Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹36.0 L
EMD Value
₹72,003
Closing Date
5 Nov 2025, 11:00 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
PURCHASE OFFICER
TATA INSTITUTE OF FUNDAMENTAL RESEARCH ,HOMI BHABHA ROAD, NAVY NAGAR, COLABA, MUMBAI-400005
Data Center solutions comprising chilled water-based Precision cooling system, racks, etc. for High Performance Server racks of High Energy Physics in Room CG18
2025_DAE_882389_1
TIFR/PD/CA25-105/251235
Limited
Laboratory and scientific equipment
Supply
120 days
TATA INSTITUTE OF FUNDAMENTAL RESEARCH, HOMI BHABH
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹72,003
Yes
21 Oct 2025
21 Oct 2025
6 Nov 2025
21 Oct 2025
5 Nov 2025
21 Oct 2025
Supply of 40 kW Actual Sensible Capacity@ 37 Deg C return air , EWT / LWT 10 Deg C / 14 Deg C Vertiv /Rittal /Swegon Blue Box make chilled water based Precision air conditioning units (300 mm wide mandatory) with horizontal air flow pattern, can be placed in-between the racks or at the ends of rows, close to the heat source cooling by ‘close Loop Architecture’ method. Unit should have Galvanized sheet metal, externally epoxy powder coated, multiple EC radial type fan, condensate pump, Filter, Microprocessor Controller, individual display, Water Flow Switch, 3-way valve, Ethernet card, water flow alarm, heater, humidity & temperature sensors, etc. as per the specification.
Supply of 42U IT server rack having a dimension of 800x2000x1200mm (WxHxD) with an add on enclosure of 800x2000x300mm at front and back of the rack and compatible chilled water based closed loop cooling solutions. The rack should have 2 Nos. of vertical PDUs rated for 22 KW, 63Amps, 3 phase, 50Hz with MCB. The rack should strictly comply with the tender technical specification
Transportation, loading/unloading and incidental cost till consignee’s site
Incidental services of supply & installation of all the accessories like ducting, insulation, interconnected refrigerant pipe, drain pipe, Grills/Diffusers as per tender specification (including installation & commissioning, supervision, demonstration, and training) at the consignee’s site
Comprehensive Maintenance Contract after warranty period for First Year
Comprehensive Maintenance Contract after warranty period for Second Year
Comprehensive Maintenance Contract after warranty period for Third Year
Comprehensive Maintenance Contract after warranty period for Fourth Year
Comprehensive Maintenance Contract after warranty period for Fifth Year
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.04 MB
VFINAL.pdf
Tender Documents • 2.02 MB
BOQ_927444.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .