Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.8 LAccepted-Finance BILASPUR | ₹4.8 L | L1 | Accepted-Finance L1 |
| 2 | L2₹5.2 L+₹32,056.43 (6.62%)Rejected-Finance | ₹5.2 L+₹32,056.43 (6.62%) | L2 | Rejected-Finance L2 |
| 3 | L3₹5.2 L+₹33,243.70 (6.86%)Rejected-Finance BILASPUR | ₹5.2 L+₹33,243.70 (6.86%) | L3 | Rejected-Finance L3 |
Tender Value
₹4.7 L
EMD Value
₹4,749
Closing Date
13 Mar 2026, 9:00 amClosed
SR. EXECUTIVE ENGINEER ED HPSEBL RAKKAR UNA
SR. EXECUTIVE ENGINEER ED HPSEBL RAKKAR UNA
Tender for Providing 1 Nos. 11 KV, VCB Outdoor Kiosk (Auto Recloser) at 33/11KV-2x6.3MVA (unmanned) Sub-Station at Santokhgarh under ESD HPSEBL Santokhgarh Ch to (T.S. No. 159/2025-26) Bid No- UED/247/2025-26.
2026_HPSEB_130728_1
BID NO- UED/247/2025-26
Open Tender
Electrical Works
Percentage
90 days
33/11KV-2x6.3MVA (unmanned) Sub-Station at Santok
AS PER SBD
5 documents required · 5 mandatory
₹590
₹4,749
18 Jul 2026
7 Mar 2026
13 Mar 2026
7 Mar 2026
13 Mar 2026
7 Mar 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1.01 | Providing, fixing, testing and commissioning, including carriage and transportation, of Outdoor IP-55, 12 kV Kiosk type VCB Switchboard. The cubicle shall be fabricated from Aluzinc or GI/GP sheets (minimum 120 micron galvanized), duly powder coated PP type in Shade-631 of IS-5. The switchboard shall be provided with 12 kV bushings of suitable current capacity (06 Nos.) at the top of the switchboard for connection of the panel through ACSR conductors. The panel shall be complete with all necessary components, control wiring, protection and operating mechanisms, suitable for independent feeder control and equipped with Auto-Recloser functionality for the feeder: - Vacuum Circuit Breaker: - 11kV, 1250A, 26.3kA for 3 Sec. Fixed Type VCB with Manual & Electrically operated, Spring Charging Mechanism with 230V AC Motor and Manual Handle, Mechanical ON/OFF indicator, Operation Counter, as per IEC/IS 62271-100.
Shunt Opening & Closing Coils 24V DC, Auxiliary contact 6NO+6NC, Anti-pumping Device 24V DC.
Potential Transformer: -Single Phase, Resin Cast, Dry type, Fixed type Potential Transformer (3 Nos) with one set of HTFS / LTFS and one no. Neutral Link (11 kV√ 3/110√ 3-110√ 3V), Class 1.0, 100VA.
Control Transformer: -Single Phase, Resin Cast, Dry type, Fixed type Control Transformer 250VA (1 No.) with DP MCB at LV Side (11kV/220V AC)
Current Transformer: -Single Phase, Resin Cast, Dry type Current Transformer (3 Nos.) Ratio 400-200/5-5A) (Core 1: for meter 0.5S, Core 2: for Protection 5P10, Core 3: for special protection PS)
Metering: - 96 sq.mm Digital Ammeter with Inbuilt Selector Switch: (1 No.)
96 sq.mm Digital Voltmeter with Inbuilt Selector Switch: (1 No.)
Tri-vector Meter Phase 4Wire system: (1 No.)
Protections: - Numerical Non-Directional lDMT combined 3 O/C+1 E/F relay with low set, high set, instantaneous feature, Broken Conductor, Auto-reclose feature, communicable type (IEC-61850),
High speed/Master trip relay (1 No.)
TCS Relay (1 No.)
Pole Discrepancy Relay (1 No.)
Indication Lamps: -VCB OFF/ON/Auto trip, Trip Circuit Healthy, Spring Charge, & R,Y,B Phase Indication Lamps (1 set)
Control Switches & Push Buttons
Breaker Control Switch (Close-Neutral-Trip) (1 No.)
Local Remote selector switch (1 No.)
Flush Head type Trip Circuit Healthy Push Button (1 No.) Control wiring with appropriate colors (1 Set)
Complete switchboard wiring to be carried out with Cu flexible wires, lugs, identification ferules, marking tags as per approved drawing and standard practice of relays / meters. For CTs and DC Circuit minimum 2.5 mm² and for other AC Circuits minimum 1.5 mm² shall be used. Every wire should be routed through terminal blocks. For CTs and PTs TTB type are mandatory to test relays and meters for injection of current and voltage from Secondary Injection Test Kit.
Busbar Ratings: - 12kV, 800A Al Busbar (Rectangular or Round) (Conductivity should be above 55%) with 12kV Rated Insulation Sleeves Hot/Cold Shrink type 1 Set)
Earth bus 40x6 mm (Aluminium) (1 Set)
Other Equipments: -Heater ON/OFF switch with filament type 80Watts space heater & thermostat, single phase switch with socket, Cubicle LED Lamp for panel illumination with snap type door limit switch, Fuses / MCBs for AC / DC control. (1Set)
Approved Make: - a) VCB – ABB/Schnieder/Siemens.
b) CT, PT & VT – Pragati/ECS.
c) INDICATOR / METERS / MCB – ABB/Schnieder/Siemens
d) CONTROL SWITCHES – Salzer/Kaycee
e) HEATER & THERMOSTAT – Reputed
f) BUSBAR – Hindalco/Jindal
NOTE: -24V DC for operation of the circuit breaker and protection relays shall be taken from the integrated power pack/supply with suitable capacity battery and charging circuit arrangement. This is to ensure the operation of the breaker in case of power supply failure (2 open and 2 close operations). If 220V AC Supply is available from HPSEBL then the Control Transformer cost shall be mentioned to reduce the cost from quoted rate. | 1 | Job | 4,74,910 | ₹4,74,910 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 4.10 MB
Tendernotice_2.pdf
PDF • 0.50 MB
BOQ_193292.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .