Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.9 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹2.0 L+₹6,650 (3.46%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | Not Admitted-Fee/PreQual/Technical 110 MINI SHOPPING COMPLEX NEHRU MARKET JAMMU | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | M/S ISHAN ELECTRICAL and MECH. ENGG. WORKS L2 | R M ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00 | Top-up of Transformer-Grade Insulating Oil & Leak Rectification
Top-up of ~600 liters of transformer-grade oil in 500 kVA Servo AVR. Leakage points sealed using high-grade sealing compounds. BDV tested post-top-up as per IS: 6792. Includes site cleaning and operational checks. as per IS: 335 (Type II), IS: 6792 | 1 | job | 1,28,000 ₹1,28,000 | 1,25,000 ₹1,25,000 Lowest |
| 2.00 | Replacement of Two Servo Control PCB Cards
Removal of faulty PCBs and installation of OEM-compatible cards. Functional testing and programming for smooth regulation. Work done as per OEM safety standards. | 1 | job | 23,600 ₹23,600 | 22,500 ₹22,500 Lowest |
| 3.00 | Replacement of One Servo Motor
Servo motor replaced with matching torque, RPM, and voltage. Includes dismantling, mounting, wiring, alignment & testing. Ensures control accuracy. AS PER IS: 996:1979 | 1 | job | 18,200 ₹18,200 | 17,000 ₹17,000 Lowest |
| 4.00 | Re-Insulation of Main Cable (125 sqmm, 3.5 Core)
Insulation repair of 30 ft long 125 sqmm cable using Class H tape and heat shrink sleeves. Tested using 1kV megger for ≥100 MΩ IR value AS PER IS: 7098, IS: 13573 | 1 | job | 7,500 ₹7,500 | 7,100 ₹7,100 Lowest |
| 5.00 | Transportation of Material & Technician Tools
Includes transportation of PCB cards, motor, tools, insulating materials, oil drums, and manpower to site location. | 1 | job | 4,900 ₹4,900 | 4,750 ₹4,750 Lowest |
| 6.00 | Installation & Commissioning Charges
Complete mechanical, electrical fitting, testing, and calibration of AVR system after repair. Functional test under load. Submission of final test report. | 1 | job | 9,700 ₹9,700 | 9,000 ₹9,000 Lowest |
| 7.00 | Provision of Stationary Viz 3 No A4 Size Rim, 10 No Black and blue ball point pens, 10 No. File cover. | 1 | job | 2,000 ₹2,000 | 1,900 ₹1,900 Lowest |
| 8.00 | HSD for inspection of work at site during Execution phase of work, | 1 | job | 4,750 ₹4,750 Lowest | 4,750 ₹4,750 Lowest |
Tender Value
₹2.0 L
EMD Value
₹4,070
Closing Date
28 Nov 2025, 12:00 pmClosed
EXECUTIVEV ENGINEER M AND H DIVISION DODA
KHELLANI DODA
Repair and Replacement of Parts of 500 KVA Servo AVR installed at Oxygen Generation Plant at Associated Hospital GMC Doda
2025_PWDJK_295584_1
MHDD/TS/2025-26/107
Open Tender
Repair and Maintenance Works
Turn-key
20 days
DODA
AS PER SBD
2 documents required · 2 mandatory
₹500
EXECUTIVEV ENGINEER M AND H DIVISION DODA
₹4,070
EXECUTIVE ENGINEER M AND H DIV DODA
9 Dec 2025
18 Nov 2025
28 Nov 2025
18 Nov 2025
28 Nov 2025
18 Nov 2025
24 Nov 2025
Amount
Top-up of Transformer-Grade Insulating Oil & Leak Rectification Top-up of ~600 liters of transformer-grade oil in 500 kVA Servo AVR. Leakage points sealed using high-grade sealing compounds. BDV tested post-top-up as per IS: 6792. Includes site cleaning and operational checks. as per IS: 335 (Type II), IS: 6792
Replacement of Two Servo Control PCB Cards Removal of faulty PCBs and installation of OEM-compatible cards. Functional testing and programming for smooth regulation. Work done as per OEM safety standards.
Replacement of One Servo Motor Servo motor replaced with matching torque, RPM, and voltage. Includes dismantling, mounting, wiring, alignment & testing. Ensures control accuracy. AS PER IS: 996:1979
Re-Insulation of Main Cable (125 sqmm, 3.5 Core) Insulation repair of 30 ft long 125 sqmm cable using Class H tape and heat shrink sleeves. Tested using 1kV megger for ≥100 MΩ IR value AS PER IS: 7098, IS: 13573
Transportation of Material & Technician Tools Includes transportation of PCB cards, motor, tools, insulating materials, oil drums, and manpower to site location.
Installation & Commissioning Charges Complete mechanical, electrical fitting, testing, and calibration of AVR system after repair. Functional test under load. Submission of final test report.
Provision of Stationary Viz 3 No A4 Size Rim, 10 No Black and blue ball point pens, 10 No. File cover.
HSD for inspection of work at site during Execution phase of work,
M/S ISHAN ELECTRICAL and MECH. ENGG. WORKS (BID ID -2652149)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.70 MB
BOQ_956934.xls
BOQ • 0.24 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .