Loading…
Loading…
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
24 Sept 2026, 6:00 pm
CWE AF BIKANER
HQ CWE AF BIKANER
REPAIR/ MAINT AND CALIBRATION OF VCB, RMU, RELAYS AND HT YARD WITH CONNECTED ITEMS, BATTERY BACKUP SYSTEM AND CONNECTED WORKS AT AF STN NAL
2026_MES_787698_1
C-81681/E8
Open Tender
Civil Works
Item Rate
210 days
GE AF NAL
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF NAL
₹90,000
Yes
3 Sept 2026
3 Sept 2026
26 Sept 2026
3 Sept 2026
24 Sept 2026
17 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Disconnecting, opening of indoor type VCB/SF6 of any description and any make of rating 11 KV 400/630/800 Amps capacity for servicing / overhauling, taking out and removing unserviceable / defective parts including cleaning & servicing, greasing, oiling of the parts, inspection/ overhauling of tripping assembly, earth fault release assembly, tripping coil, auxiliary switch, manual / motorised spring drive mechanism, motor and gear assembly, stop bolt assembly, main shaft interlocking assembly, closing spring assembly etc lubricant to function smoothly and replacement of unserviceable parts with new one,refilling SF6 Gas, Cleaning and inspecting through insulators, vacuum interuptors by carbon cleaner solution and apply dry graphite conductive sealent for electrical contacts to avoid carbon deposits on contact surfaces, cleaning all busbar by rubbing and by CRC liquid cleaner reassembling the VCB after overhauling/ servicing and its testing complete all a specified and directed.
Note: (i) Replacement of unserviceable parts shall be measured and paid separately under relevent item of Sch 'A' as supply only but fixing charges of the parts replaced /repaired is deemed to be included in the item rate.
(ii) Servicing shall be got carried out by the authorised rep of the VCB manufacturer and the service engineer will submit a service report and calibration certificate for each VCB.
(iii) Any item not included in CA and required for successful operation of the panel will be provided by the contractor & same shall deemed to be included rate quoted. (iv) Test report of all parameter duly signed by Garrison Engineer, Contractor and Engineer-in-charge shall be maintained on records . | 30 | Each Job | - | - |
| 2Supply only following parts suitable for 11KV VCB 400/630/800 Amps capacity and RMU of 2/3/4/5 Way,dismantled / fixed under Sch 'A' item No: 1 here-in-before complete all as specified and directed.( Item No 2.01 to 2.20) | |||||
| 2.01 | Isolating contact assembly 400/630/800 Amps suitable for 11 KV/400/630/800 Amp VCB Panel and for RMU | 4 | Each | - | - |
| 2.02 | TNC switch for 11 KV VCB Panel and RMU | 7 | Each | - | - |
| 2.03 | Indication lamp LED type suitable for 230 Volts AC 50Hz and 110/30 Volts DC supply. | 20 | Each | - | - |
| 2.04 | Supply only HRC fuse 11 KV grade 2 Amps to 5 Amps. | 6 | Each | - | - |
| 2.05 | Supply only HRC fuse 11 KV grade 10Amps to 20 Amps. | 8 | Each | - | - |
| 2.06 | Vacuum interrupter suitable for 400/630/800 amps, 11 KV HT VCB/ RMU complete all as specified and directed | 3 | Each | - | - |
| 2.07 | Motor & gear assembly 230V AC suitable for 400/630/800 amps, 11 KV HT VCB/RMU including testing & puting on load complete all as specified & directed. | 2 | Each | - | - |
| 2.08 | Spring bearing gear suitable for 400/630/800 amps, 11 KV HT VCB/RMU complete all as specified and directed | 2 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.53 MB
Tenderdocuments.pdf
Tender Documents • 2.28 MB
BOQ_882826.xls
BOQ • 0.46 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .