Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.1 LAccepted-Finance | L1 | Accepted-Finance Accepted | |
| 2 | L2₹34.3 L+₹1.2 L (3.62%)Accepted-Finance | L2 | Accepted-Finance Accepted | |
| 3 | L3₹41.4 L+₹8.3 L (25.0%)Accepted-Finance 30 74 BLOCK NO EXTRA 30 TRILOK PURI DELHI EAST DELHI 110091 | DELHI | EAST DELHI | DELHI | 110091 | L3 | Accepted-Finance Accepted |
Tender Value
₹53.6 L
EMD Value
₹1.1 L
Closing Date
24 Nov 2026, 3:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Executive Engineer (E) F-13, PWD, Delhi
E.E.(E), F-13, PWD, Mukarba Chowk, Delhi-110033
SH- providing electricity connection from energy meter to distribution panel on Sarai Kale Khan side.
2026_PWD_301452_1
05/EE(E)/F-13/PWD/2026-27
Open Tender
Electrical Works
Percentage
45 days
O/o E.E(E)/F-13, PWD, Mukarba Chowk
Please refer Tender documents.
14 documents required · 14 mandatory
₹0
₹1.1 L
26 Nov 2026
18 Nov 2026
24 Nov 2026
18 Nov 2026
24 Nov 2026
18 Nov 2026
30 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supplying of 1.1KV PVC insulated and PVC sheatehed XLPE armoured Aluminium conductor LT power cable of following size complete as required.
3.5C x 400 sqmm. | 750 | mtr | 5,921 | ₹44,40,750 |
| 2 | Supplying, fabrication, installation & commissioning of Outdoor cubical type LT panel suitable for 415 V, 3 Phase, 4 Wire 50 Hz AC supply system fabricated in compartmentalized depth minimum 400mm design from CRCA sheet steel of 2 mm thick forframe work and covers, 3 mm thick for gland, plates i/c cleaning & finishing complete with 7 tank process for powder coating in approved shade, having 800 Amp capacity extensible type TPN aluminium alloy bus bars of high conductivity, DMC / SMC bus bars of high conductivity,DMC/ SMC bus bar supports, with short circuit withstand capacity of 31 MVA for 1 Sec.,bottom base channel of MS section not less than 100mm x 50 mm x 5 mm thick, fabrication shall be done in transportable sections, entire panel shall have a common copper earth bar of size 25 mm x 5 mm at the rear with 2 Nos. earth stud, solid connections from main bus bar to switch gears with required size of Al. bus bars and control wiring with sq. mm. PVC insulated copper conductor S/C cable, cable alleys, cable gland plates in two half complete as required. | 3 | sqmm | 44,472 | ₹1,33,416 |
| 3 | Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, Ics=100% Icu and Operational Voltage 690V etc. as required.
100 A, 30KA, FPMCCB | 6 | nos | 8,127 | ₹48,762 |
| 4 | 250 A, 36KA, FPMCCB | 4 | nos | 18,372 | ₹73,488 |
| 5 | 400 A, 50KA, FPMCCB | 1 | nos | 44,638 | ₹44,638 |
| 6 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Above185sqmm and upto 400 sqmm | 750 | mtr | 364 | ₹2,73,000 |
| 7 | Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering.
Above185sqmm and upto 400 sqmm | 48 | mtr | 270 | ₹12,960 |
| 8 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 185 sq. mm and upto 400 sq. mm | 49 | mtr | 170 | ₹8,330 |
| 9 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) | 750 | mtr | 271 | ₹2,03,250 |
| 10 | Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering- all work up to plinth level :- 1:2:4( 1 cement : 2 coarse sand (zone 3) derived from natural sources : 4 graded stone aggregate 20mm nominal size derived from natural sources) | 2 | cum | 7,878.5 | ₹15,757 |
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.21 MB
BOQ_402483.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .