Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹82.5 LAccepted-AOC 58 CHANDRALOK BLDG MAYO HOSPITAL ROAD NAGPUR 440018 | NAGPUR | NAGPUR | MAHARASHTRA | 440018 | L1 | Accepted-AOC Eligible | |
| 2 | L2₹84.8 L+₹2.3 L (2.78%)Rejected-AOC 1101 A WING SACHDEV COMPLEX JANGAL MANGAL RAOD BHANDUP W MUMBAI 400078 | MUMBAI SUBURBAN | MAHARASHTRA | 400078 | L2 | Rejected-AOC Eligible | |
| 3 | L3₹89.1 L+₹6.6 L (7.97%)Rejected-AOC MATHOSHREE PLOT NO 55 SR NO 787 A BEHIND ASHWANI HOSPITAL GOVIND NAGAR NASIK 422 009 | NASIK | NASHIK | MAHARASHTRA | 422009 | L3 | Rejected-AOC Eligible | |
| 4 | L4₹95.6 L+₹13.0 L (15.8%)Rejected-AOC V P O SAROTARI TEHSIL BAROH DISTRICT KANGRA PIN 176037 HP | KANGRA | HIMACHAL PRADESH | 176037 | L4 | Rejected-AOC Eligible | |
| 5 | L5₹1.1 Cr+₹25.9 L (31.4%)Rejected-AOC BLOCK C 14 GROUND FLOOR PLOT 618 624 BHIVANDIWALA TERRACE JAGANNATH SHANKARSHETH MARG DHOBI TALAO NEAR KALBADEVI POST OFFICE MUMBAI 400002 | MUMBAI | MAHARASHTRA | 400002 | L5 | Rejected-AOC Eligible |
Tender Value
Refer Docs
EMD Value
₹1.8 L
Closing Date
14 Oct 2021, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE AF NAGPUR
HQ CWE AF NAGPUR VAYUSENA NAGAR NAGPUR 440007
PROVISION OF RING MAIN SYSTEM FOR ELECTRICAL SUPPLY ALONG WITH UPGRADATION OF EXISTING INSTALLATION PHASE I AT AF STATION DEVLALI UNDER GE AF OJHAR
2021_MES_466989_2
80469
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE AF OJHAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE AF OJHAR
₹1.8 L
24 Nov 2021
22 Sept 2021
19 Oct 2021
23 Sept 2021
14 Oct 2021
30 Sept 2021
60 days
Amount
Supply, laying & testing cable HT XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty)with stranded aluminium conductor, 11000 volts grade, of size 3 core 120 sq mm complete all as specified and directed.
All as per item No 1 above but of size 3 core 95 sq mm
Supply & fixing Cable joining kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
All as per item No 3 above of size 120 sqmm.
Supply & fixing Cable joining kit for 11 KV grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm complete all as specified and directed.
All as per item No 5 above of size 120 sqmm to 185 sqmm
Supply, installation, testing and commissioning 11 KV, 630 Amps, outdoor type Compact switch gear Ring Main unit Main Copper Bus bar SF6 Insulation are inside SF6 Gas tank, Nominal operating gas pressure 1.4 Bar abs, Extensible type, having 02 Nos. Load Break Switches as incoming and 01 No Vacuum circuit breaker as outgoing, (2LBS + 1VCB) all Manual Operated modules with IP class as IP 54, for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foundation work as per manufacturer's instructions, along with bottom cable entry and front cable termination complete all as specified and as directed with following accessories. & specification RMU switchgear shall be capable of withstanding the specified currents without damage in accordance with the latest versions of IEC 60694 specified including metering modulecomplete all as specified and directed.
A (I) 630A manual Load Break Switch module mechanically / electrically interlocked for making of fault current along with Earth Switch of full making capacity - 2 Nos as incoming. (ii) Short time withstand current - 21KA/ 3 sec (iii) Making Capacity - 50 KA Peak at rated voltage (iv) Auxiliary contacts - 1NO + 1NC (v) Power frequency withstand voltage - 28kVrms (vi) Impulse withstand voltage - 75Kvpeak (vii) Front cover mechanism - IP2X (viii) Cable covers - 3X (ix) Snap action mechanism for manual operation (x) Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable (xi) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) (xii) Set of 03 Nos. Ring Core Metering CTs 40-80/1A as per feeder load, 2.5VA, Class 1.0 The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063
(B) (i) 630A manual VCB module for making & breaking of fault current along with Earth Switch of full making capacity -1 No Manual operated 630 A Vacuum circuit breaker having spring stored mechanism. (ii)Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. (iii) Short time breaking current - 21KA/ 3 sec (iv) Making Capacity - 50 KApeak at rated Voltage (v) Auxiliary contacts - 1NO + 1NC (vi) Power frequency withstand voltage to Earth between Poles & Across opening span - 28KVrms (vii) Impulse withstand voltage Phase to Phase & Phase to Earth - 75kVp (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Green(ON)/Red(OFF) push buttons to operate VCB LED indicator for on, off etc. (xi) 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault Provision of power pack of suitable specification. (xii) Mechanical ON/OFF/EARTH/Spring charge Indication (xiii) Cable boxes should be Arc Proof interlocked with respective Earthing Switches. (xiv) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063 Min no. of operations of Circuit breakers at rated current (as per IEC 62271- 100) shall be guaranteed with Mechanical Endurance – Class M1 (2000operations).
Stored energy mech. for manual operation - 01 Nos Set of 03nos. Ring Core Protection CTs of ratio 40-80A/1A as per feeder load, 2.5VA, 10P10 - 01 Set Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos • R-Y-B Phase Indication Set of Coupling bus bars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle - 01 Nos Potential transformer 11KV/R3/110/R3/Acc Class-1 50VA
NOTE (a) RMU Tank shall be IAC AFL 20kA/1s tested to ensure utmost operator safety .Test report (from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU tank shall be of 304 grade, Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (e) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (f) Bus bar to be copper material. (g) Insulation of bus bar to be epoxy or PVC Sleeved insulation to be provided. (h) The Quoted rates for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed. (j) Metering Module including power pack /battery with battery charging unit
Supply, installation, testing and commissioning 11 KV, 630 Amps, outdoor type Compact switch gear ring main unit Main Copper Bus bar SF6 Insulation are inside SF6 Gas tank, Nominal operating gas pressure 1.4 Bar abs, Extensible type, having 01No Load Break Switches at Incoming and 02 No Load Break Switches at Outgoing (1LBS + 2LBS) all Manual Operated modules with IP class as IP 54, for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foundation work as per manufacturer's instructions, along with bottom cable entry and front cable termination complete all as specified and as directed with following accessories. & specification RMU switchgear shall be capable of withstanding the specified currents without damage in accordance with the latest versions of IEC 60694 specified including metering module complete all as specified and directed.
(A) (I) 630A manual Load Break Switch module for making of fault current along with Earth Switch of full making capacity - 1 Nos. (ii) Short time withstand current - 21KA/ 3 sec (iii) Making Capacity - 50 KA Peak at rated voltage (iv) Auxiliary contacts - 1NO + 1NC (v) Power frequency withstand voltage - 28kVrms (vi) Impulse withstand voltage - 75Kvpeak (vii) Front cover mechanism - IP2X (viii) Cable covers - 3X (ix) Snap action mechanism for manual operation (x) Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable (xi) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) (xii) The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063
(B) (i) 630A manual Load Break Switch module for making & breaking of fault current along with Earth Switch of full making capacity -2 No (ii)Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. (iii) Short time breaking current - 21KA/ 3 sec (iv) Making Capacity - 50 KApeak at rated Voltage (v) Auxiliary contacts - 1NO + 1NC (vi) Power frequency withstand voltage to Earth between Poles & Across opening span - 28KVrms (vii) Impulse withstand voltage Phase to Phase & Phase to Earth - 75kVp (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Green(ON)/Red(OFF) push buttons to operate VCB. (xii) Mechanical ON/OFF/EARTH/Spring charge Indication (xiii) Cable boxes should be Arc Proof interlocked with respective Earthing Switches. (xiv) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063 Min no. of operations of Circuit breakers at rated current (as per IEC 62271- 100) shall be guaranteed with Mechanical Endurance – Class M1 (2000operations).
Stored energy mech. for manual operation - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos • R-Y-B Phase Indication Set of Coupling bus bars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle - 01 Nos Potential transformer 11KV/R3/110/R3/-Acc Class1 50VA.
NOTE (a) RMU Tank shall be IAC AFL 20kA/1s tested to ensure utmost operator safety .Test report (from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU tank shall be of 304 grade, Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (e) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (f) Bus bar to be copper material. (g) Insulation of bus bar to be epoxy or PVC Sleeved insulation to be provided. (h) The Quoted rates for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed. (j) Metering Module including power pack / battery with battery charging unit.
Supply, installation, testing and commissioning 11 KV, 630 Amps, outdoor type Compact switch gear ring main unit Main Copper Bus bar SF6 Insulation are inside SF6 Gas tank, Nominal operating gas pressure 1.4 Bar abs, Extensible type, having 02 No Load Break Switches at Incoming and 01 No Load Break Switches at Outgoing (2LBS + 1LBS) all Manual Operated module mechanically /electrically interlocked with IP class as IP 54, for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foundation work as per manufacturer's instructions, along with bottom cable entry and front cable termination complete all as specified and as directed with following accessories. & specification RMU switchgear shall be capable of withstanding the specified currents without damage in accordance with the latest versions of IEC 60694 specified including metering module complete. Location:
(A) (I) 630A manual Load Break Switch module for making of fault current along with Earth Switch of full making capacity - 2 Nos as incoming mechanically /electrically interlocked. (ii) Short time withstand current - 21KA/ 3 sec (iii) Making Capacity - 50 KA Peak at rated voltage (iv) Auxiliary contacts - 1NO + 1NC (v) Power frequency withstand voltage - 28kVrms (vi) Impulse withstand voltage - 75Kvpeak (vii) Front cover mechanism - IP2X (viii) Cable covers - 3X (ix) Snap action mechanism for manual operation (x) Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable (xi) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) (xii) The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063
(B) (i) 630A manual Load Break Switch module for making & breaking of fault current along with Earth Switch of full making capacity -1 No (ii)Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. (iii) Short time breaking current - 21KA/ 3 sec (iv) Making Capacity - 50 KApeak at rated Voltage (v) Auxiliary contacts - 1NO + 1NC (vi) Power frequency withstand voltage to Earth between Poles & Across opening span - 28KVrms (vii) Impulse withstand voltage Phase to Phase & Phase to Earth - 75kVp (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Green(ON)/Red(OFF) push buttons to operate VCB. (xii) Mechanical ON/OFF/EARTH/Spring charge Indication (xiii) Cable boxes should be Arc Proof interlocked with respective Earthing Switches. (xiv) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063 Min no. of operations of Circuit breakers at rated current (as per IEC 62271- 100) shall be guaranteed with Mechanical Endurance – Class M1 (2000operations).
Stored energy mech. for manual operation - 01 Nos Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos • R-Y-B Phase Indication Set of Coupling bus bars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle - 01 Nos Potential transformer 11KV/R3/110/R3/110/R3-Acc Class-1 50VA.
NOTE (a) RMU Tank shall be IAC AFL 20kA/1s tested to ensure utmost operator safety .Test report (from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU tank shall be of 304 grade, Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (e) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (f) Bus bar to be copper material. (g) Insulation of bus bar to be epoxy or PVC Sleeved insulation to be provided. (h) The Quoted rates for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed. (j) Metering Module including power pack / battery with battery charging unit.
Supply, installation, testing and commissioning 11 KV, 630 Amps, outdoor type Compact switch gear Ring Main unit Main Copper Bus bar SF6 Insulation are inside SF6 Gas tank, Nominal operating gas pressure 1.4 Bar abs, Extensible type, having 02 No Load Break Switches at Incoming and 03 No Vacuum Circuit Breaker at Outgoing (2LBS + 3 VCB) all Manual Operated module mechanically /electrically interlocked with IP class as IP 54, for outer door separately , inside the RMU there shall be an additional cable door with IP3X and Mimic of IP2X and necessary PCC foundation work as per manufacturer's instructions, along with bottom cable entry and front cable termination complete all as specified and as directed with following accessories. & specification RMU switchgear shall be capable of withstanding the specified currents without damage in accordance with the latest versions of IEC 60694 specified including metering module complete. Location:
(A) (I) 630A manual Load Break Switch module for making of fault current along with Earth Switch of full making capacity - 2 Nos as incoming mechanically /electrically interlocked. (ii) Short time withstand current - 21KA/ 3 sec (iii) Making Capacity - 50 KA Peak at rated voltage (iv) Auxiliary contacts - 1NO + 1NC (v) Power frequency withstand voltage - 28kVrms (vi) Impulse withstand voltage - 75Kvpeak (vii) Front cover mechanism - IP2X (viii) Cable covers - 3X (ix) Snap action mechanism for manual operation (x) Cable box for front termination of the cable suitable up to 3 core 300 Sqmm, 11 KV XLPE cable (xi) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) (xii) Set of 03 Nos. Ring Core Metering CTs 40-80/1A as per feeder load, 2.5VA, Class 1.0 The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063
(B) (i) 630A manual VCB module for making & breaking of fault current along with Earth Switch of full making capacity -3 No Manual operated 630 A Vacuum circuit breaker having spring stored mechanism. (ii)Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. (iii) Short time breaking current - 21KA/ 3 sec (iv) Making Capacity - 50 KApeak at rated Voltage (v) Auxiliary contacts - 1NO + 1NC (vi) Power frequency withstand voltage to Earth between Poles & Across opening span - 28KVrms (vii) Impulse withstand voltage Phase to Phase & Phase to Earth - 75kVp (viii) Front cover mechanism - IP2X (ix) Cable covers - 3X (x) Green(ON)/Red(OFF) push buttons to operate VCB. (xi) 3O/C + 1E/F self powered numerical protection relay with Low and High set for Over current and Earth Fault. (xii) Mechanical ON/OFF/EARTH/Spring charge Indication (xiii) Cable boxes should be Arc Proof interlocked with respective Earthing Switches. (xiv) Right angle non-touch proof Termination boots - 1 Set (R,Y,B) The degree of protection required against prevailing environmental conditions, including splashing water and dust, shall be not less than IP 54 as per IS12063 Min no. of operations of Circuit breakers at rated current (as per IEC 62271-100) shall be guaranteed with Mechanical Endurance – Class M1 (2000 operations).
Stored energy mech. for manual operation - 01 Nos Set of 03nos. Ring Core Protection CTs of ratio 40-80A/1A as per feeder load, 2.5VA, 10P10 - 01 Set Capacitive voltage indication fixed type VPIS 6-12 kV - 01 Nos • R-Y-B Phase Indication Set of Coupling bus bars along with suitable coupling kit.- 01 Nos Manometer- 01 Nos Operating handle - 01 Nos Potential transformer 11KV/R3/110/R3/110/R3-Acc Class-1 50VA.
NOTE (a) RMU Tank shall be IAC AFL 20kA/1s tested to ensure utmost operator safety .Test report (from an STL member Lab) shall be submitted along with drawings of the RMUs . In case the test report is not found suitable , the RMU shall stand liable to be rejected. (b) The Vacuum Bottle shall be of same make as that of RMU to ensure better life cycle optimization for the RMU. (c) Additional items like Operating handle etc. shall be delivered with the RMU (d) RMU tank shall be of 304 grade, Non-magnetic, Non-ferrite Stainless Steel. Inferior Grade of Steel shall not be acceptable. (e) RMU shall have site replaceable bushings for ease of trouble shooting at site and quick repair and restoration at site. (f) Bus bar to be copper material. (g) Insulation of bus bar to be epoxy or PVC Sleeved insulation to be provided. (h) The Quoted rates for RMU shall be inclusive of making Platform as per OEM instructions, made with bricks and necessary PCC at Bottom and Top and plastering complete all as directed. (j) Metering Module including power pack/ battery with battery charging unit.
M&L for earthing in repair including taking out GI plate with pipe and complete with galvanised steel earth plate electrode 600x600x6mm thick,burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level,connected to galvanised iron strip 32x6 mm as earth lead by means of bolts,nuts ,washer and check nut of galvanized steel, protected by and including GI pipe 50 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concret pit in 1:2:4 type B1 using 12.5mm graded aggregate, with cast iron mild steel frame embedded in the concrete enclouser fineshed flushed & CI cover 10 mm thick of size (300mmx300mm CI) having locking arrengment hinged to CI frame all as shown under electrical plate of SSR Pt - I 2009 and as directed including painting the external surface of chamber & cover with enamel paint in diffrent colour as directed and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20 mm bore GI pipe medium grade for watering adequate quantity of charcol and common salt in alternate layer of 15cm 3ft x 3ft thick all around the electrode including necessery excavation & earth work in any type of soil , rock /strata/ other if any, complete testing on completion all as specified and directed
Note:- i) Filling the pit with black cotton soil brought at site.from out of defence land. ii) The excavated soil will be removed iii) Earth resistance should be less than 4 ohm. iv)GI strip up to 7.5 RM with GI pipe 40mm dia is included in the quoted rate. (v) If resistance value is found more than 04 ohm, any time after execution upto end of defect liability period contractor has to do needful action within 07 days without any extra cost to bring the value less than 04 Ohm, failing which the cost of the earthing (as quoted by the contractor or prevaling in the market whichever is high will be recovered from the contractor.
Supply & fix earth continuty conductor or main earthing 32X6 mm dia galvanised iron strip. (roof conductor or down conductor ) above ground level fixed to wall/ roof duly insulated on batten or recessed or chases or burried in groung/ floor or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc as required all as specified and directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 sq mm 3½ core Complete all as specified and directed .
Supply, installation, testing and commissioning of highly energy efficient outdoor type oil immersed naturally cooled (ONAN) transformer Double copper wound type of capacity 400 KVA as per latest IS code conforming to IS - 1180, Level-II with off load tap changer on primary side to vary secondary voltage within limit (+)7.5% to (-) 7.5% in step to 2.5% incl standard fittings and first filling to transformer oil as per IS 335 of 1980 with cooling system. The transformer shall be provided with cable termination box to terminate outdoor type termination of suitable size on HT side 11 KV & LT side 1100 volts. Transformer step down ratio 11000 volts/ 433 volts, 3 phase 4 wire, impedance as per. Oil type, ONAN cooled suitable for outdoor installations and double wound core type with cold rolled grain oriented silicon shell insulated laminations and clamped to minimize vibrations and noise. The winding shall be copper and shall be designed for full load current and withstand the thermal and electro magnetic stresses arising due to the through fault current vector group shall be DYn 11 including supply of all standard fittings/fixtures and comprising of the followings all as specified and directed :-
(a) HT cable termination Box. (b) LT cable termination Box (c) Rating and diagram plate (d) Earthing terminals (e) Lifting lugs (f) Oil level indicator with minimum level marking. (g) Thermometer pocket (h) Conventional Conservator with oil filling hole with cap and drain cum sampling valve. (j) Air release plug (k) Silica Gel breather (l) Off circuit tap changer with locking provision (m) Bi-directional Rollers (n) Jacking Pads (o) Radiators/ Fins and all (Epoxy painted) (p) Danger Notice Board Make : Voltamp/Crompton Greaves/JK Transformers/ GEE Industries/ Indian Transformer Ltd (ITL) NOTE: Transformer provn against above Item will be installed on trolly catered in the Schedule at Item No.15
M&L for fabrication of towing type trolley suitable for 400 KVA transformer step down outdoor type 11KV/433 V capacity complete made up of MS "I" beam of 250x 125x 6.9mm (37.3 Kg/mtr) and MS sheet for platform 6mm thick (47.1 Kg/sqmtr), mounted on 04 wheels (7.50x16 size) with rims mounted on 02 Nos front and rear axle wheel with leaf spring clamps cushioning arrangement, between platform and 02 Nos front and rear axles, complete with towing arrangement with two hook to take full load of trolley and transformer approx 3.5 Ton along with jalli (XPM) around platform on angle iron frame of size 40x40x5 mm opening arrangement from both side with locking arrangement for loading and unloading of transformer including welding, bending and drilling holes, Spray painting with two coats of synthetic enamel paint over a coat of primer overall surface all as specified and directed by Engr-in-charge. (a) Size of the transformer trolley platform shall be 4 Mtr x 2.5 Mtr and sufficient space all around after transformer installation for ventilation/ maint purpose as recommended by OEM and accommodate HT/ LT connecting cables loops on the platform. (b) The trolley shall be provided with steel square net of suitable gauge fixed on angle iron in all around the trolley body with opening arrangement as protection. (c) Necessary space for provision for PVC insulated heavy duty HT/LT Aluminium Cable of suitable size with cable lugs to connect the earthing as cut to required length -50 mtrs
NOTE:- (i) Any other works not mentioned in item above but required for smooth functioning of trolley shall be deemed to be included in the rate quoted by the contractor. (ii) Drawing of trolley shall be approved by GE before fabrication in factory/workshop.
Excavation in trenches not exceeding 1.50 mtr wide and not exceeding 1.50 meter in depth for foundation and getting out in soft/loose soil complete all as specified and directed.
All as per item No 16 above but getting out in hard soil
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each, excavated soil in trenches after the pipes have been laid and tested complete all as specified and directed.
Removing excavated soil to a distance not exceeding 50 meter and depositing where directed at a level not exceeding 1.50 meter above the starting point complete all as specified and directed.
Material & labour for fixing of DWC pipes it should be flexible & should allow deformation in diameter as well as in joints under external load & soil natural movement , socket & spigot joint with elastometric sealing ring, it should be highly corrosive resistant & it should be impact resistant, chemical resistant, flexible, light weight & it should have hih flow capacity of 77/63 mm outer and inner dia complete with coupler, elbows, joints and necessary joints required for completion of work all as specified & as directed by the Enguneer-in-charge.
Material and labour for sand cushioning with fine dry unwashed sand in trenches for protection of cables complete all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover, class HV, Type 1, flat, size 300mm x 180mm x 40mm complete all as specified and directed
Supply, install, testing and commissioning of cubicle type outdoor LT distribution panel mounted on trolley fabricated out of 3.15mm thick CRCA sheet with separate locking arrangement, painted with epoxy powder coated over a coat of red oxide primer, factory made, cubicle type, double door hinged type, provided with 3mm thick bakelite / fiber sheet for mounting electrical accessories, holes for cable entries, detachable gland plates at bottom, earth connection terminals etc. and mounted on 40x40x5 mm angle iron frame, adequate clearance for the entry and exit of cables, provision of ventilation on sides, manufacturer details and provn of cable lugs for connection etc. complete and consisting of following:- (a) MCCB 630A 4 pole, 70 KA -01 Nos ( as main incomer) thermal magnetic release type (b) LED indication lamps 3 Phase (c) Aluminum bus bar suitable current capacity complete all as specified and directed.
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 240 sq mm 3½ core Complete all as specified and directed .
sapana enterprises
DURGAI ELECTRICALS
Electromech Engineers
AGRAWAL ASSOCIATES
NATIONAL ENGINEERING CORPORATION
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .