Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.2 CrAdmitted-Finance | ₹15.2 Cr | L1 | Admitted-Finance |
| 2 | L2₹15.3 CrAdmitted-Finance | ₹15.3 Cr | L2 | Admitted-Finance |
| 3 | L3₹16.5 CrAdmitted-Finance | ₹16.5 Cr | L3 | Admitted-Finance |
| 4 | Rejected-Technical | - | - | Rejected-Technical The bidder is not fulfilling the Experience criteria of tender specification and also the bidder is not fulfilling the criteria of Minimum work experience value |
| Sl No | Description | Qty | Unit | S.T.Electricals Pvt Ltd L1 | mishrilal associates pvt.ltd L3 | Pioneer Power Engineers Limited L2 |
|---|---|---|---|---|---|---|
| 1.00PART-A | ||||||
| 2.0033 KV LINE WORK | ||||||
| 3.00Supply of following material at work site as per approved GTP by Department & shall be as per IS or as per standard norms of UPPCL/RESSPO/MVVNL/UPPWD/ Tender document / Technical Specifications. | ||||||
| 4.00 | 33 KV 3x300sqmm XLPE Cable | 30,000 | Mtr. | 2,754.12 ₹8.3 Cr | 3,150.6 ₹9.5 Cr | 2,797.69 ₹8.4 Cr |
| 5.00 | 33 KV Jointing Kit 3x300 sq mm Cable Outdoor | 68 | No. | 8,906.05 ₹6.1 L | 10,301.4 ₹7.0 L | 11,938.65 ₹8.1 L |
| 6.00 | 33 KV Jointing Kit 3x300sq mm Straight Through | 110 | No. | 21,304.9 ₹23.4 L | 28,119.4 ₹30.9 L | 28,576.65 ₹31.4 L |
| 7.00 | STP 11 M long | 30 | No | 27,482.2 ₹8.2 L | 27,647.4 ₹8.3 L | 28,979.33 ₹8.7 L |
| 8.00 | 33 KV Pin insulator | 135 | No | 387.98 ₹52,377.30 | 472 ₹63,720 | 469.94 ₹63,441.90 |
| 9.00 | 33 KV Pin with nut | 135 | No | 323.32 ₹43,648.20 | 389.4 ₹52,569 | 548.26 ₹74,015.10 |
| 10.00 | Top chanel 100X50 MM 10 kg / mtr | 975 | Kg. | 121.25 ₹1.2 L | 106.2 ₹1.0 L | 125.32 ₹1.2 L |
Tender Value
₹17.3 Cr
EMD Value
₹17.3 L
Closing Date
11 Jul 2023, 1:00 pmClosed
S.E, EUCC-V, LESA, Cis-gomti,Lucknow
Room No.61, LESA Bhawan, Near Residency, Kaiserbagh, Lucknow-226018
05/EUCC-V/LESA/2023-24
2023_MVVNL_816040_1
05/EUCC-V/LESA/2023-24
Open Tender
Electrical Works
150 days
BHATGAON SAROJINI NAGAR LUCKNOW.
As per tender document
2 documents required · 2 mandatory
₹11,800
A/c. No. 10101985364, IFSC CODE No.SBIN0003347,SBI
₹17.3 L
9 Aug 2023
28 Jun 2023
11 Jul 2023
28 Jun 2023
11 Jul 2023
28 Jun 2023
PART-A
33 KV LINE WORK
Supply of following material at work site as per approved GTP by Department & shall be as per IS or as per standard norms of UPPCL/RESSPO/MVVNL/UPPWD/ Tender document / Technical Specifications.
33 KV 3x300sqmm XLPE Cable
33 KV Jointing Kit 3x300 sq mm Cable Outdoor
33 KV Jointing Kit 3x300sq mm Straight Through
STP 11 M long
33 KV Pin insulator
33 KV Pin with nut
Top chanel 100X50 MM 10 kg / mtr
MS angle 65x65x6MM 5.8 kg / mtr
M S Earthing Rod 20x2500 mm
LT XLPE Cable AL.1X400 Sq.mm.
MS channel 100x50 mm
MS Pipe 6" dia
Cable Route Marker
Digging of pit in Kachcha/Pakka land in depth upto 1/6 length of pole, Dragging of STP from nearby place/dump, Erection of single pole along with stone pad in bottom with proper alignment on 11 mtr long ST pole and refilling with ramming of earth
Grouting of pole in depth of 01 mtr. Below ground level in ratio 1:4:8 in cement, sand and brick ballast as per RESPO norms.
Construction of pole plinth 300mm x 450 mm above ground level in ratio 1:2:4 in cement, coarse sand and stone gritt as per RESPO norms.
Painting of new erected ST pole with two coat of Red oxide paint, PO red paint at top of pole 2 mtr and balance by two coats of best quality aluminium paint ISI mark as per norms.
Fabrication & erection of 33 KV cable exposure type double pole with the provision of bus bar with fixing of necesory clamps and other acessories like danger board,number plate,barbed wire, 6 no. pin insulators with pins,2 no. channels 100x50 mm (1600mm each), 2 no.MS angle 65x65x6 mm (each 2800mm in length ) for supporting the hoisting of cable on poles.its jumpering by single core PVC aluminium cable with proper size of lug. as per RESPO norms.
Laying of D/C 33 KV 3x300 Sqmm XLPE cable in parallel in normal soil by digging of trench 1050 mm deep & 750 mm wide its boxing with bricks laying of cable & seperation of cable by brick wall, filling of sand upto top and covering with stone slab after laying of cable (Cost of all material are included in this job except 33 KV Cable).
Laying of 33 KV XLPE cable 3x300 sq mm S/C in MS- Pipe 150 mm dia by digging of trench in Kachcha/Pakka of suitable size at road crossing (All material will be provided by contractor)
Laying of single 33 KV 3x300 Sqmm XLPE Cable by drill method
Laying of single 33 KV 3x300 Sqmm XLPE Cable by drill method in HDPE Pipe 150 mm dia (All material will be provided by contractor).
Cable Laying in already constructed trench/existing pipe S/C
Cable Laying in Hume Pipe 6" dia (all Material will be Provided by Contractor)
Laying of single circuit 33 KV 3x300 sq mm XLPE cable in normal soil in switch yard as per norms. Cable trench should filled by fine sand.
Hoisting of 33 KV 3x300 Sqmm XLPE cable on D/P through GI- pipe of size 6" dia 3 mtr long including its jumpering complete with holding clamps, PG clamps, Nut & bolts (All material will be provided by contractor)
Hoisting, jumpering, clamping of 33 KV 3x300 sq mm XLPE cable on cable stand/structure with proper jumpering with help of PG clamps (required PG clamps will be provided by contractor).
Fabrication & Erection of cable stand made of two nos MS channel 100x50x3 mtr. Long jointed to each other by means of 05 nos MS strip 50x6 mm of size 150 mm Long each by welding at equal distance interval as per norms and grouting in block of 300x300x700 completely providing two nos cable clamp also.(All materials will provide by contractor).
High Pressure Testing of 33 KV cable. Testing equipment will be arranged by contractor.
33/11 KV SUB-STATION
10 MVA -33/11kV Power Transformer
05 MVA -33/11kV Power Transformer
Cost of Power Transformer Plinth with Rail Piece 90 LBS -4 mtr long 2 nos as per specification (All The material shall be provided by the contractor)
MS Round Bar 32 mm
Earthing of substation complete by round bar 32 mm dia complete as per specification and connecation of all switchyard equipment by GI Flat 50x6 mm (The contractor shall arrange all the material except MS Round Bar 32 MM)
33KV Line Isolator
33KV Bus Isolator
33 KV VCB (motorised) with structure
33 kV 1 Ph CT 200/100/1 Amp.
33 kV 1 Ph CT 400/200/1 Amp.
33 KV PT 33KV/110 V
33KV Lightning Arrestor 400 Amp
33kV Control panel for double T/F with differential relay
33kV Control panel for single feeder without differential relay
Structure for 33 KV Line/Bus Isolator as per specification(including Plinth & foundation) as per specification
Structure for 33KV Lightning Arrester (3 nos.) with Plinth & foundation
33 KV VCB plinth & foundation (2x2x1mtr.) as per specification
Structure 33 kV Single Phase CT (3 Nos.) with Plinth & foundation
33 KV bus bar gantry complete with structure
Cable Stand structure with foundation
ACSR Panther Conductor
Jumpering of complete line and transformer bay with ACSR Panther conductor by the help of PG clamp and connectors (all Material shall arranged by contractor except ACSR panther conductor)
Structure for Transformer Neutral Stand With Foundation
11 KV VCB Switchgears with Incoming CTR 800/400/5 A, 350MVA SCADA Compatible (Motorised)
11 KV VCB Switchgear outgoing 300/150/5 A SCADA compatible.(Motorised)
11 KV Bus Coupler 350 MVA SCADA Compatible (BC+BR complete set)
24 Volt battery and battery charger with cabinet complete
Heat Shinkable jointing kit suitable for 11KV XLPE 3x300 Sq.mm. cable size (Outdoor termination kit)
Heat Shinkable jointing kit suitable for 11KV XLPE 3x300 Sq.mm. cable size (Indoor termination kit)
RCC Cable trench 850x800x150 mm with cover as per drawing
Control cable trench 300x300 mm with cover
11KV/0.433KV, 3 Phase, 63 KVA Transformer (BEE standard, 3 star rating self protected type) Al. wound
STP 11 M long
Top channel 100x50mm
MS angle 65x65x6mm
M S Earthing Rod 20x2500 mm
11KV pin insulator
11KV pin with Nut
Barbed wire
Danger Board with clamp for 11 KV
Number Plates with nuts & Bolt
Stoen pad300x300x75 mm
D.O. fuse Set
Concreating of pole
MS Nut & Bolt
Clamp with Nut & Bolt
TPMO Set
11KV Lightening Arrestor
Earth wire clamp with Nut & Bolts
Pipe Boring type earthing minimum 40 mtr deep from ground level up to water level with B class GI Ppe 2" dia.connection of equipment with earhting included in the Job as per specification/Norms
11 KV 3 Core Al. XLPE Cable 3x300mm sq.
Control cable 6x2.5 mm sq.
Control cable 4x2.5 mm sq.
Control cable 2x2.5 mm sq.
11 KV 3x70mm2 XLPE Cable
11 KV 3x70mm2 J/K outdoor
11 KV 3x70mm2 J/K indoor
LT cable 3.5x70mm2
Laying of 11 KV 3x300 sq mm XLPE cable in cable trench
Laying of 11 KV 3x70 sq mm XLPE cable in cable trench
Filling of switchyard area by gravels of 20-40 mm size with 120 mm thickness
Laying of interlocking tiles in switchyard and other required place
Sub-station T/F Plinth with RCC top 1.5x1.5x1.2 Mtr.
Switchyard Fencing with toe wall including switchyard gate (as per Specification) with tenesh type wiremess 10SWG
Outdoor switch yard & aproch road Lighting
Painting of Structures in S/S (All The material shall provided by the contractor)
T & P of Sub-Station & Switchgears including chair table and primary tools etc (As per Specification)
4.5 Kg. CO2 fire extinguisher, portable type
5 kg. Dry chemical powder fire extinguisher, portable type
Fire buckets (4 nos.) with stand filled with dry sand
Rubber matting 20 sq. mm. thick size (1 X 2 mtr.)
S/S name board (SMC) with stand & single line digarm of s/s
Protection Board complete
Construction of Fire wall,RCC framed with fire bricks in between transformers (4.5x0.345x450 ) Mtr
LT Distribution panel for S/S with on 100 Amp MCCB and 2 nos outgoing MCB 32Amp, 4nos 16 amp MCB's as per specification
Hoisting of 11KV 3x300 sq mm XLPE cable in panal/cable stand or on outdoor structure/equipment with required clapm, nut /bolt and dressing of cable as per norms.
Hoisting of 11KV 3x70 sq mm XLPE cable in panal/cable stand or on outdoor structure/equipment with required clapm, nut /bolt and dressing of cable as per norms.
Earthing of substation complete as per specification (Indoor earthing)
Laying of LT cable 3.5x70 sq mm in constructed trench
Connection of LT 3.5x70 sq mm LT XLPE cable with suitable size of Outdoor/indoor with 63 KVA Transformer and LT distribution panel.
11 KV LINE WORK
Supply of following material at work site as per approved GTP by Department & shall be as per IS or as per standard norms of UPPCL/RESSPO/MVVNL/UPPWD/ Tender document / Technical Specifications.
11 KV 3x185 sq mm XLPE cable
11 KV 3x185 sq mm cable jointing kit O/D
11 KV 3x185 sq mm cable jointing kit I/D
11 KV 3x185 sqmm cable jointing kit St/Th
ST pole 11 mtr long
M.S.channel 100x50 sq mm
M.S.Angle 65x65x6 sq mm
11 kv pin insulator
11 kv pin with nut
M S Earthing Rod 20x2500 mm
1x240 LT XLPE Cable
11 KV RMU 3 WAY (Smart Type )
MS Pipe 4" dia
Cable Route Marker
Digging of pit in Kachcha/Pakka land in depth upto 1/6 length of pole, Dragging of STP from nearby place/dump, Erection of single pole along with stone pad in bottom with proper alignment on 11 mtr long ST pole and refilling with ramming of earth
Grouting of pole in depth of 01 mtr. Below ground level in ratio 1:4:8 in cement, sand and brick ballast as per RESPO norms.
Construction of pole plinth 300mm x 450 mm above ground level in ratio 1:2:4 in cement, coarse sand and stone gritt as per RESPO norms.
Painting of new erected ST pole with two coat of Red oxide paint, PO red paint at top of pole 2 mtr and balance by two coats of best quality aluminium paint ISI mark as per norms.
Fabrication & erection of 11 KV cable Exposure type double pole with the provission of bus bar with fixing of necessary clamps and other accessories like danger board, number plate, barbed wire, 9 no. pin insulators with pins, 2 No. MS-CHANNEL & 2no. MS angle for supporting the hoisting on Pole.Its jumpering by single core PVC aluminium cable with proper size of lug. as per RESPO norms.
Pipe boring type Earthing minimum 20 mtr deep from ground level or upto water level with ‘B’ class G.I. Pipe 2" dia connection of equipments through GI strip 50x6mm with earthing included in the job as per norms for Transformer /RMU/VCB/other required equipments (All required material will be provided by contractor).
Construction of Plinth for RMU 03way/04 way as per approved drawing (All material will be provided by contractor).
Construction of Retaining wall, fabrication and erection of wiremess fencing of 02 mtr height arround T/F and distribution piler box with provision of one Gate with locking arrangement made of MS Angel Iron off size 50x50x6 mm joint with nuts with bolts. The pannel must be support with ms flat size 50x50x6 mm wireness of size 10 SWG rectangle type its painting As per norms of RESPO (All material will be provided by the contractor)
Erection and commissioning of 11 KV RMU 03way/04 way
Filling by gravells 20-40 mm in empty space inside RMU.
Laying of 11 KV XLPE cable 3x185 sq mm D/C by digging of trench 900 mm deep & 600 mm wide its boxing with bricks & sand, laying of cable & separation of cables by brick wall, filling of sand upto top cover of the trench properly levelling & ramming & covering with stone slab after laying of cable (Cost of all material are included in this job except 11 KV Cable).
Laying of 11 KV 3x185 sq mm XLPE single cable in MS-Pipe 125 mm dia by digging of cable trench in Kachcha/Pakka of suitable size at road crossing/Naala crossing/other required places.
Laying of Single Circuit 11 KV XLPE cable 3x185 Sqmm in constructed trench.
Laying of Single circuit 11 KV 3x185 sqmm XLPE cable upto 1-1.5 mtr by HDD method.
Laying of Single circuit 11 KV 3x185 sqmm XLPE cable upto 1-1.5 mtr deep by HDD method in HDPE Pipe 125 mm dia.
Hoisting of 11 KV 3x185 Sqmm XLPE cable on D/P through GI- pipe of size 4" dia 3 mtr long including its jumpering complete with holding clamps, PG clamps, Nut & bolts (All material will be provided by contractor)
Proper Hoisting & clamping of 11 KV cable 3x185 sqmm in 11 KV VCB/RMU/Metering cubical/Transformer (all Material will be Provided by Contractor)
High Pressure Testing of 11 KV cable Testing equipment will be arranged by contractor.
Pioneer Power Engineers Limited
mishrilal associates pvt.ltd
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.54 MB
document.pdf
Tender Documents • 5.22 MB
BOQ_1367909.xls
BOQ • 0.53 MB
Download all tender documents and submit your bid