Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NEW DELHI | DELHI | DELHI | 110006 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | Admitted-Finance |
| 5 | Admitted-Finance HOUSE NO 40 CHOTTI BARADARI PART I GARHA ROAD NEAR MEDICAL COLLEGE JALANDHAR PB 144022 | JALANDHAR | JALANDHAR | PUNJAB | 144022 | Admitted-Finance |
Tender Value
₹77 L
EMD Value
₹1.4 L
Closing Date
17 Jul 2025, 6:00 pmClosed
CWE JABALPUR
HQ CWE JABALPUR OPPOSITE SUPPLY DEPOT SADAR 482001
SPECIAL REPAIR/REPLACEMENT OF LT PANELS OF VARIOUS CAPACITIES AT VARIOUS LOCS OF ZONE B AND C OF GE (E) JABALPUR
2025_MES_714532_1
82723/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
JABALPUR
AS PER NIT
7 documents required · 7 mandatory
₹1,000
Yes
GE (EAST) JABALPUR
₹1.4 L
Yes
29 Jul 2025
14 Jun 2025
22 Jul 2025
14 Jun 2025
17 Jul 2025
5 Jul 2025
14 Jun 2025 - 4 Jul 2025
Amount
Supply install commissioning and testing, in replacement, CPRI Approved factory fabricated, floor mounted outdoor type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 6 mm frame and 750 mm above the Normal ground level complete factory made totally enclosed dust and vermin proof double door both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, aluminium bus bar 400 Amps rating (01 Set) fixed on porcelain insulator with internal wiring with suitable size of aluminium strips to be used for incoming and outgoing connection of all switches/MCCBs & Bus-bar. Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surface externally & internally over a coat of red oxide primer including necessary PCC (1: 3 : 6) type C-2 (using 40mm graded crushed stone aggregate) as in foundation complete all as directed, comprising of the followings : -
Supply install commissioning and testing, in replacement, CPRI Approved factory fabricated, floor mounted outdoor type LT Feeder Pillar Box of suitable size fabricated out of 3.15 mm thick CRCA Sheet and angle iron 50 X 50 X 6 mm frame and 750mm above the Normal ground level complete factory made totally enclosed dust and vermin proof double door both side hinge opening arrangement on front and back with locking arrangement cable entry and exist from bottom with cable glands and gaskets, aluminium bus bar 600 Amps rating (01 Set) fixed on porcelain insulator with internal wiring with suitable size of aluminium strips to be used for incoming and outgoing connection of all switches/MCCB's & Bus-bar. Bus-bar shall be insulated with colour code sleeves/tapes and to be connected with copper lugs, including two coats of synthetic enameled paint on the surface externally & internally over a coat of red oxide primer including necessary PCC (1 : 3 : 6) type C2 (using 40mm graded crushed stone aggregate) as in foundation all as directed, comprising of the followings : -
Supply install commissioning and testing, in replacement, CPRI Approved factory fabricated, floor mounted out door type LT feeder piller box of suitable size CPRI approved factory made totally enclosed panel board complete, 50x50x6mm angle iron for legs, complete internal connection & fitting with 400 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support and the following items housed in :-
Supply, erection, testing and commissioning, in repair, outdoor type LT Bus Bar Chamber box, platform mounted, suitable for 3 phase 4 wire, 415 volts AC supply and having 4 Nos stepped type Aluminium bus bars (32mm x 5mm) for looping & branch connection system .The chamber shall be painted with powder coated paint (Shade : RAL-7032) after 7 tank pre-treatment of surfaces. The bus bar chamber shall be provided with suitable Neoprene rubber gasket to make it completely dust and vermin proof and degree of protection not less than IP-55 and general construction conforming to IS : 13947. The bus bar chamber shall be made out of 3.00mm thick CRCA mild steel sheet and 3.00mm thick gland plate , front door (01 layer) and rear Door (01 layer) opening facility and 4 side slanting canopy type roof on top and mild steel channel (75 MC) base frame at bottom. The bus bar chamber shall be provided with ventilation facility in the form of louvers for better heat dissipation. (Note : The bus bar chamber Box shall be designed in such a way that adequate workable space is made available inside the compartments and the size of the chamber shall not be less than 500mm height (without base frame & canopy), 500mm width and 450mm depth).
Supply, install, commissioning and testing,in replacement, CPRI Approved factory fabricated, floor mounted out door type LT feeder piller box of suitable size CPRI approved factory made totally enclosed panel board complete, 50x50x6mm angle iron for legs, complete internal connection & fitting with 1200 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support and the following items housed in :-
Supply install commissioning and testing,in replacement, CPRI Approved factory fabricated, floor mounted out door type LT feeder piller box of suitable size CPRI approved factory made totally enclosed panel board complete, 50x50x6mm angle iron for legs, complete internal connection & fitting with 400 Amps rated Aluminium bus bar TPN duly insulated with coloured PVC sleeve as per standard colour code and rigidly mounted on bakelite/DMC insulator bus bar support and the following items housed in :-
M & L for Earthing, in replacement, complete with galvanized steel earth plate electrode 60cmx60 cmx 6mm thick buried directly in ground vertically (earth pit not less than 2.25m deep below ground level) with top edge of the plate not less than 1.50 mtr deep below normal ground level connecting to and including GI steel strip of size 32 x 6 mm by means of bolts, nuts, check nuts, and washers of galvanized iron or steel including 40 mm dia medium grade pipe for protection of GI strip to the extent of 7.5 mtrs as earthing lead including charcoal dust and salt packed all around the earth plate in the earth pit all as per Electrical plate No 3 of SSR Part - I (2009) including PCC foundation/chamber in mix 1:2:4 type B1(using 20mm graded stone aggregate) with angle iron frame CI frame, CI cover with provision of locking arrangement and 20 mm dia light grade GI pipe from top edge of the earth plate upto MS funnel with wire mesh provided inside the concrete earth pit for watering arrangement complete including excavation and earthwork in any type of strata and testing complete including fill up the earth pit with soil for best result and removal ( for LT Panels). Note :- Earth protection pipe & earthing strip upto and including 7.5 m length is deemed included in unit rate quoted by the contractor.
Schedule of credit amount of Rs 82,460.00 to be deducted during AOC
M/S. ELECTROPOWER TECHNOLOGIES (BID ID -3354232)
Commercial Traders (BID ID -3351630)
KISHOR KALAMKAR (BID ID -3354201)
UNITED ENGINEERING CORPORATION (BID ID -3354134)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .