Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹64,464Accepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹80,445+₹15,981 (24.8%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹82,035+₹17,571 (27.3%)Rejected-AOC | L3 | Rejected-AOC L3 |
Tender Value
₹93,903
EMD Value
₹1,878
Closing Date
25 Jan 2023, 9:30 amClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer
EE,EandM, Division, APWD, Prothrapur, Port Blair
Construction of E Corner and CAAQMS Server Room at Science and Technology at Dollygunj under CD I APWD Port Blair SW Providing IEI
2023_APWD_8910_1
DB-WO/EandM/DIV/PP/22-23/118 2nd Call
Open Tender
Electrical Works
Item Rate
15 days
South Andaman
Please refer Tender documents.
5 documents required · 5 mandatory
₹0
₹1,878
11 Feb 2023
16 Jan 2023
25 Jan 2023
16 Jan 2023
25 Jan 2023
20 Jan 2023
17 Jan 2023 - 19 Jan 2023
Amount
1. WIRING Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. a) Group-C
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit along with 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ sub main wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. a) 2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
b) 4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. a) 20 mm
Providing and fixing of 3 mm thick hylam sheet cover of size 23cm x 33 cm on the existing metal box or its equivalent etc., as required
Providing and fixing of 4 inches PVC Round Plate on the existing Junction box or its equivalent etc., as required
Supplying and Fixing of 12 Module, surface plastic box along with modular base and cover plate for modular switches on surface / hylam sheet or its equivalent etc., as required
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. a) 5/6 A switch
b) 3 pin 5/6 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and Fixing of Modular AC Box 20A Modular SP Mini MCB with plastic enclosure and plug top on surface, including connection etc., as required (Make: Anchor, Model: Uno, Code : 98488 or its equivalent etc., as required
2. MCB & DB's Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 4 way (4 + 12), Double Door
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) a) 6 way , Double Door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) Single Pole
Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) 40 Amps
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. a) 40 Amps
3. Fitting and Fixtures Supplying and fixing of surface mounted 2' x 2 backlit LED Panel 36W Complete with all accessories similar to C&S Cat No.LTCSP36WLED2X2 or its equivalent including connection etc., as required
Supplying and fixing of Wall Fan 400 mm Sweep complete with all accessories similar to Havells, Model No: Swing or its equivalent including connection etc., as required
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required.
Supplying and fixing PVC batten/ angle holder including connections etc. as required.
Supplying of 9W LED Lamp directly fitted in the Batten Holder similar to Crompton Cat No. LED 9W-B22/E27-CDL/WW or its equivalent etc., as required
4. Earthing Providing earthing with safe earthing electrode of galvanization 80 to 100 microns, length 2000mm, outer dia 50 mm, inner dia 19 mm and inner space be filled with crystalline conductive mixture including filling -up with electrolite (Back fill compound) as required for safe earth electrode and providing masonary enclosure with cover plate having locking arrangement etc. as required. (Ashlok)
Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15 mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
DAYAL HALDER
M/s Sai Electrical Works
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .