| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.8 LAccepted-Finance | ₹4.8 L | L1 | Accepted-Finance Ok |
| 2 | L2₹5.4 LAccepted-Finance | ₹5.4 L | L2 | Accepted-Finance Ok |
| 3 | Rejected-Technical | - | - | Rejected-Technical EMD as FDR not submitted |
| 4 | Rejected-Technical | - | - | Rejected-Technical EMD as FDR not submitted |
| 5 | Rejected-Technical | - | - | Rejected-Technical EMD as FDR not submitted |
| Sl No | Description | Qty | Unit | N.K. BUILDCOM L1 | ISHIKA ASSOCIATES L2 |
|---|---|---|---|---|---|
| 1.01 | Disconnection of 40 HP motors from old existing panel after removing all the cables as per site requirement. (For each motor) | 2 | Job | 11,996 ₹14,155.28 | 50,000 ₹59,000 |
| 1.02 | Painting and strengthening the old cable tray as per site requirement. | 1 | Job | 4,950 ₹5,841 | 20,000 ₹23,600 |
| 1.03 | Providing and layaing of 3 core 50 sq mm armoured aluminiun cable from panel to motor through existing cable tray. | 60 | mtr. | 53,400 ₹63,012 | 75,000 ₹88,500 |
| 1.04 | S/D STARTER FOR 40HP PUMP SET: Supply and fixing of LT panel box having sheet enclosure made out of 16 SWG sheet for main incomer of supply by electricity board and size 1900x1800x350mm,totally enclosed ,power coated free standing floor mounted type, dust & vermin proof, out ward opening door having hidden hing and bolted back cover both using non-deteriorating neoprene rubber gasket. The various components and sub equipment of the panel will be shaped out of high conductivity electrolyte aluminium conductor 300AMP. and shall be liberal size. The control wiring of the panel will be done with PVC flexible wire of 1.5 mm2 each wire will be terminating a ferule crimped to the wire having the following components.:- Main Incomer: 250 A 4-pole MCCB (Breaking Capacity 36 kA or as per site requirement)Thermal based release,Under-voltage & overload protection, ON/OFF indication lamps, Digital multifunction meter with CTs (250/5A), RYB phase indicator, 1 No. 63 A MCB for control supply transformer, 1 No. , Rotory Handle for MCCB250 Amp 3P, Spreader Link For MCCB 250 Amp 3P, 250 Amp C/O Switch 4Pole, For 40 HP Pump Motors Feeder 2 Working + 1 Spare Starter (Each feeder will include) outgoing MCCB 125 Amp 4Pole, Star–Delta Starter (Automatic), Main Contactor: 80 A, Delta Contactor: 80 A, Star Contactor: 70 A, Overload Relay (Adjustable 50–70 A), Timer for star–delta transition, Phase failure relay, Single-phasing & reverse-phase protection, ON/OFF, lamps, Trip indication, Ammeter with selector switch (RYB) Digital, Auto/Manual selector switch, Start/Stop push buttons | 1 | Job | 3,24,000 ₹3.8 L | 60,000 ₹70,800 |
| 1.05 | For 5 HP vacuum Pump & dewatering pump feeder 2 Working + 1 Spare Starter (Each feeder will include) Outgoing MCB/MCCB: 25 A TP MCB,DOL Starter (Direct On Line), 18 A contactor, 2–10 A overload relay | 1 | Job | 5,800 ₹6,844 | 27,000 ₹31,860 |
| 1.06 | , Phase failure relay, ON/OFF lamps, Start/Stop Push buttons. | 20 | mtr. | 2,600 ₹3,068 | 1,50,000 ₹1.8 L |
| 1.07 | Power capacitor of 20 kvar. 415 volt 50Hz AC- 3 Nos with 40A TP MCB, All iten taken as per DJB Approved Make. | 1 | Job | 4,700 ₹5,546 | 79,000 ₹93,220 |
Tender Value
₹4.8 L
EMD Value
₹9,700
Closing Date
19 Jan 2026, 3:00 pmClosed
Executive Engineer(E and M)M-10
Command Tank 1, SFS Flats, Dwarka Sector 7, Delhi- 110075
Renovation of LT panel of secondary BPS at Dwarka Sector 17A Sarvahit Apartment.
2026_DJB_284762_3
NIT NO. 22 (2025-26)/EE(EnM)M-10
Open Tender
Miscellaneous Works
Office of Ex. Engineer(E and M)M-10
Please refer tender documents
2 documents required · 2 mandatory
₹500
Account No SB 06121000095461
₹9,700
19 Mar 2026
13 Jan 2026
19 Jan 2026
13 Jan 2026
19 Jan 2026
13 Jan 2026
Disconnection of 40 HP motors from old existing panel after removing all the cables as per site requirement. (For each motor)
Painting and strengthening the old cable tray as per site requirement.
Providing and layaing of 3 core 50 sq mm armoured aluminiun cable from panel to motor through existing cable tray.
For 5 HP vacuum Pump & dewatering pump feeder 2 Working + 1 Spare Starter (Each feeder will include) Outgoing MCB/MCCB: 25 A TP MCB,DOL Starter (Direct On Line), 18 A contactor, 2–10 A overload relay
, Phase failure relay, ON/OFF lamps, Start/Stop Push buttons.
Power capacitor of 20 kvar. 415 volt 50Hz AC- 3 Nos with 40A TP MCB, All iten taken as per DJB Approved Make.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.75 MB
nit22.pdf
Tender Documents • 0.73 MB
BOQ_376636.xls
BOQ • 0.26 MB
Download all tender documents and submit your bid