Directorate of Municipal Administration
Work of Repair, Rewinding, Reconditioning of 400 kVA, 11 kV/433 Volts Power Transformer No-2 Installed at Allipura Water Treatment Plant in Ballari City.
DMA/2026-27/EL/WORK_INDENT60283
DMA/2026-27/EL/WORK_INDENT60283
Open
Electrical
DMA City Corporation Ballari
4 documents required · 4 mandatory
Mandating satisfactory completion as a prime contractor for at least one similar work of Rs.2,77,000.00 to an extent of 50% of the cost of the work, for all works costing upto and Rs.100 lakh.
All the bidders, bidding for the Work, shall be registered with contractor registered with Electrical Inspectorate Department.
Achieved in at least two financial years an average annual financial turnover Rs.5,54,000.00 Certified turnover certificate issued by the Chartered accountant with UDIN Number.
The contractor should have liquid assets and /or availability of credit facilities of not less than Rs.1,67,000 (Unconditional Credit line/Letter of credit/Certificates from Banks for meeting the fund requirement etc.,as for format attached in Bid Document)
NOT APPLICABLE
₹500
₹13,850
6 Jul 2026
6 Jul 2026
15 Jul 2026
10 Jul 2026
Work of Repair, Rewinding, Reconditioning of 400 kVA, 11 kV/433 Volts Power Transformer No-2 Installed at Allipura Water Treatment Plant in Ballari City.
labour charges for de-commissioning work includes safe shutdown of the transformer, disconnection of HT and LT cables, draining of transformer oil, dismantling from the plinth, and preparation for tra...
Supply aluminium wire of suitable guage and Rewinding of High Voltage (HV)11 KV winding shall be carried out using EC Grade aluminium conductor of minimum 99.5% purity suitable for 11KV operation. The...
Supply aluminium wire of suitable guage and Rewinding of Low Voltage (LV) winding shall be rewound using EC Grade aluminium strip/wire suitable for 433 volts operation. The winding arrangement shall m...
EHV Grade unused uninhibited mineral insulating oil in new steel barrels of 210 litres capacity strictly confirming to IEC 60296 (latest version) ( 70kV class) Common SR 2023-24 KPTCL SR, Item No-1.15...
Suuply of Insulation Materials for rewinding and reconditioning works shall be of high quality and suitable for transformer applications. The insulation shall include DPC/Kraft paper, press boards, sp...
Conventional Bushing with metal parts for Power Transformers, 12.1 kV / 800 A - 1250 A - 2000 A Common SR 203-24 ESCOM SR , Item No-C/ii, Page no-134