Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.4 LAccepted-AOC | L1 | Accepted-AOC L1 accepted | |
| 2 | L2₹5.7 L+₹32,434 (6.00%)Rejected-Finance C O OPPOSITE MH MANDA POONCH ROAD AKHNOOR 181201 J K | JAMMU | JAMMU AND KASHMIR | 181201 | L2 | Rejected-Finance Other than L1 after deducting Sch of Credit Rs 37162.00 | |
| 3 | L3₹6.1 L+₹72,710 (13.4%)Rejected-Finance | L3 | Rejected-Finance Other than L1 after deducting Sch of Credit Rs 37162.00 | |
| 4 | L4₹7.3 L+₹1.9 L (35.1%)Rejected-Finance | L4 | Rejected-Finance Other than L1 after deducting Sch of Credit Rs 37162.00 |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
4 Nov 2021, 6:00 pmClosed
GE North Akhnoor
GE North Akhnoor C/o 56 APO
SPECIAL REPAIR OF REWIRING OF BLDG NO P01 AND P34 IN MH UNDER GE NORTH AKHNOOR
2021_MES_480427_1
GE(N)/AKH-50/2021-22
Open Tender
Civil Works
Item Rate
180 days
Akhnoor
Class E cat b i
8 documents required · 8 mandatory
₹500
Yes
GE North Akhnoor
₹20,000
Yes
10 Dec 2021
7 Oct 2021
6 Nov 2021
7 Oct 2021
4 Nov 2021
22 Oct 2021
Amount
Taking down carefully aluminium/copper point wiring (light fan socket or power) without accessories complete and making good disturbed surfaces of walls, floor to match with existing specification complete all as specified and removing from site.
Material and labour for point wiring complete with 1.5 sqmm PVC insulated, FRLS type, ISI marked,conforming to IS-694/1990 unsheathed, multistranded, single core, copper conductor cable 1100 volts grade colour code cables drawn through PVC Conduit 20 mm dia medium grade including cutting, chasing work at any height and all accessories are concealed in walls / roofs / floors / ceiling etc. metal flush box with top,bottom,side/back wall knockout for conduit entry from any direction made out of 1.60mm thick suitable for fixing of modular top cover plate as per numbers of switch modules for modular switches,sockets,fan regulators,red colour indicator, blank plates etc as approved coloures including 1.5 Sqmm PVC insulated multistranded FRLS type unsheathed(Green colour),single core cable with copper conductor cable as earth continuity conductor and connecting to common earth dolly including making good the disturbed surfaces to match with existing surface and colour coat including providing putty and white cement for smooth finishing of existing surface complete all as specified and directed for the following:- (a) One light point/fan /bell point controlled by one switch. Make of Cables: Havells, L&T, Finolex, Anchor (Note:- All necessary accessories such as modular steel box,top cover plate, blank plate, screws,washers and all modular electrical fixtures are to be used of same make/brand only and shall be deemed in to included in quoted rate only.)
All as per item no 2 above but for One 5 pin 6 amps socket point controlled by one 6 amps switch on independent board .
All as per item no 2 above but for One 5 pin 6 amps socket point controlled by one 6 amps switch on same board .
Material and labour for point wiring complete with 2.5 sqmm PVC insulated, FRLS type, ISI marked,conforming to IS-694/1990 unsheathed, multistranded, single core, copper conductor cable 1100 volts grade colour code cables drawn through PVC Conduit 20 mm dia medium grade including cutting, chasing work at any height and all accessories are concealed in walls/roofs/floors / ceiling etc. metal flush box with top,bottom,side /back wall knockout for conduit entry from any direction made out of 1.60mm thick suitable for fixing of modular top cover plate as per numbers of switch modules for modular switches,sockets,fan regulators,red colour indicator, blank plates etc as approved coloures including 2.5 Sqmm PVC insulated multistranded FRLS type unsheathed(Green colour), single core cable with copper conductor cable as earth continuity conductor and connecting to common earth dolly including making good the disturbed surfaces to match with existing surface and colour coat including providing putty and white cement for smooth finishing of existing surface complete all as specified and directed for the following:- (a) One 15 amps power socket outlet point controlled by one 16 amps switch on independent board. Make of Cables Havells, L&T, Finolex, Anchor (Note:- All necessary accessories such as modular steel box,top cover plate, blank plate, screws,washers and all modular electrical fixtures are to be used of same make/brand only and shall be deemed in to included in quoted rate only.)
Supply & fixing modular type switch 6 Amps, single pole, 1way,1 module,240V, ISI Marked complete all as specified and directed. Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
Supply & fixing modular type switch 16 Amps, single pole,1 way,1 module, 240V, ISI Marked Complete all as specified and directed. Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
Supply & fixing modular type socket shuttered type 6 Amps- 2/3 Pin combined 2 module, 240V, AC ISI Marked Complete all as specified and directed. Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
Supply & fixing modular type socket 6 A/16 Amps -2/3 Pin combined shuttered socket 2 module 240V AC ISI Marked Complete all as specified and directed .Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
Supply & fix fan regulator modular type electronic, stepped type 100 Watts, 2 module 240Volts, AC ISI marked complete all as specified and directed. Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
Supply & fix ceiling rose, 3 terminal ,PVC/polycarbonate body ISI marked, complete all as specified and directed Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
Supply and fixing buzzer, ding dong AC, 230 volts single pole complete all as specified and directed. Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
S & F modular bell push 6A , 1 module, 240V, ISI Marked Complete all as specified and directed. Make ANCHOR (ROMA), HAVELLS (CRABTREE), LEGRAND
Supply and fixing VTPN verticle loadline double door distribution box (DB) are fitted with Bus bar neutral link, blanking plates of 4 way with suitable for incomming MCCB 'I/C' frame,having isolated neutral bar, mechanical impact strength IK09,door earthing suitable for MCCB upto 125 Amp Make - Legrand, Schiender, Havells etc.
Supply and fixing sheet metal enclosure double door type for DBs single pole and neutral 12 way 240 V with 200 Amp bus bar including blanking plates where required . Make : Legrand, Schiender, Havells etc.
Supply and fixing sheet metal enclosure double door type for DBs single pole and neutral 8 way 240 V with 200 Amp bus bar including blanking plates where required . Make : Legrand, Schiender, Havells etc.
Supply and fixing sheet metal enclosure double door type for DBs single pole and neutral 4 way 240 V with 200 Amp bus bar including blanking plates where required . Make : Legrand, Schiender, Havells etc.
Supply & fix MCB SP 6 to 32 Amps 10 KA,"C" series,AC,240 Volts,50Hz , ISI marked complete all as specified and directed (In accordance with IS/IEC 60898-1) 240 V/, 50 Hz, 10 kA Suitable) complete all as specified and directed. Make : Legrand, Schiender, Havells etc.
Supply & fix MCB SPN 63 Amps 10 KA,"C" series,AC,240Volts,50Hz, ISI marked complete all as specified and directed Make - Legrand, Schiender, Havells etc.
Supply and fix Single pole and netural enclosure with two pin and earth plug and socket with one single pole MCB of capacity 20 amp 240 volts and connecting electrically including taking down unserviceable MCB complete all as specified. Make : Legrand, Schiender, Havells etc.
M & L for of sub main wiring complete with 2 run of 6 sqmm single core copper conductor (ISI marked)cable 1100 volts grade,FRLS type, PVC insulated, unsheathed,flexible,multi stranded colour coded cables drawn through rigid PVC conduit of size 25 mm dia medium grade(MMS) with all connected accessories such as Bend,Tee,Elbow,Short peices etc concealed in wall/roofs/floors and including one run of 2.5 sqmm single core copper conductor cable flexible, PVC insulated, unsheathed, multistranded, 1100 volts grade,FRLS type as earth continuity conductor connected to common earth dolly including making good the disturbed surfaces to match with existing surface including taking down of old existing submain cable complete all as specified and directed. Note : - Two run of 6 sqmm single core copper conductor cable and one run of 2.5 sqmm single core copper conductor cable as earth continuity and one run of PVC conduit shall be measured as one unit. Make of Cable Havells, L&T, Finolex, Anchor
Material and labour for Earthing complete with galvanised steel earth plate electrode 600mm x 600mm x 6mm thick buried directely in ground vertically ( earth pit not less than 2.25 meters deep below ground level) with top edge of plate not less than 1.5 metres below ground level, connected to and including galvanised iron wire 4 mm dia and light grade protection pipe of 15 mm dia from earth electrode up to test point or up to 7.5mtr whichever is less by means of GI bolts, nuts, check nuts and washers all as per electrical plate No 3 of SSR Pt-I and GI watering pipe of 20 mm dia medium grade,GI funnel with wire mesh,including charcoal, salt packed all around the earth electrode plate in layers, PCC earth pit chamber 1:3:6 type C1, of size 45cm x 45cm x 45 cm,RCC cover 1:2:4 type B1 of size 45x45x6 cm, excavation/earth work in any strata and returning filling, removal of surplus soil and testing/test point for required value including removing old item complete all as specified and directed. Note:- The required resistance of Earthing shall be less than 3 ohm, If not found to the required resisstance, the contractor has to re earthing for required resistance and the cost for the same included in the quoted rate and no extra shall be paid on failure of getting required resistance.
S& F in replacement of Energy saving 10 Watt LED Bulk head luminaries, 230V, 50Hz with oval shape, surface mounted, comprising high brightness LEDs complete all as specifed and directed. Make- Havells, Cat part No RUGBYNEONFT10WLED760SSYMBOPC or its equivalent in Bajaj, Philips, Crompton Greaves etc.
Taking down UNSV flourescent fitting and M & L for LED batten Regal suitable for T8 LED tube incl T8 LED tube crystal glass with very high efficacy suitable for installation in existing T8 fitting with G13 lamp 20 watt 4 ft long all as specified and directed. Make : Havells Part No for batten- REGALBATTENT8UPTO1X22W DSBSWH, Cat Part No- LED Tube T8 : CRYSTAL1213T8DSTL18WLED865SGLASS or equivalent in CG, Philips, Bajaj . Note :- Rate quoted shall include the cost of both batten and Tube rod T8 and shall match with the batten .
Supply and fixing ceiling fans complete with blades. Down rods, electronic regulator and accessories, 230 volt, 1200mm sweep, min air delievery 210 CFM with service value 6 BEE five star rated with brushless direct current motor (BLDC) incl taking down existing and deposit with MES all as specified and directed. Make- HAVELLS/BAJAJ/ORIENT
Taking down old unserviceable Exhaust fan of any type/size from existing location and deposit in MES store yard and Supply and fix exhaust fan single phase metal body, AC 230 Volt, 50 Hz of size 300mm sweep with louvers shouter complete with all accessories including connecting up from ceiling rose to motor all as specified and directed. Make- HAVELLS/BAJAJ/ORIENT
Material & Labour for surface & wall mounted LED tube light fitting 10 W, 2 feet long extruded PVC housing provided for efficient heat dissipation to polycarbonate diffuser & integrated electronic driver with all accessories internally prewired and including connecting up with twin core twisted flexible copper conductor cable of suitable size complete all as specified and directed. Make- Havells cat part No ENDURALINEARNEOBS10W LED865SPCWH OR equivalent in Philips/ Crompton/ Bajaj/ Wipro/Syska LED/GE lighting/Surya.
S & F in replacement of 20 Watt LED energy saving light fitting environment friendly long life LED street light made up of pressure die cast aluminium housing with acrylic cover as diffuser with IP 66 protection and impact resistance of IK 07 with GI bracket made of light grade GI pipe 40 mm dia of 1.2 mtr long bend to shape with 02 Nos of FI clamp 32 x 4mm with suitable size nuts, bolts, washers etc. and making the connection from ceiling rose to fitting with suitable size twin core copper conductor cable complete all as specified and directed. (Make- Havells, cat part No ENDURACITYLITEPLATSL20WLED757SASYBOPC or Bajaj/Philips/Crompton Greaves or its equivalent).
Supply and fixing 20 watt LED batten with battery/inverter capacity having charging time 8 hour , driver efficiency > 85%, power factor > 95% and operating voltage 270 volt Make Halonix or equivalent in make Phillips, Bajaj
Supply and fixing in replacement slim surface mounted square LED panel aluminium die cast body with premium diffuser to ensure glare free and even distribution of light square type 12 watt LED 6000K all as specified and directed. Make Halonix or equivalent in make Phillips, Bajaj, Havells
Supply, laying and testing XLPE insulated, electric cable (heavy duty) with stranded aluminium conductor, 1100 volts grade, heavy duty cable, cross-sectional area 25 Sqmm 3.5 core connected with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanised steel wire or tape and overall PVC sheathed, laid in trenches or passing through pipes including taking down old existing unserviceable cable complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately) Make POLYCAB, GLOSTER, GRANDLAY
M&L for 40mm bore Tubes, 'light grade', galvanised, for cable protection fixed on poles or laid in trenches under floor, ducts etc with fixing clamps, nuts, bolts etc complete all as specified and directed.
Excavation in trenches not exc. 1.5m wide and not exc. 1.5m deep in soft/loose soil for laying of underground cable, foundation of poles & stays etc., and getting out, complete all as specified & directed.
Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25cm, complete all as specifed & directed.
Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point, complete all as specified & directed.
Brick well burnt locally available sub class 'B' laid over sand cushioning for mechanical cable protection in trenches with width of brick perpendicular to the length of cable, complete all as specified & directed by Engineer-in-Charge.
Sand cushioning to under ground cable, laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete punned to 18cm, complete all as specified and directed. Note:- Punned thickness of sand will be measured and paid.
Usha Engineering Co.
D P ASSOCIATES
M/s Rajesh Kumar Contractor
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .