Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹17.6 LAccepted-AOC 01 BALIA BALIA SAGARDIGHI MURSHIDABAD WEST BENGAL 742237 | MURSHIDABAD | WEST BENGAL | 742237 | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹20.3 L+₹2.6 L (14.9%)Rejected-Finance | L2 | Rejected-Finance Bid is Not L1 | |
| 3 | L3₹22.0 L+₹4.3 L (24.5%)Rejected-Finance 49 1 ISWAR GUPTA ROAD KOLKATA 700 028 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | L3 | Rejected-Finance Bid is Not L1 | |
| 4 | L4₹22.3 L+₹4.6 L (26.3%)Rejected-Finance | L4 | Rejected-Finance Bid is Not L1 |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
5 Mar 2021, 6:00 pmClosed
Office of the Executive Engineer PWD Howrah Electr
Office of the Executive Engineer PWD Howrah Electrical Division Onkarmal Jetia Road Howrah 711103
Electrical Repairing At Shalimar GFD Godown, Project ID FS202135217S000
2021_WBPWD_322716_1
WBPWD/EE/HED/NIQ-31 of 2020-2021
Open Tender
ELECTRICAL WORKS ORG
Item Rate
365 days
Shalimar GFD Godown
Please refer Tender documents.
9 documents required · 9 mandatory
₹50,000
Office of the Executive Engineer PWD Howrah Electr
27 Oct 2021
4 Feb 2021
8 Mar 2021
5 Feb 2021
5 Mar 2021
16 Feb 2021
15 Feb 2021
Amount
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Finolex / polycab / KEI) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to light/fan/call bell points with Modular type switch ( L&T Entice / Legrand Myrius ) fixed on Modular GI switch board with top cover plate flushed in wall incl. mending good damages to original finish 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC. Average run 6 mtr. E20/G1.
Distn. wiring in 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (FINOLEX/POLYCAB/KEI) in 19 mm bore, 3 mm thick polythen pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6A 3 pin Modular type plug socket & Modular type switch (Brand approved by EIC) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish. 2x22/0.3 (Ph. & N) and 1x22/0.3 as ECC. On Board. E20/G3.
Supplying & Fixing GI Modular Switch Board of the following sizes complete with three no. suitable size Copper bar with holes (for Ph, N & E) fixed on bakelite/Hard Rubber insulator over the MS welded chairs incl. top cover flushed in wall for housing the board after cutting the brick wall incl. making earthing attachment, painting and mending good damages to building works.( L&T Entice / Legrand Myrius ). E17/F1.
2 Row 12 Module
2 Row 18 Module
Supply & Fixing 240 V 6 A Modular type switch ( L&T Entice / Legrand Myrius ) on existing GI Modular type switch board having top cover plate and making necessary connections as required. E17/3a
Supply & Fixing 240 V, 6A, 5 pin Modular type plug socket ( L&T Entice / Legrand Myrius ), without switch & plug top, on existing GI Modular type switch board with top cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. E17/4a.
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) ( L&T Entice / Legrand Myrius ) on existing Modular GI switch board with top cover plate incl. making necy. connections etc. E18/10.
Supplying and fixing (2+8) way double-door SPN MCB Distribution Board with IP-42/43 protection, 40A DP isolator as incomer & 8nos 6-10 A 10KA SP MCB as outgoing, flushed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. [Legrand/ABB/Schneider make] [D9/13+D5/6+D6/7]
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for (2+8) way SPN DB enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment. [Legrand make]
Supply & Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire.of decorative ceiling fans complete with all accessories including S2 (P2) type capacitor as per IEC 60252-1 with upto date amendents, [Make-Crompton Aura/Orient Gratia Class] 1200 mm sweep. C3/21a.
S & Installation outdoor type both sided door feeder piller box on bricks foundation with cement plastering and net cement finish on a height of 18” from Gr. Level. The piller box will be fabricated from 3 mm thick sheet steel for body portion and 5mm thick for top portion (roof) . The size of the piller box will be 1200(H) x 1000(W) x 600(D) mm with base channel (size:- 75mm x 40mm x 6mm ). There should be horizontal & vertical flat iron (25mm X 6mm) structure in the middle for fixing Electrical accessories. Double Locking arrangement will be made with lock and duplicate keys (7 lever godrej, navatal lock) with door handle. Two numbers lighting arrangement with control switch to be made inside the box as working light and 1 no. 250V., 5/15 combined plug socket & switch. Painting will be made by synthetic enamelled paint after 2 coats of red led primer. Bricks foundation will be cement, plastering and neat cement finish. The feeder piller box comprising the followings:-
Front side: Supplying and fixing double door 160A, Vertical TPN MCB Distribution board for MCCB incomer with IP-42/43 protection, incl. Inter connection with suitable size of copper wire and neutral link & provisionfor earthing attachment, 63A FP MCCB as incomer, 2nos 32A TP MCB & 6nos 6-32A SP MCB as out going. [Legrand make] Rear side: a) S&F L&T make MK-I FASD motor starter with 9-14A relay range. b) Supplying and fixing (2+6) way double-door SPN MCB Distribution Board with IP-42/43 protection, Astro Mini time switch [Make-L&T Cat no -T2DDT7 ], 3 pole contactors ABB make AX09 with 240 v operating coil. 240V, 63A DP change over (MCB type) Havells make incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment.
Supply and Laying of one No. 1.1KV grade following cables in underground trench 460 mm wide x 760 mm average depth, with brick protection on the top of the cable with 8 (eight) Nos. bricks per metre, including filling the space between the brick & cable and also the trench with shifted soil, leveling up and restoring surface duly rammed as per GS. (Mk. Gloster/Havells/Polycab). F2/1a
4 core 25 sqmm Al/Ar
4 core 16 sqmm Al/Ar
Supply and Laying of cable of following cables on wall surface incl. S & F MS saddles , making holes etc. as necy. mending good damages and painting (Mk. Gloster/Havells/Polycab) as per G.S. F1/2b.
4 core 25 sqmm Al/Ar
4 core 16 sqmm Al/Ar
Supply & Laying of cable as below, after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth as below and mending good the damages to original finish incl. removing the rubbish at an average depth of 100 mm in floor/pavement/wall etc. (Mk. Gloster/Havells/Polycab). F3/5i.
4 core 25 sqmm Al/Ar
4 core 16 sqmm Al/Ar
Supply & Laying of 4C x 16 sq.mm. Aluminium armoured Cable by catenary wire along the lenth of O.H. portion incl. S & F anchor bolt on both sides of wall &7/8 SWG GI (Hot Dip) stranded Wire (45 Ton quality) incl. S & F GI thimble and making off binding at both ends. (Mk. Gloster/Havells/Polycab).
S&F 45Ton quality GI turnbuckle. Approved Make.
Supplying & fixing medium gauge GI Pipe ( ISI-Medium) Protection with necessary fittings and jointing metarials as required. F6/11.
32 mm dia
40 mm dia
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below : F4/7c.
4 core 25 sqmm Al/Ar
4 core 16 sqmm Al/Ar
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials : F5/8b.
4 core 25 sqmm Al/Ar
4 core 16 sqmm Al/Ar
Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground level as below: By TATA-Medium GI pipe. G1/2a.
Cutting channel of 31 mm x 31 mm size on masonry wall incl. S&F heavy gauge polythene pipe dia as stated below, by means of iron hooks and supplying and drawing 18 SWG GI Wire fish wire incl. mending good damages to building works. 13 mm dia 3 mm thick polythene pipe without earth continuity wire. E2.2a.
Supplying and fixing PVC Rigid Conduit 'FR' [Precision Make MMS] on wall, ceiling with saddles and other accessories as required and mending good damages to building works. 20mm size
Supply & Fixing 240 V, 6 A Piano key type switch (Brand approved by EIC) on sheet metal switch board incl. S & F 100x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/ perspex cover and making necessary connections as required.
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Finolex / KEI / Polycab) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required. E9/C1.
3 x 22/0.3 (1.5 sqmm)
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC
Supply & Fixing single LED light fitting complete with all accessories directly on wall/ceiling by screws etc.of Single LED T8 T/L fittings( Philips TMC 501 P 1xT-LED 22W P3241) incl. 1x MAS LED (PC body) tube 1200mm 18W865 T8 I--2100lm) or equivalent product of Crompton in all respect. C2/14a.
Supply , fixing & Replacement 240 V 6 A Piano key type switch (Anchor) on existing sheet metal switch board having bakelite/perspex top cover and making necessary connections as required. E5/14a.
Supply , fixing & Replacement 240 V 16/20 A Piano key type switch (Anchor) on existing sheet metal switch board having bakelite/perspex top cover and making necessary connections as required. E5/14b.
Supply , fixing & Replacement 240 V, 6A plug socket (Anchor), without switch & plug top, on existing sheetmetal switch board with bakelite/perspex top cover and making necy. Connections with PVC wire and earth continuity wire etc. E5/15a.
Supply , fixing & Replacement 240 V, 20 A plug socket (Anchor), without plug top and switch, on existing sheet metal switch board with bakelite/ perspextop cover and making necy. connections with PVC wire and earth continuity wire etc. E5/15b.
Modification of wiring of existing twin FL tube light fittings for LED tube light by S&F new wires incl dismantling the existing ballast. & cleaning the fittings. As per direction by EIC.
Modification of wiring of existing Single FL tube light fittings for LED tube light by S&F new wires incl dismantling the existing ballast. & cleaning the fittings. As per direction by EIC.
S&F of 18 / 20 watts 4 ft LED tube lamp (Make:- Philips, Cat - Mas LED tube 1200 mm 18W865 T8 I--- 2100 lm or equivalent product of Crompton in all respect.
Dismantling the 450mm dia exhaust fan from its existing position & refixing the same after proper cleaning / servicing/ repairing as necessary. As per direction by EIC.
Rewinding the stator coil of 450mm sweep exhaust fan by super enameled copper wire , mica sheet, minalux paper etc. as per reqd. incl. baking, varnishing complete as per G.S.
S&F 250V 8µF. Metal body P2 type capacitor. [Epcos make]
S&F ball bearing 6201/6202 [TATA/SKF]
Dismantling the existing 9mt ST pole very carefully from the existing erected condition. & incl. excavation, filling of holes, restoring the ground surface. As per direction by EIC.
Painting of 9 mtr. Long steel Tubular pole with one coat of RO priming and Two coats of aluminium paint of approved make and brand incl. preparation of surface by sand paper/emery paper, cleaning etc. for recieving fresh coat of paint. H2/4a
Supply and Fixing of 90W LED outdoor / street light type LED light fitting complete with all accessories to be fixed/projected from the wall of the building incl. making holes to building, S&F 40 mm dia GI pipe (ISI-Medium) 1.50 mts. average length, with GI reducing socket at one end and thread at the other end & suitable bend to house the fitting & making necy. connections with S&F necy. length of 3X1.5 sqmm PVC insulated single core stranded annealed copper wire through 20mm GI flexible Conduit and making connections as required and mending good damages to wall and painting . (Make Philips/ Wipro/ Crompton) with minimum luminous efficiency 110 Lumen/ watt & IP 67 protection. C3/19.
Supply and Fixing SMC Junction Boxes on wall of dimention (250x200x105)mm with IP 67 protection (Sintex / Hensel ) make for compound light. With 4 pole terminal stud and 6A 10KA C curve SP MCB Legrand make. As per direction by EIC.
Supply , laying & Replacement of 4core 6 Sqmm multistranded heavy duty copper conductor unarmoured cable. (make: Finolex/Havells/ Polycab/ Gloster)
S.I.T.C. of Astro Mini time switch [Make-L&T Cat no -T2DDT7 ] as per direction by EIC.
S, fixing & Replacement of 440V 32A 3pole contactor with 240V operating coil. [Make: L&T MNX 32]
Dismantling the existing 12nos HPSV fittings from the carrage of High mast and deposit to section Office. as per direction by EIC.
Supply & Fixing of 240V 350W LED flood light fittings with minimum 35000 lm output, vertical & horizontal both side tiltable base complete with all accessories of following beam angles. [ make: Philips /Wipro /Crompton] as per direction by EIC.
Supply & Laying 3core 2.5Sqmm copper conductor unarmoured cable through heavy duty flexible pipe. for necy. connection . (make: Finolex/ Havells/ Polycab/ Gloster)
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. F5/9.
Dismantling the existing HPSV fittings from the Truss inside of godwan.
Supply & Fixing of 240V 250W LED flood light fittings with minimum 25000 lm output, vertical & horizontal both side tiltable base complete with all accessories of 120° beam angles. [ make: Philips /Wipro /Crompton] as per direction by EIC.
Supply & Fixing of 240V 60W LED flood light fittings with minimum 66000 lm output, vertical & horizontal both side tiltable base complete with all accessories [ make: Philips /Wipro /Crompton] to be fixed on wall with suitable fastner / MS Angle bracket. as per direction by EIC.
Painting of control box for 4nos highmast, 6nos VTPN cover made by MS sheet door both inside & out side by two coat of synthetic enamel paint. as per direction by EIC.
Labour charges for repair of existing 250W/400W HPSV fittings. as per direction by EIC.
Rate should be quoted including all Taxes & LWC (if any).
MAA TARA ELECTRO ENTERPRISE
Electromech Engineers Co-Operative Society Ltd.
JAYBEECO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .