deep with sunmica top of suitable size fixed to wall and fixing of the MCB DB on board complete all as specified and directed.
S&F in repairs, MCB DB SPN 8 Way with 100 Amps rated bus bars double door type and including provision of 2nd class hard wood board 40mm deep with sunmica top of suitable size fixed to wall and fixing of the MCB DB on board complete all as specified and directed.
S&F in repairs MCB TPN 63A 10KA 'C' series 50Hz 415 Volts AC supply all as specified and as directed.
S&F in repairs MCB TPN 32A 10KA 'C' series 50Hz 415 Volts AC supply all as specified and as directed.
S&F in repairs MCB DP 63A 10KA 'C' series 50Hz AC supply all as specified and as directed.
S&F in repairs MCB DP 40A 10KA 'C' series 50Hz AC supply all as specified and as directed.
S&F in repairs MCB DP 5-32 A 10KA 'C' series 50Hz AC supply all as specified and as directed.
S&F in repairs MCB SP 5-32A 10KA 'C' series 50Hz 240 Volts AC supply all as specified and as directed.
S&F in repairs Onload changeover switch, 415V, 4 pole, 100 Amps, fixed in and including provision of suitable size sheet metal enclosure all as specified and as directed.
S&F in repairs Onload changeover switch, 415V, 4 pole, 63 Amps, fixed in and including provision of suitable size sheet metal enclosure all as specified and as directed.
S&F in repairs Offload changeover switch, 415V, 4 pole, 63 Amps, fixed in and including provision of suitable size sheet metal enclosure all as specified and as directed.
S&F in repairs street light timer panel, 3 phase, 6 KW load, with 24 hour digital timer, 32/ TP rating contactor and 40 Amps MCB TPN, fitted in and including suitable size powder coated sheet steel enclosure complete fixed on pole/ wall with suitable size MS brackets all as specified and as directed. Make: Havells Cat No. IHXTS0306A OR eqvt in L&T /HPL
S&F in repairs street light timer panel, 3 phase, 12 KW load, with 24 hour digital timer, 65/ TP rating contactor and 63 Amps MCB TPN, fitted in and including suitable size powder coated sheet steel enclosure complete fixed on pole/ wall with suitable size MS brackets all as specified and as directed. Make: Havells Cat no IHXTSO912A OR eqvt in L&T /HPL
S&F in repairs power contactors suitable for 6 KW 3 phase street light timer panel all as specified and as directed. Make: Havells/ L&T / INDO ASIAN
S&F in repairs power contactors suitable for 12 KW 3 phase street light timer panel all as specified and as directed. Make: Havells/ L&T / INDO ASIAN
S&F in repairs control relay suitable for 6 KW 3 phase street light timer panel all as specified and as directed. Make: Havells/ L&T / INDO ASIAN
S&F in repairs control relay suitable for 12 KW 3 phase street light timer panel all as specified and as directed. Make: Havells/ L&T / INDO ASIAN
Earthing complete with galvanised steel earth plate electrode 60cmx60cmx6mm thick, burried directly in ground vertically (earth pit not less than 2.25 metre deep below normal ground level) with top edge of the earth plate at a depth not less than 1.5m below normal ground level connected to GI wire 4mm dia (7.5m long) by means of GI bolts nuts washers and GI wire protected by 15mm dia light grade GI pipe (7.5m long) and watering arrangements with 20mm dia GI pipe medium grade and GI funnel all as specified and shown in Electrical Plate No 3 of MES Schedule Part I including necessary excavation and earth work in any type of soil, charcoal, dust salt, PCC 1:2:4 type B1 in chamber, 40mm thick RCC 1:2:4 type B1 in cover slab with 8mm dia TMT bars at 100mm C/C both ways and with 8mm dia MS hook complete and testing including taking out existing unserviceable earthing all as specified and directed.
Earthing complete with galvanised steel earth plate electrode 60cmx 60cmx 6mm burried directly in ground vertically (earth pit not less than 2.25 metre deep below normal ground level) with top edge of the earth plate at a depth not less than 1.5m below normal ground level connected to GI strip of size 32x6mm (7.5m long) by means of GI nuts, bolts and washers and 50 mm dia GI pipe light grade for protection of earth lead and connected to control board of transformer and 20mm dia GI pipe medium grade (7.5m long) for watering arrangement and GI funnel all as specified and shown in Electrical Plate No 3 of MES Schedule Part I including necessary excavation and earth work in any type of soil, charcoal, dust salt, PCC 1:2:4 type B1 in chamber, 40mm thick RCC 1:2:4 type B1 in cover slab with 8mm dia TMT bars at 100mm C/C both ways and with 8mm dia MS hook complete and testing all as specified and directed.
Supplying, installing, testing and commissioning of Main switch board, cubical type, factory made, indoor type, IP 54 protection class, 415 volts , 50Hz, 3 phase, 4 wire system with 200 Amps current carrying capacity, made out of 2mm thick CRCA sheet, 1.2m x 1.0m x 0.45m size, vermin and dust proof, front operated double door with locking arrangement and ventilator slots, cable glands, lugs, etc. and painting with epoxy powder coated over a coat of red oxide zinc chromate primer suitable to accommodate and including the following mentioned fittings with internal copper wiring complete including taking down existing unserviceable switch boards of any description and size all as specified and as directed.
(a) Aluminium bus bar of 200 Amps rating for 3 phase & 100 Amps rating for neutral - 1 Set (b) MCCB 4 Pole 415 Volts 16 KA 100 Amps - 01 No. (Incoming) (c) MCB DP 240 Volts 10 KA 'C' series, 32 Amps - 07 Nos. (d) LED Indicating lamps indicating R, Y, B -01 Set (e) Space for and fixing of 7 Nos. of MES electric energy meters.
Supplying, installing, testing and commissioning of Main switch board, cubical type, factory made, indoor type, IP 54 protection class, 415 volts , 50Hz, 3 phase, 4 wire system with 200 Amps current carrying capacity, made out of 2mm thick CRCA sheet, 1.0m x 1.0m x 0.45m size, vermin and dust proof, front operated double door with locking arrangement and ventilator slots, cable glands, lugs, etc. and painting with epoxy powder coated over a coat of red oxide zinc chromate primer suitable to accommodate and including the following mentioned fittings with internal copper wiring complete including taking down existing unserviceable switch boards of any description and size all as specified and as directed.
(a) Aluminium bus bar of 200 Amps rating for 3 phase & 100 Amps rating for neutral - 1 Set (b) MCCB 4 Pole 415 Volts 16 KA 100 Amps - 01 No. (Incoming) (c) MCB DP 240 Volts 10 KA 'C' series, 32 Amps - 05 Nos. (d) LED Indicating lamps indicating R, Y, B -01 Set (e) Space for and fixing of 5 Nos. of MES electric energy meters.
ASHIRWAD ELECTRICALS
Vinod Enterprises
M/s.GOODWILL ELECTRICALS
M/s. VIJAY ELECTRICALS
DHAIRYASIL RAMAKANT DESAI
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .