| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.9 LAccepted-AOC | L1 | Accepted-AOC being L1 | |
| 2 | L2₹5.4 L+₹41,889 (8.33%)Rejected-Finance NO 1A 1 SHALOM VALLUVAR STREET SIVANANDHA COLONY COIMBATORE TAMIL NADU 641 012 | COIMBATORE | TAMIL NADU | 641012 | L2 | Rejected-Finance quoted amount is higher than 1st lowest | |
| 3 | L3₹5.5 L+₹48,189 (9.58%)Rejected-Finance | L3 | Rejected-Finance quoted amount is higher than 1st lowest | |
| 4 | L4₹6.2 L+₹1.2 L (23.6%)Rejected-Finance 158 A 2 9 DR RAJARATHINAM STREET KATTOOR COIMBATORE 641 009 TN | COIMBATORE | COIMBATORE | TAMIL NADU | 641009 | L4 | Rejected-Finance quoted amount is higher than 1st lowest | |
| 5 | L5₹7.0 L+₹2.0 L (38.9%)Rejected-Finance | L5 | Rejected-Finance quoted amount is higher than 1st lowest |
Tender Value
₹6 L
EMD Value
₹12,000
Closing Date
3 Nov 2023, 6:00 pmClosed
AGE I AF coimbatore
AGE I AF COIMBATORE AFAC COMPLEX KAMARAJAR ROAD RED FIELD POST COIMBATORE PIN -641018
MAINT AND REPAIRS TO CAPACITOR PANELS RENEWAL OF EARTHING SYSTEM AND OTHER ALLIED WORKS AT AFAC
2023_MES_622228_1
8915_E8
Open Tender
Electrical and Maintenance Works
Item Rate
330 days
AFAC
As per NIT and tender documents
8 documents required · 8 mandatory
₹500
AGE I AF Coimbatore
₹12,000
Yes
24 Nov 2023
9 Oct 2023
10 Nov 2023
9 Oct 2023
3 Nov 2023
22 Oct 2023
10 Oct 2023 - 16 Oct 2023
Amount
Excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep and getting out in hard/dense soil for laying of UG cables all as specified and as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers n. exc. 25 cm thickness with hard/dense soil all as specified and as directed.
Removing excavated materials (soils) to a distance not exc 50m and depositing where directed at a level not exc1.5 m above the starting point all as specified and as directed.
Earth cushioning to UG cables using excavated soil riddled by using large sieve to separate the composite particles/roots etc and refilling in trenches all as specified and as directed. Note: Punned thickness will be measured for payment.
Supply and lay burnt bricks sub-class 'B' designation 75 for cable protection all as specified and as directed.
M&L for XLPE insulated, screened, PVC bedded,galvanised steel strip or wire armoured,electric power cables (heavy-duty) with aluminum conductor, 1100 volts, grade cross sectional area 95 Sqmm 3.5 core including taking down unserviceable cable and incl the distrubence surface of road making good with using PCC, fixing the cable with suitable size glands, crimping type lugs etc all as specified and directed.all as directed. Make: Havells/Polycab/Finolex/Paragon/Gloster/Nicco
All as per Item No 06 here - in - before but 50 Sqmm 3.5 core
All as per Item No 06 here - in - before but 35 Sqmm 3.5 core
All as per Item No 06 here - in - before but 25 Sqmm 3.5 core
All as per Item No 06 here - in - before but 16 Sqmm 4 core
All as per Item No 06 here - in - before but 16 Sqmm 2 core
All as per Item No 06 here - in - before but 10 Sqmm 2 core
M&L for repair/servicing of capacitor panel 25 KVAR/30 KVAR/50 KVAR ) and carry out repairs such as dismantling of power contactros, auxillary contactors, CT Coil, checking the HRC fuse and replacement if any damaged, checking the control wiring and refixing all the components after proper servicing all as specified and as directed Note: Spare parts any required will be measured separately)
Supply only 3 KVAr capacitor duty contactors with built in surge suppressor. Make L&T MO C 3 or equivalent in Havells, Schneider
Supply only 5 KVAr capacitor duty contactors with built in surge suppressor. Make L&T MO C 5 or equivalent in Havells, Schneider
Supply only 10 KVAr capacitor duty contactors with built in surge suppressor. Make L&T MO C 10 or equivalent in Havells,Schneider
Supply only 10 KVAR heavy duty cylindrical capacitor Rated Voltage 440V AC, 3ø, 50Hz, Delta Connection. Make L&T, HPL, Havells
Supply only 5 KVAR heavy duty cylindrical capacitor Rated Voltage 440V AC, 3ø, 50Hz, Delta Connection. Make L&T, HPL, Havells
Supply only 3 KVAR heavy duty cylindrical capacitor Rated Voltage 440V AC, 3ø, 50Hz, Delta Connection. Make L&T, HPL, Havells
Supply only 2 KVAR heavy duty cylindrical capacitor Rated Voltage 440V AC, 3ø, 50Hz, Delta Connection. Make L&T, HPL, Havells
Material and labour for painting of steel/iron surfaces of any description over 10 cm in width or girth with cleaning, preparation of old painted surfaces and two coat of synthetic enamel paint inside/out side of panel board of any size all as specified and as directed.
M&L for servicing of Panel board double door with canopy by cleaning with blower/replacement of lugs if any,replacemenmt of burnd out copper wiring if any, cleaning and tightening of MCCB terminal connections, rectifying the loose connections, repairing or easing of door locking arrangement including hinges all as specified and as directed.
Supply and laying GI pipe light grade 50mm bore including all type fitting such as bends, elbows, tee etc fixed on walls/to poles/laid in trenches as cable protection all as specified and as directed.
Supply and fix MCCB four pole 160A 36 KA 415 V, adjustable type with spider terminal link including taking down unserviceable MCCB,s all as directed. Make: C&S /Siements/Indo asian/Havells /Schnieder
Supply and fix MCCB four pole 200A 36 KA 415 V, adjustable type with spider terminal link including taking down unserviceable MCCB,s all as directed. Make: C&S /Siements/Indo asian/Havells /Schnieder
Supply and fix MCCB four pole 400A 36 KA 415 V, adjustable type with spider terminal link including taking down unserviceable MCCB,s all as directed. Make: C&S /Siements/Indo asian/Havells /Schnieder
Supply and fix MCCB 3 pole 25-100 Amps, 16 KA 415 V, fixed type with spider terminal link including taking down unserviceable MCCB,s all as directed. Make: C&S /Siements/Indo asian/Havells /Schnieder
Supply and fix TPN MCB 63 A, C series 415 Volt including taking down unserviceable MCB's all as directed. Make: C&S/Siemens/Indo asian/Havells/Schnieder
Supply and fix TPN MCB 40 A ,C series 415 Volt including taking down unserviceable MCB's all as directed. Make: C&S/Siemens/Indo asian/Havells/Schnieder
M&L for cutting of existing bituminous road/path/hard standing suitable for laying cable protection pipe 80/50 mm dia under the road/path/hard standing at a depth not less than 60 cm below the normal ground level, returining filling soil and making good the disturbed surface of road/path/hard standing by using cement contrete mortar 1:2:4 type B1, using 20 mm graded stone aggregate 0.30 mtr wide and 0.30 mtr thick complete all as specified and directed.
Excavation by trenchless technology by boring of holes under main roads, pavement, hard standing at a depth not less than 2 m below the normal round level by trenchless technology using ultra sounding technique and necessary machine including GI pipe light grade 80 mm dia suitable for 0.4 MPA working pressure.
shalom constructions
V.R.Enterprises
POOJA ENGINEERING
p.chinnasamy
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .