Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.0 CrAccepted-AOC | ₹5.0 Cr | L1 | Accepted-AOC Accepted being L1 |
| 2 | L2₹5.2 Cr+₹23.7 L (4.79%)Rejected-Finance 1630 SECTOR 7C CHANDIGARH 160019 | CHANDIGARH | CHANDIGARH | CHANDIGARH | 160019 | ₹5.2 Cr+₹23.7 L (4.79%) | L2 | Rejected-Finance Not being L1 |
| 3 | L3₹5.3 Cr+₹38.4 L (7.75%)Rejected-Finance | ₹5.3 Cr+₹38.4 L (7.75%) | L3 | Rejected-Finance Not being L1 |
| 4 | L4₹5.4 Cr+₹41.8 L (8.43%)Rejected-Finance | ₹5.4 Cr+₹41.8 L (8.43%) | L4 | Rejected-Finance Not being L1 |
| 5 | L5₹5.6 Cr+₹67.7 L (13.7%)Rejected-Finance NOT SPECIFIED | ₹5.6 Cr+₹67.7 L (13.7%) | L5 | Rejected-Finance Not being L1 |
Tender Value
₹5.6 Cr
EMD Value
₹6.1 L
Closing Date
1 Oct 2022, 6:00 pmClosed
Chief Engineer AF Bangalore
Chief Engineer AF Bangalore No. 2 DC Area MES Road Yeshwantpur Post Bangalore 560022
PROVISION OF AIR FORCE SHARE OF WORKS FOR MAFI-II AT AF STATION HAKIMPET
2022_MES_537441_1
801530/E8
Open Tender
Civil Works
Lump-sum
540 days
Hakimpet
Class A CAT a i b ii
8 documents required · 8 mandatory
₹3,000
GE (AF) HAKIMPET
₹6.1 L
Yes
19 Nov 2022
12 Jul 2022
8 Oct 2022
12 Jul 2022
1 Oct 2022
17 Sept 2022
13 Jul 2022 - 23 Jul 2022
Amount
BOQ Dated
GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to IX are prepriced by MES under Ser No. 1 to 9. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lumpsum price worked out by the contractor for “Building or works” as listed in Schedule ‘A’ Part–I
Lumpsum price worked out by the contractor for “Internal Water Supply” as listed in Schedule ‘A’ Part - II
Lumpsum price worked out by the contractor for “Internal Electric Supply" as listed in Schedule ‘A’ Part–III
Lumpsum price worked out by the contractor for “Filling & Compaction” as listed in Schedule ‘A’ Part - IV.
Lumpsum price worked out by the contractor for “Road/Hard Standing" as listed in Schedule ‘A’ Part - V .
Lumpsum price worked out by the contractor for “Sewage Disposal” as listed in Schedule ‘A’ Part – VI.
Lumpsum price worked out by the contractor for "Boundary Wall / Fencing & Gate" as listed in Schedule ‘A’ Part - VII.
Lumpsum price worked out by the contractor for "External Water Supply" as listed in Schedule ‘A’ Part - VIII.
Lumpsum price worked out by the contractor for “External Electric Supply” as listed in Schedule ‘A’ Part – IX.
Sch 'A' Part - X : Fittings / Fixtures & Misc items. ROAD Material and labour for Providing and laying road marking paint as per IRC 35 with hot applied thermo plastic compound with reflectorising glass beads on bituminous surface, applying of hot thermo plastic compound with minimum 2.5 mm thick including reflectorising glass beads @ 250 gms per sqm inclusive of all surface cleaning, applying, labour charges, all taxes etc at site for complete finished item of work as directed by Engineer in Charge.
SEWAGE DISPOSAL Supply and fix On site LLDPE septic tank designed to carry sewage and sullage water, excavation in any type of soil, PCC 1:4:8 below foundation, Vent shaft, connection etc., complete for connection etc., complete for 5 Users
INTERNAL ELECTRIC SUPPLY Supply and fix and connecting up ceiling fan of size 1200mm sweep complete, including with cable 3 core of size 0.5 sqmm from ceiling rose to fan, including writing MES No 2cm height with synthetic enamel black paint all as specified and as directed.
Supply and fix exhaust fan 300mm sweep heavy duty 900 rpm single phase 240 volts AC 50 Hz and connecting up complete including frame and louvers and provision of copper cable 3 core of size 0.5 sqmm all as specified and as directed.
Supply and fix LED light fitting 4 feet, 1 x 20 Watt, 220Volt AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed.
Supply and Fix 20W High efficient LED Building Security light fitting around the building, Aluminium pressure Die cast housing with pure polyester powder coated for long life, High purity lenses for superior performance, IP66 protection, Suitable for external pipe dia Up to 50 mm, with Luminiare efficacy >100lm/W, driver Voltage range 150-270V AC, temperature range- 0 to 50DegC, Driver efficiency > 85%, Power factor > 0.95, THD<10%, CRI >70, Colour Temperature- 6500K, with Luminiare efficacy >100lm/W, Surge protection from overvoltage- 3.5KV in CM, Safety Extra Low Voltage Safe level<60V DC as per IEC standard, 50000 burning hours as per L70 Criteria, including provision of 40mm dia GI light grade pipe1.5 mtr length bend to shape and necessary clamps etc for fixing the light fittings on wall/pole fixed complete as specified and directed (Make: Wipro Catalogue No. LR02-251-XXX-57-XX , Philips of Catalogue No. BRP022 LED 21 CW MR S1 PSU GR Bajaj Catalogue No. BCLST 20W LED I)
Earthing complete with galvanized iron earth plate electrode of size 600mmx600mm x 6.3 mm thick buried directly under ground vertically to depth not less than 2.25 meter below ground level with top edge of plate at a depth not less than 1.5 m below ground level connected to and including GI wire 4mm dia and GI protection pipe 15mm dia and light grade connected to and including by means of bolts nuts check nuts and washers made of copper as shown plate no 3 of SSR part 1 to the extent applicable to this item including necessary excavation earth work , PCC 1;3;6 chamber RCC 1;2;4 cover 50mm tick with 6mm TMT bar 100mm center to center watering pipe medium grade 20mm bore funnel wire mesh etc. and testing on completion all as specified and as directed.
EXTERNAL WATER SUPPLY Construction of valve chamber of size 450mm x 450mm x 700mm in 200mm thick Brick walls with sub class 'B' brick built in CM 1:4, rendering 10mm thick cement plaster on fair faces of brick work finished even and smooth (with out using extra cement) and providing 3mm thick MS plate hinged cover fixed to 25mmx25mmx3mm thick angle iron frame work on brick work chamber with locking arrangement including necessary earth work, excavation, PCC bedding & coping, applying two coats of synthetic enamel paint over a coat of red oxide primer on steel surfaces and two coats of white wash on brick wall surfaces complete as required at site all as directed.
EXTERNAL ELECTRIC SUPPLY Taking out serviceable 11 KV HT UG cable from trenches and relaying in the same or other location where directed for the size 120 to 185 sqmm 3 core HT 11 KV grade for diversion of the same complete all as specified and as directed. Note: [i] Earth work for taking down of cable and earth work for relaying of cable, sand cushioning, PCC cover for cable protection, GI pipe etc shall be measured separately under relevant items of connected schedule. [ii] The rate deemed to including shifting of the cable from one location to other location.
Supply, install, testing and commissioning of HT Panel consist of 06 Nos (02 incomers, 02 bus couplers and 02 outgoings) of free standing, metal clad, modular, cubicle type dust and vermin proof, front operated 350 MVA, 630 Amps, 26.2 KA VCBs for operation on 11 KV, 3 phase, 50 Hz AC supply system suitable for indoor extensible type installation, Draw out type, horizontal/ vertical isolation type with Electrical and Mechanical interlock and automatic safety shutter gear including padlocking arrangement, isolation plugs, assembly of 3 vacuum interrupters, with epoxy support insulations and self - aligning finger type isolating contacts, track having integral racking with necessary interlocks (for insertion and withdrawal of VCB), manual and automatic motor charged independent closing/ tripping spring, trip free operating mechanism with closing and tripping push buttons and mechanical breaker, including inbuilt battery packed Power pack 230V, AC/110V DC with 7ah Battery system, indoor floor mounted overload and earth fault protection, ammeter, voltmeter, multi functional meters with CTs & PT, manufactured in confirmation to IS-3427, BS 5227complete with power and control wiring, inter connection, TP copper bus bar fully tinned and totally covered with colour coded heat shrinkable sleeves and non-hygroscopic, high dielectric strength bus bar support insulators, earthing, painting complete all as specified and as directed. (For location MAFI Power Station -1 & 2) (Make: ABB or equivalent in Crompton Greaves/ AREVA/Schinder/Siemens)
Material and labour for Boring/ drilling (horizontally ) of holes under road, pavement, hard standing by trenchless technology suitable for passing GI/HDPE pipe 80mm dia all as specified and as directed by Engineer in charge.
Supply, install, connecting, testing and commissioning of transformer of capacity 630 KVA having technical parameters as per IS 1180 (Part - I) : 2014, Level 3 Star 2 with all standard fittings and accessories, step down, Indoor type, oil immersed naturally cooled type, copper wound, HT 11000 Volts, 3 phase, 50 Hz on primary side and 433 Volts, 3 phase, 4 wire on secondary side, 50 Hz with off load tap changer having tappings on HT side to vary secondary voltage by +/- 7.5 %. complete with standard fittings, cable end box both on HT and LT side, LT terminals extended with 20 mm x 3 mm "L" type copper strip connected with bracing for connecting cable lugs on LT side including initial filling of oil conforming to IS 335-1981 complete all as specified and as directed.
Supply, install, connecting, testing and commissioning of transformer of capacity 200KVA having technical parameters as per IS 1180 (Part - I) : 2014, Level 3 Star 2 with all standard fittings and accessories, step down, Indoor type, oil immersed naturally cooled type, copper wound, HT 11000 Volts, 3 phase, 50 Hz on primary side and 433 Volts, 3 phase, 4 wire on secondary side, 50 Hz with off load tap changer having tappings on HT side to vary secondary voltage by +/- 7.5 %. complete with standard fittings, cable end box both on HT and LT side, LT terminals extended with 20 mm x 3 mm "L" type copper strip connected with bracing for connecting cable lugs on LT side including initial filling of oil conforming to IS 335-1981 complete all as specified and as directed. Note for item Nos. 21 & 22: (a) Contractor shall obtain proper approval of make from the GE before commencement of work. (b) Manufacturer's test certificate shall be submitted. (c) The quoted rate shall be inclusive of construction of PCC Platform of size 1m x 1mx 100mm thick for installing the transformer.
Supply install testing and commissioning of voltage stabilizer conforming to 159815 (Part I) : 1994 (second revision) (Reaffirmed 2019). Copper wound with protection of over load / short circuit and high/low voltage, single phasing, phase reversal with by pass arrangement for automatic operation, three phase, naturally oil cooled, indoor type & designed for input variation between 300 V to 480 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 630 KVA complete all as specified and as directed.
Supply install testing and commissioning of voltage stabilizer conforming to 159815 (Part I) : 1994 (second revision) (Reaffirmed 2019). Copper wound with protection of over load / short circuit and high/low voltage, single phasing, phase reversal with by pass arrangement for automatic operation, three phase, naturally oil cooled, indoor type & designed for input variation between 300 V to 480 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 200 KVA complete all as specified and as directed.
Supply , install, test and commissioning of LT Panel board made out of 2 mm CRCA Sheet indoor cubical type totally enclosed weather dust and vermin proof with front and rear opening of 440 Volts 3 phase 4 wire 50 Hz having copper bus bar capacity 1250 Amps and half neutral with copper bus bar RYB duly insulated complete including internal wiring with copper conductor including two coats of primer and one coat of spray painting including connecting all in coming and out going cable feeders with necessary lugs ferrules etc. The panel should have angle iron support on the base all around including pcc foundation support , well finishing with cement mortar, Comprising of the following switchgear and accessories are as under:- (MAFI Power station-1) (a) Mains Incoming : ACB 800 Amps 4 Pole 50 KA - 01 No (b) For DG sets : ACB 800 Amps 4 Pole 50 KA - 02 Nos (c) For DG sets : Bus coupler ACB 800 Amps 4 Pole 50 KA - 01 No (d) For outgoing to Isolation Transformer : ACB 800 Amps 4 Pole 50 KA - 01 No
(a) ACB 4 pole 800A, 415V, 50KA 1 Sec 50Hz supply. Make:- Siemens / ABB / Schneider/L&T. (b) Mounting - Draw out mounting with safety shutters. (c) Type of operation : Electrically operated with 230V AC motor with manual Handle. (d) Closing/Tripping coil/U-V Voltage : 230V AC. (e) Relay type : Microprocessor based with earth leakage, over current, short circuit protections for generator applications (in 02 generator feeders) other ACB with industrial application (Siemens - ETU series 45 or equivalent). (f) Aux Contacts : Min 7 NO +7 NC, 3NO + 3NC extended upto panel terminal blocks for remote PLC interlock. (g) Multifunction meter :- Each ACB panel bay will display current / voltage through MFM of Make: Elite/Secure, Conserve /Schneider. (h) Local/Remote switch :- Panel needs to be equipped with local/remote switch with wiring of remote upto terminal block. (j) Hard wire interlock :- Among DG-1, DG-2 & Mains ACB come in force, If L/R switch is on remote and as soon as turned to local then it can be controlled manually from TNC (Trip, neutral and close switch). (k) Indication : Green (ON) and RED (OFF) indication of each ACB panel console. (l) Extended cable bus bar :- 400 sqmm 3.5 core AL XLPE 3 runs of cables going to be terminated in each of DG-1, DG-2 feeders, Hence proper bus bar chamber size to accommodate all cables. (m) PLC Interlock :- Wiring needs to be provided for remote close, remote trip and U-V inside panel upto outgoing terminal of each ACB panel bay with at least 3NO+3NC Aux contacts wired upto terminal block so that can be used for further remote interlock. (n) Interpanel hard wired interlock :- will be provided by ACB panel manufacturer closing circuit interlocks as detailed above. (o) Electrical TNC (Trip-Neutral-close) :- Trip, Neutral and close switch for manual operation needs to be provided by ACB panel manufacturer.
Supply, Install, testing and commissioning of indoor type Isolation Transformer 630 KVA three phase, wet type, delta star metallic body unbalanced type copper wound with standard fittings and accessories for input voltage 400 V AC, 3 phase, output voltage 400V AC, 3 phase of frequency of 50 Hz, voltage regulation 4% max with following description :- (a) Method of cooling - Oil immersed naturally cooled (b) Temperature rise in winding (degree C) over and ambient 55 deg. (c) As per IS : 1180 (Part - I) : 2014 level 3 star 2. Size of PCC platform for transformer required is 1m x 1m x 100mm thick, efficiency shall be more than 98% (d) Mounting on wheels (e) Class of insulation F (f) Earth to neutral voltage should be less than one volt complete all as specified and as directed. Location- MAFI Power station-1
Supply, Install, testing and commissioning of indoor type Isolation Transformer 200 KVA three phase, wet type, delta star metallic body unbalanced type copper wound with standard fittings and accessories for input voltage 400 V AC, 3 phase, output voltage 400V AC, 3 phase of frequency of 50 Hz, voltage regulation 4% max with following description :- (a) Method of cooling - Oil immersed naturally cooled. (b) Temperature rise in winding (degree C) over and ambient 55 deg. (c) As per IS : 1180 (Part - I) : 2014 level 3 star 2. Size of PCC platform for transformer required is 1m x 1m x 100mm thick, efficiency shall be more than 98% (d) Mounting on wheels (e) Class of insulation F (f) Earth to neutral voltage should be less than one volt complete all as specified and as directed. Location- MAFI Power station-2
Supply , install, test and commissioning of LT Panel board made out of 2 mm CRCA Sheet indoor cubical type totally enclosed weather dust and vermin proof with front and rear opening of 440 Volts 3 phase 4 wire 50 Hz having copper bus bar capacity 400 Amps and half neutral with copper bus bar RYB duly insulated complete including internal wiring with copper conductor including two coats of primer and one coat of spray painting including connecting all in coming and out going cable feeders with necessary lugs ferrules etc . The panel should have angle iron support on the base all around including pcc foundation support , well finishing with cement mortar, Comprising of the following switch gear and accessories are as under:- ( MAFI Power station-2 )
(a) Mains Incoming : ACB 315 Amps 4 Pole 50 KA -01 No (b) Outgoing : (i) ACB 315 Amps 4 Pole 50 KA-01 No (ii) MCCB 12-63Amps 4pole - 12 Nos (iii) MCCB 16 Amps 2pole - 04 Nos (iii) MCCB 100 Amps 4pole - 01 No MCCB 16 Amps 2 pole - 1 Nos for sub station (a) ACB 4 pole 400A, 415V, 50KA 1 Sec 50Hz supply. Make:- Siemens / ABB / Schneider /L&T. (b) Mounting - Draw out mounting with safety shutters. (c) Type of operation : Electrically operated with 230V AC motor with manual Handle. (d) Closing/Tripping coil/U-V Voltage : 230V AC. (e) Relay type : Microprocessor based with earth leakage, over current, short circuit protections (Siemens - ETU series 45 or equivalent). (f) Aux Contacts : Min 7 NO +7 NC, 3NO + 3NC extended upto panel terminal blocks for remote PLC interlock. (g) Multifunction meter :- Each ACB panel bay will display current / voltage through MFM of Make: Elite/Secure, Conserve /Schneider. (h) Local/Remote switch :- Panel needs to be equipped with local/remote switch with wiring of remote upto terminal block. (j) Indication : Green (ON) and RED (OFF) indication of each ACB panel console. (k) Extended cable bus bar :- Hence proper bus bar chamber size to accommodate all cables. (l) PLC Interlock :- Wiring needs to be provided for remote close, remote trip and U-V inside panel upto outgoing terminal of each ACB panel bay with at least 3NO+3NC Aux contacts wired upto terminal block so that can be used for further remote interlock. (m) Electrical TNC (Trip-Neutral-close) :- Trip, Neutral and close switch for manual operation needs to be provided by ACB panel manufacturer.
Supply, install, test and commissioning of LT Panel board made out of 2 mm CRCA Sheet indoor cubical type totally enclosed weather dust and vermin proof with front and rear opening of 440 Volts 3 phase 4 wire 50 Hz having copper bus bar capacity 400 Amps and half neutral with copper bus bar RYB duly insulated complete including internal wiring with copper conductor including two coats of primer and one coat of spray painting including connecting all in coming and out going cable feeders with necessary lugs ferrules etc. The panel should have angle iron support on the base all around including pcc foundation support, well finishing with cement mortar, Comprising of the following switch gear and accessories are as under:- (MAFI Power station-1 )
(a) Mains Incoming : ACB 800 Amps 4 Pole 50 KA -01 No (b) Outgoing : (i) ACB 630 Amps 4 Pole 50 KA-02 Nos (ii) MCCB 12-63Amps 4pole - 14 Nos (iii) MCCB 16 Amps 2pole - 02 Nos (iii) MCCB 100 AMps 4pole - 01 No MCCB 16 Amps 2 pole - 1 Nos for sub station (a) ACB 4 pole 630A, 415V, 50KA 1 Sec 50Hz supply. Make:- Siemens / ABB / Schneider / L&T. (b) Mounting - Draw out mounting with safety shutters. (c) Type of operation: Electrically operated with 230V AC motor with manual Handle. (d) Closing/Tripping coil/U-V Voltage : 230V AC. (e) Relay type : Microprocessor based with earth leakage, over current, short circuit protections (Siemens - ETU series 45 or equivalent). (f) Aux Contacts : Min 7 NO +7 NC, 3NO + 3NC extended upto panel terminal blocks for remote PLC interlock. (g) Multifunction meter :- Each ACB panel bay will display current / voltage through MFM of Make: Elite/Secure, Conserve /Schneider. (h) Local/Remote switch :- Panel needs to be equipped with local/remote switch with wiring of remote upto terminal block. (j) Indication : Green (ON) and RED (OFF) indication of each ACB panel console. (k) Extended cable bus car :- Hence proper bus bar chamber size to accommodate all cables. (l) PLC Interlock :- Wiring needs to be provided for remote close, remote trip and U-V inside panel upto outgoing terminal of each ACB panel bay with at least 3NO+3NC Aux contacts wired upto terminal block so that can be used for further remote interlock. (m) Electrical TNC (Trip-Neutral-close) :- Trip, Neutral and close switch for manual operation needs to be provided by ACB panel manufacturer.
Material and labour for earthing complete with GI plate electrode 600x600x6mm thick, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5m below ground level connected to earth lead of 32x6 mm GI strip by means of bolts, nuts, washers of galvanized, incl GI protection pipe 40mm size light grade all as shown in electrical plate No.3 of SSR Part-I including necessary excavation and earth work. PCC 1:3:6 type C1 chamber, RCC cover in 50mm thick 1:2:4 type B1 with 8mm CTD 140mm centre to centre with suitable handle, watering pipe 20mm dia light grade pipe with funnel, charcoal salt connected to earthing test point all as specified including testing and commissioning on completion all as specified and as directed. Note :- Length of GI strip of size 32X 6 mm upto 7.5 mtr shall be measured as one unit only
Supply, install and testing of maintenance free chemical earthing system confirming to IS: 3043 and as per the detailed specification given below : (a) Earth Electrode : The Earth electrode shall be non-corrosive, solid steel round rod of size 17.20mm dia, 3000mm long, made of high tensile low carbon steel with molecularly bonded copper coating of thickness 250 microns on the outside. (b) Bore hole : The electrode shall be installed in a 1200 mm dia 3000mm deep augured bore hole and to be filled 400 mm outer dia with black soil (Note:- Rates should be including supply and filling of black soil in proper manner) (C) Ground enhancing compound : The augured bore hole shall be filled with highly conductive and eco friendly ground enhancing carbon based backfill compound suitable for any type of soil. The quantity of ground enhancing compound shall not be less than 30 Kg per pit. (d) Earth termination clamp : The electrode shall be provided on its top with an earth termination clamp made of electrolytic grade copper for connecting earth continuity conductor with stainless steel hardware. (e) Earth chamber : PCC chamber 300 x 300 x 300mm with cover shall be provided on the top of the earth system on 100mm thick PCC 1:3:6 bed concrete. The Chamber shall be flushed with the ground surface.
(f) Earth point test box: Copper strip of size 25X3 mm size, 200mm long mounted on insulators and enclosed in MS sheet box made of 2 mm thick and size 250X200X120 mm sloped top outdoor type duly painted with two coats of synthetic enamel paint over a coat of red oxide primer shall be provided at a suitable location. (g) Copper Strip : Copper strip of size 25X3 mm from earth pit to test point box upto 7.5 meter. Make : MEPL/Smart Solutions or equivalent approved
Material and Labour for earthing pit display boards made out of 3mm thick MS sheet of size 30 x 35cm welded to 75cm long 25 x 25 x 5 mm thick MS angle iron grouted in PCC 1:3:6 (with 20mm stone aggregate) to a depth of 20 cm and applying two coats of synthetic enamel paint of approved color over a coat of red oxide primer and writing the letters on plate for showing the following details: 1. EARTHING PIT NO. : 2. DATE OF MEASUREMENT : 3. NEXT DUE DATE : 4. STANDARD VALUE : 5. VALUE OBTAINED : 6. MEASURED BY : 7. SUPERVISED BY :
Supply and lay Insulation mat of 1 mtr width x 2 mtr length x 3 mm thickness (Voltage grade 11KV) ISI marked IS 15652-2006, (superseding IS 5424), CPRI approved complete all as specified and as directed.
Supply and fix omnidirectional light fitting of capacity 8W, 230V, AC with LED source clear lens including fixing arrangement like small channel, nut and bolts, PCC grouting including fixing arrangement for junction box, suitable to the base of light fitting and as per the site requirement including connection with suitable flexible wire three core 1.5 sqmm size from junction box to light complete all as specified and directed at site. (Note:- Junction box will be measured and paid separately)
Material and labour for PVC junction box out door type of size 280 mm x 170 mm x 130 mm with front openable hinged cover complete with two number aluminium bus bars mounted on porcelain insulator including clamps of MS flat iron 25 x 3 mm with bolts and nuts to fixed on pole/wall all as specified and directed.
Design, Supply, installation, testing and commissioning of Cubical type floor mounted chamber for MCB DB 12 Way, size 0.4 Width x 0.3M height x 0.25M depth, outdoor type factory fabricated made out of CRCA sheet of 3.15 mm thick ,fully enclosed and angle iron frame of size 25 x 25 x 5mm thick including provn legs of length 45 CM long and grouting in PCC 1:2:4 20CM above the ground level and front openable door, dust and vermin proof and rear opening complete with locking arrangement, provn of suitable cable glands, duly powder coated of approved quality over a coat of red primer with sufficient free space complete all specified and directed. (Note:- MCB DB shall be measured and paid separately)
Supply, Install, testing and commissioning of indoor type Automatic power factor correction panel consisting of MPP-H capacitor and MCCB as incomer complete 400 KVAR with 5 steps (5x5 + 4x10 + 4x15 + 3x25 + 4x50 KVAR) including incomer MCCB of 500 Amps415V, 36KA, 4 Pole complete all as specified and as directed.
Supply, Install, testing and commissioning of indoor type Automatic power factor correction panel consisting of capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase ,440 V, 50 Hz System for permissible non- linear load 15% of 125 KVAR (3x5 + 3x10 + 2x15 + 2x25) KVAR capacity including incomer MCCB of 200 Amps415V, 16KA, 4 Pole complete all as specified and as directed.
Supply and Fix MCB TPN 40 Amps 10KA 415 volts all as specified and as directed.
Material and labour for Straight through joint kit heat shrinkable type suitable to size 10 to 16 sqmm 4 core 1100V grade including jointing materials complete all as directed.
Material and labour for cable route marker made out of GI angle iron of size 25x25x3mm thick 60cm long for "HT CABLE" route marking embossed on GI circular plate 150mm dia 3mm thick including grouting in PCC 1:3:6 type C1 block concrete of size 20x20x20cm including necessary formwork complete all as specified and as directed.
Supply and fix AC Voltage stabilizer copper wound with high / low voltage cut off of capacity 2 KVA with input volt 180 to 250 Volts and output 200- 240 Volts +/- 2 % variation comprising voltmeter fuse unit socket connected lead etc with time delay system complete all as specified and as directed.
Supply and fix cable jointing kit for 11 KV grade cable for straight through, heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured, Aluminium conductor cable of size 95 Sqmm complete all as specified and as directed.
Supply, install, testing and commissioning of HT panel consist of 03 Nos VCBs (01 incomers and 02 outgoings) of free standing, metal clad, modular, cubicle type dust and vermin proof, front operated 350 MVA, 630 Amps, 26.2 KA VCBs for operation on 11 KV, 3 Phase, 50 Hz AC supply system suitable for indoor extensible type installation, draw out type, horizontal / vertical isolation type with electrical and mechanical interlock and automatic safety shutter gear including padlocking arrangement, isolation plugs, assembly of 3 vacuum interrupters with epoxy support insulations and self aligning finger type isolating contacts, track having integral racking with necessary interlocks (for insertion and withdrawal of VCB), manual and automatic motor charged independent closing / tripping spring, trip free operating mechanism with closing and tripping push buttons and mechanical breaker including inbuilt battery packed power pack 230V, AC/110V DC with 7ah Battery system, indoor floor mounted overload and earth fault protection, ammeter, voltmeter, multifuctional meters with CTs & PT, manufactured in confirmation to IS-3427, BS 5227 complete with power and control wiring, inter connection, TP copper bus bar fully tinned and totally covered with colour coded heat shrinkable sleeves and non hygroscopic, high dielectric strength bus bar support insulators, earthing, painting complete all as specified and as directed. (for location Main receiving station) Make : ABB or equivalent in Crompton Greaves / AREVA / Schinder)
(A) Specification for Each VCB (i) Bus bar chamber with 3 phase copper bus bar 1000 Amps rating duly color coded insulated - 01 set (set of three) (ii) Electrical shunt trip coil 110 V DC - 01 No (iii) Electrical closing coil 110 V DC - 01 No (iv) 11 KV CT chamber incorporating 3 Nos single phase resin cast current transformer ratio (100-50) A/ 5-5A class 1.0 for metering & class 5P 10 for protection and burdon 7.5 VA - 1 set.
Material and labour for PCC block 300x300x600mm by using 20mm graded aggregate for fixing of GI pipe 50mm bore complete all as specified and as directed.
Returning and filling of trenches in two parts (i) using riddled soil obtained from excavated soil upto depth of 30cm (8cm below cable and remaining above cable) for cushioning of cable and (ii) refilling the trench of remaining depth with normal excavated soil all as specified and directed. Note :- (i) Excavated soil shall be riddled by using sieve to separate composite particles etc as per IS 1255-1983 and refilling in trenches as in cable cushioning.
AIR CONDITIONING Supply and install hi wall split units indoor /outdoor complete with cordless remote control unit and with inbuilt with air ioniser on plasma filter for better indoor air quality with min. 5 star rating and EER 3.2 of capacity of 2 Ton capacity complete all as specified and directed.
Material and labour for Wiring for sub main with the 2 X 4 Sqmm + 1 x 4 Sqmm earth wire of FR PVC insulated copper conductor single core cable drawn in and including suitable size of non metallic rigid PVC conduit and all accessories (Concealed) complete all as specified and directed.
Supply and fix Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 240 Volt 20 Amp complete all as specified and directed.
Supply and fix AC Voltage stabilizer copper wound with high / low voltage cut off of capacity 5 KVA with input volt 180 to 250 Volts and output 200- 240 Volts +/- 2 % variation comprising voltmeter fuse unit socket connected lead etc with time delay system complete all as specified and as directed.
SAGGI ELECTRIC COMPANY
SHRI GANESH ENTERPRISES
M/s R.L.PAREEK
United Sales Corporation
Sant Construction Co.
Phoenix Infra
B D Raizada Projects Pvt Ltd
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .