Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance GROUND FLOOR G 1154 A MANSAROVAR PARK SHAHDARA DELHI 110032 | SHAHDARA | DELHI | 110032 | Admitted-Finance |
| 2 | Admitted-Finance C 344 GALI NO 2 BLOCK C WEST KARAWAL NAGAR DELHI 110094 | NORTH EAST | DELHI | 110094 | Admitted-Finance |
Tender Value
₹45.0 L
EMD Value
₹90,038
Closing Date
12 Jan 2022, 3:00 pmClosed
Executive Engineer (E)
O/o EE (E), PWD NES/ M-251, LM Bund Road, Ramesh Park, Delhi-92
Repair/ replacement of defective Electrical equipments i.e. Fittings, Fans, Air Conditioners, Water Cooler and R.O. and other accessories at District Courts Karkardooma Delhi.
2022_PWD_214178_1
73/EE (E)/PWD NE and Shah. Elect. Divn./2021-22
Open Tender
Electrical Works
Item Rate
90 days
KKD Court Complex
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹90,038
Yes
13 Jan 2022
5 Jan 2022
12 Jan 2022
5 Jan 2022
12 Jan 2022
5 Jan 2022
Amount
SUB HEAD-I (For Lawyers Chamber Block D, E, F, G & H)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
3 x 4 sq. mm
3 x 6 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75 mmX75 mm)
3 Module (100 mmX75 mm)
6 Module (200 mmX75 mm)
8 Module (125 mmX125 mm)
12 Module (200 mmX150 mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
3 pin 5/6 A socket outlet
15/16 A switch
6 pin 15/16 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) 8 way (4 + 24), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 100 A
Supplying, Installation, Testing and Commissioning of 36 to 40-watt surface/ recessed mounted LED Luminaries of size 600 mm (Length) x 600 mm (Width) housing made with white powder coated CRCA sheet metal and polycarbonate diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 100 luman per watt. and colour temperature of 6000 K, CRI >80 with driver having power factor > 0.90, THD < 20% and efficiency > 85% driver should be IC Complete, with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help of 4 nos. fastener Hook, Clutch wire and sleeve i/c testing, commissioning etc. complete as required
Supplying, installation, testing and commissioning of new 36 to 40 watt recessed mounted LED Luminaries of size 300 mm (Length) x 1200 mm (Width) housing made with white powder coated CRCA sheet metal and polycarbonate diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 120 luman per watt. and colour temperature of 6000 K, CRI >80 with driver having power factor > 0.90, THD < 20% and efficiency > 85% driver should be IC Complete, with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help of 4 nos. fastener Hook, Clutch wire and sleeve i/c testing, commissioning etc. complete as required.
Supplying, Installation, Testing & Commissioning of LED downlighter round type surface mounted with following technical specification: - i). System Lumen output >1800 ii). System Efficiency >100 lm/Watt iii). Input Power not more than 7 W iv). CCT >5700, CRI> 70, PF > 0.95, THD< 10% v). Life 50 K hours @ L70
Supplying and replacement of existing damaged fitting into 9 to 12 watt and length upto 600 mm high efficiency LED linear batten Luminaries made out of Aluminium housing and having polycarbonate diffuser with inbuilt APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 25000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 100 luman per watt. and colour temperature of 6500 K, CRI >80 including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable etc. complete as required.
Supplying, Installation, Testing & Commissioning 18 to 20 watt 1200 mm long high efficiency LED linear batten Luminaries having aluminium extruded housing and polycarbonate diffuser within built APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 120 luman per watt and colour temperature of 6000 K, CRI >80 including connect ion with 1 5 sq. mm PVC insulated copper conductor FRLS cable i/c dismantling of existing old fitting if any etc. complete as required.
Replacement of defective/worn-out fl. fittings with new 20 to 22 watt square 300 mm. x 300 mm. surface mounted LED flat panel suitable for operation on 150 to 265V single phase A.C. supply i/c connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable polycarbonate diffuser within built APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 100 luman per watt. and colour temperature of 6000 K, CRI >80 i/c dismantling of existing old fitting if any etc. Complete as required.
Supplying, Installation, Testing and Commissioning of 1200 mm sweep ceiling fan, made out of aluminium housing and aluminium blades ISI marked and 5 star rating including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing M.S flat Fan hook if required etc. complete as required.
Supplying and fixing of 400 mm. sweep wall fan oscillation type suitable of operation on single phase 230 volts 50 Hz. on existing wall/ surface i/c connection with 1.5 sq. mm. FRLS PVC insulated copper conductor cable etc. complete as required.
Supplying, Installation, Testing and Commissioning of stainless-steel storage type water cooler (150/150) liter Capacity fully stainless steel mounted on cement concrete foundation of suitable size/ height as per site requirement, water cooler suitable for operation on 230 volts 50 Hz single phase AC supply including suitable compressor etc. making water line and electrical connections etc. complete as required.
Supplying, Installation, Testing and Commissioning of 50 LPH capacity Reverse Osmosis (RO system) water Purification unit i/c Providing suitable wall/floor mounting bracket, water connection from the available water inlet point with suitable C.P. angle valve and outlet upto the nearest drain with suitable PVC pipe, complete etc. as required.
Supplying installation, testing, erection & commissioning of outdoor floor mounted compartmentalized type Feeder Pillar depth not less than 300 mm, fabricated with 2 mm thick CRCA sheet suitable for 415/ 500 volts 50 Hz A.C. supply with CRCA sheet on bottom for taking load of cable gland necessary individual gland plates for cable gland, cable alley, locking arrangements as per direction of engineer in charg complete with bus bar chamber having 100 Amp TPN Al busbar duly sleeved and Numbering, i/c supplying and fixing the following mounting inside the panel - interconnections with suitable size Al. bus bar/copper cable for suitable size for following outgoing and incoming MCCB’s, earthing studs, powder coating/ stove enamelled painting after 7 tank treatment process, with following accessories as reqd. of (not less than 0.36 Sq. mtr.) Incoming 100 Amp 4 Pole 18 KA MCCB with suitable rotary handle & spreader link - 1 Nos. Multifunction meter with suitable CTs-1 nos. RYB LED indicator with suitable single pole MCB- 1 Set Outgoing DP 63 Amp MCB - 12 Nos
Supplying, laying & fixing of one number PVC insulated and PVC sheathed/XLPE power aluminium armoured conductor cable of 1.1 KV grade of following size direct on wall/surface as required. 3.5 x 25 sq. mm.
SUB HEAD-II (For Court Block ACI, B & JKL)
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required. Group C
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
3 x 4 sq. mm
3 x 6 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.
1 or 2 Module (75 mmX75 mm)
3 Module (100 mmX75 mm)
6 Module (200 mmX75 mm)
8 Module (125 mmX125 mm)
12 Module (200 mmX150 mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
3 pin 5/6 A socket outlet
15/16 A switch
6 pin 15/16 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12-way, Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) 8 way (4 + 24), Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 100 A
Supplying, Installation, Testing and Commissioning of 36 to 40-watt surface/ recessed mounted LED Luminaries of size 600 mm (Length) x 600 mm (Width) housing made with white powder coated CRCA sheet metal and polycarbonate diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 100 luman per watt. and colour temperature of 6000 K, CRI >80 with driver having power factor > 0.90, THD < 20% and efficiency > 85% driver should be IC Complete, with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help of 4 nos. fastener Hook, Clutch wire and sleeve i/c testing, commissioning etc. complete as required
Replacement of defective/worn-out Flood light fitting by Supplying, Installation Testing and Commissioning of 150-watt LED Flood Light fitting aluminium die cast housing, IP 66 with high power LED as light source, system lumen efficiency of ≥ 120 lm/W, colour rendering (CRI) ≥ 70, and correlated colour temperature (CCT) of 5500 - 6500 (±300K). The luminaries should have 10KV surge protection, PF≥0.95, the total harmonic distortion≤ 10% operatable in voltage range of 120-270 V, total burning hours 50000 with LM 70/79/80 Certificates The driver used must be a constant current driver with efficiency of ≥ 85% and driving current ≤ 725mA complete r on surface with suitable fasteners as required and as per direction of Engineer-In charge. i/c dismantling of existing fittings. The manufacturer should provide LM 80 reports along with warrantee of 5 years for luminaires i/c drivers etc. as required.
Supplying, Installation, Testing and Commissioning of 1200 mm sweep ceiling fan, made out of aluminium housing and aluminium blades ISI marked and 5-star rating including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing M.S flat Fan hook if required etc. complete as required.
Supplying and fixing of 400 mm. sweep wall fan oscillation type suitable of operation on single phase 230 volts 50 Hz. on existing wall/ surface i/c connection with 1.5 sq. mm. FRLS PVC insulated copper conductor cable etc. complete as required.
Supplying and replacement of existing damaged fitting into 9 to 12 watt and length upto 600 mm high efficiency LED linear batten Luminaries made out of Aluminium housing and having polycarbonate diffuser with inbuilt APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 25000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 100 luman per watt. and colour temperature of 6500 K, CRI >80 including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable etc. complete as required.
Supplying, Installation, Testing & Commissioning 18 to 20 watt 1200 mm long high efficiency LED linear batten Luminaries having aluminium extruded housing and polycarbonate diffuser within built APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 120 luman per watt and colour temperature of 6000 K, CRI >80 including connect ion with 1 5 sq. mm PVC insulated copper conductor FRLS cable i/c dismantling of existing old fitting if any etc. complete as required.
Replacement of defective/worn-out fl. fittings with new 20 to 22 watt square 300 mm. x 300 mm. surface mounted LED flat panel suitable for operation on 150 to 265V single phase A.C. supply i/c connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable polycarbonate diffuser within built APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 100 luman per watt. and colour temperature of 6000 K, CRI >80 i/c dismantling of existing old fitting if any etc. Complete as required.
Supplying, Installation, Testing and Commissioning of 1.5 TR capacity Minimum 3 Star rating Split Type AC. Unit complete with indoor, outdoor unit, remote control with eco-friendly, Refrigerant suitable for 230 volt, single phase, 50 HZ AC supply complete alongwith 5 mtr. Copper pipe i/c dismantling of existing worn-out AC unit etc. as required.
Providing and fixing of readymade MS fabricated and duly painted, wall bracket type stands for mounting the Split A.C. outdoor unit including grouting on the wall and making good the damages to surface complete with rubber vibration pads on outdoor unit bolts etc. complete as required.
Supplying and fixing extra length of copper refrigerant pipe of size 5/8”, ¼” with insulation and 3 core X 2.5 sq. mm. copper cable, drain pipe etc. including all connection in the existing split type AC units as required at site.
Replacement of defective/ worn-out Air conditioning with new 1.5 Ton Nominal capacity minimum 5-star Window Type Air Conditioner suitable for operation on 230 volt, 50 Hz single phase AC supply with energy efficient rotary compressor with cordless remote, capable of performing, Cooling, Dehumidifying, Air-Circulating, Filtering i/c necessary wooden packing to suit the existing opening etc. complete as required.
Supplying, Installation, Testing and Commissioning of Air Purifier having coverage area minimum 425 sq. ft. and minimum clean air delivery rate 200 cu. Mtr. per hour etc. complete as required.
Supplying, Installation, Testing and Commissioning of stainless-steel storage type water cooler (150/150) liter. Capacity fully stainless steel mounted on cement concrete foundation of suitable size/ height as per site requirement, water cooler suitable for operation on 230 volts 50 Hz single phase AC supply including suitable compressor etc. making water line and electrical connections etc. complete as required.
Supplying, Installation, Testing and Commissioning of 50 LPH capacity Reverse Osmosis (RO system) water Purification unit i/c Providing suitable wall/floor mounting bracket, water connection from the available water inlet point with suitable C.P. angle valve and outlet upto the nearest drain with suitable PVC pipe, complete etc. as required.
Supplying, Installation, Testing and Commissioning of 15-liter capacity geyser made out of copper/stainless steel tank suitable for operation on 220 volts to 265 volts single phase A.C. supply etc. i/c electrical connections, testing, etc. complete as per site requirement.
Supply of Oil Heater 2500-watt Copper
Less of Account of buy back of following dismantled material
Assorted PVC insulated copper wire
Assorted size MCB DB
Assorted size TP MCCB
Assorted LED fittings/ Downlighter
Burnt-out Ceiling Fans
Burnt-out Wall/ Air Circulator Fans
Assorted Capacity Water Cooler
Assorted capacity RO System
Assorted Split/ Window AC
Assorted flood light fittings
Assorted Material like Conduit, Switches, Sockets, Sheet, Box, Regulator, damage DP Sheet enclosure etc.
Krishna Electreical Works
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .