construction of 220/132 kV Transformer Bays (HV & LV sides) along with Transformer Foundations at 220/132/33 kV GSS Begusarai and GSS Motipur, including erection, testing and commissioning of old 100 MVA Power Transformers.
141756
NIT No. 43/PR/BSPTCL/2026
Open Tender
ELECTRICAL
Patna
• Name and designation of the officer of the Bidder to whom all reference shall be made for expeditious technical co-ordinationn.
• Place of manufacture: (Item wise)
• Services or facilities available
• Availability of spare parts
ELECTRICAL
ITEM RATE
L1
1
26 documents required · 26 mandatory
₹11,800
Processing Fee: 11800
₹12.4 L
CE(O&M) , 4th Floor , Vidyut Bhawan - II , Pin Code- 8000001
14 Oct 2026
14 Oct 2026
12 Nov 2026
16 Oct 2026
11 Nov 2026
16 Oct 2026
5 Nov 2026
Name and Address of the fire protection system supplier
Number of Fire Protection System executed by the supplier and duration of successful operation as on date of bid opening for each type fire protection system
Automatic HVW / MVW spray type fire protection system
Automatic Hydrant type fire protection system
Confirm that fire protection system supplier have designed, erected, tested & commissioned fire protection system of each type as in 2(a), (b) & (c) above as per the recommendations of TAC of India or any other international reputed authority like (FOC, London or NFPA, USA et) and are in successful operation for at least two years.
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR ISOLATORS & ISOLATORS WITHOUT EARTHING SWITCHES
Description
Normal / Tendam
Name and manufacturer and country
Type Designation
Covering Standard
Class(Outdoor/Indoor)
Rated Voltage(KV)
Frequency (Hz)
Rated Current of Isolator(Amps) under site conditions
No.of Poles
Maximum capacity for interrupting magnetising current of transformer or charging current of line when equipped with arching contacts (Amps)
Maximum capacity for interrupting magnetising current of transformers or charging current of line when not equipped with arcing contacts(Amps)
No.of Operations possible without deterioration contacts
Rated Short time current (KA rms)
for 1 Sec.
for 3 Sec.
Rated peak Short circuit current(KA peak)
for 1 Sec.
for 3 Sec.
Rated current which can be made by earthing Switches(Amps)
Type of mounting
Phase Centres (mm)
Minimum Phase to Phase clearance (mm)
Minimum Phase to Ground clearance (mm)
No.of Pedestal Insulators per Phase
No.of breaks/Phase
Type of Interlock between isolating Switch & circuit breaker
Creepage Distance (mm) for heavily polluted atmosphere
Total
Protected
Main Contacts(fixed & moving)
Material
Whether contacts Silver Plated
Thickness of Silver coating(mm)
Contact area(sq.mm)
Contact Pressure(kg/cm²)
Current carrying capacity (Amps)
Arching Contacts
Material
Whether contacts silver plated
Thickness of silver coating(MM)
Current carrying capacity (Amps)
Type of bearings
Location of Bearings
Type of lubricant for bearings
Size of Weight of Switch base per pole(mm)
Weight of one complete pole(Kg.)
Operating mechanism
Manual Operation Whether separate operating mechanism for operating of main blades and earthing blades.
Height of operatring handle above foundation(mm)
Force required for 3 Phase operation (Kg.)
Length of operation handle (m)
Torque on operating rod to operate three pole gang- operated earthing switch(Kgm)
Weight of Operating mechanism (Kg.)
Electrical Operation
Motor(AC/DC)
Rated Voltage of Motor (Volts)
Power Required
for Closing operation (Watts)
for opening operation(Watts)
Running time of motor
for Closing operation (Sec.)
for opening operation(Sec.)
Auxiliary Switches
Number of normally open and normaly cleared
Rated Voltage
Rated Current
Test Voltage
Insulation Levels. Isolators and Isolator-cum-earthing switches
1.2/50 microsecond dry impulse withstand voltage (Positive & negative polarity (KV peak)
Across the Isolating distance
To earth and between Poles
One minute dry power frequency withstand voltage(Kv rms)
Across the Isolating distance
To earth and between Poles
One minute wet power frequency withstand voltage(KV rms)
Minimum visible corona discharge voltage (KV rms)
Insulation Strength of auxiliary gear (KV rms)
Maximum temperature rise of main contact at rated current corresponding to an ambient temperature of air in Shade(°C)
Maximum temperature rise of main contact at rated short time current (°C)
For 1 Sec.
For 3 Sec.
Rated mechanical terminal load (excluding wind loads(Kg.)
Galvanisation
Governing Standard
Method of Galvanisation
Weight of Zinc coating Gm/cm²
Loading details for design of foundation
for isolator
for isolator-cum-earthing Switch
Weight of 3 Phase Isolator complete with operating mechanism including support frame works. Etc. (Kg.)
Weight of 3 Phase Isolator-cum-earthing switch without operating mechanism(Kg.)
Weight of the heaviest package(Kgs.)
Space requirements I.e. (length, width & height)
Isolator
Isolator-cum-earthing switch
SCHEDULE FOR GUARANTEED TECHNICAL PARTICULARS FOR CONTROL CABLES
Description
Standard Applicable
Voltage Grade
Suitable for Service Voltage and System of Earthing.
Maximum Conductor temperature
Continuous
Short Time
Conductor(Copper)
Material
Form of Conductor
Number of Cores
Number of diameter (Stranded/Solid) of wire per core.
Insulation
Material Insulation
Thickness
Average Dielectric Strength
Dielectric Constant
Suitability with regard to temperature moisture ozone, acid and alkaline surroundings
Thickness of sheath over conductor, if any………..mm.
Material of sheath over cable
Thickness of sheath over cable………mm.
Electrical Performance
Conductor resistance at 20°C per KM
Maximum conductor temperature
Under full load
Under transient condition
Maximum operation Voltage……..Volts
Insulation resistance of 1 Km of cable at 20°C Mega Ohms
Power afactor or loss angle.
Tan delta of dielectric materials
Dielectric loss per km at rated voltage.
Power frequency with stand voltage KV rms.
Current loading data for the cable for specified operating temperature.
Type of Cable : Single core or stranded
In air in cable trays
In cable channels
In cleode ducts
In cable conduits and Pipes
Derating factors for
Ambient temperature
Grouping of 3 or 4 cables in air.in trays, channels for different spacing between cable and in closed ducts in touching position.
Allowable short circuit current for one Sec.
D.C.Withstand voltage
A.C. 50 Cycles/ second impedance.
A.C. 50 Cycles/ second impedance.
Weight of Cable
Wt. Of conductor per Km.
Wt. Of PVC compound per Km.
Complete wt. Per Km.
Wt. Of Armour
Overall diameter
Maximum length per drum
Drum dimensions
Gross weight of cable drum
Maximum Pulling tension
Minimum bending radius
I.S.I. Certification No.
GUARANTEED TECHNICAL PARTICULARS FOR PG CLAMPS/BUS SUPPORT CONNECTOR/T-CONNECTOR, PALM CONNECTOR SUSPENSION FITTING AND TENSION FITTING (TO BE FILLED BY TENDERER)
Description
For Zebra conductor
Maker's Name and Country
Material
Slipping Strength
Breaking Strength
Electrical conductivity
Resulting heating cycle test carried out
Value of Electrical resistance.
Corona formation voltage & Radio Interference level.
Standard specification to which conforms
Make of Bolts & Nuts
Packing Details
Drawings indicating all dimensions and material used to be submitted
Details of type test report submitted for each type of clamps and connector.
Weight of each complete set with bolts & nuts PG Clamp/T Connector/Bus support/Any other type
Non ferrous parts
Ferrous parts
Number and weight of only bolts & nuts used in each set.
Minimum Thickness ocurring at any part of the clamps connector.
SCHEDULE OF THE GUARANTEED TECHNICAL PARTICULARS FOR SF6 CIRCUIT BREAKERS
Description
Name of the manufacturer
Manufacturer’s type and designation
Governing Standard
Rated voltage (kV)
Maximum continuous rated service voltage
Frequency (Hz)
Class
Normal Current rating (amps)
Short time current rating (kA)
a) For 1 second
Maximum temperature rise over ambient 50°C due to rated current in main contacts, measured after breaking test
Rated short circuit breaking current
Making capacity ( kA peak)
Total break time (milli second)
Arcing time (milli seconds)
Making time (milli seconds)
Minimum reclosing time at rated interrupting capacity from the instant of trip coil energisation (milli seconds)
Minimum dead time
Data on restriking voltage for 100%, 50%, 30% rated capacity
Maximum interrupting capacity under phase opposition condition ( MVA - indicate value as per test report)
Maximum line charging current breaking capacity and corresponding over voltage recorded (Amps - indicate value as per test report)
Maximum line charging current breaking capacity without over-voltage exeeding 2.5 times the rated phase to neutral voltage (Amps - indicate value as per test report)
Maximum cable charging current breaking capacity and corresponding over-voltage recorded in test
Maximum shunt capacitor/Reactor bank switching capacity ( Single bank MVA)
Maximum breaking capacity on Kilometric faults (MVA)
Maximum over-voltage on switching transformer on no load and the charging current
Dry 1 minute power frequency test withstand voltage, for complete Circuit Breaker
Wet 1 minute power frequency test withstand voltage for complete Circuit Breaker
1.2/50 microseconds wave impulse withstand voltage for complete Circuit Breaker
Make and type
Weight
Transport Dimension
Insulation class
Visible Corona discharge voltage
Dry 1 minute power frequency flashover voltage
Wet 1 minute power frequency flashover voltage
1.2/50 microsecond impulse flashover voltage
Creepage distance to ground for heavily polluted atmosphere
Minimum clearance in air
No. of poles per Circuit Breaker
No. of breaks per pole
Total length of break per phase (mm)
Type of main contacts
Material of main contacts
Whether main contacts are silver plated ( Yes/No)
Thickness of silver coatings on main contacts
Contact pressure on main contacts (kg/sq. meter)
Type of arcing contacts
Contact pressure on arcing contacts (kg/sq. meter)
Type of auxiliary switches
Material of switch contacts
Whether contacts are silver plated (Yes/No)
No. of auxiliary switch contacts operating with all three poles or single pole of a breaker
No. of auxiliary switch contacts operating with individual pole of a breaker
No. of spare auxiliary switch contacts operating with all 3 poles or single pole of breaker
No. of spare auxiliary switch contacts operating with individual pole of a breaker
No. of operation possible without maintenance
Mounting flange details
Type of Operating mechanism
Tripping and Closing Circuit Voltage
Power required for trip coil
Power required for Closing coil
Details of push button switches
Contingencies for which alarm provided
Weight data for supporting structure
Weight of supporting steel structure per breaker
Time required for motor to charge the closing spring (minute)
Details of running hour meters
Details of start counter
Dimension of the control cabinets
Weight of control cabinet
Weight of 3 phase breaker complete with operating mechanism insulating supports frame work, etc.
Impact loading for foundation design to include dead load plus impact value on opening at max.
Weight of the heaviest package
Circuit Breaker
Air Compressor of SF6
Duration of service of the breaker after first filling of SF-6 without any replenishment
Type of flow of SF-6 (Axial/Radial)
Type of nozzles (single/double)
Material of Nozzles
Dead or live tank
Normal operating pressure (kg/sq.cm)
Normal gas density (gm/cc)
Minimum gas density ( gm/cc)
Requirement of gas per breaker(kg)
Lockout pressure ( Kg/sq.cm)
Details of gas fillers
Life of gas fillers
Guaranteed maxm. leakage per hour under climatic conditions specified in the tender during operation.
Working on single or dual pressure
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR 220 KV ,132kV AND 33kV CLASS GAPLESS LIGHTING ARRESTOR
Description
Model
Standard
No.of units per arrester
Class
Nominal System Voltage
Ratings(rms)
Highest System Voltage
Maxm. Continuous Operating Voltage(MCOV)
Nominal Discharge current(8x20)
Maximum residual voltage(8x20) (Lightning Impulse)
Switching current Impulse residual Voltage (45x90)
at 1000 AMP Maximum Minimum
at 1000 AMP Maximum Minimum
High current Impulse withstand
Steep Front Current Impulse Max. Residual Voltage (10 KA of 10 MS)
Lightning Impulse residual Voltage (KVP)(8x20)
Long duration Discharge Class-III
Energy discharge Capability (KJ/KV)
Pressure Relief Class
Max. Radio Interference Voltage at COV(MV)
Reference Voltage at AMB, TEMP
Reference Current at AMB, TEMP
Resistive/Capacitive Components of Continuous Current at Ambient temperature.
Power Freq. O/v Capability (RMS) for
Capability of wiothstand over voltage immediately after discharge Energy Equivalent to maxm. capability of the Arrester
Arrester Housing Insulation withstand valuses
Lightning Impulse
Switching Impulse
Power Frequency Dry/Wet.
Creepage Distance (mm)
Cantilever Strength
Voltage/Time Curve
Other dimensional details
Diameter of Zinc Oxide blocks(in mm)
Height of discs (in mm)
Energy dissipation capability of the disc in assembled condition inside LA
Calculation showing KJ/per KV rating of the disc.
Details of thermal circuit employed for dissipation of heat.
Copy of latest type test Report furnished or not
Height of complete unit from base to lineside(mm)
In case ring type blocks are used indicate dimension of O.D & I.D.
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR CURRENT TRANSFORMER
Description
Manufacturer's name & type designation
Rated Voltage
Rated Primary Current
Rated Secondary current
No. of Cores
Secondary Voltage
Short time thermal rating of Primary(Amps)
One Second
Three Second
Rated dynamic current of Primary (Peak value)
Rated continuous thermal current
Temperature rise at rated continuous thermal current over ambient temperature of 50°C.
Winding
Oil at the top
Exposed current carrying parts.
One minute power frequency dry withstand test voltage(KV rms)
Magnetisation curve of CT core
Characteristics:-
Ratio and phase angle curves
Magnetisation curves
Ratio correction factor curves
Limits of composite error at rated primary saturation current (for protective CT core)
Variation in ratio and phase angle error due to variation
Voltage by 1%
Frequency by 1 %
Current density in primary windings
Weight of coil
Total weight
Mounting details
Overall dimensions
Overall creepage distance in mm
Total
Protected
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS OF DISC INSULATORS
Description
Disc insulators
Maker's name & Address
Type of Insulator
Size & Designation of Ball & Socket
Disc Diameter(mm)
Unit Spacing(in mm)
Creepage distance (in mm)
Colour
Surface
Electro-Mechanical Strength(in Kg.)
Minimum failing load(in kg.)
Impulse withstand test voltage
Impulse withstand test voltage (1.2x50 Micro-second-Ve wave, KV(Peak)
Power frequency dry withstand test voltage, KV rms
Power frequency wet withstand test voltage, KV rms
Power Frequency dry flashover voltage, KV rms
Power frequency wet flashover voltage,KV rms
Impulse flash over voltage 1.2x50 micro Sec. + Ve wave , KV (Peak)
Impulse flash over voltage 1.2x50 micro Sec. - Ve wave , KV (Peak)
Power frequency puncture voltage, KV rms
Net weight of single Insulator unit(in kg.)
I.S.S. to which insulator will conform
Type of locking Device and its dimension
Reference of drawings enclosed
Reference of Type test and other Test Reports enclosed.
Whether inter changeability guaranteed
Details of Galvanisation of ferrous parts
Other details, if any
SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS FOR HARDWARE FITTINGS(MOOSE, PANTHER AND E/W)
Description
Accessories/Fittings for ACSR Panther/ Moose Conductor.
M.S.COMP.JOINT
Manufacturer's name/Address
Material
Outer sleeve
Inner Sleeve
Outside dimension of sleeve:
Before Compression-
After Compression
Length of Sleeve before compression
Aluminium
Steel
Aluminium
Steel
Weight of Sleeve:
Aluminium
Steel
Total
Slipping strength expressed as percent age of U.T.S. of ACSR Conductor
Breaking strength expressed as percentage of UTS of ACSR Conductor
Conductivity expressed as % of conductivity of ACSR Conductor
Resistance expressed as percentage of measured resistance of equivalent length of conductor
Reference drawing
I.S.S.to which conforms
Galvanisation
Packing details
Any other particulars if any
REPAIR SLEEVE:
Manufacturer's name/Address
Material
Outside dia of sleeve :
Before compression
After compression
Length of Sleeve;
Before compression
After compression
Weight of sleeve
Breaking strength expressed as percentage of UTS of ACSR Conductor
Conductivity expressed as % of conductivity of ACSR Conductor
Resistance expressed as percentage of measured resistance of equivalent length of conductor
I.S.S.to which conforms
Reference drawing
Packing details
Any other particulars if any
HARDWARE FITTINGS
Disc Insulators for which suspension/Tension fittings should match
Type of insulator
Size & designation of ball & Socket
Porcelain disc dia
Unit spacing
Electro-mechanical Strength
Standard to which disc will conform
INSULATOR STRING ARRANGEMENTS
No.of disc per string
Length of string assembly(in mm)
Electro-mechanical strenght(in Kg)
Creepage distance (mm)
Reference drgs.
Weight of String assembly
CLAMP:
Manufacturer & Name & Address
Manufacturing Process
Material
Breaking strength (minimum)
Slipping strength
Angle of inclination of jumper terminal
ISS to which conforms
HARDWARE (Material)
Socket Clevis
Ball Clevis
Anchor Shackles
Ball Hooks
Chain link
Socket Link
Yoke Plate
Shackle
ARCING HORN
Material
Nuts & Bolts
Reference drawing
Test Report
Any other particulars if any
PERFORMED ARMOUR RODS
Maker's name & Address
Total weight of a set of armour rods(Kg)
No. of wire per Set
Diameter of wire
Length of wire
Percentage tolerance on length of dia of wire
Overall dia of conductor after use of the armour rods(mm)
Centre making provided (Y/N)
Pitch of Helix
Direction of lay
Corona & RI performance values
Efficiency of damping
Packing details
End condition
Any other particulars if any
Reference drawing
VIBRATION DAMPERS
Maker's name/Address
Total wt. Of each damper(Kg.)
Diameter of balancing weight(mm)
Length of balancing weights (mm)
Weight of each balancing weight(Kg)
Tolerance in Balance weight %
Material, quantity length and size of messenger cable
Slipping strength of messenger cable(Kg)
Diagram showing power dissipated by the damper for various vibration frequency & amplitude
Damping effeciency of damper
Natural frequency of the damper
Upper CPS
Lower CPS
The number of dampers required per span for various span length and their spacing
Position of fixing damper on the conductor from the clamp mouth
At tension Points :
First damper(mm)
Second damper(mm)
Third damper(mm)
At suspension Points (after fixing armour rod)
First damper(mm)
Second damper(mm)
Third damper(mm)
Corona & RI performance value
Packing details
Reference Drg.
ACCESSORIES/FITTINGS FOR 7/9 SWG EARTHWIRE
COMPRESSION JOINTS:
Manufacturer's name & Address
Reference Drawing
Material
Weight
Minimum failing load
Galvanisation
Ferrous part
Quality of Zinc used
No.of dips which the materials can withstand
2 minutes
½ minutes
Standard to which conforms
Packing details
Any other particulars
VIBRATION DAMPER
Manufacturer's name & Address
Reference Drawings
Total wt. Of each damper
Dia of balancing wt. (mm)
Length of balance wt.(mm)
Weight of each balance wt.
Tolerance in balance wt.
Material quality, length size of messenger cable
Slipping strength of messenger cable(Kg)
Diagram showing power dissipated by the damperfor various vibration frequency and amploitude
Damping effeciency by damper
Upper CPS
Lower CPS
No.of damper required for span for various span length and their spacing
Position of fixing damper on the wire from the damp clamp mouth
Packing
Any other particulars
SUSPENSION & TENSION CLAMPS WITH FLEXIBLE COPPER BOND:
Manufacturer's Name/Address
Reference Drawing
Materials
Weight
Slip Strength
Minimum failing load
Galvanisation:
Ferrous part
Spring Washer
Quality of Zinc
No.of dip which the clamp can withstand
3 minutes
½ minutes
Standard to which conforming
composition of material
Packing details
Any other Particulars
REPAIR SLEEVE:
Manufacturer's name & Address
Material
Outside dia of sleeves
Before Compression
Aftere compression
Length of Sleeve
Before Compression
Aftere compression
Weight of Sleeve
Conductivity
Breaking strength
Resistance
ISS to which conforms
Reference Drawing
Packing Details
Any other particulars
SCHEDULE OFGUARANTEED TECHNICAL PARTICULARS OF POST INSULATORS
Description
Maker's name & Address
Type of insulator
Dimension
Height in mm
Maximum diameter in mm
Minimum diameter in mm
Creepage distance in mm(not less than)
Total
Protected
Cantilever in Kg.
Upright
Invereted
Tensile strength
Torsional Strength in Kg.
Visible discharge test voltage (Power frequency )KV rms
1 min. P.F.witstand Test Voltage in KV (rms)
Impulse Voltage withstand test in KV (Peak) positive & negative
Power frequency Flashover Voltage in KV(rms)
Impulse flashover voltage in KV (Peak) positive & negative
Net weight per unit
Name of Bidder:
Address of bidder:
Telegraphic address of the Bidder.:
Name and designation of the officer of the Bidder to whom all reference shall be made for expeditious technical co-ordinationn.
Place of manufacture: (Item wise)
Services or facilities available:
Availability of spare parts.:
Bidder's proposal number & date:
Offer is valid upto
i) Earnest money deposited or not
Whether terms of taking over, guarantee, Insurance are acceptable or not
Whether the delivery & execution schedule indicated in the specification acceptable
Whether liquidated damage for delay in delivery and Execution as indicated in the specification is acceptable
Whether latest copy of income tax clearance certificate and sales tax certificate enclosed with the bid or not.
Whether terms of payment indicated in the specification acceptable.
Whether terms as stipulated under security deposit /CONTRACT PERFORMANCE GUARANTEEEis acceptable.
Whether bank guarantees as stipulated under advance payment, Security deposit and performance guarantee clause of the Specification will be submitted
Whether agreeable to enter into a contract (As per the Performa enclosed) in the event of an order.
I) Are the prices quoted in price bid FIRM(only firm prices are acceptable)
Whether prices quoted are also applicable On reduced quantity or not? Rebate, on any account, if any may be mentioned.
Whether a statement showing deviations for General conditions enclosed.
Whether a statement showing deviations from Technical specificationn enclosed.
Whether the bidder is agreeable to execute the Contract in case deviation stipulated by him are not acceptable to BSPTCL
a) Whether excise duty is leviable? (for the items to be supplied by the contractor directly to the BSPTCL.)
a) Whether sales tax is chargeable? (for the items to be supplied by the contractor directly to the BSPTCL.)
Whether certificate of past performance enclosed or not
Annual details of similar works executed for Past 5 years.
Whether unit FOR destination price (landed) of all individual items quoted in the price bid or not?
Whether all commercial terms are accepted or not
Whether all technical specifications accepted or not
Whether prices are quoted for all works including Design, Engineering, drawing, supply of materials / Equipments, erection and commissioning of complete Substation and .s (all works involved.)
Power of Attorney authorizing the signatories of the tenderer to fill up & sign the tender is furnished in the tender or not.
Whether certificates granted by bankers regarding credit limit allowed to the Contractor and Bankers assessment of their Solvency submitted
Whether Audited balance sheets of last five years submitted or not
Furnish MAAT for last five financial years i.e.
To confirm whether the price for “supply” and “erection component” for sub station automation system has been quoted in complete shape considering the system as a whole including mandatory spare . Also, that the break up and details of different component of SAS has been described in complete shape in the techno commercial bid plus price schedule. Also that the quoted price of project includes provision of guarantee to be extended by contractor for SAS for a period of 5 years, after successful availability test.
Confirm that the total price for the complete project including design & drawing has been furnished and no extra claims shall be made for any other work required for completion of the project
POINTS TO BE CONFIRMED OR CLARIFIED BY THE BIDDER
Offer must be made complete in all respects as per Technical specification
Prices of spares and tools and plants shall be furnished separately by the bidder on FOR site basis inclusive of all taxes etc. BSPTCL reserves the right to vary the quantity of spares during order.
All distribution Boards shall be fully enclosed, cabined type, fabricated from CRCA sheet steel minimum thickness as Specified in specification suitable for either wall/column/floor mounting. Indoor panels shall be dust and vermin prof. Outdoor panels shall be weather proof with canopy.
Though in the Specification for some equipments, particular make and type have not been mentioned, Equipments of make and types which are being used satisfactorily in BSPTCL, will be preferred. However, in case of equipments of makes, not supplied earlier to BSPTCL the credentials and updated performance reports regarding supplies made to other central and state Power utilities should be furnished. BSPTCL reserves the right to opt for the make and type.
Only type tested equipments and materials shall be supplied by the contractor
All street light poles must have independent LILO junction box, isolating switches and fuses.
For inside Control Room area and separate switchyard area tenderer shall have to arrange independent cable trays/racks for entire scheme with separate arrangement for D.C. cables.
Tenderer shall note and confirm that their scope of work shall fully comply with the requirement as detailed in BSPTCL's Specn.
The Insurance covering Transit Risk, Transportation Risk, handling (during loading and unloading), risk during storage, erection, commissioning, theft and fire shall be done and borne by the Tenderer for all the equipment/items devices pertaining to the sub-stn under turnkey package till the installation is handed over to BSPTCL authorities.
Tenderer to note and confirm that the freight charges including handling charges during loading and unloading shall be borne by the bidder. All the materials sent by the Tenderer to site by road transportation shall be suitably packed. No separate freight charges shall be paid by BSPTCL.
Tenderer to note and confirm that storing of all materials under this contract shall be within the Tenderer's scope of work and adequate security arrangement for the stores as well as in the areas of erection till the date of handling over, shall be tenderer's responsibility.
Tenderer to note and confirm that the BSPTCL and his duly authorised representative shall have an access to the contractor's premises, manufacturer's work for all tests of the equipment, cable etc. as listed in the schedule of tender. Inspection and testing shall be carried out as per tender specification.
All plants/equipment and materials to be supplied for the project shall be guaranteed as per BSPTCL specifications.
Tenderer to note and confirm that all the supplies shall conform to relevant ISS, IEC, I.E. RULES and BSPTCLspecifications. No material will be accepted unless covered by relevant ISS, IEC on any other relevant approved specification as required.
Tenderer to note and confirm that the installation shall be complete in all respects for efficient and trouble free service For this purpose any part or parts required whether specifically mentioned or not shall be deemed to be within tenderer's Scope.
Tenderer to note that erection tools and tackles as may be required to complete installation work shall be arranged by you at no extra cost to BSPTCL. All per commissioning checks and commissioning tools and istruments shall have to be arranged by the bidder at no extra cost to BSPTCL.
Tenderer to note and confirm that connectors, hardwares required for substation shall be quoted in lump sum basis which will be utilised in switchyard and shall be as per the approved drawing. These should be type tested.
Tenderer to note and confirm that without the written consent of BSPTCL they will not assign or sublet the total contract or any part there of other than for any part of the work for which the maker are named in the contract. Such contract if given shall not relieve him from any obligation, duty or responsibility as per the terms and conditions of the specification and the contract.
Tenderer to note and confirm that all the cable trays/racks/ladders/cable end boxes/conduties/electrical equipment (such as switchboard, panels, junction boxes etc shall be effectively grounded with 50x6 Flat.)
Tenderer to note and confirm the following for the civil work required to complete foundation under the scope of vendor on turnkey basis.
Tenderer to note and confirm the following drawings and details in quadruplicate shall be furnished as per tender specifications
Tenderer to note and confirm that the minimum illumination level of various area shall be as under (data to be used for reference purpose) which shall also conform to the latest CBIP & ISS.
GENERAL
Tenderer to note and confirm that AC/DC change over BSPTCL Indoor type suitable for mounting complete with AC/DC conductor, auxiliary conductor, timer, test push button, DC Voltmeter, DC feeder shall have to be included in your price.
Tenderer to note and confirm that the lighting switch boards flash type with 5 A switch and 5A socket including space for fixing electronic hand regulator shall be used.
Tenderer to note and confirm that any additional requirement for AC/DC changeover board, lighting junction boxes and lighting board are required to fulfill the entire installation, depending on the requirement, shall be within the scope of work with no extra cost to BSPTCL.
Tenderer to note and confirm the following for the civil work required to complete foundation under the scope of vendor.
Tenderer to confirm that they will furnish following documents:
Sales tax on Works contract, Turnover Tax on any other similar taxes under the Sales Tax, Act, as applicable, are included in the Bid/tendered price and BSPTCL/Purchaser shall not bear any expenditure/liability on this account. Entry tax, if any shall be extra.
The tenderer prices quoted in price schedule included all import duties and levies including licence fees lawfully payable by the contractor on imported goods/items and other taxes and duties on bought-out components, materials, equipments and other items and no such taxes, duties & levies shall be additionally payable by the BSPTCL. Tenderer are also to confirm that no taxes and duties (except octrai/entry tax if applicable) shall be payable by the BSPTCL/Purchaser on bought-out items which are dispatched by the Sub-vendors of the contractor directly to the project site on sale-in-transit basis. However, BSPTCL shall provide necessary concessional sales tax declaration from, as concessional sales tax has been included in the price for such sale in transit transactions. The applicable Octroi/entry tax, as indicated in price also be reimbursed by the BSPTCL subject to furnishing of documentary proof.
It is hereby confirmed that the bidder/tenderer is making the offer on the basis of a divisible supply-cum-Erection Contract on a single source responsibility basis. The supply portion of the Contract will relate to supply of equipments/materials and erection portion will relate to transportation, insurance, storage, intallation, construction, stringing, testing and commissioning etc as defined in price schedules. The Tender/bidder has no objection if the contract is considered to be placed in to separate contracts, i.e., one contract for supply of all equipment on ex-works basis and second contract for all services such as in land transportation, insurance, handling at site, storage, isurance, erection, testing and commissioning etc of materials/ items as defined in the tender specifications.
It is hereby confirmed that if any income-tax, surcharge on income tax or any other corporate tax is applicable/payble under the law, the same shall be paid by the contractor.
It is confirmed that the contract shall be executed strictly in accordance with the specifications and documents except for the variations and deviations, all of which have been detailed out exhaustively in the following schedules irrespective of what soever has been stated to the contrary any where else in the tender/offer/bid.
Schedule of deviations against technical specifications
Schedule of deviations against general conditions of the contract.
Schedule of revision of prices against deviations as detatiled under schedule "C" and "D"
Confirm that the following clauses as specified in the tender specifications are accepted unconditionally and no deviations/exceptions are taken on any account whatsoever.:
Prices
Security Deposit
Earnest Money
Liquidated damage for delay,stage penalty, incentives.
Guarantee
Terms of payment
Performance guarantee
Taking over
Insurance
Negligence
Agreement
Time for execution of the contract
Confirm that additional conditions, deviations, if any, found in the proposal documents other than those stated in the deviation schedules, save the pretaining to any rebate, offered, shall stand with drawn.
Unit rates of items/equipments/works as and where required have been furnished
The details of equipments/materials proposed to be supplied as bought out items have been furnished in a separate schedule.
The required documents related to the pre-qualification of he tenderers as detailed in the tender specifications has been furnished in the tender. The documents for the fulfillment of the requirement of the tender specifications have been furnished.
Confirm that if the offer is submitted against the tender is accepted by the BSPTCL, the contractor agree to submit engineering data, provide services and complete the entire work in accordance with schedule indicated in the tender/offer. It has been clearly understood that the time for completion of the project is the essence of the contract and hence the execution schedule shall be strictly adhered to the execution schedule has been furnished with the offer.
Separate schedule for each item for which L.S. price have been quoted should be furnished with part I of the tender.
Confirm that all equipments and materials confirming strictly to the tender specification only shall be offered to be delivered in case the order is placed on the bidder. In case of any deviations in the technical specification or make of offered materials/equipments, the BSPTCL shall not be responsibble for any delay even if it is approved.proved.
Confirm that no extra claim shall be entertained by the BSPTCL for the specified scope of work
To confirm whether the price for “supply” and “erection component” for sub station automation system has been quoted in complete shape considering the system as a whole including mandatory spare . Also, that the break up and details of different component of SAS has been described in complete shape in the techno commercial bid plus price schedule. Also that the quoted price of project includes provision of guarantee to be extended by contractor for SAS for a period of 5 years after successful availability test.
To confirm whether 10% BG would be furnished by that contractor towards employing vendor support if any during guarantee period of SAS as per Cl. 1.3.39.1 of Vol. I of tender specification. Please specify clearly whether support of vendor would be obtained for SAS system or the contractor itself is capable for design, manufacture, supply and installation of SAS system.
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'P-III'
Description (Clause/ Page)
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'C'
Description (Clause/Page)
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'C'
Description
F.O.R. Site
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'E'
Description
F.O.R. Site
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'F'
Name of drawing
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'G'
Details of works
Details of works
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'H'
Name of equipments & works
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'I'
Deviation if any
Increase
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'J'
We have noted that to be qualified for award, tenderers shall provide evidence satisfactory to the BSPTCL of their capability and adequacy of resources to carry out the contract effectively. The following information/ documents are furnished/submitted along with our bid :
Copies of original documents defining the constitution of legal status, place of registration and principal place of business; written power of attorney of the signatory of the bid to commit the bidder.
The audited balance sheets for the last five years.
Other details in support of Qualifying Requirement have been filled in formats given at the subsequent pages of this Schedule. All individual firms and each Partner of a Joint Venture bidding for the package are requested to complete the information in the form. The requisite information to be provided for all firms (individual sole bidders as well as partner of Joint Venture bidder).
Joint Venture Summary : If bidder is a joint Venture of two or more Partners.
The following is the list of orders executed by us for 220 KV and above voltage Sub-Station and ., the details of which are furnished in the support of Qualifying Requirements.
Customer
No of 220 KV or above line Bays
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'PXX-2'
Financial Year (Specify)
In accordance with the tender documents, Certificate(s) from Banker issued on ____________ (date) as per requisite format, various fund based/non-fund based limits sanctioned to the Bidder or each member of the Joint Venture and the extent of utilisation as on date is/are enclosed at _________________________.
The monthly cash flow projection for execution of the Contract is as follows :
Month
Details of Bidder's Banks :
Address of Banker
Details of Litigation History
Award for or against Applicant
Certify that the above informations furnished by me are true and correct to the best of my knowledge.
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'PXX-4'
Item Description
Description of Work
Finalisation of Sub - Vendors
Completion of detailed engineering
Procurement of raw materials / bought out items
Manufacturing
Type testing (if required)
Despatch and receipt at site
Soil investigation
Establishment of site office
Erection in during civil / works
Testing & Commissioning
Commissioning & issuance of taking over
Required supplementary information and supportive document to complement the bid be submitted as attachment to shedule 'PXX-VI'
Description
SCHEDULE "A" OF PRICE - P-I
SCHEDULE "B" OF GENERAL PARTICULARS -PII & III
SCHEDULE "C" OF DEVIATIONS FOR SUPPLY AND DELIVERY AGAINST TECHNICAL SPECIFICATION -PIV
SCHEDULE "D" OF DEVIATIONS AGAINST GENERAL CONDITIONS OF THE CONTRACT - PV
SCHEDULE "E" OF ERECTION AND MAINTENANCE TOOLS. - PVI
SCHEDULE "F" OF SPARES - PVII
SCHEDULE "G" OF DRAWINGS - PV III
SCHEDULE "H" OF PAST EXPERIENCE - PIX
SCHEDULE "I" OF DELIVERY - PX
SCHEDULE "J" REVISION OF PRICES - PXI
COPY OF ELECTRICAL CONTRACTOR’S LICENCE.
AUTHORITY OF SEEK REFERENCES FROM THE TENDERER’S BANKERS.
FOR LETTER OF UNDERTAKINGS - PXV
BALANCE SHEET FOR LAST 5 YEARS i.e, PROFIT & LOSS STATEMENT. (FURNISH MAAT VALUE)
POWER OF ATTORNEY IN RESPECT OF TENDERERS SIGNATURE - PXVIII
ATTORNEY IN RESPECT OF JOINT VENTURES-PXIX
FOR QUALIFICATION REQUIREMENT - PXX
FOR TENDER TECHNICAL BID - PXXI
FOR TENDER PRICE BID - PXXII
DETAILS OF LIQUID ASSETS.
FOR EVIDENCE OF ACCESS TO OR AVAILABILITY OF CREDIT FACILITIES - PXXIV
FOR DETAILS ABOUT BOUGHT OUT ITEMS-PXXV
WORK COMPLETION SCHEDULE FOR SUB STATION WORK AND TRANSMISSION LINE -PXXVI
WORK COMPLETION SCHEDULE FOR WORK -PXXVII
EMD- PXXVIII
UNPRICED-PRICE SCHEDULE TO BE FURNISHED ALONGWITH PART-I OF TENDER
AN AFFIADEVIT CONFORMING THAT ALL THE DETAILS AND DOCUMENTS FURNISHED ALONG WITH THE TENDER ARE CORRECT AND TRUE COPIES OF ORIGINALS
Copies of original documents defining the constitution or legal status, place of registration and principal place of business, written power of attorney of the authorized signatory of the bid to commit the tender.
Total annual turnover in construction work of a similar nature performed by the tenderer in his own name (not by any other company whose name has subsequently been changed so as to form the current tenderer) in each of the last five years.
Experience in executing similar projects (Nature & Volumes) for each of the last 5 (five) years, and details of work in hand and contractual commitments, clients who may be contacted for further information on those contracts. The copy of performance certificate issued by end users/utilities may be furnished.
Qualifications and experience of key site management and technical person proposed for the contract.
A certificate from a bank or reputable firm of accountants conforming the liquidity (liquid asset and credit facilities) of the tenderer at a date one month prior to the last date for submission of tenders.
Solvency Certificate to be furnished.
Evidence of adequacy of working capital for this contract i.e. evidence of access of line (s) of credit and availability of other financial resources.
Authority to seek references from the tenderers bankers.
Information regarding any current litigation in which the tenderer is involved, the parties concerned and disputed amount.
Statement of safety policy and safety statistics for the last 5 years.
Copy of QA Certification and associated documentation.
Please note that the non submission of any document and confirmation of the above matters shall lead to out right rejection of the tenders/ offers/ bids without any further correspondence.
NAME OF BIDDING FIRM
ADDRESS
Fax No.
MODE OF APPLICATION(Single/JV)
APPLIACANT INFORMATION
Year of Incorporation:
IV Applicant:
Year of Incorporation:
CONTACT PERSON
AUTH. SIGNATORY
N= No. of years prescribed for completion of works for which bids are invited. (considering the project completion period of 24 months, N=2, for 18 months N=1.5, For 15 Months N=1.25)
N= No. of years prescribed for completion of works for which bids are invited. (considering the project completion period of 24 months, N=2, for 18 months N=1.5)
Description of Item
220 kV EQUIPMENT
Circuit Breaker (3 phase)
3150A, 50KA for 1sec with support structure,SF6,3P,marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) (C2-M2 type with Spring- Spring mechanism).
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 50 kA for 1 sec with two earth switch (Double break Isolator)
1600 A, 50 kA for 1 sec with one earth switch (Double break Isolator)
1600 A,50 kA for 1 sec without earth switch (Double break Isolator) (Tandem arrangement)
CURRENT TRANSFORMER 5 Core (1 phase) WITH MARSHALING BOXES TERMINAL CONNECTORS (The windings of CT shall be of Copper only)
1600-800-400-200/1-1-1-1-1 A, 150% extended current rating, 50 kA for 1sec, 0.2s class 5 core
216 kV Surge Arresters (1 phase) class-IV (SH Class) with terminal connectors suitable for twin moose and surge counter etc.
Portable discharge rods
ERECTION HARDWARE (220 kV)
Erection Hardware (Without BPI)
Transformer bay
220 kV Solid Core, Bus post Insulators (including requirement for wave trap)
132 kV EQUIPMENT
Circuit breaker (3 phase)
3150 A, 40 kA for 1sec SF 6 CB, C2-M2 Class with support structure, marshalling boxes, terminal connectors suitable for twin moose etc.(current rating shall be equal to the current rating for which the short cuircuit test reports shall be furnished.) (Spring- Spring Mechanism )
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 40 kA for 1sec with one earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)(Tandem arrangement)
2500 A, 40 kA for 1sec without earth switch (Double break high level beam mounted Isolator)
145kV (5-Core) CT (1 Ph.)with marshelling boxes & terminal connectors (The windings of CT shall be of Copper only)
1200-600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,40 kA with 150% extended current rating with marshalling boxes, terminal connectors suitable for twin moose etc.
120 kV Surge Arresters SH class-IV(I PHASE)with terminal connectors and surge counter.
ERECTION HARDWARE (132 kV)
Insulator strings antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, Connectors (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.)
Transformer bay
132 kV Solid Core, Bus post Insulators for erection hardware
CONTROL & RELAY PANELS
220 kV (Simplex panels)
Circuit breaker Relay Panel All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy. Bay control unit (BCU) along with bay mimic to be provided for each bay separately in Control panel. ABT Energy Meter (0.2s class) of CR Panels – The metering system shall be housed in rack with draw out type feature capability for inserting the meter module. The test terminal blocks shall be provided on all meters to facilitate testing of meters in service. Main energy meter & back up meters shall be having the feature of draw out type modular units and shall have automatic CT short circuiting so that meter can be taken out for testing without shut down requirements. The same Energy meters could be used as either ABT or NON ABT meters. It shall have the facility of interchangeability between NON ABT to ABT Energy Meter at site as per reqesuirement. The above Energy metres should have been type tested for compliance of above features with proven performance. (The meters must be meeting all complaince of SAMAST). Note:- The communication system at GSS required for communication from remote end to SLDC Patna will be under scope of Bidders.
CB relay panel with A/R
220/132/33 KV Transformer protection panel (HV and IV sides) with numerical differential protecton relays with earth fault/ over current relay complying to IEC 61850 (Edition-2) Protocol with optical fiber ports sufficient DI/DO ports for scheme with additional 6 DI and 6 DO Ports for spare. All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy and 0.2s class ABT energy meters (with Modem) on both HV & IV side to be provided. (Relay shall have feature of PRP and Load blinder). Separate REF relays for HV and IV both with complete scheme for protection to be provided.
Bus bar protection panel (bus bar protection will be low impedance, de-centralised type and will have minimum 4 zones with numerical type of relays complying IEC 61850 (Edition-2) Protocol as and where applicable with complete cabling works.(covering entire scope of future with necessary software for future extension)
FIRE PROTECTION SYSTEM
Portable Fire Extinguishers
6 Kg DCP Type
6.5 Kg CO2 Type
12 Fire buckets with covered stand
Complete HVW spray system with complete O/G & U/G piping and accessories etc. (all items) with all required materials and equipments out side the pump house for 100MVA, 1 Nos, 220/132 Power Transformers as per tender specification. - For 1x100MVA Transformer
Outdoor lighting (Switchyard and Street lighting) (All Luminaire used shall be of LED type only. However, conventional type Luminaire (HP Sodium vapour Lamps in High Flood Lighting) may be used additionally in Switchyard area)
Lighting panel
Lighting panel (Outdoor) Type ACP - 3
LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements)
Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type - MP : as per Tech.Specification
Lighting fixture Type - SC : as per Tech.Specification
15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO)
Cables alongwith associated accessories like clamps, glands, lugs and straight joints etc. (Actual Quantity shall be as per approved cable schedule)
Power cables (PVC) 1.1 kV
Any other size as per requirement
Control cable (PVC) 1.1 kV
Materials for earthing mat with all materials and accessories as well as spikes as per requirement of design as per IEEE standards for complete earthing of grid Sub-Station with the followings. (The quantity is tentative and final quantity will depend on actual design):-
40 mm MS rod for main earth mat (To be procured directly from SAIL/RINL/TATA or from their stockyard)
75x12 mm G.I Flats for risers for equipments, columns and structures
50x6 mm G.I flats for risers for all other equipments etc.
Materials for Earthing pits with supply of all earthing materials including base plate etc. complete in all respect as per Technical Specifications
Treated Earth Pit (Earth electrode to be erected by rigging 140/150mm dia bore using power rig and to be filled with mixer of A4 grade bentonite powder, salt and available site soil)
Un-Treated Earth pit
Sub- Station galvanized Steel structure (220 kV, 132 KV & 33 KV) (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design)
Lattice structure with fasteners etc. (for Gantry, Tower, Beam)
Standard structure for equipment support i.e. Pipe type (other than CB)
Cable Racks as per design requirement for Switchyard and Control room building.
Sub-Station automation system comprising of necessary equipments & materials wth networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet with Part-I of the tender) whereever applicable, the communication protocol shall be preferably IEC 61850 (Edition-2). SAS to be integrated with the original implemented SAS of M/s GE. It is sole responsibility of bidder/contractor to integrate the SAS with the existing SAS and transportaion of data upto SLDC, Patna.
Tripping coil 220KV Breaker (With flange)
Closing coil 220KV Breaker (With flange)
Tripping coil 132KV Breaker (With flange)
Closing coil 132KV Breaker (With flange)
Description of Item
220 kV EQUIPMENT
Circuit Breaker (3 phase)
3150A, 50KA for 1sec with support structure,SF6,3P,marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) (C2-M2 type with Spring- Spring mechanism).
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 50 kA for 1 sec with two earth switch (Double break Isolator)
1600 A, 50 kA for 1 sec with one earth switch (Double break Isolator)
1600 A,50 kA for 1 sec without earth switch (Double break Isolator) (Tandem arrangement)
CURRENT TRANSFORMER 5 Core (1 phase) WITH MARSHALING BOXES TERMINAL CONNECTORS (The windings of CT shall be of Copper only)
1600-800-400-200/1-1-1-1-1 A, 150% extended current rating, 50 kA for 1sec, 0.2s class 5 core
216 kV Surge Arresters (1 phase) class-IV (SH Class) with terminal connectors suitable for twin moose and surge counter etc.
Portable discharge rods
ERECTION HARDWARE (220 kV)
Erection Hardware (Without BPI)
Transformer bay
220 kV Solid Core, Bus post Insulators (including requirement for wave trap)
132 kV EQUIPMENT
Circuit breaker (3 phase)
3150 A, 40 kA for 1sec SF 6 CB, C2-M2 Class with support structure, marshalling boxes, terminal connectors suitable for twin moose etc.(current rating shall be equal to the current rating for which the short cuircuit test reports shall be furnished.) (Spring- Spring Mechanism )
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 40 kA for 1sec with one earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)(Tandem arrangement)
2500 A, 40 kA for 1sec without earth switch (Double break high level beam mounted Isolator)
145kV (5-Core) CT (1 Ph.)with marshelling boxes & terminal connectors (The windings of CT shall be of Copper only)
1200-600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,40 kA with 150% extended current rating with marshalling boxes, terminal connectors suitable for twin moose etc.
120 kV Surge Arresters SH class-IV(I PHASE)with terminal connectors and surge counter.
ERECTION HARDWARE (132 kV)
Insulator strings antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, Connectors (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.)
Transformer bay
132 kV Solid Core, Bus post Insulators for erection hardware
CONTROL & RELAY PANELS
220 kV (Simplex panels)
Circuit breaker Relay Panel All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy. Bay control unit (BCU) along with bay mimic to be provided for each bay separately in Control panel. ABT Energy Meter (0.2s class) of CR Panels – The metering system shall be housed in rack with draw out type feature capability for inserting the meter module. The test terminal blocks shall be provided on all meters to facilitate testing of meters in service. Main energy meter & back up meters shall be having the feature of draw out type modular units and shall have automatic CT short circuiting so that meter can be taken out for testing without shut down requirements. The same Energy meters could be used as either ABT or NON ABT meters. It shall have the facility of interchangeability between NON ABT to ABT Energy Meter at site as per reqesuirement. The above Energy metres should have been type tested for compliance of above features with proven performance. (The meters must be meeting all complaince of SAMAST). Note:- The communication system at GSS required for communication from remote end to SLDC Patna will be under scope of Bidders.
CB relay panel with A/R
220/132/33 KV Transformer protection panel (HV and IV sides) with numerical differential protecton relays with earth fault/ over current relay complying to IEC 61850 (Edition-2) Protocol with optical fiber ports sufficient DI/DO ports for scheme with additional 6 DI and 6 DO Ports for spare. All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy and 0.2s class ABT energy meters (with Modem) on both HV & IV side to be provided. (Relay shall have feature of PRP and Load blinder). Separate REF relays for HV and IV both with complete scheme for protection to be provided.
Bus bar protection panel (bus bar protection will be low impedance, de-centralised type and will have minimum 4 zones with numerical type of relays complying IEC 61850 (Edition-2) Protocol as and where applicable with complete cabling works.(covering entire scope of future with necessary software for future extension)
FIRE PROTECTION SYSTEM
Portable Fire Extinguishers
6 Kg DCP Type
6.5 Kg CO2 Type
12 Fire buckets with covered stand
Complete HVW spray system with complete O/G & U/G piping and accessories etc. (all items) with all required materials and equipments out side the pump house for 100MVA, 1 Nos, 220/132 Power Transformers as per tender specification. - For 1x100MVA Transformer
Outdoor lighting (Switchyard and Street lighting) (All Luminaire used shall be of LED type only. However, conventional type Luminaire (HP Sodium vapour Lamps in High Flood Lighting) may be used additionally in Switchyard area)
Lighting panel
Lighting panel (Outdoor) Type ACP - 3
LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements)
Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type - MP : as per Tech.Specification
Lighting fixture Type - SC : as per Tech.Specification
15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO)
Cables alongwith associated accessories like clamps, glands, lugs and straight joints etc. (Actual Quantity shall be as per approved cable schedule)
Power cables (PVC) 1.1 kV
Any other size as per requirement
Control cable (PVC) 1.1 kV
Materials for earthing mat with all materials and accessories as well as spikes as per requirement of design as per IEEE standards for complete earthing of grid Sub-Station with the followings. (The quantity is tentative and final quantity will depend on actual design):-
40 mm MS rod for main earth mat (To be procured directly from SAIL/RINL/TATA or from their stockyard)
75x12 mm G.I Flats for risers for equipments, columns and structures
50x6 mm G.I flats for risers for all other equipments etc.
Materials for Earthing pits with supply of all earthing materials including base plate etc. complete in all respect as per Technical Specifications
Treated Earth Pit (Earth electrode to be erected by rigging 140/150mm dia bore using power rig and to be filled with mixer of A4 grade bentonite powder, salt and available site soil)
Un-Treated Earth pit
Sub- Station galvanized Steel structure (220 kV, 132 KV & 33 KV) (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design)
Lattice structure with fasteners etc. (for Gantry, Tower, Beam)
Standard structure for equipment support i.e. Pipe type (other than CB)
Cable Racks as per design requirement for Switchyard and Control room building.
Sub-Station automation system comprising of necessary equipments & materials wth networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet with Part-I of the tender) whereever applicable, the communication protocol shall be preferably IEC 61850 (Edition-2). SAS to be integrated with the original implemented SAS of M/s GE. It is sole responsibility of bidder/contractor to integrate the SAS with the existing SAS and transportaion of data upto SLDC, Patna.
Tripping coil 220KV Breaker (With flange)
Closing coil 220KV Breaker (With flange)
Tripping coil 132KV Breaker (With flange)
Closing coil 132KV Breaker (With flange)
Description of Item
Transformer
Erection, testing and commissioning of 100 MVA Power transformer
Removal of transformer from sleepers, dragging (upto 100 feet) and placing it on plinth including fixing and fitting of wheels etc.
Dragging of Transfermer beyon 100 feet up to 300 feet
Transformer Oil for the above with 10% extra oil
220 kV EQUIPMENT
Circuit breaker (3 phase)
3150A, 50KA for 1sec with support structure,SF6,3P,marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) (C2-M2 type with Spring- Spring mechanism).
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors (Motor Operated) with moving contact of HDEC copper only.
1600 A, 50 kA for 1 sec with two earth switch (Double break Isolator)
1600 A, 50 kA for 1 sec with one earth switch (Double break Isolator)
1600 A,50 kA for 1 sec without earth switch (Double break Isolator) (Tandem arrangement)
CURRENT TRANSFORMER 5 Core (1 phase) WITH MARSHALING BOXES TERMINAL CONNECTORS
1600-800-400-200/1-1-1-1-1 A, 150% extended current rating, 50 kA for 1sec, 0.2s class 5 core
216 kV Surge Arresters (1 phase) class-IV (SH Class) with terminal connectors suitable for twin moose and surge counter etc.
Erection Hardware(220KV)
Erection Hardware (Without BPI)
Transformer bay
220KV solid core, Bus Post insulators (including requirement of wave trap) (Break up of quantity to be furnished by bidder)
132 kV EQUIPMENT
Circuit breaker (3 phase)
3150 A, 40 kA for 1sec SF 6 CB, C2-M2 Class with support structure, marshalling boxes, terminal connectors suitable for twin moose etc.(current rating shall be equal to the current rating for which the short cuircuit test reports shall be furnished.) (Spring- Spring Mechanism )
ISOLATORS (3 phase), with solid core insulators, marshaling boxes, terminal connectors (Motor Operated) with moving contact of HDEC copper only.
1600 A, 40 kA for 1sec with one earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)(Tandem arrangement)
2500 A, 40 kA for 1sec without earth switch (Double break high level beam mounted Isolator)
145kV (5-Core) CT (1 Ph.)with marshelling boxes & terminal connectors (The windings of CT shall be of Copper only)
1200-600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,40 kA with 150% extended current rating with marshalling boxes, terminal connectors suitable for twin moose etc.
120 kV Surge Arresters SH class-IV(I PHASE)with terminal connectors and surge counter.
Erection Hardware (132 KV)
Insulator strings antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, Connectors (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.)
Transformer bay
132 kV Solid Core, Bus post Insulators for erection hardware
CONTROL & RELAY PANELS
220 kV (Simplex panels)
Circuit breaker Relay Panel All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy. Bay control unit (BCU) along with bay mimic to be provided for each bay separately in Control panel. ABT Energy Meter (0.2s class) of CR Panels – The metering system shall be housed in rack with draw out type feature capability for inserting the meter module. The test terminal blocks shall be provided on all meters to facilitate testing of meters in service. Main energy meter & back up meters shall be having the feature of draw out type modular units and shall have automatic CT short circuiting so that meter can be taken out for testing without shut down requirements. The same Energy meters could be used as either ABT or NON ABT meters. It shall have the facility of interchangeability between NON ABT to ABT Energy Meter at site as per reqesuirement. The above Energy metres should have been type tested for compliance of above features with proven performance. (The meters must be meeting all complaince of SAMAST). Note:- The communication system at GSS required for communication from remote end to SLDC Patna will be under scope of Bidders.
CB relay panel with A/R
220/132/33 KV Transformer protection panel (HV and IV sides) with numerical differential protecton relays with earth fault/ over current relay complying to IEC 61850 (Edition-2) Protocol with optical fiber ports sufficient DI/DO ports for scheme with additional 6 DI and 6 DO Ports for spare. All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy and 0.2s class ABT energy meters (with Modem) on both HV & IV side to be provided. (Relay shall have feature of PRP and Load blinder). Separate REF relays for HV and IV both with complete scheme for protection to be provided.
Bus bar protection panel (bus bar protection will be low impedance, de-centralised type and will have minimum 4 zones with numerical type of relays complying IEC 61850 (Edition-2) Protocol as and where applicable with complete cabling works.(covering entire scope of future with necessary software for future extension)
FIRE PROTECTION SYSTEM
Portable Fire Extinguishers
6 Kg DCP Type
6.5 Kg CO2 Type
12 Fire buckets with covered stand
Complete HVW spray system with complete O/G & U/G piping and accessories etc. (all items) with all required materials and equipments out side the pump house for 100MVA, 1 Nos, 220/132 Power Transformers as per tender specification. - For 1x100MVA Transformer
Outdoor lighting (Switchyard and Street lighting) (All Luminaire used shall be of LED type only. However, conventional type Luminaire (HP Sodium vapour Lamps in High Flood Lighting) may be used additionally in Switchyard area)
Lighting panel
Lighting panel (Outdoor) Type ACP - 3
LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements)
Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type - MP : as per Tech.Specification
Lighting fixture Type - SC : as per Tech.Specification
15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO)
Cables alongwith associated accessories like clamps, glands, lugs and straight joints etc. (Actual Quantity shall be as per approved cable schedule)
Power cables (PVC) 1.1 kV
Any other size as per requirement
Control cable (PVC) 1.1 kV
Materials for earthing mat with all materials and accessories as well as spikes as per requirement of design as per IEEE standards for complete earthing of grid Sub-Station with the followings. (The quantity is tentative and final quantity will depend on actual design):-
40 mm MS rod for main earth mat (To be procured directly from SAIL/RINL/TATA or from their stockyard)
75x12 mm G.I Flats for risers for equipments, columns and structures
50x6 mm G.I flats for risers for all other equipments etc.
Materials for Earthing pits with supply of all earthing materials including base plate etc. complete in all respect as per Technical Specifications
Treated Earth Pit (Earth electrode to be erected by rigging 140/150mm dia bore using power rig and to be filled with mixer of A4 grade bentonite powder, salt and available site soil)
Un-Treated Earth pit
Sub- Station galvanized Steel structure (220 kV, 132 KV & 33 KV) (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design)
Lattice structure with fasteners etc.
Pipe type structure
Cable Racks as per design requirement.
All Materials required for intergration with existing Sub- Station automation system at GSS Motipur comprising of necessary equipments & materials with networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet). whereever applicable, the communication protocol shall be preferably IEC61850.
Particulars
Soil Investigation in all kinds of Soil
Earthwork in excavation over areas including disposal of excavated earth, all lead and lift & disposed earth to be levelled and neatly dressed.
Surface dressing of the ground including removing vegetation and inequalities and disposal of rubbish, all lead and lift. All kinds of soil.
Antiweed treatment in switch yard area as per building specification and direction of E/I
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering-all works upto plinth level. 1:3:6 (1 Cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering-all work upto plinth level. 1:4:8 (1 Cement: 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering,shuttering,finishing and reinforcement-All work puto plinth level. 1:1:5:3(1 cement: 1.5 coarse sand:3 graded stone aggregate 20 mm nominal size)
Providing and laying in position brick bat cement concrete of specified grade all work. 1:5:10 (1 Cement: 5 coarse sand : 10 brick aggregate 40 mm single size)
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-8mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-10mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-12mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.TMTC-500-16mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.TMTC-500-20mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-25mm dia. & above
Centering and shuttering including strutting,propping etc. and removal of form for Foundations, footings, bases of columns etc. for mass concrete.
Providing Stone Aggregate (Single size) 40 mm nominal size
Providing unskilled labour for spreading stone aggregate in switchyard area
Steel work welded in built up sections/framed work including cutting hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel, etc. as required. In gratings, frames, guard bar, ladders, railings, brackts. gates & similar works.
P/F/F STEEL ANGLES (50*50*6)
P/F/F Flats upto 10mm in thickness
Applying priming coat: With ready mixed zinc chromate yellow primer of approved brand and manufacture on steel galvanized iron/steel works
Painting with ready mixed paint of approved brand and manufacture in all shades to give an even shade:New steel work (two or more coats)
Description of Item
220 kV EQUIPMENT
Circuit Breaker (3 phase)
3150A, 50KA for 1sec with support structure,SF6,3P,marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) (C2-M2 type with Spring- Spring mechanism).
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 50 kA for 1 sec with two earth switch (Double break Isolator)
1600 A, 50 kA for 1 sec with one earth switch (Double break Isolator)
1600 A,50 kA for 1 sec without earth switch (Double break Isolator) (Tandem arrangement)
CURRENT TRANSFORMER 5 Core (1 phase) WITH MARSHALING BOXES TERMINAL CONNECTORS (The windings of CT shall be of Copper only)
1600-800-400-200/1-1-1-1-1 A, 150% extended current rating, 50 kA for 1sec, 0.2s class 5 core
216 kV Surge Arresters (1 phase) class-IV (SH Class) with terminal connectors suitable for twin moose and surge counter etc.
Portable discharge rods
ERECTION HARDWARE (220 kV)
Erection Hardware (Without BPI)
Transformer bay
220 kV Solid Core, Bus post Insulators (including requirement for wave trap)
132 kV EQUIPMENT
Circuit breaker (3 phase)
3150 A, 40 kA for 1sec SF 6 CB, C2-M2 Class with support structure, marshalling boxes, terminal connectors suitable for twin moose etc.(current rating shall be equal to the current rating for which the short cuircuit test reports shall be furnished.) (Spring- Spring Mechanism )
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 40 kA for 1sec with one earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)(Tandem arrangement)
2500 A, 40 kA for 1sec without earth switch (Double break high level beam mounted Isolator)
145kV (5-Core) CT (1 Ph.)with marshelling boxes & terminal connectors (The windings of CT shall be of Copper only)
1200-600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,40 kA with 150% extended current rating with marshalling boxes, terminal connectors suitable for twin moose etc.
120 kV Surge Arresters SH class-IV(I PHASE)with terminal connectors and surge counter.
ERECTION HARDWARE (132 kV)
Insulator strings antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, Connectors (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.)
Transformer bay
132 kV Solid Core, Bus post Insulators for erection hardware
CONTROL & RELAY PANELS
220 kV (Simplex panels)
Circuit breaker Relay Panel All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy. Bay control unit (BCU) along with bay mimic to be provided for each bay separately in Control panel. ABT Energy Meter (0.2s class) of CR Panels – The metering system shall be housed in rack with draw out type feature capability for inserting the meter module. The test terminal blocks shall be provided on all meters to facilitate testing of meters in service. Main energy meter & back up meters shall be having the feature of draw out type modular units and shall have automatic CT short circuiting so that meter can be taken out for testing without shut down requirements. The same Energy meters could be used as either ABT or NON ABT meters. It shall have the facility of interchangeability between NON ABT to ABT Energy Meter at site as per reqesuirement. The above Energy metres should have been type tested for compliance of above features with proven performance. (The meters must be meeting all complaince of SAMAST). Note:- The communication system at GSS required for communication from remote end to SLDC Patna will be under scope of Bidders.
CB relay panel with A/R
220/132/33 KV Transformer protection panel (HV and IV sides) with numerical differential protecton relays with earth fault/ over current relay complying to IEC 61850 (Edition-2) Protocol with optical fiber ports sufficient DI/DO ports for scheme with additional 6 DI and 6 DO Ports for spare. All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy and 0.2s class ABT energy meters (with Modem) on both HV & IV side to be provided. (Relay shall have feature of PRP and Load blinder). Separate REF relays for HV and IV both with complete scheme for protection to be provided.
Bus bar protection panel (bus bar protection will be low impedance, de-centralised type and will have minimum 4 zones with numerical type of relays complying IEC 61850 (Edition-2) Protocol as and where applicable with complete cabling works.(covering entire scope of future with necessary software for future extension)
FIRE PROTECTION SYSTEM
Portable Fire Extinguishers
6 Kg DCP Type
6.5 Kg CO2 Type
12 Fire buckets with covered stand
Complete HVW spray system with complete O/G & U/G piping and accessories etc. (all items) with all required materials and equipments out side the pump house for 100MVA, 1 Nos, 220/132 Power Transformers as per tender specification. - For 1x100MVA Transformer
Outdoor lighting (Switchyard and Street lighting) (All Luminaire used shall be of LED type only. However, conventional type Luminaire (HP Sodium vapour Lamps in High Flood Lighting) may be used additionally in Switchyard area)
Lighting panel
Lighting panel (Outdoor) Type ACP - 3
LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements)
Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear (Make Philips/CGL/Bajaj/ Havells)
Supply of Complete fitting of LED Flood Lighting Luminairs (<150 Watt) having minimum System Lumen Output of 14000 with all accessories (Make Philips/CGCEL/Bajaj/ Havells) Confirming to IP:65
LED Flood light 120 watt Cool Type
Lighting fixture Type - MP : as per Tech.Specification
Lighting fixture Type - SC : as per Tech.Specification
15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO)
Cables alongwith associated accessories like clamps, glands, lugs and straight joints etc. (Actual Quantity shall be as per approved cable schedule)
Power cables (PVC) 1.1 kV
Any other size as per requirement
Control cable (PVC) 1.1 kV
Materials for earthing mat with all materials and accessories as well as spikes as per requirement of design as per IEEE standards for complete earthing of grid Sub-Station with the followings. (The quantity is tentative and final quantity will depend on actual design):-
40 mm MS rod for main earth mat (To be procured directly from SAIL/RINL/TATA or from their stockyard)
75x12 mm G.I Flats for risers for equipments, columns and structures
50x6 mm G.I flats for risers for all other equipments etc.
Materials for Earthing pits with supply of all earthing materials including base plate etc. complete in all respect as per Technical Specifications
Treated Earth Pit (Earth electrode to be erected by rigging 140/150mm dia bore using power rig and to be filled with mixer of A4 grade bentonite powder, salt and available site soil)
Un-Treated Earth pit
Sub- Station galvanized Steel structure (220 kV, 132 KV & 33 KV) (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design)
Lattice structure with fasteners etc. (for Gantry, Tower, Beam)
Standard structure for equipment support i.e. Pipe type (other than CB)
Cable Racks as per design requirement for Switchyard and Control room building.
Sub-Station automation system comprising of necessary equipments & materials wth networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet with Part-I of the tender) whereever applicable, the communication protocol shall be preferably IEC 61850 (Edition-2). SAS to be integrated with the original implemented SAS of M/s GE. It is sole responsibility of bidder/contractor to integrate the SAS with the existing SAS and transportaion of data upto SLDC, Patna.
Tripping coil 220KV Breaker (With flange)
Closing coil 220KV Breaker (With flange)
Tripping coil 132KV Breaker (With flange)
Closing coil 132KV Breaker (With flange)
Description of Item
220 kV EQUIPMENT
Circuit Breaker (3 phase)
3150A, 50KA for 1sec with support structure,SF6,3P,marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) (C2-M2 type with Spring- Spring mechanism).
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 50 kA for 1 sec with two earth switch (Double break Isolator)
1600 A, 50 kA for 1 sec with one earth switch (Double break Isolator)
1600 A,50 kA for 1 sec without earth switch (Double break Isolator) (Tandem arrangement)
CURRENT TRANSFORMER 5 Core (1 phase) WITH MARSHALING BOXES TERMINAL CONNECTORS (The windings of CT shall be of Copper only)
1600-800-400-200/1-1-1-1-1 A, 150% extended current rating, 50 kA for 1sec, 0.2s class 5 core
216 kV Surge Arresters (1 phase) class-IV (SH Class) with terminal connectors suitable for twin moose and surge counter etc.
Portable discharge rods
ERECTION HARDWARE (220 kV)
Erection Hardware (Without BPI)
Transformer bay
220 kV Solid Core, Bus post Insulators (including requirement for wave trap)
132 kV EQUIPMENT
Circuit breaker (3 phase)
3150 A, 40 kA for 1sec SF 6 CB, C2-M2 Class with support structure, marshalling boxes, terminal connectors suitable for twin moose etc.(current rating shall be equal to the current rating for which the short cuircuit test reports shall be furnished.) (Spring- Spring Mechanism )
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 40 kA for 1sec with one earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)(Tandem arrangement)
2500 A, 40 kA for 1sec without earth switch (Double break high level beam mounted Isolator)
145kV (5-Core) CT (1 Ph.)with marshelling boxes & terminal connectors (The windings of CT shall be of Copper only)
1200-600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,40 kA with 150% extended current rating with marshalling boxes, terminal connectors suitable for twin moose etc.
120 kV Surge Arresters SH class-IV(I PHASE)with terminal connectors and surge counter.
ERECTION HARDWARE (132 kV)
Insulator strings antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, Connectors (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.)
Transformer bay
132 kV Solid Core, Bus post Insulators for erection hardware
CONTROL & RELAY PANELS
220 kV (Simplex panels)
Circuit breaker Relay Panel All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy. Bay control unit (BCU) along with bay mimic to be provided for each bay separately in Control panel. ABT Energy Meter (0.2s class) of CR Panels – The metering system shall be housed in rack with draw out type feature capability for inserting the meter module. The test terminal blocks shall be provided on all meters to facilitate testing of meters in service. Main energy meter & back up meters shall be having the feature of draw out type modular units and shall have automatic CT short circuiting so that meter can be taken out for testing without shut down requirements. The same Energy meters could be used as either ABT or NON ABT meters. It shall have the facility of interchangeability between NON ABT to ABT Energy Meter at site as per reqesuirement. The above Energy metres should have been type tested for compliance of above features with proven performance. (The meters must be meeting all complaince of SAMAST). Note:- The communication system at GSS required for communication from remote end to SLDC Patna will be under scope of Bidders.
CB relay panel with A/R
220/132/33 KV Transformer protection panel (HV and IV sides) with numerical differential protecton relays with earth fault/ over current relay complying to IEC 61850 (Edition-2) Protocol with optical fiber ports sufficient DI/DO ports for scheme with additional 6 DI and 6 DO Ports for spare. All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy and 0.2s class ABT energy meters (with Modem) on both HV & IV side to be provided. (Relay shall have feature of PRP and Load blinder). Separate REF relays for HV and IV both with complete scheme for protection to be provided.
Bus bar protection panel (bus bar protection will be low impedance, de-centralised type and will have minimum 4 zones with numerical type of relays complying IEC 61850 (Edition-2) Protocol as and where applicable with complete cabling works.(covering entire scope of future with necessary software for future extension)
FIRE PROTECTION SYSTEM
Portable Fire Extinguishers
6 Kg DCP Type
6.5 Kg CO2 Type
12 Fire buckets with covered stand
Complete HVW spray system with complete O/G & U/G piping and accessories etc. (all items) with all required materials and equipments out side the pump house for 100MVA, 1 Nos, 220/132 Power Transformers as per tender specification. - For 1x100MVA Transformer
Outdoor lighting (Switchyard and Street lighting) (All Luminaire used shall be of LED type only. However, conventional type Luminaire (HP Sodium vapour Lamps in High Flood Lighting) may be used additionally in Switchyard area)
Lighting panel
Lighting panel (Outdoor) Type ACP - 3
LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements)
Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear (Make Philips/CGL/Bajaj/ Havells)
Supply of Complete fitting of LED Flood Lighting Luminairs (<150 Watt) having minimum System Lumen Output of 14000 with all accessories (Make Philips/CGCEL/Bajaj/ Havells) Confirming to IP:65
LED Flood light 120 watt Cool Type
Lighting fixture Type - MP : as per Tech.Specification
Lighting fixture Type - SC : as per Tech.Specification
15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO)
Cables alongwith associated accessories like clamps, glands, lugs and straight joints etc. (Actual Quantity shall be as per approved cable schedule)
Power cables (PVC) 1.1 kV
Any other size as per requirement
Control cable (PVC) 1.1 kV
Materials for earthing mat with all materials and accessories as well as spikes as per requirement of design as per IEEE standards for complete earthing of grid Sub-Station with the followings. (The quantity is tentative and final quantity will depend on actual design):-
40 mm MS rod for main earth mat (To be procured directly from SAIL/RINL/TATA or from their stockyard)
75x12 mm G.I Flats for risers for equipments, columns and structures
50x6 mm G.I flats for risers for all other equipments etc.
Materials for Earthing pits with supply of all earthing materials including base plate etc. complete in all respect as per Technical Specifications
Treated Earth Pit (Earth electrode to be erected by rigging 140/150mm dia bore using power rig and to be filled with mixer of A4 grade bentonite powder, salt and available site soil)
Un-Treated Earth pit
Sub- Station galvanized Steel structure (220 kV, 132 KV & 33 KV) (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design)
Lattice structure with fasteners etc. (for Gantry, Tower, Beam)
Standard structure for equipment support i.e. Pipe type (other than CB)
Cable Racks as per design requirement for Switchyard and Control room building.
Sub-Station automation system comprising of necessary equipments & materials wth networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet with Part-I of the tender) whereever applicable, the communication protocol shall be preferably IEC 61850 (Edition-2). SAS to be integrated with the original implemented SAS of M/s GE. It is sole responsibility of bidder/contractor to integrate the SAS with the existing SAS and transportaion of data upto SLDC, Patna.
Tripping coil 220KV Breaker (With flange)
Closing coil 220KV Breaker (With flange)
Tripping coil 132KV Breaker (With flange)
Closing coil 132KV Breaker (With flange)
Description of Item
Transformer
Erection, testing and commissioning of 100 MVA Power transformer
Removal of transformer from sleepers, dragging (upto 100 feet) and placing it on plinth including fixing and fitting of wheels etc.
Dragging of Transfermer beyon 100 feet up to 300 feet
Transformer Oil for the above with 10% extra oil
220 kV EQUIPMENT
Circuit breaker (3 phase)
3150A, 50KA for 1sec with support structure,SF6,3P,marshalling boxes, terminal connectors etc.(current rating shall be equial to the current rating for which the short cuircuit test reports shall be furnished.) (C2-M2 type with Spring- Spring mechanism).
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 50 kA for 1 sec with two earth switch (Double break Isolator)
1600 A, 50 kA for 1 sec with one earth switch (Double break Isolator)
1600 A,50 kA for 1 sec without earth switch (Double break Isolator) (Tandem arrangement)
CURRENT TRANSFORMER 5 Core (1 phase) WITH MARSHALING BOXES TERMINAL CONNECTORS (The windings of CT shall be of Copper only)
1600-800-400-200/1-1-1-1-1 A, 150% extended current rating, 50 kA for 1sec, 0.2s class 5 core
216 kV Surge Arresters (1 phase) class-IV (SH Class) with terminal connectors suitable for twin moose and surge counter etc.
Erection Hardware(220KV)
Erection Hardware (Without BPI)
Transformer bay
220KV solid core, Bus Post insulators (including requirement of wave trap) (Break up of quantity to be furnished by bidder)
132 kV EQUIPMENT
Circuit breaker (3 phase)
3150 A, 40 kA for 1sec SF 6 CB, C2-M2 Class with support structure, marshalling boxes, terminal connectors suitable for twin moose etc.(current rating shall be equal to the current rating for which the short cuircuit test reports shall be furnished.) (Spring- Spring Mechanism )
ISOLATORS (3 phase), with solid core insulators, marshalling boxes, terminal connectors suitable for twin moose (Motor Operated for main and earth switch both) with complete moving contact of HDEC copper (without any Aluminium part) only. Current density not exceeding the limits as indicated below: Hollow tube Sections and Other Sectionsand contacts (Copper) –1.6 A/sq mm
1600 A, 40 kA for 1sec with one earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)
1600 A, 40 kA for 1sec without earth switch (Double break Isolator)(Tandem arrangement)
2500 A, 40 kA for 1sec without earth switch (Double break high level beam mounted Isolator)
145kV (5-Core) CT (1 Ph.)with marshelling boxes & terminal connectors (The windings of CT shall be of Copper only)
1200-600-300-150/1-1-1-1-1 A, 5 core 0.2s class ,40 kA with 150% extended current rating with marshalling boxes, terminal connectors suitable for twin moose etc.
120 kV Surge Arresters SH class-IV(I PHASE)with terminal connectors and surge counter.
Erection Hardware (132 KV)
Insulator strings antifog type & hardware, spacers, conductor, Bus bar material,BMK (Bay Marshalling Kiosk-One no. for each bay), Clamps, Connectors (Compression type except for IPS Tube, which may be bolted type) including, Junction box, PVC pipes for equipment and lighting, all accessories etc. for the following: (The Main Bus shall be of quad ACSR Moose conductor and Transfer Bus, TBC as well as other Feeder & Jumper shall be strung with double Moose conductor). ACSR Moose conductor to be supplied by Tenderer. (Note - It is mandatory to furnish Billing Breakup Unit (BBU) schedule for each and every item during engineering and approval by ordering authority without which payment shall not be released.)
Transformer bay
132 kV Solid Core, Bus post Insulators for erection hardware
CONTROL & RELAY PANELS
220 kV (Simplex panels)
Circuit breaker Relay Panel All indicating meters and multifunctions meters shall be communicable type with 0.5 class accuracy. Bay control unit (BCU) along with bay mimic to be provided for each bay separately in Control panel. ABT Energy Meter (0.2s class) of CR Panels – The metering system shall be housed in rack with draw out type feature capability for inserting the meter module. The test terminal blocks shall be provided on all meters to facilitate testing of meters in service. Main energy meter & back up meters shall be having the feature of draw out type modular units and shall have automatic CT short circuiting so that meter can be taken out for testing without shut down requirements. The same Energy meters could be used as either ABT or NON ABT meters. It shall have the facility of interchangeability between NON ABT to ABT Energy Meter at site as per reqesuirement. The above Energy metres should have been type tested for compliance of above features with proven performance. (The meters must be meeting all complaince of SAMAST). Note:- The communication system at GSS required for communication from remote end to SLDC Patna will be under scope of Bidders.
CB relay panel with A/R
FIRE PROTECTION SYSTEM
Portable Fire Extinguishers
6 Kg DCP Type
6.5 Kg CO2 Type
12 Fire buckets with covered stand
Complete HVW spray system with complete O/G & U/G piping and accessories etc. (all items) with all required materials and equipments out side the pump house for 100MVA, 1 Nos, 220/132 Power Transformers as per tender specification. - For 1x100MVA Transformer
Outdoor lighting (Switchyard and Street lighting) (All Luminaire used shall be of LED type only. However, conventional type Luminaire (HP Sodium vapour Lamps in High Flood Lighting) may be used additionally in Switchyard area)
Lighting panel
Lighting panel (Outdoor) Type ACP - 3
LED Lighting Fixtures and receptacles (including accessories/ materials etc. as per requirement like junction box, cable/wires, flexible conduits (if required) from junction box to lighting fixtures, mounting arrangements)
Lighting fixture Type- SF1: as per Tech. Specification (1x400W HP Sodium Vapour lamps in high flood lighting fixture mounted on Swivel support, integral control gear (Make Philips/CGL/Bajaj/ Havells)
Lighting fixture Type- SF2: as per Tech. Specification (2x400W HP Sodium Vapour lamps in high flood lighting, non-integral control gear (Make Philips/CGL/Bajaj/ Havells)
Supply of Complete fitting of LED Flood Lighting Luminairs (<150 Watt) having minimum System Lumen Output of 14000 with all accessories (Make Philips/CGCEL/Bajaj/ Havells) Confirming to IP:65
LED Flood light 120 watt Cool Type
Lighting fixture Type - MP : as per Tech.Specification
Lighting fixture Type - SC : as per Tech.Specification
15A, 240V : Outdoor receptacles 2 pole, 3 pin type (Type RO)
Cables alongwith associated accessories like clamps, glands, lugs and straight joints etc.
Power cables (PVC) 1.1 kV
Any other size as per requirement
Control cable (PVC) 1.1 kV
40 mm MS rod for main earth mat (To be procured directly from SAIL/RINL/TATA or from their stockyard)
75x12 mm G.I Flats for risers for equipments, columns and structures
50x6 mm G.I flats for risers for all other equipments etc.
Materials for Earthing pits with supply of all earthing materials including base plate etc. complete in all respect as per Technical Specifications
Treated Earth Pit (Earth electrode to be erected by rigging 140/150mm dia bore using power rig and to be filled with mixer of A4 grade bentonite powder, salt and available site soil)
Un-Treated Earth pit
Sub- Station galvanized Steel structure (220 kV, 132 KV & 33 KV) (SAIL/RINL/TATA or its authorised approved rerollers) (The quantity is tentative and final quantity will depend on actual design)
Lattice structure with fasteners etc. (for Gantry, Tower, Beam)
Standard structure for equipment support i.e. Pipe type (other than CB)
Cable Racks as per design requirement for Switchyard and Control room building.
All Materials required for intergration with existing Sub- Station automation system at GSS Motipur comprising of necessary equipments & materials with networking and interfacing, complete in all respect (Break up of item to be given by contractor in technical data sheet). whereever applicable, the communication protocol shall be preferably IEC61850.
Particulars
Soil Investigation in all kinds of Soil
Earthwork in excavation over areas including disposal of excavated earth, all lead and lift & disposed earth to be levelled and neatly dressed.
Surface dressing of the ground including removing vegetation and inequalities and disposal of rubbish, all lead and lift. All kinds of soil.
Antiweed treatment in switch yard area as per building specification and direction of E/I
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering-all works upto plinth level. 1:3:6 (1 Cement: 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering-all work upto plinth level. 1:4:8 (1 Cement: 4 coarse sand : 8 graded stone aggregate 40 mm nominal size)
Providing and laying in position specified grade of reinforced cement concrete excluding the cost of centering,shuttering,finishing and reinforcement-All work puto plinth level. 1:1:5:3(1 cement: 1.5 coarse sand:3 graded stone aggregate 20 mm nominal size)
Providing and laying in position brick bat cement concrete of specified grade all work. 1:5:10 (1 Cement: 5 coarse sand : 10 brick aggregate 40 mm single size)
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-8mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-10mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-12mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.TMTC-500-16mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete.TMTC-500-20mm dia.
Reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete. TMTC-500-25mm dia. & above
Centering and shuttering including strutting,propping etc. and removal of form for Foundations, footings, bases of columns etc. for mass concrete.
Providing Stone Aggregate (Single size) 40 mm nominal size
Providing unskilled labour for spreading stone aggregate in switchyard area
Steel work welded in built up sections/framed work including cutting hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel, etc. as required. In gratings, frames, guard bar, ladders, railings, brackts. gates & similar works.
Description
Total Price for Supply of all materials and equipments including GST.(A)
Total Price for Freight& Insurance including GST.(B)
Total Price for Erection, Testing & Commissioning Charges including GST.(C)
Total Price for Civil Work including GST.(D)
Total Price for the project inclusive of GST (A+B+C+D)
Total Price for Supply of all materials and equipments including GST.(E)
Total Price for Freight& Insurance including GST.(F)
Total Price for Erection, Testing & Commissioning Charges including GST.(G)
Total Price for Civil Work including GST.(H)
Total Price for the project inclusive of GST (E+F+G+H)
Total Price for the complete project inclusive of GST (5+10)
Total Price for the complete project inclusive of GST (in Word)
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
T Doc NIT 43 floating Begusarai.pdf
NIT • 3.33 MB
nit notice -43.pdf
NIT • 0.12 MB
TS-elec nit 43Transformer Bay at Begusarai Motipur.pdf
NIT • 34.95 MB
Technical sheet-GSS.xlsx
NIT • 0.05 MB
TECHNO COMMERCIALSHEET.xls
NIT • 0.14 MB
price boq nit43 floating.xlsx
NIT • 0.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .