| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.4 LAccepted-AOC G 86 DATA RAM SECTOR 18 ROHINI NEW DELHI DELHI 110085 | NORTH WEST DELHI | DELHI | 110085 | L1 | Accepted-AOC Being as lowest tender | |
| 2 | L2₹11.4 L+₹54,800 (5.05%)Rejected-Finance RAMA PARK A 121 BLOCK A UTTAM NAGAR WEST DELHI DELHI 110059 | DELHI | WEST DELHI | DELHI | 110059 | L2 | Rejected-Finance other than lowest | |
| 3 | L3₹13.1 L+₹2.2 L (20.6%)Rejected-Finance | L3 | Rejected-Finance other than lowest | |
| 4 | L4₹13.4 L+₹2.5 L (23.3%)Rejected-Finance H 13 GEETANJALI PARK WEST SAGARPUR NEW DELHI 110046 | NEW DELHI | DELHI | 110046 | L4 | Rejected-Finance other than lowest | |
| 5 | L5₹15.8 L+₹4.9 L (45.3%)Rejected-Finance | L5 | Rejected-Finance other than lowest |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
10 Oct 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (N) DELHI CANTT -10
GE (N) DELHI CANTT -10
REPAIR MAINT OF EXTERNAL EXTERNAL ELECTRIC SUPPLY SYSTEM REPLACEMENT OF UNSV LT SWITCHGEARS PANEL BOARDS CABLES ETC WITH CONNECTED WORKS AT KWC TIMARPUR UNDER GE N DELHI CANTT
2020_MES_370357_2
GE/NORTH-45/2020-21
Open Tender
Civil Works
Works
180 days
GE (N) DELHI CANTT -10
as per NIT
8 documents required · 8 mandatory
₹500
Yes
GE (N) DELHI CANTT -10
₹30,000
Yes
2 Nov 2020
19 Sept 2020
12 Oct 2020
19 Sept 2020
10 Oct 2020
26 Sept 2020
60 days
Amount
Excavation in trenches not exc 1.5 Mtr wide and n.exc 1.5 mtr in depth, getting out for electric cable complete in any type of soil complete
Removing surplus excavated soil to a distance n.exc 50 mtr and depositing where directed at a level n. exc 1.5 mtr above starting point
Returning, filling in, soil obtained from excavation including spreading, levelling, watering and well ramming in layers n.exc 25cm thick complete
Supply and laying sub class 'B' bricks laid dry and flat across the length of cable for protection of cable complete
M & L for sand cushioning for protection of cable with screen wash river sand complete
M&L for boring/ making hole under road by drilling machine or hand drill without damaging of road for laying U/G cable for size 40/50/80 mm bore of GI pipe complete all as specified & directed
M&L (in replacement) for GI tubing light grade with all necessary fittings laid in trenches/under road crossing/fixed on pole/wall/under floor including suitable mild steel FI clamps of required size complete for following sizes :-
(a) 40 mm bore
(b) 50 mm bore
(c) 80 mm bore
Dismantling & taking out HT/LT burnt cable ends of any size from transformer/LT panel/LT feeder pillar box/trenches any type/size, for repair/making suitable for reconnection to cable, providing lugs to burnt end of cables, preparing fresh terminals and reconnection, fixing the removed portion of cable with transformer/in trenches/along pole/ panel/feeder pillar box, including excavation of loop & refilling complete using old bricks and sand returning filling the excavated soil complete
Dismantling & taking out defective LT PVC/XLPE cable from trenches including excavation and earth work, cutting and removing defective parts and supply and fixing straight through joint heat shrink kit complete including jointing material and making connection of LT cables for the following sizes :-
(a) 25 sqmm 3.5 core to 50 sqmm, 3.5 core
(b) 70 sqmm 3.5 core to 95 sqmm, 3.5 core
(c) 120 sqmm 3.5 core to 240 sqmm 3.5 core
Supply and laying in repair cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of following size (Note :- Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
(a) 10 Sqmm 2 core
(b) 16 Sqmm 4 core
(c) 35 Sqmm 4 core
(d) 50 sqmm 3.5 core
(e) 70 sqmm 3.5 core
(f) 120 sqmm 3.5 core
(g) 185 sqmm 3.5 core
(h) 240 sqmm 3.5 core
(j) 300 sqmm 3.5 core
S&F in repair of 1100 volt grade, heavy duty cable PVC insulated aluminium conductor, multistand 10 sqmm twin core flat or circular, served with inner sheathing of PVC tape and overall PVC sheathed in service connections suspended complete all as directed
Checking all incoming & outgoing connections and Mechanism, cleaning, servicing, overhauling, testing it for proper tripping system complete of 11 KV VCB of of Make Crompton Greaves, installed at sub-station bldg, Inspecting, servicing and testing all the connections of control wiring availability of proper DC supply and AC supply, cleaning of contacts, & terminals, using the blower for dusting, servicing of gears, including replacement of faulty control fuses, faulty wiring & faulty indication lamp, checking & closing of tripping system, taking out relay (over current relay and earth fault relay) from the 11 KV VCB and calibrating the relay and proper setting of relay and refixing back in existing position & testing for proper tripping/functioning system complete all as specified & directed (Note : Necessary certificate for calibration of relay with setting detail shall be submitted by the contractor)
Disconnection of all electric connection & taking out old/defective Current Transformer (CT) from 11 KV VCB panel and Supply, fixing, installation & testing of Current transformer, indoor, comprising of 3 Nos single phase resin cast CTs of 100-50/5+5 amps ratio, Class 5P-10 with suitable VA burden and accuracy suitable for protection & metering incl making suitable arrangement for fixing in existing VCB panel and connection incl disconnection & taking out old/faulty current transformers (CTs) from 11 KV VCB panel complete all as specified & directed (Make-ABB/Crompton/Schneider/Siemens/Pactil/AE)
Disconnection of all electric connection and taking down defective/unsv 11 KV PT and Supply, fixing, installation & testing of Potential transformer (PT) 3 phase, dry and draw out type 11 KV/110 Volt, with suitable VA burden per phase, accuracy class 1.0 complete with HT & LT HRC fuses for primary & secondary in VCB complete all as specified & directed (Make-ABB/Crompton/Schneider/Siemens/Pactil/AE)
S&F in repair Charging Motor assembly set in existing VCB panel of Make Crompton Greaves incl all connections & fixing arrangement and testing complete all as specifed & directed
S&F in repair power pack unit suitable for 220 volts AC input & 110 volts DC output complete with 12 volts, 7 AH sealed lead acid batteries and suitable voltmeter etc suitable for operation of HT Panel including taking out old complete all as specified and directed
S&F in repair heater, 230 Volt, as per existing wattage suitable for 11 KV HT VCB panel including electric connection complete all as specified & directed (Make - As per sample) Note for item No. 12 to 18 :- (i) All the instruments and T&P required for the above jobs shall be arranged by the contractor at site and cost of the deemed to be included in the above rates. (ii) The all above checking, inspection, installation & testing work shall be performed by HT expert/engineer.
M&L for on line Dehydration of HV/EHV grade transformer oil including filteration using automatic centrifuging machine minimum three cycles to achieve dielectric strength 50 to 60 KV breaking capacity by absorbing and abolishing all sludge particles as per BS-66-1963 including topping up with new transformer oil as required complete all as directed Note- (i) Centrifuging Machine with all T&P & testing machine of oil required for dehydration shall be arranged by the contractor.(ii) Oil required for topping up the transformer will be measured & paid separately
M&L in replacement of Silica Gel (Blue colour) in breather of transformer after cleaning of breather complete
M&L in replacement of breather of transformer of any make/capacity upto 400 KVA with exising size complete
Supply & filling new transformer oil of having dielectric strenght 60 KV to top up level complete all as specified and directed (Make- Savita/apar/Powerlink/Powerzone/HP/arihant//zebron/apolo/indotech)
S&F in repair LT Porcelain bushing with brass stud screwed with brass nuts, bolts and cork washer for transformer of capacity upto 400 KVA complete
S&F in repair HT 11 KV porcelain bushing with brass stud screwed with brass nuts, bolts and cork washer for transformer of capacity upto 400 KVA complete
M&L for painting of transformer of capacity upto 400 KVA, outside portion only with one coat with spray painting with synthetic enamel paint after preparation of surface neat and clean for painting including numbering SM/MES No. with white paint complete all as directed
M&L (in repair) cable jointing kit for 11 KV cable for end termination cold shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following size:-
(a) Size 70 sqmm to 95 sqmm, Indoor type
(b) Size 120 sqmm to 185 sqmm, Indoor type
(c) Size 70 sqmm to 95 sqmm, outdoor type
(d) Size 120 sqmm to 185 sqmm, outdoor type
M&L (in repair) cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable complete all as specified & directed of following size :-
(a) Size 70 sqmm to 95 sqmm
(b) Size 120 sqmm to 185 sqmm Note for item No 26 and 27 : Make - Raychem/Cabseal/M-Seal/Denson
Supply & laying in trenches/through pipes/ducts or on poles XLPE armoured cable of following sizes with aluminum conductor, 11 KV `E’ complete all as specified & directed of follwing sizes (Note :-Excavation & earth work, sand cushioning, bricks protection & GI pipe where required shall be measured & paid seperately) :-
(a) 95 Sqmm 3 core
(b) 120 Sqmm 3 core
Taking out and repairing/overhauling of 11 KV air break gang operated switch tripple pole, mechanically operated mounted on insulators and steel frame installed vertically / horizontally, repairing defective copper strap, knife rod, movable post, insulator 200 amps capcity, ON/OFF handle, replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothing and polishing of electric contacts with providing conducting jelly of contacts refixed the same after repair complete all as directed
Cutting/pruning of tree branches along/around over head line at places within a radius of 2 mtr from fasted conductor and removing from site complete all as directed
M&L for painting of steel tubular poles 9 mtr to 11 mtr length with applying two coats of aluminium paint including cross arms and clamps except embedded portion of pole in ground and concrete after removing old painted surfaces by scraping of poles complete and two coat for making colour band/strip 30 CM with synthetic enamel paint of approved/yellow & black colour up to 1.2 mtr from coping level including numbering of poles complete all as directed
M&L for painting of RCC poles 8.5 mtr to 11 mtr long with two coat of cement based paint and two coat of synthetic enamelled paint in yellow & black stip 30cm up to 1.5 mtr above the ground level including preparation of surfaces complete and painting of connected cross arms, clamps with aluminium paint all as specified and directed.
M & L for spray painting of old/existing LT panel/feeder piller box any size/type with powder coated paint withsmoke grey paint in outer/inner side of complete panel after cleaning and preparing surface complete all as specified & directed
Supply, installation, testing & commissioning (in replacement) of Gang operated air break switch with drop out fuse unit complete with 12 insulator set, HT 11 KV triple pole, 200 amps current rating complete with drop out fibre glass tube fuse, mechanically operated mechanism from ground level consisting of operating rod of 25 mm bore medium grade GI pipe of suitable length with locking arrengment, flat iron clamp 50mm x 6mm including MS channel of suitable size and length for fixing GOD including bolts, nuts and washers incl jumper connection with copper flexible designed jumper complete all as specified and directed
M&L for dismantling, shifting & re-installation of old LT panel board of any size/type at new site after disconnection all incoming & outgoing connections/cables, LT Panel to be mounted/ grouted on new PCC blocks/foundation of suitable size at new location using 1:2:4 type C1 with 20 mm graded stone aggregate, incl connections of all incoming/outgoing cables with required excavation of loop & refilling, using lugs, nut, bolts, proper connection to main earth lead, glands to be provided/replaced as required at cable entries and spray painting with powder coated paint with smoke grey paint in outer/inner side of panel after cleaning and preparing surface incl sign writing complete all as directed.
M & L for repair/overhauling of old LT panel board of any size/type incl cleaning with compressed air, tightening of all electric connections to bus bar & switchgears, re-fixing of door (front & backside) with proper fixing & locking arrangement, replacement of wornout lugs, nut, bolts, proper connection to main earth lead, glands to be provided/replaced as required at cable entries, fixing of door front & back side with proper locking arrangement, repair to PCC foundation as required at site and spray painting with powder coated paint with smoke grey paint in outer/inner side of panel after cleaning andpreparing surface incl sign writing complete all as directed
Supply, installation and connecting to electrical system, LT distribution switch board panel cubical type for out door use, double door, with rigid hinges, door handles locking arrangement back side openable, compartmentalized design, mounted on suitable PCC blocks, fabricated out of CRCA sheet 3mm thick, suitably spaced, totally enclosed in chamber for reception of 3 phase, 440 V, 50 HZ, AC supply including all connection with aluminum strips, internal wiring with suitable size (minimum 1.5 sqmm) of PVC copper conductor wire with lugs. Panel shall be effectively PVC gasketed and sealed, glands to be provided at cable entries, powder coated painting and sign writing for in/out going connections all as specified & directed and comprising of following as under :-
(a) 4 Nos bus bars of high conductivity aluminium alloy, 3 Nos for phase (R,Y,B) rating 300 amp rating and 1 No for neutral rating 150 amp, mounted on DMC support with heat shrink sleeve - 01 set.
(b) MCCB 4 pole, 250 amp, 415 volts, 25 KA - 01 No ( Incoming)
(c) MCCB 4 pole 100 amp, 415 volts, 16 KA - 02 Nos. (outgoing)
(d) MCCB 4 pole 63 amp, 415 volts, 16 KA - 03 Nos. (outgoing)
(e) MCB SPN 63 amp, 240 volts, 'C' series,10 KA - 02 Nos. (outgoing)
(f) Voltmeter (0-500V) digital type -01 No
(g) Ammeter (0-300 amps) digital type with CT's - 01 No
(h) Indication lamp (R,Y,B), LED type - One set of three
(j) Grouting of panel including PCC work (Note :- Make of MCCB/MCB - Schneider/ABB/L&T/Legrand)
Servicing & overhauling of Air Circuit Breaker (ACB) of any capacity by taking out from existing LT panel, cleaning all parts internally and externally, checking of the proper tension of the springs mechanical mechanism, tightening of connection of moving, fixing contact, floating contacts, servicing of motor & charging system incl replacement of faulty parts/spares and re-fixing it on its original position and testing complete all as directed
M&L for repair/overhauling of existing APFC panel of 80 KVAR rating incl cleaning with compressed air, tightening of all electric connections, replacement of wornout/unserviceable parts such as automatic power factor controller relays, capacitors, contactors, CTs, cable of suitable capacity/rating with supply & replacement of lugs, nut, bolts, internal wiring with suitable size of PVC copper conductor wire, lugs/ thimbles of required size, incl any work not included above but considered necessary for efficient performance of APFC panel and testing on completion complete all as specified & directed. (Note :- Spare parts such as capacitors, relay, MCBs, contactor & indiacator lamps will be measured and paid separately)
Supply only following item/spares for APFC Panel :-
(a) Capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase 440 volts & 50 Hz system for permissible non- linear load 15% of 10 KVAR capacity (Make-Schneider/L&T/Havells)
(c) MCB SP 6 amps, 240 Volts, 10 KA, C series
(d) MCB TP 32 amps, 415 Volts, 10 KA, C series
(e) Indicator lamp (Red), 110 Volt or 220 Volt
M&L in replacement of danger notice plate of 1.6mm thick mild steel sheet, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size for HT/LT 20 x 15 cm size complete all as directed
S&F (in replacement) following items in the existing panel / location and connection with using aluminum lugs incl making necessary alteration in panel/door as required for proper fixing & connection complete all as specified and directed :-
(a) MCCB 3 pole 63 amps, 16 KA breaking capacity, 415 Volt
(b) MCCB 4 pole 63 amps, 16 KA breaking capacity, 415 Volt
(c) MCCB 4 Pole 100 amps, 16 KA breaking capacity, 415 Volt
(d) MCCB 4 Pole 125 amps, 16 KA breaking capacity, 415 Volt
(e) MCCB 4 Pole 200 amps, 25 KA breaking capacity, 415 Volt
(f) MCCB 4 Pole 250 amps, 35 KA breaking capacity, 415 Volt
(g) MCCB 4 Pole 350 amps, 35 KA breaking capacity, 415 Volt
(h) Volt meter (0 to 500 volts) digital type, three phase of size 96mm x 96mm
(j) Amp meter (0 to 500 amps) digital type, three phase of size 96mm x 96mm with suitable CTs
(k) Indicator lamp, LED type Note (i) MCCB should be properly fited in existing compartment and operating handle of MCCB should be proper in opening existing cover/door of compartment of LT panel board. (ii) Make of MCCB/MCB/Contactor - Schneider/ABB/L&T/Legrand)
S&F (in replacement) lightning arrester, metal oxide type (gap less) for out door use complete with all fittings and fixing arrangements, transmission class, discharge capacity 65 kilo amps, suitable for 11000 volts including brackets, clamps, nuts, bolts, washers and connecting to earth wire 4mm dia GI with manufacturers test certificate complete all as specified & directed (Make : Rashtriya/Jaipuria Bros/OBLUM/GE Power/BHEL)
Supply only earth/ discharge rod suitable for 11 KV, single phase, highly insulated, FRP material, Telescopic type, smooth & glossy surface, push button type locking system, total 3 section, assembled length not less than 15 feet, top section dia not less than 25mm & bottom section dia not less than 45 mm, die cast aluminium earthing instrument for 30 mm dia, incl 6 sqmm copper cable not less than 06 mtr long, crocodile grouting clamp with cover complete all as specified & directed.
S&F steel tubular electric pole, swaged type (single swan neck), type 410 SP-31 (9 metre long) complete with CI base plate, bolts, nuts & screws all as specified including the following:- (a) Excavation in post hole not exceeding 1.5 Mtr wide & 2 Mtr deep for pole foundation & getting out in soft loose soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 metres. (b) M&L for Providing PCC 1:4:8, type D2 (using 40 mm graded stone aggregate) in foundation 600mm x 600mm x 1500 mm (planting depth) for concrete encasing the pole upto GL © M&L for Providing PCC 1:3:6, type C2 (using 40 mm graded stone aggregate) for plinth block /Collar above GL, 300 mm high and 450 mm dia (d) M&L for painting of pole externally with one coats of black bituminous paint (upto planting depth) and above plinth block/ concrete collar with two coats of aluminium paint over a coat of red oxide primer including preparation of surfaces including painting of 30 cm wide black bands/strip 3 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 Mtr above coping level complete all as directed
Dismantling and taking out unsv / damaged PCC pole any size/type complete
S&F (in replacement) bracket for street light made out of 40 mm bore GI pipe medium grade not less than 1.2 mtr length bent to shape fixed on pole/wall with and including 50x6mm FI clamps = 02 Nos with nut bolts, washers including painting of clamps with two coats of synthetic enamel paint over a coat of red oxide primer complete
M&L in repair for loop junction box, outdoor type, size 30cmx20cmX15cm, made out of engineering plastic one piece moulding type, bus bar rating 63 amps 4 strips aluminium with bus bar mounting colour R, Y, B, N on DMC unbreakable insulator with cable entry main supply from bottom side and pole light connection from back side, simens grey colout, shock proof, rust proof, fire retardant, having front opening and locking arrangement with MCB SP 10 amps - 01 No, box duly fixed on the pole with flat iron clamp of size 25 mmX3mm with nuts & bolts complete all as specified and directed (Note : Cost of incoming& outgoing cable lugs & glands of suitable size deemed to be included in the quoted rate) (Make : Unilac / Universal Switch Gear Control / Sintex / Tricolite)
M&L (in replacement) for LED street/security light fittings 45 watt, made up of of pressure die cast aluminium housing with toughned glass and individual high power LEDs with secondary optics, IP 66 protection, to be mounted on existing/ new GI bracket and connecting the street light fitting using 1.5 Sqmm PVC insulated copper cable complete all as directed. (Note - New GI bracket with clamp shall be measured & paid seperately) (Make of LED light fitting :- Havells/Philips/Wipro/GE)
All as above but LED light fitting 60 watt
All as above but LED light fitting 90 watt
M&L for LED Flood Light luminaire, energy saving & enviornmental friendly, long life diecast aluminium, IP65, with high power LED as light source incl necessary fixing arrangement with clamps of suitable size and connection using 1.5 Sqmm PVC insulated copper cable complete all as directed for following wattage (Make : Havells/Philips/wipro/GE) :-
(a) 70 Watt
(b) 100 Watt
S&F (in replacement) LED Post top lantern luminaire 40 Watt, 5700 K, energy saving, environmental friendly, long life aesthetically designes with symmetrical light distribution, spun aluminium landscape luminaire with high power LED as light source, clear acrylic cover, IP-65 incl connection using 1.5 Sqmm PVC insulated copper cable complete complete all as directed (Make: Havells/Philips/Wipro/GE)
S&F hand charging handle rod suitable for existing 11 KV VCB of make Crompton Greaves complete all as specofied & directed
Checking & locating of fault in underground HT/LT cable of any size by cable fault locator machine complete all as directed
M&L for replacment of double compression stainless steel gland for power cable incl electric connection complete with new lugs/thimble complete all as directed (Make- Jainson/Dowell/Action/3M) of following sizes :-
(a) Size 22.9 mm dia suitable for 16 sqmm 4 core LT cable
(b) Size 28.9 mm dia suitable for 25 Sqmm 3.5/4 core LT cable
(c) Size 32.1 mm dia suitable for 35 to 50 sqmm 3.5/4 core LT cable
(d) Size 37.7 mm dia suitable for 70 sqmm 3.5/4 core LT cable
(e) Size 41.7 mm dia suitable for 95 sqmm 3.5/4 core LT cable
(f) Size 47.1 mm dia suitable for 120 sqmm 3.5/4 core LT cable
(g) Size 51.4 mm dia suitable for 150 sqmm 3.5/4 core LT cable
(h) Size 56.6 mm dia suitable for 185 sqmm 3.5/4 core LT cable
Repair of earth pit incl required exacavation, earth work and PCC work to make good damaged/disturbed surfaces of earth pit chamber & making new pit cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced and lifting handle on RCC cover with 8 mm MS bars at 150 mm centre to centre both ways incl supply & fixing of wire mesh and funnel including re-connection of earth wire/strip with panel/transformer using GI nut, bolts & washer complete all as specified & directed
M & L for earthing complete with galvanised steel earth plate electrode 600x600x6mm thick directly buried in ground (earth pit not less than 2.25 m deep below ground level) with top edge of earth plate not less than 1.5m below the ground level connected to GI earth wire 4mm dia by means of bolts nuts check nuts and washers of galvanised iron at 2 points & GI pipe 15 mm bore light grade for protection of earthing wire PCC chamber 1:3:6 (type C-1) using 20mm graded stone aggregate, watering pipe 20mm bore light grade, funnel with wire mesh, 50 mm thick cover of RCC 1:2:4 type B-1 using 20mm graded stone aggregate reinforced with 8 mm MS bars at 150 mm centre to centre both ways and charcoal dust and common salt all as shown in electrical plate No. 3 of MES SSR part-I and including excavation & earth work & connecting the earthing point/equipment and testing complete
All as per item No. 58 herein before but with GI strip 32 x 6mm as earthing lead (earth strip will be protected by using 50mm bore GI pipe 'light grade')
Shifting of LT panel board of any size/type from E/M yard, fixing/installation at directed location and connecting to electrical system, panel to be mounted/ grouted on suitable PCC foundation with required/ suitable civil work as directed, incl connections of all incoming/outgoing cables/ submain wirings, using lugs/ gland, nut, bolts, proper connection to main earth lead including dismantling, taking out & shifting old/unsv panel to MES store yard complete all as specified & directed
Dismantling ACSR conductor any size and depositing to MES store yard complete
Schdule of Credit - 50713.000)
HANUMAN BUILDERS
Pall Associates
J.P. Enterprises
Surjit and Sons
m/s VK construction company
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .