Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.9 LAccepted-AOC | ₹18.9 L Quoted ₹19.2 L | L1 | Accepted-AOC L1 Bidder |
| 2 | L2₹21.2 LRejected-Finance OPPOSITE GHOOM DRC PO GHOOM DISTT DARJEELING WB PIN 734 102 | DARJEELING | WEST BENGAL | 734102 | ₹21.2 L | L2 | Rejected-Finance HIGHER THEN L1 BIDDER |
| 3 | L3₹22.3 LRejected-Finance NEAR PAYAL CINEMA P O SEVOKE ROAD SILIGURI 734 001 | DARJEELING | WEST BENGAL | 734001 | ₹22.3 L | L3 | Rejected-Finance HIGHER THEN L1 BIDDER |
| 4 | L4₹22.9 LRejected-Finance | ₹22.9 L | L4 | Rejected-Finance HIGHER THEN L1 BIDDER |
| Sl No | Description | Qty | Unit | Janata Enterprises L3 | Darjeeling Enterprises L1 | SANJAY KAUSHIK L4 | Damdoo Bhutia L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | Disconnecting the electric supply, taking down the old u/s Disc insulator and Supply & Fixing Disc insulator single disc 11 KV grade porcelain vitreous brown or green 145mm high and 255 mm dia complete all as directed. | 3 | Each Job | 1,875 ₹5,625 | 1,700 ₹5,100 | 1,600 ₹4,800 | 1,670 ₹5,010 |
| 2.00 | Disconnecting the electric supply, taking down the old u/s pin type insulator and Supply & Fixing pin type insulator 11 KV grade porcelain vitreous brown or green insulator including one galvanised iron washer and one nut 150mm high and 150 mm dia including taking out old unserviceable one complete all as directed. | 6 | Each Job | 800 ₹4,800 | 700 ₹4,200 | 730 ₹4,380 | 682 ₹4,092 |
| 3.00 | M&L for Cable jointing kit for 11 KV (earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old u/s one complete all as directed | 2 | Each job | 13,200 ₹26,400 | 11,500 ₹23,000 | 12,870 ₹25,740 | 13,000 ₹26,000 |
| 4.00 | M&L for Cable jointing kit for Eleven KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old u/s one complete all as directed by Engr-in-charge . | 1 | Each Job | 31,500 ₹31,500 | 29,800 ₹29,800 | 28,000 ₹28,000 | 30,120 ₹30,120 |
| 5.00 | M&L for Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old u/s one complete all as directed | 2 | Each Job | 13,000 ₹26,000 | 11,300 ₹22,600 | 11,880 ₹23,760 | 12,150 ₹24,300 |
| 6.00 | Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/ dense soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as specified and as directed. | 31.65 | Cum | 610 ₹19,306.50 | 530 ₹16,774.50 | 530 ₹16,774.50 | 520 ₹16,458 |
| 7.00 | Excavation in trenches not exc. 1.5M wide and exc.1.5M & upto 3.0 Mtr in depth for foundation of stay/ pole and etc and getting out in hard/dense soil complete all as specified complete all as directed. | 0.49 | Cum | 720 ₹352.80 | 625 ₹306.25 | 630 ₹308.70 | 620 ₹303.80 |
| 8.00 | Returning, filling in soils including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick complete all as directed by Engr-in-Charge | 18.75 | Cum | 225 ₹4,218.75 | 195 ₹3,656.25 | 190 ₹3,562.50 | 188 ₹3,525 |
| 9.00 | Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed. | 11.28 | Cum | 460 ₹5,188.80 | 360 ₹4,060.80 | 440 ₹4,963.20 | 430 ₹4,850.40 |
| 10.00 | M&L for sand cushioning for protection of PVC cable with approved sand of uniform thickness, laid dry, by filling in trenches and punning to proper required cover all as directed. | 7.78 | Cum | 3,600 ₹28,008 | 3,210 ₹24,973.80 | 3,400 ₹26,452 | 3,500 ₹27,230 |
Updated dates
Tender Value
₹18 L
EMD Value
₹36,000
Closing Date
15 Nov 2025, 6:00 pmClosed
CWE
HQ 136 WORKS ENGINEERS PIN - 914136 C/O 99 APO
REPAIR/MAINT/IMPV OF HT INSTALLATIONS, HT CABLING SYSTEM, SWITCHGEARS, TRANSFORMERS ETC AND ALLIED WORKS AT JALAPAHAR UNDER AGE (I) DARJEELING
2025_MES_729848_2
CWE/136-WE/26 OF 2025-26
Open Tender
Electrical and Maintenance Works
280 days
DARJEELING
Class E, Category b(ii)
8 documents required · 8 mandatory
₹500
Yes
AGE (I) Darjeeling
₹36,000
Yes
15 Jan 2026
25 Oct 2025
17 Nov 2025
25 Oct 2025
15 Nov 2025
2 Nov 2025
25 Oct 2025 - 29 Oct 2025
Amount
Disconnecting the electric supply, taking down the old u/s Disc insulator and Supply & Fixing Disc insulator single disc 11 KV grade porcelain vitreous brown or green 145mm high and 255 mm dia complete all as directed.
Disconnecting the electric supply, taking down the old u/s pin type insulator and Supply & Fixing pin type insulator 11 KV grade porcelain vitreous brown or green insulator including one galvanised iron washer and one nut 150mm high and 150 mm dia including taking out old unserviceable one complete all as directed.
M&L for Cable jointing kit for 11 KV (earthed) grade cable for outdoor end termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old u/s one complete all as directed
M&L for Cable jointing kit for Eleven KV (earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old u/s one complete all as directed by Engr-in-charge .
M&L for Cable jointing kit for 11 KV (earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 Sqmm including taking out old u/s one complete all as directed
Excavation in trenches not exceeding 1.5m wide and not exceeding 1.5m in depth and getting out in hard/ dense soil for foundation of poles, structures, stay rods, laying of underground cable etc complete all as specified and as directed.
Excavation in trenches not exc. 1.5M wide and exc.1.5M & upto 3.0 Mtr in depth for foundation of stay/ pole and etc and getting out in hard/dense soil complete all as specified complete all as directed.
Returning, filling in soils including spreading, leveling, watering and well ramming in layers each not exceeding 25cm thick complete all as directed by Engr-in-Charge
Removing excavated soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
M&L for sand cushioning for protection of PVC cable with approved sand of uniform thickness, laid dry, by filling in trenches and punning to proper required cover all as directed.
M&L for laying un-reinforced precast concrete cable cover, class HV , type 1 with , size 300 mmX180mmX 40mm complete all as directed.
M/L for cement concrete in foundation (1:4;8) type D2 using 40 mm graded broken stone aggregate for base of foundation complete as specified
M/L for cement concrete in foundation (1:3;6) type C2 using 40 mm graded broken stone aggregate including form work complete as specified
PCC (1:2:4) type B1 (using 20mm graded stone aggregate) as in coping including necessary formwork complete all as specified and as directed.
Supply and lay GI tubing 80 mm dia, light grade for cable protection at road crossing / on poles and tubing sealed at both ends after laying the cables complete all as directed. Make: Tata/Jindal
Supply & lay in repair, connection testing and commissioning of 3 core, 95 Sqmm, 11000 Volts grade(Earthed) XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavy duty) with aluminum conductor laid in trench/under ground/wall/surafce/tunnel/duct including taking out unserviceable burnt out cable complete all as directed.
S&F in repairs test, erection & commissioning of Steel tubalar swaged poles staying in a truely vertical position till the foundations are properly set with the help crane complete with cast iron base plate, finial taper plug, bolts, nuts & screws including drilling of holes to poles for clamps & hooks for running of earth wire/Strip complete all as specified type 410 SP-55, 11 mtrs HT poles complete all as specified and as directed. Note:- (i) Earth work, PCC, coping shall be measured and paid separately. (ii) The rates include staying the poles in atruely vertical position till the foundations are properly set. (iii) The rates include cast iron base plate, nuts, bolts, screws, painting of steel tubular poles, drilling of holes in steel tubular poles for fixing of clamps, hooks for continuous earth wire/strip.
S&F in repairs test, install & commissioning of HT 11 KV outdoor type gang operated air break switch triple pole mechanically operated suitable for horizontal or vertical mounting (suitable for existing one) on insulator and steel frame with operating mechanism worked from ground level for current rating up to 400 Amps and connecting up with jumpers, testing and commissioning including dismantling/disconnecting & taking down the old unserviceable one complete all as specified and as directed.
S&R in repairs stay assembly comprising of MS stay plate 6 mm thick and of size 300 x 300 mm and 20 mm dia MS stay rod, 2150 mm long including thimbles, GI stay wire comprising of stay strand 7/3.15 mm dia of required length complete all as shown on electrical plate No.1 on page No.495 of MES SSR Part-I 2009 including necessary excavation PCC 1:3:6 Type C2 (using 40mm graded stone aggregate), loop insulator as specified in SSR and including taking down old unserviceable one complete all as specified and as directed.
M&L for loop type insulator, vitreous porcelain, white, brown or green, large size with overall dimensions 90 x 140mm size, clearance of hole 25.5 mm complete all as specified and directed by Engr-in-Charge.
M&L of cross arms i.e bracing supporting clamps back plates, nuts, bolts and washers complete including one under coat and one finishing coat with synthetic enamel paint over a coat of red oxide primer & including taking down old unserviceable complete all as directed.
Supply and install lightening arrestor expulsion type complete with all fittings transmission class, discharge capacity 65 Kilo Amps suitable for 11 KV connecting testing & including taking down old unserviceable complete all as specified and as directed.
M&L ACSR jumpers in HT/LT over head line upto 10 mm dia as that of existing size including sleeves/holding clamp/ binding wire, nuts & bolts washersetc as required complete all as specified and as directed.
M&L of danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white, with letters, figures and convention skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 11 KV of size 25 x 20 cm complete all as specified and as directed.
M&L for Cradles, hexagonal/rectangular fabricated with galvanised steel 4mm dia & including taking down old unserviceable complete all as specified and as directed.
M&L for ACSR conductor, steel reinforced for LT / ht over head lines on poles including streching tightining of poles insulator with binding wire of suitable size with insulator/streching of ACSR conductor including disconnecting/taking out old existing unsv ACSR conductors complete all as specified and directed.
M&L for Disconnection of all Primary/Secondary connections of the defective transformer rating up to 200kVA out door / indoor type, any make, taking down / out from plinth / pole / platform with the help of suitable crane and transporting the same carefully to workshop for repair and bringing back and test, install & commissioning in its original existing position by making all neccessary connections complete all as specified and as directed. Note :- Crane and Transporting Charges including in the Job.
All as per item no. 27 above but for capacity above 200 KVA and upto 400 KVA with complete Testing and Commissioning all as specified and as directed.
M&L for Opening top cover of transformer taking out complete oil and keeping in clean and dry container, taking out core & winding from the body, remove the sludge from tank complete and segregation of HT/LT leg coil from transformer including job assembling of jointing the connections pf HT/LT coil in core assembling complete insulation works, setting of core, making new connections (as per existing connections), proper alignment of job including keeping in oven chamber of as per IS Specification of respective transformer capacity for remove the moisture as well as fixing of upper yoke lamination, checking, tightening, nuts, bolts, washers and all types of gasket (Bushing and tank) etc and megger including two coats of anti corrosive paint aftre cleaning inside transformer tanks and two coats of outside painting including writing KVA Capacity, repairs of body by means of welding, jointing if required complete for capacity up to 200 KVA with complete Testing and Commissioning all as specified and as directed.
All as per item no. 29 above but for capacity above 200 KVA and upto 400 KVA with complete Testing and Commissioning all as specified and as directed.
M&L for Making Primery coil with insulated copper wire of required gauge craft paper cotton tape HT insulation as per specification of old existing transformer including making of coil as required of various capacity of transformer complete all as specified and as directed.
M&L for Making Secondary coil with insulated copper wire of required gauge craft paper cotton tape LT insulation as per specification of old existing transformer including making of coil as required of various capacity of transformer complete all as specified and as directed.
M&L for Reconditioning of over heated HT/ LT coil of transformer up to 500 KVA after removing all old insulation any type and re-insulation as required and remaking of LT coil complete all as specified and as directed.
M&L for Opening of the 11 KV / 0.433 KV Distribution transformer rating up to 400 KVA on site by removing the inspection cover / top cover, decanning of the transformer oil up to the required level, check leaked cork seal (if any), check the un sericeable insulators & LT/HT bush (if any) complete from the shell and making connections of LT/HT bush, insulators & cork seals to avoid leakage and refilling oil back to existing postion into the transformer complete testing & commissioning complete all as specified and as directed. (Note: Spares shall be measured and paid separately under relevant items.)
Supply only HT bushing including metal parts and washer complete for any make of transformer mounted on plinth/pole and transformer rating up to 400 KVA capacity complete including taking down old u/s one all as specified and as directed.
Supply only LT rod / studs for any make of transformer rating up to 500kVA mounted on pole/plinth, made of brass with nut and washers, Insulator and fittings etc as per size and shape of original complete including taking down old u/s one complete all as specified and as directed.
Supply only Gasket set (crok sheet) for any make of transformer rating upto 500 KVA for top of transformer or conservator tank after decanning the required level of oil including taking down old u/s one complete all as directed.
M&L for Replacement of air breather with filled silica gel suitable for any make of tranformer rating up to 400 KVA mounted on plinth/pole including taking out old u/s one complete all as specified and as directed.
Supply and filling of transformer oil in transformer plinth / pole mounted including testing insulation and vescocity of oil all as specified and directed by Engineer-in-Charge.
M&L for Dehydration including filtration cleaning of transformer oil in transformer indoor/ outdoor type by centrifusion / machine having minimum capacity 1000 ltrs/ hrs including testing insulation and vescocity of oil before and after dehydration complete all as directed.
Dismantling pole by uprooting and taking out from PCC foundation complete and shifting to other location as directed including fixing the pole including excavation and earth work, PCC 1:4:8 type D2 (using 40mm graded stone aggregate) as base concrete and PCC 1:3:6 type C2 (using 20mm graded stone aggregate) in both foundation and coping of poles all as specified in SSR Part I-2009 and applying two coats of aluminium paint to pole surface complete all as directed.
M&L for Painting the HT poles of OH lines and HT Four poles/two poles and single pole structure complete with cross arms any height and any description thoroughly with necessary cleaning agent including scrapping up of old corroded paint dirt/dust/rust carefully and applying one coats of aluminum paint including marking yello/black strips and white washing of pole coping complete all as specified and as directed.
Restreching/Restringing, tightening and repair to overhead line ACSR conductor of any size on LT poles including necessary Aluminium binding wire connectors PVC sleeves for jumper, fixing of insulators and prunning of tree complete all as specified and directed.
Cutting and trimming trees branches any girth and any size touching to overhead lines and cleaning the distance 1.5 mtr length both side of OH line with in a span of 50 mtrs each disposing the same, clearing the site all as directed by Engineer-in-Charge.
Supply and fixing cable route indicator for HT UG Cable of 11000 Volts bolted with 40 x 6 mm flat iron member of height 0.60 mtr, and 80 mm dia CI plate embedded in PCC 1 : 3 : 6 type C2 of size 20 x 20 x 30 cm block complete all as specified and directed.
Arresting leakage of transformer fins by brazing / welding etc, after removing of oil from inside of transformer w/o openinh top cover and refilling of oil by opening top cover of transformer of capacity upto 500KVA.
M&L in replacement of operating GI pipe 25mm dia upto 7.5 mtr long with clamp, nut, bolts, washers and necessary operating handle suitable for GOD complete all as specified and directed.
Servicing / calibration / trouble shooting / repairing / adjustment of over current relay, earth fault relay, Spring, spring charge mechanism, close coil, trip coil, including connected accessories cleaning of all contacts with CTC, of the 11KV HT VCB panel of 630A, 50 Hz by qulified technical personel incl fixing of spares to make functional in all respects including identifying the deffective parts.
Supply only following spares in repairs suitable for 11KV HT VCB of maximum short circuit current rating 25/26.3 KA 630A/400A after taking down the old spares-
LED indicating lamps R/Y/B 110V AC
LED indicating lamps amber 110V DC
LED indicating lamps white 110V DC
Trip circuit push button with NO contracts.
Door Limit switch
Tripping coil
Closing coil
PT Fuse 3.15A
Fuse Link 2A, 4A, 6A
Fuse Link 10A
Breaker control Switch 25A
Anti condensation space heater
Fuse Holder with base 32A
Thermostat
Test and Service Limit Switch
Single Phase Power Pack with capacitor back-up; input Voltage 230V AC 1Ph Output Voltage -110V DC,100W.
Spring charging motor/ motor coil 230V, RPM 7000,
S&F 11 KV Rasin cast CT, BIL 12 KV/28KV /75KV P, Ratio 100/5+5A, Core- I :1.0 15VA, Core II: 5P10, 15VA, STC- 26.3KA for 1Sec on P2 Side.
S&F in repairsresin cast PT, 11KV Resin Cast 3Ph PT, BIL=12KV/28KV/75KVP; Ratio:11kv/3/110V/3/110V/3; LV Winding 1 :100VA, Cl:0.5; LV Winding 2 :100VA, Cl:3P; OVF=1.9 Continuous for 8 hour with 3.15A Primary Side (HV side) fuse.
S & F 11KV Resin Cast Three Phase PT, BIL=12KV/28KV/75KVP; Ratio:11kv/3/110V/3/110V/3; LV Winding 1 :100VA, Cl:1.0; OVF=1.2 Continuous / 1.5 for 30-sec with 3.15A Primary Side (HV Side) Fuse.
S&F Spout suitable for VCB panel of ABB Make for HT 11, 3PH incl all allied works complete.
Attending breakdown of VCB Panel as and where required trouble shooting / repairing / adjustment of the 11KV HT VCB panel of 630A, 50 Hz by qulified technical personel to make functional in all respects including identifying the deffective parts.
M&L for fabrication of Panel/ VCB cover plate/door made out of 3.15mm (10SWG) thick CRCA duly painted with powder coated paint and making holes at desired position for fixing of bolts/screws/hinges etc complete all as specified and as directed.
Labour for Busbar re-insulation with heat shrinkable insulating material suitable for 11KV Busbars of set of VCB panel including all allied works complete all as specified and as directed. [re-insulation with heat shrinkable insulating tape measured separately]
Heat shrink tube suitable for HT 11 KV busbar of VCB panel
Self amalgamating tape suitable for HT 11 KV busbar of VCB panel
Busbar support insulator for holding HT 11KV Busbars of VCB panel complete all as specified and as directed.
M&L for course agreegate for filling as directed of Gauge 40 to 90 mm, deposited, spread and levelled in layers not exc. 150mm thick, watered and rammed to a True Surface, complete all as specified and as directed.
Cutting anxious green growth / vegetation growth for cleaning out the area around the transformer/ 4P/ 2P structure/ yards at ground level by cutting out roots, un wanted plants bushes and removal of the same by surface excavation not exceeding 30 cm deep average 15 cm complete.
Earthing complete with galvanized steel earth plate electrode 600x600x6 mm thick buried directly in ground (earth pit not less than 2.25 m deep below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected to galvanized earth strip 32 x 6 mm (up to 7.5 m in length from earth plate) by means of bolts and nuts checknuts and washers of galvanized iron or steel all as specified and shown in electrical plate no 3 of SSR part I including necessary excavation and earth work in any type of soil PCC 1:3:6 type C1 chamber with RCC 1:2:4 type B1 40 mm thick cover with MS rod 8mm dia 150mm long reinforcement, watering funnel, 40 mm dia light grade for protection of earth electrode 20 mm dia for watering all as specified and directed and tested on completion.
Note 1:- (Applicable for all parts/items) : The bidders/contractors are advised to read tender document, all drawings & all corrigendum / amendments and general condition of contracts before entry / quoting the rates. Note 2:-The contract sum shall be arrived at after deducting amount of schedule of credit from the total quoted amount.
Damdoo Bhutia (BID ID -3469901)
Janata Enterprises (BID ID -3469694)
SANJAY KAUSHIK (BID ID -3469955)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
BOQ_825024.xls
BOQ • 0.29 MB
PDFTENDERDOCUS.pdf
Tender Documents • 1.15 MB
Download all tender documents and submit your bid