Ex. ENGINEER (ELECT)-I
OFFICE OF THE Ex. ENGINEER (ELECT)-I, SHAHDARA (N) ZONE, KeshavChowk, Delhi-110053
Improvement of HVAC Plant Installed in MCH Block at Swami Dayanand Hospital Under Shahdara (North) Zone
2023_MCD_169403_1
EE(E)-I/Sh.N/MCD/23-24/TC-39/1
Open Tender
Electrical Works
Item Rate
90 days
As per NIT
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
₹38,084
5 Dec 2023
3 Oct 2023
11 Oct 2023
3 Oct 2023
10 Oct 2023
3 Oct 2023
Amount
OD items
OD4723/2023-2024:Supplying, Installation, Testing & Commissioning of Display Card of Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards.
OD4724/2023-2024:Supplying, Installation, Testing & Commissioning of synthetic screw Compressor Oil (Approx 50 Ltr.) Carrier Make for Chiller Machine i/c Testing, Commissioning Complete as Required.
OD4725/2023-2024:Supplying, Installation, Testing & Commissioning of Oil Level Switch to be installed in Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards.
OD4726/2023-2024: Supplying, Installation, Testing & Commissioning of Oil Filter (External) for Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards.
OD4727/2023-2024:Supplying, Installation, Testing & Commissioning of Oil Filter (Internal) for Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards.
OD4728/2023-2024:Supplying, Installation, Testing & Commissioning of Oil Transducer to be installed in Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards
OD4729/2023-2024: Supplying, Installation, Testing & Commissioning of Economizer Transducer to be installed in Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards.
OD4730/2023-2024:Supplying, Installation, Testing & Commissioning of PDS-SCPM3 Card Chiller to be installed in Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards.
OD4731/2023-2024:Supplying, Installation, Testing & Commissioning of PD4-EXV 32 Gb, 500, 192 EE Card to be installed in Carrier Make Chiller Machine i/c Testing, Commissioning Complete as Required for 120 TR Chiller Machine and as per OEM standards.
OD4732/2023-2024:Supplying, Installation, Testing & Commissioning of Expansion Tank made out of 20 Gauge Ms Sheet and covered with 19 mm Nitrile Insulation properly pasted with suitable adhesive to be installed at Terrace with suitable foundation arrangement i/c Lifting Shifting etc. as Required (1 mtr height x 1 mtr depth x 1 mtr length).
OD4733/2023-2024:Repair of PCB Card of Rapid Cool Make Hot Water Genrator capacity 75 KW make KEPL i/c Testing, Commissioning Complete as Required.
OD4734/2023-2024: Providing and fixing water barrier of Glass Cloth wrapping over the nitrile foam to restrict the water droplets for prevention of conditioned temperature etc complete as required. 7 mm
OD4735/2023-2024:Providing and applying Star Bond adhesive for protection to insulated ducting with the help of brush to make the solid leak proof from various joints etc as required. It is a protective coating of installation which can bear temperature upto 112 degree Celsius. Colour white, viscosity @ 30 degree Celsius - 65000 CPS, Specific gravity - 1.4
OD4736/2023-2024:Supplying, Installation, Testing & Commissioning of 7.5 KW/10 HP VFD input 3 x 380-480 V, 50/60 Hz, 25.6/22.1 A, output 3 x 0 VIn 0.400 Hz, 15.5/14.0A Danfos Make alongwith Control Panel i/c Testing, Commissioning Complete as Required.
OD4737/2023-2024:Descaling and washing of cooling coil of AHU with the help of vaniclean chemical, greasing the blower motor, testing complete etc as required. Capacity 2500 - 3000 CFM, make ADGETECH.
OD4738/2023-2024:Descaling of condenser of 120 TR AC Plant with Vaniclean, recirculating the same to remove the scale including changing rubber gasket of end covers including complete testing commissioning as required. (make - Carrier)
OD4739/2023-2024:Servicing of FCU"s installed at various locations in the hospital i/c cleaning of filters, cleaning of choked drain lines / cleaning of coils with the help of vemiclan. Capacity 1.5 ton - 2 ton, make Hi-Tech Engineers.
OD4740/2023-2024:Servicing of 415 V, 3 phase, 4 wire, 50 Hz Electrical Panel along with busbar, incomer MCCB 1000 A, outgoing MCCBs of 200 A-2 Nos., 63 A-3 Nos., 32 A-6 Nos., 3 phase star-delta starter, 20 HP-3 Nos., 3 phase DOL starter 10 HP-3 Nos., 7.5 HP-6 Nos. (Make L&T) along with associated Switch Gears i/c complete testing commissioning as required.
OD4741/2023-2024:Repairing of Secondary Chilled water pump of 7.5 KW/10 HP make-Kirloskar, rpm- 1440, Hz-50, 415 V, A-14.3 with rewinding, bearing, changing of mechanical seal, alignment, balancing complete testing , commissioning etc. as required.
OD4742/2023-2024:Repairing of Primary Chilled water pump of 5.5 KW/7.5 HP make-Kirloskar, rpm- 1455, Hz-50, 415 V, IP-55 with rewinding, bearing, changing of mechanical seal, alignment, balancing complete testing , commissioning as required.
OD4743/2023-2024:Top up of Refrigerant (R-134 A) in the chiller machine i/c complete testing , commissioning complete as required.
OD4745/2023-2024:16.2.8 Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. (a) 100 mm dia. (32 mm thick insulation)
OD4746/2023-2024:16.5.1 Supplying, laying, fixing, testing and commissioning of following thickness closed cell elastrometric nitrile rubber of class 'O' applied by suitable adhesive, as per specifications and as required complete in all respect. 32mm
OD4747/2023-2024:16.26.2 Supply, Installation, Testing and commissioning of factory built floor mounted chilled water double skin type horizontal/vertical air handling units made of 25mm thick panels consisting of pre plasticized G.I. casing of thickness 0.8mm outside layer and 0.8 mm inside layer with polyurethane foam (PUF) insulation factory injected between them by injection moulding machine, complete with blower section with blower suitable for static pressure as required, minimum 2 bend GSS/PVC eliminators, cooling coil section with aluminium finned copper tubes (tubes thickness not less than 0.5mm) cooling coil of 6 row deep, filter section with 50mm thick metal viscous/ washable synthetic type air prefilters, belt drive package with TEFC drive motor of efficiency class IE3 suitable for 415 ± 10% volts, 50Hz, 3 Phase AC supply suitably designed for variable frequency drive applications, drain connections, stainless steel (18G) drain pan with PUF insulation, 150 mm dia. dial type pressure gauges (2 nos.) and industrial type thermometers (2 nos.) at the inlet and outlet of coil, auto purge valve wherever required, necessary vibration isolation arrangement etc. complete as per specification and of following capacities. 5100 CMH
OD4748/2023-2024:16.7.1.7 Butterfly Valve (Manual) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified. 50 mm dia
OD4749/2023-2024:16.7.1.6 Butterfly Valve (Manual) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified. 65 mm dia
OD4750/2023-2024:16.7.1.5 Butterfly Valve (Manual) with C I body SS Disc, Nitrile Rubber Seal & O- Ring PN 16 pressure rating for chilled water/hot water circulation as specified. 80 mm dia
OD4751/2023-2024:16.7.4.6 Y - Strainer of ductile CI body flanged ends with stainless steel strainer for chilled/ hot water circulation including insulation as specified. 65 mm dia
OD4752/2023-2024:16.7.2.6 Balancing Valve with built in measuring facility with CI body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation as specified. 65 mm dia.
OD8397/2023-2024:16.2.9 Supplying, laying/ fixing, testing and commissioning of following nominal sizes of chilled water piping inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated with following closed cell elastometric nitrile rubber of minimum 45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at 20 deg mean temperature class 'O' insulation applied by suitable adhesive complete including repairing of damage to building etc. as per specifications and as required complete in all respect. (a) 80 mm dia. (32 mm thick insulation)
OD8635/2023-2024:18.7.8 Providing, laying, testing & commissioning of 'C' class heavy duty MS pipe conforming to IS 3589/IS 1239 including welding, fittings like elbow, tees, flanges, tapers, nuts bolts, gaskets etc. fixing the pipe on the wall/ ceiling with suitable clamp/support frame and painting with two or more coats of synthetic enamel paint of required shade complete as reqd. 150 mm dia
OD8636/2023-2024:2.2.5 Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 200 A, 25 KA, TPMCCB
M/s Kelvin Associates
Bidder Name
M/s Kelvin Associates
COOL INDIA
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .