Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.4 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹25.7 L+₹28,487.50 (1.12%)Rejected-Finance 72 USMAN ENCAVE SECTOR O ALIGANJ LUCKNOW 226004 UP | LUCKNOW | LUCKNOW | UTTAR PRADESH | 226004 | L2 | Rejected-Finance Reject being Not Lowest Bidder | |
| 3 | L3₹26.9 L+₹1.6 L (6.19%)Rejected-Finance 307 SADAR BAZAR LUCKNOW UP 226002 | LUCKNOW | UTTAR PRADESH | 226002 | L3 | Rejected-Finance Reject being Not Lowest Bidder |
Tender Value
Refer Docs
EMD Value
₹56,000
Closing Date
6 Oct 2020, 6:00 pmClosed
GE E/M Lucknow
Garrison Engineer E/M, 36 LBS Marg, Lucknow Cantt, Lucknow (U.P.) PIN 226002
PROVN OF THREE PHASE ELECTRIC DISTRIBUTION SYSTEM FOR OTM ACCN AT CHANKYA MARG AND SPL REPAIR/REPLACEMENT OF UNSV OH LINE INTO UG CABLE AT USMAN ROAD AND CONNECTED AREAS UNDER GE E/M LUCKNOW
2020_MES_375772_1
GE/EM/LKO/EXT(ELECT)/T-48 OF 2020-2021
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Lucknow
Class D or above category b(i)
8 documents required · 8 mandatory
₹500
Yes
GE E/M Lucknow
₹56,000
Yes
29 Oct 2020
8 Sept 2020
8 Oct 2020
8 Sept 2020
6 Oct 2020
23 Sept 2020
Amount
LT under ground electric power cable crossed linked polyethylene ( XLPE) insulated, galvanised steel strip or wire armoured, ISI-7098 Marked, with aluminium conductor multi stranded , heavy duty 1100 Volts grade of size 16 sqmm cross sectional area, 4 core ,complete all as specified laid in trenches/ laid under floor or fixed naked with walls / on poles/ in ducts /in GI pipes etc. with and including MS Clamps, nuts , bolts, washers including jointing and testing complete complete all as specified and directed by Engineer-in- Charge. Note : Excavation, earth work, sand cushioning, protection bricks/ tiles/ block and pipe shall be measured and paid separately under appropriate items.
All as per Item No.1 above but size 25 sq mm 4 core
All as per Item No.1 above but size 50 sq mm 3.5 core
All as per Item No. 1 above but size 95 sq mm 3.5 core
All as per Item No.1 above but size 120 sq mm 3.5 core
All as per Item No.1 above but size 185 sq mm 3.5 core
All as per Item No.1 above but size 300 mm 3.5 core.
Taking down unserviceable UG cable off sizes complete all as specified and directed by Engineer-in- Charge. Note :- Excavation, earth work shall be measured and paid separately
Excavation in trenches not exc 1.5m wide and and not exc. 1.5m depth wide in soft/loose soil for laying electric cables/pipes etc including getting out excavated earth and trimming the sides and bottoms of trenches , complete all as specificed and directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the cables have been laid and tested, complete all as specified and directed by Engineer-in-Charge.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point , complete all as specified and directed by Engineer-in-Charge.
Sand cushioning to cables with a layer of sand 8 cm deep before laying the cable and 15 cm depth (punned down to 10 cm depth after laying and stretching of cable), complete all as specificed and directed by Engineer-in-Charge. Note: Punned thickness (over all 18 cm) shall be measured & paid.
Protection of cable with one layer of bricks laid flat butting to each other in such a way that the length of the bricks is at right angle to the central axis of the cable using old size sub-class ‘B’ bricks, complete all as specified and as directed by Engineer-in-Charge.
Plain cement concrete 1:3:6 type C-2 using 40 mm graded stone aggregates, as in coping of poles, complete all as specified and as directed by Engineer-in-Charge.
Boring / drilling (Horizontly ) manually under existing road Max 10 M in width suitable for passing GI tubing 40 to 100 mm bore, complete all as specified and as directed by Engineer-in-Charge.
End termination heat shrinkable joint including sleeves suitable for LT XPLE underground aluminium conductor cable 1000 Volt of grade 25 Sqmm to 50 Sqmm x 3.5/4 Core cross sectional area including testing after jointing as in replacment after disconnecting the cable from Panel / Pole, preparing the end for jointing including all earth work,complete all as specified and directed by Engineer-in-Charge.
All as per Item No.16 above but of size 70 to 120 Sqmm
All as per Item No.16 above but size 185 sq mm
Mild steel galvanized tubes light grade ISI marked 40mm bore laid in trenches / road crossing/ fixed to pole /walls/path/drain /floor etc in and including taking down old unservicable G I pipe ,compllete all as specified and as directed by Engineer-in-Charge.
All as per Item No.19 above but of size 50 mm bore
All as per Item No.19 above but of size 80 mm bore
Earthing complete with galvanised steel plate earth electrode 600X600X6mm thick buried directly in ground (earth pit not less than 2.25 meter below ground level) with top edge of the plate not less than 1.5 metre below normal ground level connected to GI strip 32x6mm at two points by means of bolts and nut, check nut and washers including charcoal dust, common salt, necessary excavation in hard/dense soil, returning filling in and removal of surplus soil to a distance up to 50metres, PCC pit in 1:3:6 type CI (using 20mm grade stone aggregate) RCC 1:2:4 type B-1 (using 20mm grade stone aggregate ) 50mm thick pit cover, reinforced with 8mm dia TMT bars 75mm c/c, both ways MS handle 12mm dia, GI funnel, wire mesh and GI watering pipe of 20mm bore GI (light grade) and earth lead protection pipe 40mm bore (light grade) all as specified, directed and shown in electrical plate No 5 of SSR Part-I and testing ,including dismanteling of old unserviceable earthing , complete all as specified and as directed by Engineer-in-Charge. Note : (i) The unit rate includes earth lead and protection pipe up to maximum 7.5 metre from earth plate to earth point/test point. (ii) Earth pit shall be constructed minimum 1.00 metre away from earth.
M&L for outdoor type cubical panel board made out of 3.15 mm thick CRCA sheet and inner shell made out of 1.6 mm thick CRCA sheet and MS angle section 50x50x6 mm, factory fabricated front openable double door system suitable for 3 phase 4 wire 415 volts, powder coat RAL 7035 painting having thickness 90 microns comprising of the following :- a) The TPN busbar duly plated copper busbar fitted in cascaded moulding. b) Incoming MCCB 400 Amps 36 kA, 415 volts, FP - 01 Nos c) Outgoing MCCB 250 Amps 25 kA, 415 volts, FP - 01 Nos d) Outgoing MCCB 200 Amps 25 kA, 415 volts, FP - 02 Nos e) Outgoing MCCB 160 Amps 16 kA, 415 volts, FP - 01 Nos Voltage/Ampere/Frequency meter multi functional meter - 01 No f) LED indicator lamp RYB - 01 Set of three
M&L for outdoor type cubical panel board made out of 3.15 mm thick CRCA sheet and inner shell made out of 1.6 mm thick CRCA sheet and MS angle section 50x50x6 mm, factory fabricated front openable double door system suitable for 3 phase 4 wire 415 volts, powder coat RAL 7035 painting having thickness 90 microns comprising of the following :- a) The TPN busbar duly plated copper busbar fitted in cascaded moulding. b) Incoming MCCB 250 Amps 36 kA, 415 volts, FP - 01 Nos c) Outgoing MCCB 200 Amps 25 kA, 415 volts, FP - 01 Nos d) Outgoing MCCB 160 Amps 16 kA, 415 volts, FP - 01 Nos e) Outgoing MCCB 100 Amps 16 kA, 415 volts, FP - 02Nos , Voltage/Ampere/Frequency meter multi functional meter - 01 No f) LED indicator lamp RYB - 01 Set of three
M&L for out door type busbar panel board made out of 3.15 mm thick MS sheet and MS angle section 50x50x6 mm factory fabricated suitable for 3 phase 4 wire 415 Volt, 50 Hz, powder coat painted comprising of the following:- a) TPN, Aluminium bus bar 400 Amps insulated with colour coded heat shrinkable sleeve and shall be mounted on suitable size “F” class insulators. b) Incoming MCCB 200 Amps 36 KA, 415 Vots, 50 Hz, FP. – 1 No c) LED Indicator lamp RYB - 01 set of three. d) Necessary excavation, earth work, PCC lean type D2 and PCC type C2 platform complete all as required.
Dismantling taking down old cross arms, clamps, braces etc of any section from pole including nuts, bolts, washers complete all as specified and as directed by Engineer-in-Charge. Note - Cost of cutting of bolts (Slag bolts) if reqd shall deemed to be included in the unit rate quoted for this item.
Disconnecting, dismantling and taking down carefully GI earth wire conductor from poles of any size and setting a side complete all as specified and as directed by Engineer-in-Charge.
Disconnecting, dismantling and taking down carefully ACSR conductor from poles of any size and setting a side complete all as specified and as directed by Engineer-in-Charge.
Dismantling insulators any type, any size complete all as specificed and directed by Engineer-in-Charge.
Supply & fix single pointed air termination copper rod, 12 mm dia, 300 mm long complete all as specificed and directed by Engineer-in-Charge.
Aluminium strip 25 x 3.15 mm with saddles and fixing screws etc. for roof conductors and down conductors above ground complete all as specificed and directed by Engineer-in-Charge.
GI strip 32X6 mm with seddle and fixing srew PVC dash fastener ,insulator ,fixed form test point to earth on wall or burried in ground / drawn into hum pipe complete all as specificed and directed by Engineer-in-Charge.
Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw complete all as specificed and directed by Engineer-in-Charge.
Supply, installation, testing and commissioning indoor type cubical panel board ( size not less than 1500X1500x 500 mm with separate incoming and out going cable compartment , drawing as approved by GE ) outer shell made out of MS sheet as specified thicness and mounted on MS base frame channel 100X5 mm on ground , frame factory fabricated with front openable single door system lockable/openable by Keys having chromium plated 19 mm dia fancy lock, louvers and air vent gasket for natural flow of air “U” type gasket shall be used to make the outer shell completely vermin proof .suitable for 3 phase 4 wire 415 Volt, 50 Hz, CPRI approved for 35 MVA rupturing capacity at 415 Volts factory fabricated having modern fabrication comprising of the following:- a) The TPN busbar (600 Amp )duly plated Aluminium bus-bar fitted in cascaded moulding. (b) Brass gland andcrimpinglugs for sending and receiving cable c ) All load Managers to have para meters like KW,KVA,A,V, PF, KVAR,Active & reactive componemt of Power RS 485 port to have BMS component - 01 No d) All Ammeter with CT and Voltmeter and(E) 3 Ph Energy meter 5 A/-with CT 300/5 . -01 nos ) LED indicator lamp RYB - 01 Set of three INCOMING 1) Incoming MCCB 400 Amps 36 kA, 415 volts, FP - 01 Nos, with on and off switch with rotory handle and RYB indicator with dual source energy meter whitch show energy consumption , voltage, ampear and power factory. OUTGOING (1) Outgoing MCCB 63 Amps 16 kA, 415 volts, FP - 08 Nos, with on and off switch with rotory handle Make Schneider, Legrand, L&T,Seimens etc
M&L for outdoor type cubical panel board made out of 3.15 mm thick CRCA sheet and inner shell made out of 1.6 mm thick CRCA sheet and MS angle section 50x50x6 mm, factory fabricated front openable double door system suitable for 3 phase 4 wire 415 volts, powder coat RAL 7035 painting having thickness 90 microns comprising of the following :- a) The TPN busbar duly plated copper busbar fitted in cascaded moulding. b) Incoming MCCB 250 Amps 36 kA, 415 volts, FP - 01 Nos c) Outgoing MCCB 200 Amps 25 kA, 415 volts, FP - 01 Nos d) Outgoing MCCB 160 Amps 25 kA, 415 volts, FP - 01 Nos e) Outgoing MCB SPN 32/40Amp Amps 25 kA, 415 volts, FP - 2 Nos e) Outgoing 3 PH Time switch32 Amp 3 Pole /230 V analog time switch - 1 Nos Voltage/Ampere/Frequency meter multi functional meter - 01 No f) LED indicator lamp RYB - 01 Set of three
S&F out door luminaries light fully cast aluminium body finished with stove enameled paint acrylic window cover (Total Height 3 Mtr ), fully cast Aluminium heavy pole designer leg and broader designer base finished with stove enamelled paint diameter apprx 78 mm body surmounted with fully cast aluminium body finished with PU paint with acrylic window covermax length of fitting 2480 mm ,B-22 Brass holder including 03 Nos LED Bulb 18 Watt complete with all foundation work with nut ,bolt and washers etc. Make as per Mepro Cat Pt Nos MCPL-04,CDPB-06,PTL-003 or equivalent as per Appx.
Unnati Engineers
M/s Vatsh Raj and co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .