Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.8 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED BEING LOWEST AND REASONABLE. | |
| 2 | L2₹19.3 L+₹20,644.66 (1.08%)Rejected-Finance FLAT NO 93 POCKET 03 SECTOR 11 DWARKA NEW DELHI 110 075 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110075 | L2 | Rejected-Finance Not the lowest bidder | |
| 3 | L3₹25.5 L+₹6.4 L (33.3%)Rejected-Finance A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L3 | Rejected-Finance Not the lowest bidder | |
| 4 | L4₹30.2 L+₹11.1 L (58.0%)Rejected-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L4 | Rejected-Finance Not the lowest bidder | |
| 5 | Rejected-Technical 3788 SHAH GANJ GB ROAD NEW DELHI 110006 | NORTH | DELHI | 110006 | - | Rejected-Technical Present residual work in hand is more than 5 times |
| Sl No | Description | Qty | Unit | Ridhi engineers and builders L3 | OM ASSOCIATES L1 | M/S ADHIKARI CONSTRUCTION CO. L4 | M/S PRADEEP ENTERPRISES L2 |
|---|---|---|---|---|---|---|---|
| 1.00 | M&L for rewinding of HT/LT coils of transformer of capacity 25 KVA to 500 KVA, (11KV/433V) with super enamelled copper winding wire of existing gauge and existing number of turns alongwith insulating material i.e leatheroid, paper insulation, cotton tapes, empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , heating/drying etc including replacement of top cover gasket made out of sheet 4 mm thick including leak proofing by shalak solution complete all as specified and directed.
Note :- (i) Transformer rewinding will be done at workshop of approved manufacturer available in CE zone list .
(ii) Transformer will be inspected by 'Rep of HQ CWE(AF) TKD before and after repair. (iii) During taking down/repair of u/s transformer, contractor shall arrange the transformer of the same rating in place of existing one so that power supply is constantly supplied to the user and for that no extra cost will be paid to the contractor. | 660 | KG | 750 ₹4,95,000 | 500 ₹3,30,000 | 899 ₹5,93,340 | 220 ₹1,45,200 Lowest |
| 2.00 | Taking down/dismantling from foundation base and refixing back to the site after repair of any capacity of transformer by using suitable crane complete and including tranportation shifting to approved manufacturer/Workshop including testing and commissioning all as directed.
Note- Dismantling and fixing after rewinding and Transportation from 54 ASP to Workshop and workshop to 54 ASP will be paid as one job) | 3 | Each Job | 9,000 ₹27,000 | 3,000 ₹9,000 Lowest | 9,999 ₹29,997 | 3,500 ₹10,500 |
| 3.00 | Dehydration/filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 40 KV at 2.5 mm gap as per IS-355 in existing position by means of suitable dehydrating mechanism of transformer of any capacity and transformer oil for topping up at various sub station complete all specified and as directed.
Note: Transformer oil for TOP UP shall be measured and paid separately under respective item of this schedule. | 4,502 | Litre | 15 ₹67,530 | 10 ₹45,020 | 9.99 ₹44,974.98 Lowest | 28 ₹1,26,056 |
| 4.00 | Supply only transformer oil of approved quality (Dielectric strength not less than 50 KV) ISI marked for filling in transformer for topping up all as directed .
Make - HP, Servo, Savita
. Note- The transformer oil will be brought at site in sealed container at the time of filling/Top up. | 500 | Litre | 145 ₹72,500 | 130 ₹65,000 Lowest | 199 ₹99,500 | 200 ₹1,00,000 |
| 5.00M&L for painting of transformer with MES approved colour scheme after cleaning the body surface of transformer after preparation of old painted surface by rubbing with emery Paper to remove oil stains, dust etc and applying one coat of synthetic enamel paint by spray paint incl writing SM No/MES No , capacity of transformers of following capacity all as directed. Note- The contractor has to arrange their own local generator for supply to the spray painting machine. Make-Berger, Asian Paints, nerolac | |||||||
| 5.01 | 25 KVA to 100 KVA | 2 | Each | 2,500 ₹5,000 | 1,000 ₹2,000 | 999 ₹1,998 Lowest | 999 ₹1,998 Lowest |
| 5.02 | 150 KVA to 300 KVA | 1 | Each | 3,500 ₹3,500 | 1,200 ₹1,200 | 999 ₹999 Lowest | 999 ₹999 Lowest |
| 5.03 | 320 KVA to 400 KVA | 3 | Each | 3,500 ₹10,500 | 1,300 ₹3,900 | 999 ₹2,997 Lowest | 999 ₹2,997 Lowest |
| 5.04 | 500 KVA | 1 | Each | 4,500 ₹4,500 | 2,000 ₹2,000 | 999 ₹999 Lowest | 999 ₹999 Lowest |
| 6.00 | M&L for replacement of HT 11 KV 3 phase outdoor type single throw, single break off load gang operated insulator air break switch 200 A capacity with 9 insulators for horizontal mounting with fixed and moving contact complete with operating rod of suitable length and size, locking arrangement etc including taking down of unserviceable ones all as specified and directed.
Make :- Jaipuria,Rashtriya,power grid,MG materials BHEL, Pactil, Atlas | 6 | Each | 7,500 ₹45,000 | 7,000 ₹42,000 | 4,999 ₹29,994 Lowest | 12,000 ₹72,000 |
Tender Value
₹39.9 L
EMD Value
₹79,740
Closing Date
11 Dec 2025, 6:00 pmClosed
CWE (AF) Tughlakabad
HQ CWE AF TUGHLAKABAD AF STATION, TUGHLAKABAD PO SANGAM VIHAR NEWDELHI-110080
REPAIR MAINT OF HT ELECTRIC SUPPLY NETWORK SYSTEM REPLACEMENT OF UNSERVICEABLE HT UG CABLES MAINTENANCE AND UPKEEP OF HT CONTROL GEARS,VCBs RMUs TRANSFORMERS ACBs HT JOINTS AND FAULT FINDING HT PANELS AND MISC CONNECTED ITMES
2025_MES_741200_1
CWE/TKD/GUR/TOKEN-46 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (AF) Gurgaon No 1
Please refer Tender documents.
7 documents required · 7 mandatory
₹0
₹79,740
20 Feb 2026
24 Nov 2025
13 Dec 2025
24 Nov 2025
11 Dec 2025
4 Dec 2025
Amount
M&L for rewinding of HT/LT coils of transformer of capacity 25 KVA to 500 KVA, (11KV/433V) with super enamelled copper winding wire of existing gauge and existing number of turns alongwith insulating material i.e leatheroid, paper insulation, cotton tapes, empire tapes, wooden block packings, PVC sleeves, soldering and varnishing with insulating varnish , heating/drying etc including replacement of top cover gasket made out of sheet 4 mm thick including leak proofing by shalak solution complete all as specified and directed. Note :- (i) Transformer rewinding will be done at workshop of approved manufacturer available in CE zone list . (ii) Transformer will be inspected by 'Rep of HQ CWE(AF) TKD before and after repair. (iii) During taking down/repair of u/s transformer, contractor shall arrange the transformer of the same rating in place of existing one so that power supply is constantly supplied to the user and for that no extra cost will be paid to the contractor.
Taking down/dismantling from foundation base and refixing back to the site after repair of any capacity of transformer by using suitable crane complete and including tranportation shifting to approved manufacturer/Workshop including testing and commissioning all as directed. Note- Dismantling and fixing after rewinding and Transportation from 54 ASP to Workshop and workshop to 54 ASP will be paid as one job)
Dehydration/filtration of transformer oil by means of centrifugal filtration plant to achieve the specified dielectric strength of 40 KV at 2.5 mm gap as per IS-355 in existing position by means of suitable dehydrating mechanism of transformer of any capacity and transformer oil for topping up at various sub station complete all specified and as directed. Note: Transformer oil for TOP UP shall be measured and paid separately under respective item of this schedule.
Supply only transformer oil of approved quality (Dielectric strength not less than 50 KV) ISI marked for filling in transformer for topping up all as directed . Make - HP, Servo, Savita . Note- The transformer oil will be brought at site in sealed container at the time of filling/Top up.
M&L for painting of transformer with MES approved colour scheme after cleaning the body surface of transformer after preparation of old painted surface by rubbing with emery Paper to remove oil stains, dust etc and applying one coat of synthetic enamel paint by spray paint incl writing SM No/MES No , capacity of transformers of following capacity all as directed. Note- The contractor has to arrange their own local generator for supply to the spray painting machine. Make-Berger, Asian Paints, nerolac
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
M&L for replacement of HT 11 KV 3 phase outdoor type single throw, single break off load gang operated insulator air break switch 200 A capacity with 9 insulators for horizontal mounting with fixed and moving contact complete with operating rod of suitable length and size, locking arrangement etc including taking down of unserviceable ones all as specified and directed. Make :- Jaipuria,Rashtriya,power grid,MG materials BHEL, Pactil, Atlas
M&L in replacement horn gap fuse 11 KV 200 Amps horizontal/vertical type for outdoor fuse including all connected accessories complete all as specified and directed.
Dismantling and taking down old unsv LA and Supply, install, test and commission lightening arrestor suitable for HT 11 KV expulsion type 65 KA 11 KV rating complete all as specified directed. Make: Jaipuria/ Rashtriya/Pactil
Dismantling and taking down old rusted cross arms and M&L cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts and wasters,welding, bending cold or hot, drilling holes for bolts in any shape or size as indicated or directed and inclusive of one primer coat of red oxide primer and two coats of aluminum paint complete all as specified and directed.
Replacement of breather assembly of approved make filled with silica gel sealed packing of silica get to brougt at site for fixing of breather assembled at site suitable for transformers of following capacity - Make :- ITL , microdial or equivalent
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
Supply and replacement of silica gel suitable for transformers breather and protect VCBs, RMUs from moisture at 11 KV sub stations complete as per site requirement all as specified and directed by Engr-in-Charge .
Replacement of brass spindle for terminal on HT side threaded complete with nut, washers etc of suitable dia for transformers of following capaicty :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
All as per item No 12 here-in-before but for LT side of transformers of following capacity :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
Replacement of ceramic bushing and Gasket on LT side of transformers of following capacities. Make : Mysore Potteries/BHEL
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
All as per item No 14 above, but on HT side of transformer of following capacites :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
Replacement of arc horn surge arrester complete with mounting ring, nut bolt etc complete of approved make suitable for transformers of following capacity :-
25 KVA to 100 KVA
150 KVA to 300 KVA
320 KVA to 400 KVA
M&L boring of hole for laying of cable by trenchless technology under the road, path, culvert etc including HDPE/PPR pipe 150 mm bore as a cover to protect cable . Note: Contractor will liaison with civil authority at his own cost for seeking permission if required )
Taking down U/S cable 95 sqmm/120 sqmm 3 core cable from trenches complete all as specified and directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts(earthed) , grade cross sectional area 95 sqmm 3 core for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Supply, laying, jointing and testing in replacement of HT XLPE insulated ,screened,PVC bedded galvanised steel strip or wire armoured ,electric power cables(heavy duty) with aluminium conductor,11000 volts(earthed) , grade cross sectional area 120 sqmm 3 core for working voltage upto 11000 Volts, including cable lugs for providing connections as in repair complete all as specified and as directed.
Excavation in trenches n.exc 1.5 mtr wide and n. exc 1.5 mtr in depth and getting out in soft/ loose for laying cables, erection of poles complete all as specified and as directed.
Returning, filling in including spreading, levelling, watering and well ramming in layers not exc 25 cm in soft/loose soil complete all as specified and as directed.
Removing surplus excavated soil nexc 50 mtr and depositing where directed at a level n-exc 1.5 mtr above the starting point complete all as specified and as directed.
M&L for Sand cushioning/sand covering including well ramming for underground cable protection complete all as specified and as directed .
Supply and laying un-reinforced precast concrete cable cover, class HV,type 1,flat ,size 300 mm X 180mm X 40 mm of approved make complete all as specified and as directed.
S & F in replacement of cable route indicator for HT UG Cable of 11000 Volts 80 mm dia CI Plate marked on HT cable bolted with 40 x 5 mm flat iron member of height 0.9 mtr, embedded in PCC 1 : 3 : 6 type C2 of size 20 x 20 x 30 cm block complete all as specified and directed.
M&L in replacement for GI pipe light grade of size 80mm dia.for laying in trenches/ under floor/on walls for protection of UG cables complete all as specified and directed .
Taking out the HT 11 KV metalclad Vaccum circuit breaker of capacity 630A/1250 A, 11000 volts,3 ph, 50 Hz, any capacity, any make and any type from the cubical panel, for repairs/overhauling and servicing including replacement of wornout parts comprising the following works. (a) Removing the complete fixed contacts, moving contacts, cleaninig the contacts, removing the fittings and fixing back to the breakers after adjusting the pressure. (b) Checking charging motor, motor relay, anti pump relay of the breaker, lubricate and align properly for smooth and perfect operation. (c) Check and service the operating mechanism closing mechanism, and tripping mechanism including spring pressure, position etc.The labour charges are deemed to be included in the quoted unit rate for this item. Note : (i) Servicing shall be performed by authorised service personnel of OEM i.e M/s CG/ABB/Schneider,Siemens (ii) Servicing certficate shall be provided to engineer-in-charge. (iii) Replacement of minor spares like Push button lever, Green push button, red push buttons and shaft for operating handles etc. are inclusive of rate quoted by tenderer. (iv) Measurment of resistance value, tools , labour, petroleum jelly are incl in this quoted rates. (v) Part will be replaced under relevent items Note:- New parts shall be measured paid seperately except heater of VCB under relevant items of this schedule. This item includes heater of VCB. Make - CG/ABB/Schneider, Siemens
M & L for Calibration of VCBs relay by injecting high voltage through CTs checking the over load system of VCB upto 90% rated load and artificial fault creation and setting of relay by 10 to 15% of rated load removing unseviceable overload and earth fault relay including connections with power pack, opening out the trolley, checking the operation of VCB mechanically and electrically through shunt trip coil includng energizing of automatically, checking of TNC switch including testing and commissioning complete all as specified and directed by Engr-in-charge. Note :- Calibration to be carried out by authorised person and test certificate shall be furnished Make - CG/ABB/Schneider, Siemens
S & F in replacement of shunt closing release coil 24 V /110 V DC /AC suitable for 12 kV 1250 A 31.5 kA suitable model for CG/ABB/Schneider/Seimens breaker complete all as specified and directed.
S & F in replacement of unserviceable strip heaters 80 watt from HT panel of 11 KV substations complete as specified and directed by Engr-in-Charge.
S & F in replacement of Geared motor (EL) 220-250 V AC/DC suitable for 12 kV 1250 A 31.5 kA suitable model for breaker complete all as specified and directed Make :- CG/ABB/Schneider/Seimens
S & F in replacement of unserviceable limit switch for spring charging motor for suitable model of HT panel of 11 KV substations complete as per direction of Engr-in-Charge. Make :- CG/ABB/Schneider/Seimens
S & F in replacement of tripping coil 24/110 V DC Suitable for 12 kV 1250 A 31.5 kA suitable model for breaker complete all as specified and directed. Make :- CG/ABB/Schneider/Seimens
S & F in replacement of racking mechanism to restrict unecessary blocking of trolley arrangement suitable model for breaker complete all as specified and directed. Make :- CG/ABB/Schneider/Seimens
S & F in replacement of unserviceable housing of pole assembly for suitable model breaker from HT panel of 11 KV substations complete as per direction of Engr-in-Charge. Make :- CG/ABB/Schneider/Seimens
S & F in replacement of combined over current and earth fault relay REJ601/7SR1205 including fixing in HT panels at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. Make CG/ABB/Schneider /Seimens
S & F in replacement of Master tripping relay of auxillery voltage 24 V/110V AC/DC of Make CG/ABB/Schneider//Seimens incl fixing in HT panels at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge.
S & F in replacement of auxiliary contact suitable including fixing in HT panels at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. for Make CG/ABB/Schneider//Seimens
S & F in replacement of tulip contact/shawer contact 08/12 fingers of suitable model for circuit breaker complete all as specified and directed Make CG/ABB/Schneider
S & F in replacement of busbar insulator of including fixing in HT panels at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. Make CG/ABB/Schneider//Seimens
S & F in replacement of unsv thermostat from HT panel of 11 KV substations complete as specified and directed by Engr-in-Charge.
S & F in replacement of unsv spout contact of VCB panel for suitable model from HT panel CG/ABB/Schneider/Seimens of 11 KV substations complete as per direction of Engr-in-Charge.
S & F in replacement of Pole assembly (Vacuum interrupter Bottle assembly) with case complete for breaker of suitable for existing model for fixing in substation complete all as specified and directed. Make :- CG/ABB/Schneider/Seimens
S & F in replacement of Vacuum interrupter pulling rod suitable for suitable breaker for existing model complete all as specified and directed. Make :- CG/ABB/Schneider/Seimens
S & F in replacement of unsv spout of VCB panel for suitable model from HT panel of 11 KV substations complete as per direction of Engr-in-Charge. Make :- CG/ABB/Schneider/Seimens
S&F in replacement of Current transformer of rating 500-250/5A size and model as suitable as existing CTs installed at 11 KV Sub Stations of complete all as specified and directed. Make CG/ABB/Schneider/Siemens/Schneider.
S&F in replacement of Current transformer of rating 200-100/5A size and model as suitable as existing CTs installed at 11 KV Sub Stations of complete all as specified and directed. Make CG/ABB/Schneider/Siemens/Schneider
S&F in replacement of potential transformer of rating 11000/110V size and model as suitable as existing PTs installed at 11 KV Sub Stns of complete all as specified and directed. Make CG/ABB/Schneider/Siemens/Schneider
S & F in replacement of TNC switch for VCBs at different 11 KV substations complete all as per direction by Engr-In-Charge.
S & F in replacement PT fuse of capacity 11KV suitable to fit on exisitng PTs in 11 KV incomer VCBs complete all as per direction by Engr-In-Charge. .
S & F in replacement of Digital type voltmeter to measure AC voltage 0 to 500 Volts with 1.0 accuracy class, stranded voltage burden 0.25 VA MAX/Phase working on AC auxillary supply voltage 230 volts, flush mounted type of size 96mm x 96mm x 75mm suitable for VCBs complete all as specified and directed. Make :- CG/ABB/Schneider/Seimens
S & F in replacement of Digital type ammeter with 1.0 accuracy class (+)1% of full scale 1 count 0 to 300 Amps, stranded voltage burden 0.25 VA MAX/Phase working on AC auxillary supply voltage 230 volts, Sencing CT 5 Amps flush mounted type of size 96mm x 96mm x 75mm suitable for ABB/Schneider/Seimens VCBs complete all as specified and directed.
S & F in replacement door lock suitable for existing complete all as specified and directed. Make :- VCBs ABB/Schneider/Seimens
S & F in replacement PVC unsheathed multi stranded copper cable (FR-LSH) 1.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs,nuts and bolts in VCBs complete all as specified and directed.
S & F in replacement PVC unsheathed multi stranded copper cable (FR-LSH) 2.5 Sqmm nominal cross sectional area 1100 volts conforming to IS 694 including electrical connection suitable size of lugs,nuts and bolts in VCBs complete all as specified and directed.
Taking down of HT RMU after disconnecting HT supply and reinstalled the same after repairing, servicing and testing of HT RMU and breakers, removing moisture and dust from HT bus bar and from inside of RMU panel of 11 KV substations complete all as specified and directed. Note- (i) The Job shall be carried out through OEM only. (ii) Mesurement of (IR) resistance value tools, labour, petroleum jelly are included in this quoted rates. (iii) Parts will be replaced under relevent items.
S & F in replacement of combined over current and earth fault relay of existing make incl fixing in RMU at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. Make :- ABB/Schneider/Seimens
S & F in replacement of pressure guage of RMU complete of including fixing in HT panels at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. Make :- ABB/Schneider/Seimens
S & F in replacement of indicator with electric wiring complete of including fixing in RMU at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. Make :- ABB/Schneider/Seimens
S & F in replacement of cable boot of including fixing in RMU at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. Make :- ABB/Schneider/Seimens
S & F in replacement of bushing with O ring of including fixing in RMU at 11 KV sub stations with connections complete as per diagram from OEM all as specified and directed by Engr in Charge. Make :- ABB/Schneider/Seimens
Supply and filling SF6 gas upto required level by using gas filling adopter including testing after completion complete all as specified and as directed. Note:- Necassary filling kit shall be provided by contractor and quoted rates are deemed to be included for the same.
S & F in replacement of RMU Mechanism suitable for existing model fo RMU complete all as specified and directed. Make :- ABB/Schneider/Seimens
S & F in replacement push button red/green including fixing in RMU at 11 KV sub stations with connections complete all as specified and directed by Engr in Charge. Make :- ABB/Schneider/Seimens
S & F in replacement of tripping coil 24 V DC suitable for existing RMU complete all as specified and directed. Make :- ABB/Schneider/Seimens
S&F in replacement of Current transformer of rating 400-200/1A size and model as suitable as existing RMU complete all as specified and directed. Make :- ABB/Schneider/Seimens
Supply only Contactor RT - 24VDC, suitable for RMU 11 KV, complete all as specified and directed. Make: CG/ABB/Schneider Ltd, Cat No.-NHSN710013P11, Equivalent model of Crompton, Siemens.
Supply only Operating handle Standard, suitable for RMU 11 KV, complete all as specified and directed. Make: CG/ABB/Schneider Ltd, Cat No.-1VDP000443R1, Equivalent model of Crompton, Siemens.
M&L for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 50-95 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as directed by Engr-in-charge .Make: Denson/ MS Seal/ M Seal
M&L for cable end termination jointing kit HT 11 KV grade earthed system (heat shrinkable) outdoor type complete with jointing material suitable for HT XLPE cable 120-185 sqmm 3 core 11 KV grade earthed system incl taking down old unsv HT joint complete all as directed by Engr-in-charge .Make: Denson/ MS Seal/ M Seal
M & L for straight through joint heat shrinkable 11 KV earthed system suitable for XLPE cable of size 3 core 50-95 Sqmm incl taking down old unsv HT joint complete all as directed by Engr-in-charge . Make: Denson/ MS Seal/ M Seal
M & L for straight through joint heat shrinkable 11 KV earthed system suitable for XLPE cable of size 3 core 120-185 Sqmm incl taking down old unsv HT joint complete all as directed by Engr-in-charge Make :- Denson/ MS Seal/ M Seal
Note for item No. 70 to 73 : (i) Cost of necessary excavation and earth work (by hydra machine or manual which suits), labour, Jointing kit complete, fixing charges & T&P including removing of grass/shrubs nearby the fault location shall be deemed to include in quoted rate . (ii) This item also includes charges for exacavation in concrete/pitched road (by hydra) in case fault occurs in the cable below not exceeding 5 metre of depth under the road. Make 3M, Denson, M-seal
Locating of fault in existing HT 11 KV 3 core 95/120 sqmm XLPE 11 KV(E) under ground cable by means of hiring fault locating machine mounted on 4 wheeler vehicle to locate fault in Defence/Civil area approximately 1.0 to 5.0 KM range by deploying skilled supervisior and labour for the purpose complete with all T&P & labour to find fault as per direction of Engr-in-charge. Note-(1) The area of this contract is very critical for safety reason so as to contractor has to arrange 24X7 hours fault locating machine and jointing kit when fault occurs and when denied or delayed beyond 12 hours of occurance of fault/ in time requirement by the contractor, double of quoted rate as panelty will be imposed .
Dismantling and taking down old unsv Steel tublar HT pole and Supply, transportation upto site of work and erection of Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-55 (11.0 metres long) and including marking alternate 05 Nos white and sky blue 30cm height with two coats of synthetic enamel paint incl numbering on poles all as specified. (Note :-Excavation and earth work and PCC for foundation, channel, clamps nuts, bolts to be measured and paid separately). Make NTC Kanpur, Sohan lal, QSPL Kanpur
M&L for dismantling of upper cover of servo Voltage stabilizer of capacity 200 KVA after disconnecting electrical connection for overall servicing , cleaning of dust and replacement of complete old wiring with FRLS PVC insulated copper conductor of existing size in proper layout and tight with tie including replacement of any unserviceable parts i.e main transformers and dimmerstat (Variac) three phase , servo moter , electronic card, carbon bush or any other parts complete including testing, all as specified and directed . Note :- Replacement of any unserviceable parts will be measured and paid separatly under relevant items except replacement of old wiring which are deemed to be included in the quoted rate.
M&L for dismantling of upper cover of servo Voltage stabilizer of capacity 300 KVA after disconnecting electrical connection for overall servicing , cleaning of dust and replacement of complete old wiring with FRLS PVC insulated copper conductor of existing size in proper layout and tight with tie including replacement of any unserviceable parts i.e main transformers and dimmerstat (Variac) three phase , servo moter , electronic card, carbon bush or any other parts complete including testing, all as specified and directed . Note :- Replacement of any unserviceable parts will be measured and paid separatly under relevant items except replacement of old wiring which are deemed to be included in the quoted rate.
M&L for dismantling of upper cover of servo Voltage stabilizer of capacity 500 KVA after disconnecting electrical connection for overall servicing , cleaning of dust and replacement of complete old wiring with FRLS PVC insulated copper conductor of existing size in proper layout and tight with tie including replacement of any unserviceable parts i.e main transformers and dimmerstat (Variac) three phase , electronic card, servo moter , carbon bush or any other parts complete including testing, all as specified and directed . Note : Replacement of any unserviceable parts will be measured and paid separatly under relevant items except replacement of old wiring which are deemed to be included in the quoted rate
Supply only Main Transformer of suitable size upto the capacity of upto 200/300 KVA stabilizer complete all as specified and as directed. Make Vintec electronic/volina
Supply only Main Transformer of suitable size upto the capacity of upto 500 KVA stabilizer complete all as specified and as directed. Make Vintec electronic/volina
Supply only Carbon bush of suitable size upto the capacity of upto 500 KVA stabilizer complete all as specified and as directed. Make Vintec electronic/volina
Supply only indicators of RYB of suitable size upto the capacity of upto 500 KVA voltage stabilizer complete all as specified and as directed . Make Vintec electronic/volina
S & F MS chequred sheet made to shape for duct cover thickness not less than 5mm complete all as directed .
M&L for replacement of danger notice plate of 1.6 mm thick mild steel sheet ,vitreous enamelled white with letters,figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts and nut of approved size,for HT ,25 X 20 cm size complete all as specified and as directed.
M&L for replacement of Off load tap changer of Transformer Rating from 200 KVA as per the existing make of transformer. Make ITL or equivalent
M&L for replacement of Off load tap changer of Transformer Rating from 400 KVA as per the existing make of transformer.
M&L for PCC 1:4:8 type D-2 using 40mm graded aggregate, mechanically crushed stone for mass filling in pole pit and foundation etc complete all as specified and directed.
M&L for cement concrete (1:3:6) type C-2 using 40mm graded stone aggregate as coping of pole and strut, stay around the pole etc all as specified and directed.
M & L of PCC 1:2:4 Type B-1 using 20 mm graded aggregate for coping of poles including necessary farm work and finishing the exposed surface even and smooth with out using extra cement complete all as specified and directed at site.
M&L for drilling hole under hard standing /road in different location as per site requirement (between 03 mtr to 12mtr maximum) for laying of pipe for protection of cable etc by means of mannual bookle and without disturbing the top surface and making good the disturbed surface if any complete as sepecified and directed.
M & L for shifting transformer/ RMU/ Stabilizer from one to another site/Power house/ store by providing crane/hydra as required at site complete all as per direction of Engr-in-Charge. Note:- movement of item by crane/hydra for atleast upto 500 meter considered as one job)
M&L for spraying chemical (Roundup) on area to remove unwanted vegitation/grass at various locations as directed by Engr-in-Charge. Note: (i) Labour and equipments to spray chemical on required area are incl in quoted rates. (ii) Spray will be repeated quarterly or as per direction of Engr in Charge.
M&L for Danmet Chemical spray (DC> 2-26 having container 415ml/300g for precision blended multipurpose product for prevents corrosion penetrates, lubricates, displaces and seals out moisture release rusted mechanism cleanse etc. Make : Danmet Chemical Pvt Ltd
M & L for highly HT insulating opaque red coloured ANTI TRACK COMPOUND SPRAY 320 of MOSIL LUBICANTS that forms flexible chemical resistank coating to class H winding for electrical apparatus, in 500 ml spray bottles to protect HT equipments, bus bar, CTs, PTs from current leakage due to moisture complete all as specified and directed by Engr-in-Charge.
S & F of Dew Guard (Moisture absorber) of size 100x150x2 mm shall be made of synthetic rubber and a super absorbent polymer and covered by a non woven fabric, absorbency of 0.8g (H2O) / 1g (product) @25 deg C and 95% RH or higher, works between a large temperature range of -30 deg C to +90 deg C, halogen and silicon free, Make :- Hensel model No HDG 100 suitable model of ABB/Seimens HT panel of 11 KV substations complete all as specified and directed by Engineer-in-Charge.
M & L for surface cleaning of steel tubular poles HT 11 mtrs long including removing rusted particles and painting with two coats of synthetic enamel aluminium paint including cross arms, bracing, supports, clamps, eye hooks, security light bracket, clamp etc and providing black & white strips alternatively 30cm Each from coping upto 1.5 mtr height starting with black strip using synthetic enamel paints incl repairing and painting on coping with cement base white paint complete all as directed. Note: (i) The quoted rate shall includes marking of numbers on Each HT pole as per direction of Engr-in-Charge. (ii) The quoted rates shall including the repairing of coping with cement / PCC.
Dismantling and taking down old unsv earthing and M&L for earthing complete with galvanized steel plate earth electrode 60cmx60cmx6mm thick surrounded by char coal and salt buried directly in ground vertically in pit of depth not less then 2.25 mtr below ground level with top edge of the earth plate at depth of not less then 1.5 mtr below ground level surrounded from all sides by char coal dust and common salt in alternate layers of 15 cm depth and earth plate electrode connected to galvanised earth lead strip of size 25X4.0 mm by means of GI nuts bolts, check nuts and washers and connected to earthling test point drawn through 40 mm dia GI pipe for protection of GI pipe including 20mm dia GI pipe for watering GI funnel , PCC earth pit (1:3:6) type C-2 with CI frame and RCC cover all as shown in electrical Plate No 3 on SSR Part-I including testing all as directed by Engr-In-Charge.
S & F of stay assembly complete with all accessories such as stay plate 300mmx300mmx6mm, stay rod 20 mm dia and 215cm long threaded end with nuts including 14mm dia GI stay bow. turn buckle, etc. complete, all as shown in Electrical plate No 1 of SSR part I 2009 complete including dismantling and taking down of old unserviceable stay assembly all as specified and as directed. Note- The quoted rate shall include the cost of loop type insulator, stay clamps, excavation, PCC, stay wire, stay bow, turn buckle, nuts etc., excavation, demolition and removal of demolished concrete complete.
S & F in replacement of gate valve with drain plug of suitable size for existig transformer, complete all as specified and as directed by Engr-in-Charge.
S & F in replacement of conservator tank for step down distribution transformers of capacity upto 500 KVA complete all as per specification and direction of Engr-in-Charge.
M&L for repairing the GOD mechanism pipe and handle lever, etc. by way of welding, greasing and including S & F of new male and female with copper strip contact complete all as specified and directed
S & F self-fusing Ethylene Propylene Rubber(EPR) based high-insulating voltage tape of width not less than 19 mm and thickness not less than 0.75 mm of any length to protect HT/LT XLPE cable from moisture and current leakage complete all as specified and directed by Engr-in-Charge .
Supplying and laying in replacement of synthetic Rubber insulated mats 2.5 mm thick for voltage upto 11 kv for electrical purpose as per IS 15652-2006, (superseeding IS 5424) suitable for electrical shock safety of sizes 10m x 1m complete all as specified and diercted.
Supply in replacement of Tinned copper fuse wire of size 27/33 S.W.G. for GOD ISI marked all as specified and as directed.
Schedule of Credit
M/S PRADEEP ENTERPRISES (BID ID -3497499)
Ridhi engineers and builders (BID ID -3494982)
M/S ADHIKARI CONSTRUCTION CO. (BID ID -3496659)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.37 MB
merger_file.pdf
Tender Documents • 1.71 MB
BOQ_829960.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .