Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹97.1 LAccepted-AOC 93 61 AGARWAL FARM MANSAROVER JAIPUR 302020 | JAIPUR | JAIPUR | RAJASTHAN | 302020 | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹1.1 Cr+₹8.9 L (9.14%)Rejected-Finance 70 VARDHMAN NAGAR A P O SHYAM NAGAR AJMER ROAD JAIPUR PIN 342019 | JAIPUR | 342019 | L2 | Rejected-Finance NOT LOWEST | |
| 3 | L3₹1.1 Cr+₹15.1 L (15.5%)Rejected-Finance 499 A VIDHYUT NAGAR A AJMER ROAD JAIPUR 302021 | JAIPUR | JAIPUR | RAJASTHAN | 302021 | L3 | Rejected-Finance NOT LOWEST |
Tender Value
Refer Docs
EMD Value
₹1.9 L
Closing Date
27 Jan 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE JAIPUR
HQ CWE JAIPUR
ADDN/ALTN INCLUDING REPAIR AND PROVN OF ALLIED SERVICE TO MARRIED ACCN JCOs AND ORs AT QUEENS ROAD ZONE III AT JAIPUR MIL STN (INTERNAL AND EXTERNAL ELECTRICAL SERVICES)
2020_MES_408174_1
CWE/82014/JPR(S)/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
JAIPUR
Please refer tender documents
5 documents required · 5 mandatory
₹1,000
Yes
GE SOUTH JAIPUR
₹1.9 L
Yes
25 Feb 2021
30 Dec 2020
29 Jan 2021
30 Dec 2020
27 Jan 2021
13 Jan 2021
60 days
Amount
S&F Water heater storage type, electrical supplied and installed complete of capacity 25 litres, 5 star, class-I complete Ivory colour, 2 KW, safe shock plug, three flexible wattage option, multi function safety valve, oncology glass coated heating elements, inner tank made up of ultra thick super cold rolled steel plate, rated pressure 8 bar including providing hold fastener of suitable size including drilling and fixing etc complete all as specified and directed. Make: Havells Model Puro Turbo DX or equivalent in Crompton Greaves/Bajaj/Racold/V-Guard.
Supply & laying GI tubing of size 15 mm dia medium grade with all fitting and fixed complete to walls and ceilings or laid in floors etc complete all as specified and directed.
S&F Stop valves of size 15 mm dia bore cast copper alloy screwed down, high pressure with crutch or butterfly handle screwed both ends for iron pipe etc complete all as specified and directed.
S&F Bib taps,15 mm dia bore cast copper alloy with crutch of butter fly handle screwed down , screwed for iron pipe or for brass ferrule and fixed etc complete all as specified and directed.
M&L for Sub main wiring with two runs of 4 Sq.mm single core PVC insulated but in unsheathed multi stranded copper conductor cable 1100 volts grade drawn through and including of 25mm dia PVC rigid conduit medium with conduit accessories and fixed to the surface of wall/ceiling as per ISI including 4.0 Sq.mm PVC insulated copper conductor earth continuity wire etc complete all as specified and directed.
S&F single pole and neutral enclosure with two pin and earth plug and socket complete with one single pole MCB with 240 Volts 20 Amp. etc complete all as specified and directed.
M&L for cutting chassis in cement plaster/brick wall/stone wall/ tiles in 10 cm girth complete for fixing GI Pipe etc complete all as specified and directed.
M&L rendering 10mm thick on brick masonry surfaces or surface other than fair faces of brick work on wall in CM (1:3) finished even and smooth without using extra cement etc complete all as specified and directed.
PVC connections 15mm size with PTMT nuts of length 600mm etc complete all as specified and directed.
M&L for Cutting GI tubing 20mm and making threads in existing pipe including GI Tee 20x15 mm etc complete all as specified and directed.
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan, not exceeding 1.5 metre in depth and getting out in any type of soil.
Excavation in trenches not exceeding 1.5 metre wide, exceeding 1.5 metre and not exceeding 3 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan, not exceeding 1.5 metre in depth and getting out in any type of soil.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm. etc complete as per specified and directed.
Removal of excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5 m above the starting point .etc complete all as specified & directed.
M&L for sand cushioning to PVC underground cable with screened and washed sand and punning to provide a required cover etc complete all as specified & directed.
M&L bricks for protection cover to underground cable (with old size sub class `B` bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10 mm as directed by Engineer in-charge.
Supplying and laying un-reinforced precast cable covers class HV, type I, flat, size 300mm x 180mm x 40mm etc complete all as specified & directed.
M&L pre-stressed cement concrete poles, 11metre long with minimum cross section 152 mm x 152 mm at top and minimum cross section 152 mm x 260 mm at bottom, class-9, conforming to IS-1678 etc complete all as specified & directed.
Supply, installing, testing and commissioning of Air-break, gang operated, triple pole switch, outdoor, horizonal/Vertical mounting type (SI marked), mechanically operated, mounted on insulators and frame work with operating mechanism worked from ground level, with locking arrangements including Godrej pattern 65mm pad locks with two keys, complete suitable for HT 11 KV, 50 Hz AC supply including necessary electric connections, complete all as specified and directed by Engineer-in-Charge of following rating 200 amp rating complete with fuse mounts, fuse carriers and HT fuse elements.
S&F lightning arrester expulsion type for 11KV complete with all fittings transmission class discharge capacity 65 KA etc complete all as specified and directed .
M&L for cross arms, bracings, supports, clamps and back plates etc fabricated from structural steel sections including nuts bolts and washers, welding, bending, cold or hot, drilling holes for bolts, in any shape or size including providing one primer coat, one under coat and one finishing coat of paint etc complete all as specified and directed by Engineer in Charge
Supply, laying and testing cable XLPE insulated, screened PVC bedded, galvanised steel strip or wire armoured electric power cables heavy duty with stranded aluminium conductor, 11KV (Earthed) grade cross sectional area 185 Sq.mm 3 core etc complete all as specified and directed by Engineer in Charge.
M&L for cable end termination, jointing kit, HT 11 KV grade, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade of sizes 185 Sq.mm x 3 core etc complete all as specified and directed.
M&L for cable end termination, jointing kit, HT 11 KV grade, heat shrinkable, indoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade of sizes 185 Sq.mm x 3 core etc complete all as specified and directed.
M&L for cable, jointing kit, HT 11 KV grade, heat shrinkable, straight through type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade of sizes 185 Sq.mm x 3 core etc complete all as specified and directed.
S&F of chain link fencing of size 100mm x 100mm, 4mm dia including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc including provision of binding wire and taking out old fencing etc complete all as directed and specified.
M&L for Danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size for HT 25X20cm etc complete all as specified and directed .
Supply & fixing HT cable route indicator cast iron of suitable size along HT cable trench including painting and grouted in ground in PCC complete all as specified and directed by Engineer-in-Charge
Supply & fixing LT cable route indicator cast iron of suitable size along LT cable trench including painting and grouted in ground in PCC complete all as specified and directed by Engineer-in-Charge
Supply, install, testing and commissioning out door type, step down transformer, 11 KV/433 volts ( at no load) AC 3 phase 50 Hz, of 250 KVA capacity, double copper wound, oil immersed, naturally cooled, (ON AN), with external cooling tubes/fins, vector group DYN -11 with neutral brought out on ( LV side )and having tapings at ± 2.5% to be changed by means of hand operated OFF load tap changer confirm to IS-1180 Part-I, 2014 level-2 & shall comprise of the following:- (a) One cable box on HT side (Primary side consisting of 3 Nos porcelain bushings with copper rods complete with nuts& bolts. (b) One cable box on LT side (secondary side consisting of 4 Nos porcelain bushing with copper rods complete with nuts & washer). (c) Oil conservator oil level gauge. (d) Dehydrating breather with first fill of dehydrating agent (silica gel). (e) Explosion vent, thermometer pocket on tank cover, oil drain filter valve, lifting lugs, oil filling hole with cap/ plug, air release valve plug & 4 Nos plain solid cast steel detachable rollers. (f) One 100mm dia dial type thermometer, vapour pressure type, having range 0-120 degree Celsius having maximum temperature reading indicator with resetting. (g) Two earthing terminals on tank cover to facilitate fixing of 50X6 mm galvanised iron earth strip for earthing of body. (h) Rating plate & terminal marking plate. (j) Extra bushing for neutral, in the LT cable box for providing independent set of earthing for neutral. (k) First filling of new & unused transformer oil, IS-335 Marked within (Make -savita/power link) filter & tested upto 40 KV di electric strength at 2.5 mm air gap between testing electrodes.
Supply, install, testing and commissioning out door type, step down transformer, 11 KV/433 volts ( at no load) AC 3 phase 50 Hz, of 315 KVA capacity, double copper wound, oil immersed, naturally cooled, (ON AN), with external cooling tubes/fins, vector group DYN -11 with neutral brought out on ( LV side )and having tapings at ± 2.5% to be changed by means of hand operated OFF load tap changer confirm to IS-1180 Part-I, 2014 level-2 & shall comprise of the following:- (a) One cable box on HT side (Primary side consisting of 3 Nos porcelain bushings with copper rods complete with nuts& bolts. (b) One cable box on LT side (secondary side consisting of 4 Nos porcelain bushing with copper rods complete with nuts & washer). (c) Oil conservator oil level gauge. (d) Dehydrating breather with first fill of dehydrating agent (silica gel). (e) Explosion vent, thermometer pocket on tank cover, oil drain filter valve, lifting lugs, oil filling hole with cap/ plug, air release valve plug & 4 Nos plain solid cast steel detachable rollers. (f) One 100mm dia dial type thermometer, vapour pressure type, having range 0-120 degree Celsius having maximum temperature reading indicator with resetting. (g) Two earthing terminals on tank cover to facilitate fixing of 50X6 mm galvanised iron earth strip for earthing of body. (h) Rating plate & terminal marking plate. (j) Extra bushing for neutral, in the LT cable box for providing independent set of earthing for neutral. (k) First filling of new & unused transformer oil, IS-335 Marked within (Make -savita/power link) filter & tested upto 40 KV di electric strength at 2.5 mm air gap between testing electrodes.
M&L for earthing complete with copper plate electrode 60cm X 60cm X 3.15mm thick buried directly vertically in ground earth pit not less than 2.25 M deep below normal ground level with top edge of the plate not less than 1.5 M below normal ground level connected to copper strip 20 X 3 mm size by means of bolts, nuts, check nuts and washer of copper all as shown in electrical plate No 3 of SSR- I connected to continuous earth wire on pole all as specified and testing on completion, including provision of earth strip protected by 32mm dia GI light grade protection pipe from test point to main board and 20 mm GI medium grade watering pipe funnel, hinged type angle iron frame pit and CI cover charcoal, salt and copper strip including excavation and earth work etc complete all as specified and directed .
M&L for Earthing complete as per electrical plate No 3 of MES SSR Part I with galvanised steel plate earth electrode 600mm x 600mm x 6.0mm, buried directly vertically in ground in a pit of depth not less than 2.25 metres below ground level with the top edge of earth plate at a depth not less than 1.5m below normal ground level connected to and including galvanised iron or steel earth lead wire 4mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel earthing wire protected by galvanised iron or steel pipe 15mm bore medium grade and connected to continuous earth wire on pole/ test point. Watering pipe shall be 20mm bore GI medium grade including excavation and earth work in any type of soil, PCC pit and RCC cover complete all as specified and tested complete.
M&L earthing complete as per electrical plate No. 3 of MES SSR Part-I with galvanised steel earth plate electrode 60cmx60cmx6.0mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less then 1.5 metre below normal ground level connected to and including galvanised iron or steel earth strip 32mm x 6mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron or steel pipe 40 mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover complete all as specified & tested complete.
M & L for Supplying, laying, connecting and testing in trenches, under floors/ roads or on walls Cable XLPE insulated screened PVC bedded galvanized steel strips or wire armoured, electric power cables (heavy duty) ISI marked with stranded aluminium conductor, 1100 volts grade, of size following sizes :-
(a) 25 Sq.mm 4 core
(b) 50 Sq.mm 3.5 core
(c) 70 Sq.mm 3.5 core
(d) 95 Sq.mm 3.5 core
(e) 150 Sq.mm 3.5 core
(f) 240 Sq.mm 3.5 core
M&L for boring of existing road/path upto 100 mm bore for laying of GI pipe protection for UG cable including making good disturbed area/surface etc complete all as specified and directed.
S&F for galvanised steel tubing light grade size upto 100 mm bore for protection of underground cable on poles / walls under road crossing etc conforming to IS-1239 including taking out/down of existing GI pipe etc complete all as specified and directed.
Supply, install, testing and commissioning (including CPRI type test certified) factory made LT feeder pillar box (KIOSK) outdoor type, floor mounted, compartmentalised and IP-65 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15 mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear open able hinged double door shutters with aprons for cable entry and locking arrangement complete :- (LTP-1) INCOMING:- (a) MCCB 400 amps, 4 pole, 50 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators. (c) Digital Load manager multi functional energy meter having facility to measure true RMS value, KWH, neutral current, for quadrant energy, max demand (KW, KVA, Kvar & Amp), CT operated 415 volts, 50 Hz AC supply including CTs. -01 set. (d) LED indicating lamps (R, Y & B) -01 Set. OUTGOING:- (a) MCCB 100 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos (b) MCCB 63 amps, 4 pole, 30 KA , with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No. (c) Time Switch Astro rex D21- 01 No. (d) DP Contactor 40 Amp - 01 No. (e) Aux Change Over Switch SP 6 Amp - 01 No. (f) MCB DP 'C' Curve 40 Amp - 01 No. (g) MCB SP 'C' curve 20 Amp - 01 No. (h) MCB DP 'C' Curve 63 Amp - 01 No.
Supply, install, testing and commissioning (including CPRI type test certified) factory made LT feeder pillar box (KIOSK) out door type, floor mounted, compartmentalised and IP-65 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear open able hinged double door shutters with aprons for cable entry and locking arrangement complete :- (LTP 2) INCOMING:- (a) MCCB 320 amps, 4 pole, 50 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators. (c) Digital Load manager multi functional energy meter having facility to measure true RMS value, KWH, neutral current, for quadrant energy, max demand (KW, KVA, Kvar & Amp), CT operated 415 volts, 50 Hz AC supply including CTs. -01 set. (d) LED indicating lamps (R, Y & B) -01 Set. OUTGOING:- (a) MCCB 100 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 03 Nos (b) Time Switch Astro rex D21- 01 No. (c) DP Contactor 40 Amp - 01 No. (d) Aux Change Over Switch SP 6 Amp - 01 No. (e) MCB DP 'C' Curve 40 Amp - 01 No. (f) MCB SP 'C' curve 20 Amp - 01 No. (g) MCB DP 'C' Curve 63 Amp - 01 No.
Supply, install, testing and commissioning (including CPRI type test certified) factory made LT feeder pillar box (KIOSK) out door type, floor mounted, compartmentalised and IP-65 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear open able hinged double door shutters with aprons for cable entry and locking arrangement complete :- (LTP-3) INCOMING:- (a) MCCB 320 amps, 4 pole, 50 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators. (c) Digital Load manager multi functional energy meter having facility to measure true RMS value, KWH, neutral current, for quadrant energy, max demand (KW, KVA, Kvar & Amp), CT operated 415 volts, 50 Hz AC supply including CTs. -01 set. (d) LED indicating lamps (R, Y & B) -01 Set. OUTGOING:- (a) MCCB 100 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos (b) MCCB 63 amps, 4 pole, 30 KA , with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No. (c) Time Switch Astro rex D21- 01 No. (d) DP Contactor 40 Amp - 01 No. (e) Aux Change Over Switch SP 6 Amp - 01 No. (f) MCB DP 'C' Curve 40 Amp - 01 No. (g) MCB SP 'C' curve 20 Amp - 01 No. (h) MCB DP 'C' Curve 63 Amp - 01 No.
Supply, install, testing and commissioning (including CPRI type test certified) factory made LT feeder pillar box (KIOSK) out door type, floor mounted, compartmentalised and IP-65 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear open able hinged double door shutters with aprons for cable entry and locking arrangement complete :- (LTP-4=LTP-5 ) INCOMING:- (a) MCCB 400 amps, 4 pole, 50 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 600 Amp, 4 pole, not less than 60cm long mounted on insulators. (c) Digital Load manager multi functional energy meter having facility to measure true RMS value, KWH, neutral current, for quadrant energy, max demand (KW, KVA, Kvar & Amp), CT operated 415 volts, 50 Hz AC supply including CTs. -01 set. (d) LED indicating lamps (R, Y & B) -01 Set. OUTGOING:- (a) MCCB 100 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 05 Nos (b) Time Switch Astro rex D21- 01 No. (c) DP Contactor 40 Amp - 01 No. (d) Aux Change Over Switch SP 6 Amp - 01 No. (e) MCB DP 'C' Curve 40 Amp - 01 No. (f) MCB SP 'C' curve 20 Amp - 01 No. (g) MCB DP 'C' Curve 63 Amp - 01 No.
Supply, install, testing and commissioning (CPRI type test certified)factory made LT feeder pillar box (KIOSK) outdoor type IP 65, platform mounted, suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet with base frame 40x40x6 mm angle iron, duly powder coated finish having front and rear open able hinged double door shutters with aprons and cable allay for cable entry and locking arrangement complete including provision of 65mm Godrej (freedom) lock with 2 keys. The scope of work includes provision of the following :- FP 1=FP2=FP3=FP4=FP7=FP8=FP9=FP12=FP13 INCOMING:- (a) MCCB 100 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp, 4 pole, not less than 60cm long mounted on insulators. (c) LED indicating lamps (R, Y & B) -01 Set. OUTGOING:- (a) MCCB 32 amps, 4 pole, 18 KA, with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 05 Nos
Supply, install, testing and commissioning (CPRI type test certified)factory made LT feeder pillar box (KIOSK) outdoor type IP 65, platform mounted, suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet with base frame of size 40x40x6 mm angle iron, duly powder coated finish having front and rear open able hinged double door shutters with aprons and cable allay for cable entry and locking arrangement complete including provision of 65mm Godrej (freedom) lock with 2 keys. The scope of work includes provision of the following :- (FP-5=FP6=FP14=FP15) INCOMING:- (a) MCCB 100 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 200 Amp, 4 pole, not less than 60cm long mounted on insulators. (c) LED indicating lamps (R, Y & B) -01 Set. OUTGOING:- (a) MCCB 32 amps, 4 pole, 18 KA, with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 07 Nos
Supply, install, testing and commissioning (CPRI type test certified) factory made LT feeder pillar box (KIOSK) outdoor type IP 65, platform mounted, suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet with base frame of size 40x40x6 mm angle iron, duly powder coated finish. having front and rear open able hinged double door shutters with aprons and cable allay for cable entry and locking arrangement complete including provision of 65mm Godrej (freedom) lock with 2 keys. The scope of work includes provision of the following :- (FP 10=FP11=FP16) INCOMING:- (a) MCCB 100 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 01 No (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 400 Amp, 4 pole, not less than 60cm long mounted on insulators. (c) LED indicating lamps (R, Y & B) -01 Set. OUTGOING:- (a) MCCB 32 amps, 4 pole, 18 KA, with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 04 Nos
Supply, install, testing & commissioning automatic power factor correction (APFC) panel capacity 90 KVAR with metalized polypropylene capacitor bank MPP heavy duty of following capacity or nearest higher suitable to make step banking as per load requirement with minimum 12 steps intelligent relay controller having provision of multifunctional LCD display, set optimising control of capability with having facility of display system voltage, reactive power, active power apparent power apparent current total harmonic display VTHD, ITHD plus individual harmonic display of voltage and current temperature with alarm output including alarm system and front panel programming including connection with PVC copper conductor cable of suitable size housed in powder coated PBI sheet housing with hinged door dust proof and connecting with main etc. all as directed with following components (All components & capacitor bank shall be housed in enclosure factory made out of 16 SWG MS sheet outdoor in installation KIOSK type dust and vermin proof with suitable ventilating shutters (louvers) powder coated sheet metal feeder pillar box as per IS-5039 all as specified having locking arrangement , set of CTs Discharge reactors contactor heavy duty 4 pole 415 Volt with AC coil including MCBs indicating lamps and bypass system Alarm bell 240 volts 50 Hz -01 No. etc complete to achieve point 0.99/1.0 near to unity including necessary foundation pillar type copper bus bar of suitable size 3 phase system etc complete all as specified and directed.
M&L for straight through jointing kit complete with accessories suitable for XLPE armoured aluminium conductor cable 1.1 KV grade etc complete all as specified and directed of following sizes :-
(a) 10 to 35 Sq.mm 3.5 Core
(b) 50 to 70 Sq.mm 3.5 Core
(c) 95 to 150 Sq.mm 3.5 Core
M&L for PCC (1:3:6) type C2 using 40 mm grade stone aggregate in base & foundation of pole/earthing chamber/chamber cover including necessary form work etc complete all as specified and directed.
M&L for PCC 1:2:4 type B1 using 20mm graded stone aggregate in coping of existing/new poles including necessary form work, finished the exposed surfaces fair and even without using extra cement etc complete all as specified and directed.
Construction of RCC platform of size 1.5mx1.5mx2.0m with following operations:- (a) Excavation and earth work shall be in any type of soil and shall be deposited to a distance exceeding not exceeding 50 meters including returning filling etc. (b) Foundation PCC subbase 100mm thick (1:4:8) type D-2 using 40 mm graded crushed stone aggregate. (c) Step Brickwork in CM (1:6) below GL with width 545mm, 345mm and 230mm with each step 200mm height over PCC subbase as above (d) Platform shall be plastered the external surfaces above GL 15mm thick in CM(1:4) and finished with two coats of cement base paint over one coat of primer (e)Top of platform shall be provided in 150mm thick RCC in (1:2:4) type B-1 with 8mm dia bars both side 200mm c/c reinforcement, over 100mm thick broken stone boulders over sand filling compacted in layer not exceeding 25cm each by watering and ramming etc complete all as specified and directed by Engineer-in-Charge.
Taking out old U/S LT cables from Existing LT panel to feeder pillar/bus bar chamber of different size etc complete all as specified and directed by Engineer-in-Charge.
Taking out old U/S LT Panel of different type/size including disconnecting all electrical connections etc complete all as specified and directed by Engineer-in-Charge.
Taking out old U/S Feeder pillar of different type/size including disconnecting all electrical connections etc complete all as specified and directed by Engineer-in-Charge.
Schedule of Credit
Pioneer Enterprises
DIVYA ASSOCIATES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .