Er. A.K. Chhibber
Office of the Deputy General Manager, JKPCC Ltd., Unit Electrical, Rail Head Complex Jammu.
Internal Electrification works of Govt. Polytechnic College (Administrative Block) Udhampur.
2019_PWDJK_89214_1
e-NIT NO 15/ELECT of 2019-20 Dt. 24-12-2019
Open Tender
Electrical Works
Item Rate
365 days
UDHAMPUR
Please refer Tender documents.
6 documents required · 6 mandatory
₹1,000
Yes
Financial Controller, JKPCC Ltd.
₹84,000
Yes
Dy. Gen. Mgr. Elect. Unit, JKPCC Ltd.
3 Feb 2020
27 Dec 2019
22 Jan 2020
27 Dec 2019
21 Jan 2020
4 Jan 2020
3 Jan 2020
Amount
Sub Head-I(Wiring) Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in Existing surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 20mm
Wiring for Light /Power Plug with 2 x 4 sq.mm FRLS PVC Insulated Copper Conductor single core cable in Existing surface/Recessed medium class PVC Conduit along with 1 No. 4 sq.mm FRLS PVC Insulated copper conductor single core cable for loop earthing as required.
Wiring for Circuit/Submain Wiring along with earth Wire with the following Sizes of FRLSPVC insulated copper conductor,single core Cable in Existing surface/Recessed medium class PVC conduit as required. 2 X 2.5 SQ.MM + 1 X 2.5 SQ.MM EARTH WIRE
4 X 10.0 SQ.MM + 2 X 6.0 SQ.MM EARTH WIRE
4 X 6 sq. mm + 2 X 6 sq. mm earth wire
4 X 4 sq. mm + 2 X 4 sq. mm earth wire
2 X 16 sq. mm + 1 X 6 sq. mm earth wire
Supplying and Fixing following modular switch/socket on the existing modular plate and switch box including connections but excluding modular plate etc. as required 5/6 amps switch
3 Pin 5/6 amp socket outlet
Supplying and fixing modular blanking plate on the existing modular plate and switch box excluding modular plate as required
Supplying and fixing Stepped Type Electronic Fan Regulator on the existing Modular Plate Switch Box including Connections but Excluding Modular Plate etc. as Required
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 6 pin 15/16 amps modular socket outlet and 15/16 amps modular switch,connection,painting etc. as required.
Supplying and Fixing suitable size G.I box with modular plate and cover in front on surface or in recess,including providing and fixing 3 pin 25 amps modular Multi pin socket outlet with connection,painting etc. as required.
Sub Head-III(DB's and MCB's) Supplying and fixing following way,Prewired TP&N PPI Distribution Board of Sheet Steel for 415 Volts on surface/Recess complete with Ready to use DBs - Provided with 100A insulated phase bus-bars,neutral bar/s with shroud/s, earth bar/s , sticking saddles , cement spill protector ,color-coded interconnecting wire set , cable ties , blanking plates and circuit identification labels.The D.B should be IK-09 Compliant.(The Cost of D.B is without MCB's)(IP Rating-43) 4 Way (8 Module Incomer),(2+2+2 incomer DP RCCB),(4+4+4) SP MCB's O/G's)
8 Way (8 Module Incomer),(2+2+2 incomer DP RCCB),(8+8+8 SP MCB's O/G's)
12 way (8 Module Incomer),(2+2+2 incomer DP RCCB),(12+12+12 SP MCB's O/G's)
Supplying,Installation ,Testing and Commissioning of Four Pole 415V ,MCB in the existing MCB DB With Connections Testing and Commissioning etc as Required. 63 Amps
Supplying and Fixing Following rating,Double Pole (Single Phase and Neutral),240 Volts Residual Current Circuit Breaker (RCCB) having a sensitivity of current upto 300 ma in the existing MCB DB Complete with connections ,testing and commissioning as required. 40 Amps
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess,complete with tinned copper bus bar, neutral bus bar, earth bar,din bar, interconnections, powder painted including earthing etc.as required. (But without MCB/RCCB/Isolator) 12 way, Double door
Supplying,Installation ,Testing and Commissioning of Double Pole 240V ,MCB in the existing MCB DB With Connections Testing and Commissioning etc as Required
Supplying,Installation ,Testing and Commissioning of 1P+N(2 Module) Surge Protection Device(SPD) Type 2,I max 15 KA
Supplying and fixing 5 amps. to 32 amps.rating 240 volts 'C' series, miniature circuit breaker of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole
Supply and Fixing Single Pole Blanking Plate in the Existing MCB DB complete as Required
Supplying,Installation ,Testing and Commissioning of 3P+N(2 Module) Surge Protection Device(SPD) Type 2,I max 15 KA
Supplying and Laying of B-Class 100 mm Dia Size G.I Pipe under the Road/Floor not less than 1 mtr below the Ground Level including cutting the Road/Floor and making Good the same as required.
Sub Head-IV(Lightning Conductor and Earthing) ENVIRONMENTALLY SAFE MAINTENANCE FREE EARTHING SYSTEM Necessary soil treatment is to be made by the contractor in order to improve the Pit resistance value. Supply, installation, testing and commissioning of Advanced Maintenance Free environment friendly Earthing system consisting of 1 no. of 3mtr length, 17.2 mm dia UL certified earth electrode made of high tensile low carbon steel circular rods, molecularly bonded copper on outer surface (minimum copper bonding thickness-250 microns) with GI terminals to connect incoming strips, (Environment friendly backfill compound duly certified as per ANSI/NSF standard 60/Toxic content certificate as safe for use near potable ground water resources strictly as per specification enclosed. Make- SHREE ELECTRODES/OBO BETTERMANN/ERICO(2 Nos UPS and 4 Nos Main L.T Panel) Earth pit chamber (300mm x 300mm) with CI cover for the above.
Providing and Fixing 25 mm x 5 mm Copper Strip in 40 mm dia. G.I Pipe FRL Earth Electrode including connection with Brass nut ,bolt,spring,washer,excavation and refilling etc. as required.
Sub Head -V(SITC of Fans and Fittings) SITC of Ceiling Fan,Capacitor type suitable for low voltage operation including wiring the down rods of standard length(Upto 30 cm)with 1.5 sq.mm FR PVC insulated,copper conductor,single core cable including providing and fixing phenolic laminated sheet cover on the Fan Box etc as Required. 1200 MM SWEEP(5 STAR)
SITC of pre-wired Surface Mounted LED Ceiling Light(Batten Type for "T8" Tube Light) Fitting with 2 Nos of 18 W LED Tube Light ,Driver Etc. including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required .(Make:- LL13-181-650)/WIO 922208)
SITC of pre-wired Surface Mounted LED Ceiling Light12 w including connections with 1.5 sq.mm FR PVC insulated copper conductor single core cable and earthing etc as required.(WIPRO LD80-101-XXX-60-SM)
Supply of AC 230/250 Volts, 50 Hz exhaust fan with louveres of Following Sizes including connection etc. complete as required . 300 mm
Sub Head-VI(Meter Board and Safety Items) Providng and Fixing carbon dioxide (CO2) Type fire Extinguishers of 4.5 Kg Capacity Conforming to IS: 2878-1976 and cylinders fully charged as required.
Provding of set of 4 Nos 9.5 Ltrs Capacity GI bucket painted in post office red colour with prior coat of red oxide paint and written with white paint"FIRE" and mounted on MS angle iron frame with capacity including filling of sand etc.
Supplying of First Aid Box as approved by St. John Ambulance Brigade/Indian Red Cross Conforming to IS:2217-1963
Providing of rubber Mat 1 mtr wide and 12 mm thick to withstand 15 KV dielectric strength as per IS: 5424-1969
Under Ground Cables and Accessories Supplying and Laying of 1 No. DWC High Density Poly ethylene Pipe having Corrugation on Outer wall and Plain surface inner wall Conforming to IS: 14930 Part-1 and 2 Complete with accessories for Protection of 1.1 KV Grade under Ground cable Directly in Ground at a Depth of 50 CM including excavation and Refelling the Trench Etc.as Required. 160mm/136mm
Supplying and Laying of 1 No. PVC/XLPE insulated and PVC Sheathed /XLPE Power Cable of 1.1 KV Grade of Following Sizes in the existing RCC/Hume/DWC/Stone ware/Metal Pipe as Required. 3.5 C X 185 Sq.mm A2XFY
3.5 C X 95 Sq.mm A2XFY
Supply and Making end Termination with Brass Compression Gland and Aluminium Lugs for the Following Sizes of PVC insulated and PVC Sheathed/XLPE Aluminium Conductor Cable of 1.1 KV Grade as Required 3.5 C X 185 Sq.mm A2XFY
3.5 C X 95 Sq.mm A2XFY
V 2 ASSOCIATES
M/S PATIAYA ENTERPRISES
M/S MAGOTRA ENGINEERS and CONTRACTOR
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .