Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹63.8 LAccepted-AOC | L1 | Accepted-AOC BEING LOWEST | |
| 2 | L2₹68.9 L+₹1.5 L (2.20%)Rejected-Finance | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹71.1 L+₹3.7 L (5.51%)Rejected-Finance CHATAI SHEEP WARD NO 07 NEW MARKET ROAD AHIWARA DURG CHHATTISGARH 490036 | DURG | CHHATTISGARH | 490036 | L3 | Rejected-Finance NOT LOWEST | |
| 4 | L4₹73.3 L+₹5.9 L (8.74%)Rejected-Finance | L4 | Rejected-Finance NOT LOWEST | |
| 5 | L5₹79.7 L+₹12.3 L (18.3%)Rejected-Finance 67 KAILASH VIHAR TIWARIPUR BAGIA JAJMAU KANPUR 208010 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208010 | L5 | Rejected-Finance NOT LOWEST |
Tender Value
₹1.1 Cr
EMD Value
₹1.9 L
Closing Date
14 Feb 2022, 6:00 pmClosed
CWE AF GWALIOR
CWE AF GWALIOR - 474020
SPECIAL REPAIR/REPLACEMENT OF OH LINES TO UNDERGROUND CABLE FROM TOWER NO. 03 TO OFFICERS MESS AT AF STN GWALIOR
2022_MES_502826_1
85017/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
AF STATION GWALIOR
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹1,000
Garrison Engineer (AF) ADM Area Gwalior
₹1.9 L
Yes
24 Feb 2022
20 Jan 2022
16 Feb 2022
20 Jan 2022
14 Feb 2022
7 Feb 2022
Amount
Dismantling/disconnecting and taking out the old unserviceable/defective items of Structural steel rusted broken or damaged including old cross arms, mild steel clamps, bolts/nuts etc and keeping aside for further disposal in accordance of direction of Engr-in-Charge.
Dismantling/disconnecting and taking out the old unserviceable/defective items of ACSR/copper conductor out lived broken unserviceable of any type including removing binding wire from insulators/jumpers. etc and keeping aside for further disposal in accordance of direction of Engr-in-Charge.
Dismantling/disconnecting and taking out the old unserviceable/defective insulator of any type including hardware. etc and keeping aside for further disposal in accordance of direction of Engr-in-Charge.
Dismantling/disconnecting and taking out the old unserviceable steel pole of any size or any type etc and keeping aside for further disposal in accordance of direction of Engr-in-Charge.
Dismantling/disconnecting and taking out the old GI wire of any size or any type including guarding, cradles, stay wires, etc. and keeping aside for further disposal in accordance of direction of Engr-in-Charge.
Supply, laying , jointing & testing XLPE insulated,screened ,PVC bedded, galvanised steel strip or wire armoured, HT electirc power cable ( heavy duty) with standard aluminium conductor , 11000 Volts grade of cross sectional area 120 Sq mm 3 core laid in trenches /wall/pole complete all as specified and directed. Note : Excavation , earth work, sand cushioning for cable and cable protection cover shall be measured & paid under respective item.
S&F for Cable jointing kit suitable for HT 11 KV (Earthed) grade for cold shrink type joint complete with jointing materials & accessories for HT XLPE Aluminium conductor cable of size 120 Sqmm to 185 Sqmm , 3 core , indoor type including testing complete all as specified and directed.
S&F for Cable jointing kit suitable for HT 11 KV (Earthed) grade for cold shrink type joint complete with jointing materials & accessories for HT XLPE Aluminium conductor cable of size 120 to 185 Sqmm, 3 core, outdoor type including jointing & testing complete all as specified and directed.
S&F for Cable jointing kit suitable for HT 11 KV (Earthed) grade for straight through cold shrink type joint complete with jointing materials & accessories for HT XLPE Aluminium conductor cable of size 120 Sqmm to 185 Sqmm 3 core including jointing & testing complete all as specified and directed. Note for item No. 07 to 09:- Exavaction, returning filling, collecting of old cable protection cover and relaying after jointing the cable is included in quoted unit rate.
Supply, installation, Commissioning and testing HV Junction box panel board of suitable shape and size as approved by GE for 3 phase 11000 Volts , AC , 50 Hz supply, outdoor cubical type, dust and vermin proof, pedestal mounting type suitable for outdoor applications having suitable shape/ size canopy on top, made out of 3.15 mm thick mild steel sheet with using 25mm x 25mm x 5mm angle iron frame and supports, duly finished with powder coated using two coats of synthetic enamel paint of approved colour over a coat of red oxide primer all over exposed steel surfaces complete including locking arrangement and panel legs embedded with PCC 1:3:6, type C-1(using 20 mm graded crushed stone aggregate) and bus bar of aluminium conductor suitable shape & size for 3 phase rating of 600 Amps IP-65 protection complete all as specified and directed.
M & L for laying & jointing 100 mm bore GI water tubing, light grade as in sleeving etc laid in trenches / ducts / horizontal bore hole complete all as specified and directed by Engineer-in-Charge.
M&L for Boring of hole under road, pavement, hard-standing by trenchless technology using ultra sound technique and necessary machine with & including HDPE pipe of 150 mm dia suitable for 0.4 Mpa working pressure complete all as specified and directed. Note : Pipes shall be laid minimum 1.00 mtr below/under existing road surfaces/taxi track / apron /floors etc)
Excavation in trenches in soft & loose soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection PCC covers any type/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m complete all as specified and directed. Note : Excavation shall be made carefully in order to avoid damage of existing cables and protection covers
Returning, filling in including spreading, leveling, watering and well ramming in layers of 25 cm thick after the cables etc. are laid, jointed & tested complete all as specified and directed by Engineer-in-Charge.
Removal of surplus excavated spoil not exceeding 50 Mtr distance and depositing where directed by Engineer-in-Charge at a level not exceeding 1.5 m above the starting point complete all as specified.
Material & labour for sand filling with clean dry fine sand unwashed including gently punning around cables in trenches for cable protection complete all as specified and directed by Engineer-in-Charge. NOTE:- For measurement purpose punned thickness shall be considered as per clause 19.75 of SSR Part-I.
Supplying & Laying un-reinforced pre-cast flat concrete cable protection cover of class LV low voltage , type I, size 250 mm x 150mm x 40mm, factory made, complete all as specified and directed by the Engineer-in-Charge.
Supplying & Laying un-reinforced pre-cast flat concrete cable protection cover of class HV high voltage , type I, size 300 mm x 180mm x 40mm, factory made, complete all as specified and directed by the Engineer-in-Charge.
Disconnecting, taking out and removing old existing unserviceable underground, LT 1100 Volt cable size 10 Sqmm to 25 Sqmm 3.5 core of any description and in any position complete including taking down existing protection pipe of cable ,seviceable bricks/ cable covers etc. and stack up at the site properly complete all as specified and directed by the Engineer-in-Charge .
Disconnecting, taking out and removing old existing unserviceable underground, LT 1100 Volt cable size 35 Sqmm to 70 Sqmm any core of any description and in any position complete including taking down existing protection pipe of cable ,seviceable bricks/ cable covers etc. and stack up at the site properly complete all as specified and directed by the Engineer-in-Charge .
Laying, jointing and testing 1100 Volt grade LT XLPE/PVC insulated, armoured, heavy duty, aluminium conductor cable of size 10 Sqmm to 25 Sqmm any core , laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed by the Engineer-in-charge .
Laying, jointing and testing 1100 Volt grade LT XLPE/PVC insulated, armoured, heavy duty, aluminium conductor cable of size 35 Sqmm to 70 Sqmm any core , laid in trenches/ducts, floors, fixed to walls etc. complete all as specified and directed by the Engineer-in-charge .
Supply, laying , jointing & testing XLPE insulated,armoured , (heavy duty) with standard aluminium conductor , 1100 Volts grade of cross sectional area 16 Sq mm 4.0 core complete all as specified and directed. Note for item No 21,22&23 : Excavation , earth work, sand cushioning for cable and cable protection cover shall be measured & paid under respective item.
Supply, laying , jointing & testing XLPE insulated,armoured , (heavy duty) with standard aluminium conductor , 1100 Volts grade of cross sectional area 35 Sq mm 3.5 core complete all as specified and directed. Note : Excavation , earth work, sand cushioning for cable and cable protection cover shall be measured & paid under respective item.
M & L jointing and testing for provision of straight through joints, heat shrinkable, suitable for XLPE, LT UG Cable, 1100 Volts grade, for size 10 Sqmm to 16 Sqmm any core complete all as specified and directed by the Engineer-in-Charge.
M & L jointing and testing for provision of straight through joints, heat shrinkable, suitable for XLPE, LT UG Cable, 1100 Volts grade, for size 25 Sqmm to 50 Sqmm ,3.5 core complete all as specified and directed by the Engineer-in-Charge.
Demolition for cement concrete/road in ground floor and paving not exceeding 15 cm thickness below or above ground level including removal of rubbish to a distance exceeding 1.50 Km but not exceeding 5.00 Km etc complete all as specified and directed.
M&L for making two holes (each hole of 20 mm dia) in existing street light steel tubular pole by using gas welding/ electric arc welding for insertion of wire for street lights. The holes should be made first at 1500 mm above ground level and second 1200 mm below top end of the pole including grinding the surface of pole for proper smoothness all as specified and directed.
S&F Weather Proof thermo plastic (Polystyrene) Cable Junction box , having protection class IP-66 and overall size 210mm x 155mm x 92mm with metric knockouts on the wall, fixed / mounted on the pole with aluminium strip 25 mm x 3mm , clamp, GI bolts, nuts, washers and 2 Nos polymide weather proof cable glands of cable sealing range 10mm to 17mm (complete with check nut) including 1 No, 30 Amps 4 Way cable connector and 1 No., 6 Amps SP MCB complete all as specified and directed .
M & L for earthing complete with Gl electrode of size 600 mm x 600 mm x 6.00mm thick buried directly in ground vertically in pit of depth not less than 2.25 mtr below normal ground level with top edge of the earth plate not less than 1.50 mtr below normal ground level connected to Gl earth strip 32 mm X6 mm as main earthing lead by means of bolts, nuts, check nuts and washers of brass connected including gun metal or phosphorus bronze of size 75x75x25 mm drilled and screwed including 3 Nos 8 mm dia 25 mm long hexagonal head screwed all as specified including excavation and earth work and disposal of surplus soil including 40 mm dia Gl tubing light grade and necessary fitting for protection of Gl strip including laying of charcoal, dust and common salt PCC (1:3:6) type C-l( using 20 mm graded crushed stone aggregate) earth pit with 40x40x6mm mild steel angle iron frame & 40mm thick pre cast RCC cover (1:2:4) type B-1 (using 20 mm graded crushed stone aggregate) reinforced with 8mm dia TMT bars @ 75mm C/C both way with mild steel handle 12 mm dia round bars ,10mm thick plastering with cement mortar (1:4) internally and upto 150 mm below ground level externally, PGI funnel with wire mesh 20mm dia Gl pipe for watering complete all as shown on electrical plate No.3 of SSR Part -1 2009 and connected in earth test including testing completed all specified and directed. Note: (i) Earth strip and its protection pipe up to and including 7.5 mtr only from the top of earth electrode are included in this item. (ii) Test result of earthing to be submitted by the contractor for all earthing. (iii) Earth filling shall be done by vegetable soil. (iv) Soil should be free from stone, boulders,aggragates,gravel etc. (v) The rate quoted by the bidders shall be also be deemed to include :-(a) Excavation upto 5 mtr depth and returning filling in any type of soil and disposal of surplus soil. (b) Supply of charcoal and common salt.
S & F in Automatic street light Switch for automatic switching OFF street light at 30 Lux level and switching ON at 10 Lux of natural light the sensor along with suitable power contactors of rating 63 Amps ,3 Phase, MCB 63 Amps SPN-03 Nos should be enclosed in pole/wall mountable enclosure made of rust proof, Electric shock proof, Termite proof and FR grade conforming to IP55. The contactors, MCBs and circuit wiring should suitable enough to take load of 25 KW equally distribution over three phase 415 Volts A/C including all connected acessories complete all as specified and directed. Make:- HAVELLS Cat Part No- IHXT509120 or equivalent Make in Legrand/L&T all as specified and directed.
S&F PVC insulated, sheathed twin core 2.5 Sqmm size aluminium wire duly passing through the holes of existing steel poles/ street light brackets including necessary connection at pole mounted street light junction box and at the street light luminaries all as specified and directed.
Supply, Installation, testing factory made LT Feeder Pillar Box (of size 60 cmx45cmx30cm for 3 Phase, 4 Wire, 415 Volts, AC, 50 Hz, Outdoor, Cubical Type, Weather, Dust and Vermin proof, Pedestal mounting type, front operated applications having size of Aluminium bus bar rating capacity 400 Amps and neutral 300 Amps rating capacity mounting of insulators, Controlled by MCCB, 100 Amps, 3 pole, 415 Volts, AC supply, having breaking capacity Icu = 16 KA fixed type, on incomming side, canopy on top and gland provision in the bottom made out of 3.15 mm thick MS sheet duly powder coated of approved shade with using 40mmX40mmX6 mm angle iron frame and supports including necessary excavation and grouting work in PCC 1:2:4 Mix, Type B1 complete all as specified and directed.
M&L for PCC 1:4:8, type D-2 (using 40mm graded crushed stone aggregate) as in foundation/repairs to damaged road/footpath/plinth for panels etc. including necessary formwork complete all as specified & directed.
M&L for PCC 1:2:4,type B-1 (using 20mm graded crushed stone aggregate) as in repair to footpath/hard standing/plinth for panels etc. including necessary formwork complete all as specified & directed.
S & F cable route indicators made out from CI round disc duly marked as "MES HT CABLE"etc in specified colour mounted on angle iron frame of size 40 mm x 40 mm x 5mm thick and 1200 mm long leg made out of 40 mm x 40 mm x 5mm welded to frame and embedded in cast in situ PCC block of size 150 X 150 x 300 mm deep of mix 1:3:6 type C-1(using 20 mm graded crushed stone aggregate) including required earthwork & excavation and painting of MS/iron work with two coats of synthetic enamel paint over a coat of red oxide primer etc complete all as specified & directed.
M/s DN Gupta and Company
M/S SANTOSH CONSTRUCTION CO
Allied Agencies
Ashirwad Contractor and Supplier
POONAM ELECTRIC INDUSTRY
NIHAL ENTERPRISES
Raja enterprises
Jyoti enterprises
HAMTECH ENGINEERING PRIVATE LIMITED
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .