VISHWNATH KHICHI
ED - Karnal
Replacement of 04 No. 10 Passenger lifts and replacement of fire alarm system in Judicial Court Complex, Distt. Karnal (Pdg. fire alarm system only) Recall
2025_HRY_434420_1
2025653B7FA1 CD51 40BB A6DC C1BCB8BC63C1665BAR
Open Tender
Electrical Works
Works
90 days
Karnal
2 documents required · 2 mandatory
₹5,000
₹53,840
Yes
22 May 2025
18 Mar 2025
3 Apr 2025
19 Mar 2025
2 Apr 2025
19 Mar 2025
Amount
SITC of addressable multi sensor smoke detector with inbuilt fault isolator including mounting base with RED LED should blink in normal conditions and LED should be continues in fire conditions complete as required with inbuilt Isolators as per NFPA 72 style 7 wiring requirements for maintaining operational availability of all elements in the loop in the eventof a short circuit and to meet style 7 requirements: Compensation feature and Automatic addressing. Detector should monitor Electromagnetic interference and report to the panel-current and average values. Detector should have IP30 or better protection rating. Shall be UL/EN/VDS certification. Detectors should have Inbuilt Isolators. Make: Eaton, Bosch, Siemens
Supply erection testing and commissioning of addressable Heat detector with inbuilt fault isolator with fixed and rate of raise 60 degree feature and minimum 70 degree including mounting base with RED LED should blink in normal conditions and LED should be continues in fire conditions. etc complete as required. Each Detector should inbuilt Isolators as per NFPA 72 style 7 wiring requirements for maintaining operational availability of all elements in the loop in the event of a short circuit and to meet style 7 requirements. High resistance to electro magnetic Detector should monitor Electromagnetic interference and report to the panel current and average values. Detector should have IP30 or better protection rating. Shall be UL/EN/VDS certification. (Detectors should have Inbuilt Isolators). (Make: Eaton, Bosch,Siemens)
Supplying, installation, testing and commissioning of repeater panel wih 320 character/ Touch screen LCD display with inbuilt reset, acknowledge and silence switches complete as required
Supply, installation, testing and commissioning of intelligent Analog Addressable type Manual Call Point with inbuilt fault isolator with RED LED should blink in normal conditions and LED should be continues in fire conditions. having Surface or flush mounting option fully compliant to EN 54 having auto addressing with back box for mounting as required conforming to BS5839 standards and duly approved by EN54/UL/VDS required to complete thejob in all respect up to the entire satisfaction of Engineer in Charge of work. Make : (Make: Eaton, Bosch, Siemens)
Supplying, installation, testing and commissioning of addressable horn cum strobe with inbuilt fault isolator complete as required as per EN Standard Make (Eaton/Bosch/Siemens)
SITC of minimum 1000 Mtr. Range Kheral/National make SIRON generator provided at the roof of the building with separate Power SITC, relay with all labour and material required to complete the job-in all respect up to the entire satisfaction of Engineer In Charge of work.
Supply, installation, testing and commissioning of Addressable Control Relay Module with inbuilt fault isolator should have soft addressing features, isolator should be inbuilt with flexible network structures with a maximum switching current of 1A @30V DC.I should have inbuilt isolator. Shall be EN54/UL/VDS Certification Make: (Make: Eaton, Bosch,Siemens)
SITC of Addressable Monitor Module with inbuilt fault isolator for monitoring of a line with EOL resistor/ Potential free contact/voltage monitoring, it should have soft addressing features, isolator should be inbuilt shall be EN54/UL/VDS approved. (In case of 2 monitoring features in one module (points) each point shall be consider separately for payment). Make: (Make: Eaton, Bosch,Siemens)
Supply and erection of 2.5 Sqmm 02 Core copper wire including making necessary connection etc. complete with all labour and material to complete the job in all respect upto the entire satisfaction of Engineer in Charge of the work. Make as per approved Make list
SITC of CQRS (Clean Agent Gas (HFC 236 fa) Gas Based Suppression System Direct System - 4Kg - with 10 Mtr HST (Heat Sensing Tube) (For Open Cabinet with natural airflow Panel along System operating pressure 15 bar at 20°C ,System operating temperature range : -20°C to plus 60°C,The sensing tube must be made of a special modified Polyamide (PA) in Black color with an outer diameter of 6mm,Tube’s technical specifications should be certified by the OEM to its own specifications,The complete system should be tested and Certified to Standard LPS 1666:Issue 1.0 by LPCB (warranty Period 2 Years) without Monitoring Panel Kit
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .