| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical BASUDEBPUR BELKHALI HOWRAH PIN 711 322 | HOWRAH | HOWRAH | WEST BENGAL | 711322 | Accepted-Technical accepted |
| 2 | Rejected-Technical | Rejected-Technical valid shortfall documents was not submitted |
| 3 | Rejected-Technical 197 4 KANTADANGA ROAD P O FINGAPARA KANKINARA NORTH 24 PARGANAS PIN 743129 | KANKINARA | NORTH 24 PARGANAS | WEST BENGAL | 743129 | Rejected-Technical valid shortfall documents was not submitted |
Tender Value
₹6.5 L
EMD Value
₹12,998
Closing Date
12 Feb 2026, 2:00 pmClosed
EE_KCED_PWD
Khadya_Bhawan_11A_Mirza_Ghalib_Street_Block_A_3rd_Floor_Kokata_700087
Repairing, Rectification, Testing, Commissioning and Cleaning of Fire Detection Systems of Khadyashree Bhawan.
2026_PWDE_994295_1
WBPWD/EE/57/IR/T/KCED/I of 2025-26
Open Tender
Electrical Work/ Equipment
Item Rate
30 days
Khadyashree Bhawan.
Please refer Tender documents.
4 documents required · 4 mandatory
₹12,998
Office_of_EE_KCED_PWD
25 Feb 2026
27 Jan 2026
16 Feb 2026
27 Jan 2026
12 Feb 2026
5 Feb 2026
3 Feb 2026
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Multisensor detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with inbuilt optical smoke sensors and heat detector sensor with inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. The detector should have 360 degree optical view with single / multiple LED that blinks on actuation of detector. Reverse polarity or faulty zone wiring shall not damage the detectors. (Approved Make : ESSER/Notifire/Bosch)
Supply, Installation,Testing & Commisioning of Micropresssor controlled Addressable Heat detector IP 42 ( VDS / UL /ERTL/ LPCB / FM approved ) with combination of fixed type & Rate of Rise of Temperature feature. Detector shall have maimum triggering temperature programmable from 60 deg. C to 80 deg. C., having high level of immunity to electromagnetic influances and show alarm signal limit temperature is reached. Detector shall have inbuilt short circuit fault isolator as per NFPA style 7 wiring complete with base (Note : Detectors without built-in fault isolator is also acceptable provided one independent short circuit fault isolator per detector is to be provided extra without extra cost) the detectors should have built in response indicator with LED indicator. (Approved Make : ESSER/Notifire/Bosch)
Supply, Installation,Testing & Commisioning of Addressable Manual Call Point ( VDS / UL /ERTL/ LPCB / FM approved ) with in built short circuit fault isolator as per NFPA style 7 wiring complete as required. (Approved Make : ESSER/Notifire/Bosch)
Supply, Installation, Testing & Commissioning of IP Addressable Loop Powered Hooter ( sound output of minimum 90 db ) cum strobe (strength of light 10 cd) complete with inbuilt short circuit fault isolator. Degree of protection IP65 ( VDS / UL /ERTL/ LPCB / FM approved) approved. (Approved Make : ESSER/Notifire/Bosch)
Supply, Installation, Testing & Commissioning of Addressable Monitor Modules & Transponder with necessary relay module ( VDS / UL /ERTL/ LPCB / FM approved ) for monitoring Flow switches / Fire exit doors / AHU/ Lift etc. with inbuilt short circuit fault isolator and minimum (04) four potential free contact with adjustable setting parameter likes of Input or output, complete in single or multiple housing with degree of protection IP 42 with flash LED indicator that conforms module is operational and integrated buzzer signaling maintenance alarm, complete as required. (Approved Make : ESSER/Notifire/Bosch)
Supplying, installation, testing and commissioning of LED type Response Indicator ( VDS / UL /ERTL/ LPCB / FM approved) having 2 Nos. red coloured LED lamps including connections etc. (Approved Make : ESSER/Notifire/Bosch)
Supply & Laying of 2 Core 1.5 sq.mm FRLS shielded copper Cable (For Loop) (Make. Finolex/ RR Kable/Polycab) through 20 mm dia PVC 'FR' type Rigid Conduit pipe with necessary arrangement as per G.S. (Make : Precision/ / Polycab) on the surface of the wall.
Re-Programmimg of EN54 standard, VDS Approved Microprocessor based 6 Loop Capable fire alarm control panel fully networkable with each loop capable of taking atleast 127 devices and each loop should be connected to a dedicated loop card.(Model -ESSER/Notifire/Bosch) as per direction of the E.I.C
N.B.: Within seven working days of receiving the work layout, the agency should prepare a layout drawing, get it duly signed by the EIC, and obtain approval from this office before starting the work.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
cancelled_1.pdf
pdf • 0.52 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.65 MB
BOQ_2432586.xls
BOQ • 0.35 MB
2911.pdf
Tender Documents • 0.51 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .