Loading…
Loading…
| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹6.0 LAdmitted-Finance 60 K N C ROAD NAYAN KANAN BARASAT KOL 700124 | BARASAT | NORTH 24 PARGANAS | WEST BENGAL | 700124 | -38.07% | ₹6.0 L | L1 | Admitted-Finance |
| 2 | L2₹6.2 LAdmitted-Finance | -35.49% | ₹6.2 L | L2 | Admitted-Finance |
| 3 | L3₹6.3 LAdmitted-Finance 04 SUDARSHNA COOLING CENTRE ADP ROAD CHRISTIANPATTY NAGAON ASSAM 782001 UDYAM AS 22 0000781 | NAGAON | ASSAM | 782001 | -35.02% | ₹6.3 L | L3 | Admitted-Finance |
| 4 | L4₹8.9 LAdmitted-Finance | -8.10% | ₹8.9 L | L4 | Admitted-Finance |
Tender Value
₹9.6 L
EMD Value
₹19,300
Closing Date
19 Jan 2026, 3:00 pmClosed
AGM EM FCI RO Assam
FCI RO Assam
Installation of industrial sockets and laying of new cables in Godown and Minished of FSD Cinnamara to provide power supply for operating the power sprayer machine and belt conveyor machine
2026_FCI_892937_1
15/EM/2025-26
Open Tender
Electrical Works
60 days
FCI FSD Cinnamara
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹19,300
6 Feb 2026
8 Jan 2026
20 Jan 2026
8 Jan 2026
19 Jan 2026
8 Jan 2026
Supplying of aluminium conductor PVC insulated, PVC sheathed/ XLPE insulated inner sheathed steel strip armoured power cable of 1.1 KV grade conforming to IS:7098(Part-I) 1988 or latest amended following sizes etc .
(a) 4X 95 sqmm armoured
(b) 4X70 sqmm armoured
(c) 4X 50sqmm armoured
(b) 4X10 sqmm armoured
(c) 4X6 sqmm armoured
Laying and fixing of one number PVC insulated and PVC sheathed /XLPE power cable of 1.1 KV grade of following size on wall surface as required.
(a) Upto 35 sq. mm (clamped with 1mm thick saddle)
(b) Above 35 sq. mm and upto 95 sq.mm (clamped with 25x3 mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. (a) Above 35 sq. mm and upto 95 sq.mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. (a) Above 35 sq. mm and upto 95 sq.mm
Laying of one no PVC insulated and PVC sheeted power cable with 7/18 stay wire with sutable clamp as required for cable size of Above 35 sq. mm and upto 95 sq. mm
Supplying and fixing of light class G.I. pipe of 100 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required.
(a) 3½ X 95 sq. mm (45mm)
(b) 3½ X 70 sq. mm (38mm)
(c) 4 X 50 sq. mm (35mm)
(d) 4 X 10 sq. mm (25mm)
(e) 4 X 6 sq. mm (22 mm)
Supplying and fixing 30 A, 415 V, TPN Industrial type socket outlet,with 4 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, TPMCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required. (a)200 mm X 150 mm X 60 mm deep
Supply and fixing 4 way connector terminal in the existing metal box complete with connections, testing and commissioning etc. as required.
Providing and fixing 12 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Fabrication, supplying and istallation of out door type floor mounted MV 3 phase 4 wire 50 Hz AC Feeder Pillar distribution board of size 800 mm x 400mm x 300mm fabricated with 2.00 mm (SWG-14) sheet steel for frame work and cover, angle iron legs of 450 mm in length in brick foundation with net plaster finishing, cable gland plate including cleaning and finishing with powder coated painting complete having 200 amps capacity TPN aluminum alloy bus bar, including bus bar support, both side hinged doors with locking arrangement, ventilation, cable termination plate, 2 No. earth studs with provision of fixing the following units including internal connection with contol wires of following MCCB/C/O. (a) 63 A 4 pole MCCB - 1 No (b) 32 A TPN - 1 No (C) 32 A SPN - 5 No
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
(a) Single pole and neutral
(b) Triple pole and neutral
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
MTF.pdf
Tender Documents • 0.75 MB
BOQ_938556.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid