| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.2 LAccepted-AOC 403 GH MANSADEVI COMPLEX PANCHKULA 134109 HARYANA | PANCHKULA | HARYANA | 134109 | L1 | Accepted-AOC L1 | |
| 2 | L2₹11.4 L+₹1.2 L (11.5%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹11.7 L+₹1.5 L (14.9%)Rejected-Finance HOUSE NO 95 STREET NO 08 JAWAHAR COLONY NEAR LAXMI DAIRY FARIDABAD SECTOR 22 HARYANA 121005 | FARIDABAD | HARYANA | 121005 | L3 | Rejected-Finance Other than L1 |
Tender Value
₹14.3 L
EMD Value
₹28,700
Closing Date
12 Apr 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Cdr, HQ 138 WE
HQ 138 Works Engineers PIN-914138 C/O 56 APO
MAINT AND REPAIRS HT NETWORK INCL TRANSFORMERS OF VARIOUS CAPACITY INCLUDING TOPPING UP, FILTERATION OF OIL, PAINTING AND CERTAIN RELATED MISC WORKS ETC AT BASE CAMP UNDER GE PARTAPUR
2023_MES_585896_1
138WE/L-09/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE Partapur
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
GE Partapur
₹28,700
Yes
1 May 2023
15 Mar 2023
19 Apr 2023
15 Mar 2023
12 Apr 2023
29 Mar 2023
Amount
Re-stringing, restretching ACSR conductor of overhead HT line ,three run on steel poles after removing binding from insulator and rebinding the conductor with insulator including providing new binding wire jumpering providing with sleeves of appropriate size, ACSR conductor with colour code sleeves after restraining and removing unavoidable sags in the lines, complete all as specified and as directed by Engr-in-charge.
M&L for Aluminium conductor steel reinforced (ACSR) in replacement as in over head conductor including provision of aluminium tapes for binding all as specified and directed by Engr-in-Charge. Note : (i) weight of ACSR conductors shall be determined by measuring the horizontal distance between center of two adjacent poles and compounding the weight of conductors of size and length provided and 3% extra added for sag, jointing, jumpers etc. (ii) The weight of the aluminium tapes shall not be added in the weight of the conductors for payment purpose. (iii) Size of ACSR conductor will be decided by GE/Engr-in-Charge as per electric load and site requirement.
Supply and fix in replacement Pin type insulator, porcelain, vitrous, white brown or green insulator incl one galvanized mild steel spindle, two galvanised iron washer and one galvanized iron nut of size 100mm height and 65mm dia for 1100 Volts, complete all as specified and as directed by the Engr-in-charge.
Supply and fix in replacement Pin type insulator, porcelain, vitrous, white brown or green insulator incl one galvanized mild steel spindle, two galvanised iron washer and one galvanized iron nut of size 150mm height and 150mm dia for 11000 Volts, complete all as specified and as directed by the Engr-in-charge.
Supply and Fix in replacement Shackle type porcelain, vitreous, brown or green insulator 1100 volts working pressure, 75mm height and 90mm dia with and including galvanised mild steel straps, washer, insulator bolts 12mm dia, and nuts complete after removing unserviceable item, complete all as specified and as directed by the Engr-in-charge.
M&L disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green 'Two-in-series' assembly for tension with tension clamps for conductors, working pressure 11000 volts, complete all as specified and as directed by the Engr-in-charge.
M&L stay assembly complete with accessories i.e stay plate 230mm x 230mm x 6mm with 16mm dia rod, galvanized thimbles, G.I. stay wire 7/4 SWG, loop type insulators, vitreous porcelain, white brown or green of large size with overall dimensions 90mm x 140mm, clearance of hole 25.5mm, etc and all other accessories as shown in electrical plate No.1 on Ser Page No.495 of MES Schedule Part-I (specification) complete including taking out existing unservicable stay complete all as specified and directed. Note : Excavation and earth work and concrete for stay pit shall be measured and paid for separately, complete all as specified and as directed by the Engr-in-charge.
M&L for loop type insulator, vitreous porcelain white, brown or green large size (65 x 90mm), clearance of hole 16mm, complete all as specified and as directed by Engr-in-Charge.
S&F in replacement Cross arm bracing, supports clamps and back plated fabricated from structral steel section including nuts, bolts ,washers, welding,bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, complete all as specified and as directed by Engineer-in-Charge.
M&L for galvanised stay strand of size 7/4mm, complete all as specified and as directed by Engr-in-Charge.
S & F of gaurding wire ,cradles, hexagonal/rectangular, fabricated with galvanised steel wire 3.15 or 4mm dia, complete all as specified and as directed by Engr-in-Charge.
M&L XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables HT (heavyduty) with aluminium conductor, 11000 volts, grade cross sectional area 95 sqmm 3 core, complete all as specified and as directed by Engr-in-Charge.
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground( earth plate not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 2.5 mtr below the normal ground level connected to galvanized iron earth strip of size 32 x 6 mm thick by means of nuts bolts, nuts, check nuts and washers of GI steel all as shown in electrc plate Ni 5 connected to earth test point all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe light grade 40mm bore and GI watering pipe 20mm bore medium grade with funnel and wire mesh ,40mm thick pre cast RCC M-15 ( Nominal mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40X40X3mm frame for cover,PCC M-15 ( Nminal mix) pit, excavation and earth work in any type of soil and connected , complete all as specified and as directed by Engr-in-Charge.
M&L for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thickness not less than 6mm thick buried directly in ground( earth plate not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 2.5 mtr below the normal ground level connected to galvanized iron lead wire 4 mm dia by means of nuts bolts, nuts, check nuts and washers of GI steel all as shown in electrc plate Ni 5 connected to earth test point all as specified and indicated complete and including charcoal dust,salt etc and GI protection pipe light grade 40mm bore and GI watering pipe 20mm bore medium grade with funnel and wire mesh ,40mm thick pre cast RCC M-15 ( Nominal mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40X40X3mm frame for cover,PCC M-15 ( Nminal mix) pit, excavation and earth work in any type of soil and connected , complete all as specified and as directed by Engr-in-Charge.
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtrs in depth for laying of cable, fixing of stay etc 10 Sqm on plan and n exc 1.5 in depth and getting out in hard/dence soil , complete all as specified and as directed by Engr-in-Charge.
Returing, filling in incl spreading, levelling watering and well remming in layers n.exc 25cm width, Complete all as specified and as directed by Engineer-in-Charge.
Removing excavated soil to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 m above starting point , complete all as specified and as directed by Engr-in-Charge.
M&L sand cushioning for under ground cable 8 cm before laying the cable and 15 cm after laying and streching the cable, complete all as specified and as directed by Engr-in-Charge. Note:- Punned thickness only be measured for payment as per SSR.
Supplying and laying reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm, complete all as specified and as directed by Engr-in-Charge.
Supply and laying/fixing in replacement, GI pipe medium grade 50 mm bore (dia) including all type fittings fixed on walls/to poles with clamps /laid in trenches as cable protection, complete all as specified and as directed by Engr-in-Charge.
Supply and laying/fixing in replacement, GI pipe medium grade 80 mm bore (dia) including all type fittings fixed on walls/to poles with clamps /laid in trenches as cable protection, complete all as specified and as directed by Engr-in-Charge.
S & F Cable jointing kit for 11 KV (Earthed) grade cable for indoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, complete all as specified and as directed by Engr-in-Charge.
S & F Cable jointing kit for 11 KV (Earthed) grade cable for outdoor type end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, complete all as specified and as directed by Engr-in-Charge.
S&F Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, complete all as specified and as directed by Engr-in-Charge.
S&F Lightning arresters expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp suitable for 11000 volts, complete all as specified and as directed by Engr-in-Charge.
S&F Gang Operated Device (GOD) Triple pole, mechanically operated, mounted on insulator and steel frame, with operating mechanism worked from ground level, for current rating upto 200 amps suitable for 11000 volts, complete all as specified and as directed by Engr-in-Charge.
S&F Expulsion fuse single pole suitable for 6600 vollts, 50 Amps, complete all as specified and as directed by Engr-in-Charge.
Supply and laying in repairs synthetic Insulating Mat of size 2m X 1m and 2.5 mm thick for 11100 Volts made from synthetic insulating material, free from any insertions leading to detoriation of insulating properties. Note : The upper surface should have small aberration (Rough Surface) with out edges to avoid slippery effects.The mat should be fire retardant & self extiguishing, complete all as specified and as directed by Engr-in-Charge.
Material and Labour for PCC 1:3:6 type C-2 using 40mm graded crushed stone aggregate as in foundation, filling or mass concrete as in foundation stays etc, complete all as specified and as directed by Engr-in-Charge.
M&L for dehydration and decentrifuging of Transformer Insulating oil after decanning it from drain plug and carrying out chemical process to remove moisture and refill the oil after achieving a dielectric strength of 40 KV for sphere to sphere gap of 2.5mm duly tested and approved by Engineer-in-Charge.
M&L for Transformer Insulating Oil as per IS 335 : 1993 with density 0.89 gm/cum Max. Flash point 140 0C Min. Dielectirc Strength 40 KV Min (rms). The oil shall not contain anti oxidant additives. Water Content 50 PPM Max, complete all as specified and as directed by Engr-in-Charge.
M&L for Brass LT Studs including gas kit and seal for up to 200 KVA transformers duly approved by Engineer-in-Charge.
M&L for Brass HT Studs including gas kit and seal for up to 200 KVA transformers duly approved by Engineer-in-Charge.
M&L for Brass LT Studs including gas kit and seal for 200 to 400 KVA transformers duly approved by Engineer-in-Charge.
M&L for Brass HT Studs including gas kit and seal for 200 to 400 KVA transformers duly approved by Engineer-in-Charge.
M&L for Brass LT insulating bushes for up to 200 KVA transformers duly approved by Engineer-in-Charge.
M&L for Brass HT insulating bushes for up to 200 KVA transformers duly approved by Engineer-in-Charge.
M&L for Brass LT insulating bushes for 200 to 400 KVA transformers duly approved by Engineer-in-Charge.
M&L for Brass HT insulating bushes for 200 to 400 KVA transformers duly approved by Engineer-in-Charge.
Replacement of breather assembly complete with silica jel in transparent container with metallic top & bottom cup with pipe entry of 15/20 mm dia, including air oil bath tub, complete all as specified and as directed by Engr-in-Charge.
Replacement of existing unserviceable silica jel with new crystal clear silica jel for the breather of transformer, complete all as specified and as directed by Engr-in-Charge.
M&L carrying out lab test for acidity of transformer oil for various transformers and submission of test reports on the proper format, complete all as specified and as directed by Engr-in-Charge.
Supply and Fixing First Aid Box wall mounted type duly empanelled as "FIRST AID BOX" and front opening single hinged door with locking arrangements, complete all as specified and as directed by Engr-in-Charge.
Material and labour for arrest the leakage of Transformer Oil from the LT/HT side busings of Transformer capacity 200 KVA to 400 KVA including the following:- (a) Taking down the top cover and refixing after repair duly pasted with gasket. (b) Taking out the transformer oil from the transformer upto the level suitable to carry out the repair work. (c) Taking out the bushings and supply and replacement of the same duly coupled with suitable gasket nuts, bolts and washers. (d) Refilling of transformer oil after completion of repair work and ensure that the leak has been arrested. (e) Reassembling complete and testing and commissioning. (f) Supply and replacement of brass spindle on LT/HT side.
darshan kumar gandhi
RND ENGINEERS & CONTRACTORS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .