Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹99.0 LAccepted-AOC | ₹99.0 L Quoted ₹1.0 Cr | L1 | Accepted-AOC Being reasonable and Lowest L1 |
| 2 | L2₹1.1 Cr+₹8.6 L (8.26%)Rejected-Finance | ₹1.1 Cr+₹8.6 L (8.26%) | L2 | Rejected-Finance Being other than L1 |
| 3 | L3₹1.2 Cr+₹12.1 L (11.6%)Rejected-Finance FLAT NO 201 GF KAMAL VIHAR CGHS LTD PLOT NO 5 SECTOR 7 DWARKA NEW DELHI 110075 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110075 | ₹1.2 Cr+₹12.1 L (11.6%) | L3 | Rejected-Finance Being other than L1 |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not approved due to two class below |
Tender Value
₹1.1 Cr
EMD Value
₹1.8 L
Closing Date
4 Feb 2020, 6:00 pmClosed
Col SS Bose
HQ CWE (AF) Chakeri, Kanpur
REPLACEMENT OF OLD CENTRAL AC PLANT OF AOVH LAB OF 01 BRD AND AC PLANT AT SITE-I (RSG) ARD-24 AT 29 ED AND MANNING OPERATION AT AFS KANPUR
2019_MES_283603_2
82103/E8
Open Tender
Electrical and Maintenance Works
Item Rate
183 days
Chakeri Kanpur
Class B cat (i)
8 documents required · 8 mandatory
₹1,000
GE (AF) E/M Chakeri
₹1.8 L
29 May 2020
27 Dec 2019
10 Feb 2020
27 Dec 2019
4 Feb 2020
18 Jan 2020
Amount
SCH 'A' PART-I AC PLANT WORK AND CIVIL WORKS: - Dismantling and taking down old central AC plants various type comprising of compressors, compressor motors, condenser pumps, coooling tower, AHU, panel board with control switches, condenser water pipe lines etc. and all connected items including dismantling of foundation of equipment from AVOH Lab (3 x 25 TR) Plant & SITE-I (RSG) ARD-24 of 29 ED (4x13 TR) for faciliating replacement of BER plants with new plants and removing from site complete all as specified & directed. NOTE:- AC duct shall be removed upto plenum level only & AC duct inside building is not to be removed. However, diffusers & grills shall be replaced on requirement basis.
Supply, Installation, Testing & Commissioning of water cooled scroll chiller units having minimum capacity 25.5 TR with multi scroll compressor with microprocessor control. The Unit shall have compressor mounting arrangemrnt on rubber Grommets with metal sleeves. Water cooled shell & tube type condenser. DX type evaporator duly insulated. Thermostatic expansion valve with Extl. Equalizer. Unit shall have filter dryer, pressure switch i.e HP/LP, Electronic Thermostat Flow switch at chiller, Integral refrigerant piping & wiring, Accessories as required and called for automatic and safety control, mounted in central console Electronic microprocessor with soft starter panel central overloaded protector including comprising of following accessories/facilities:- (A) Mode: (i) Auto/Manual (ii) Single Phasing Protection, (iii) Compressor Restart Protection, (iv) 10- Sec Time Delay between System, (v) Short Circuit Protection 5 deg C - Anti Freeze Protection, (vi) Display on Micro control indicating compressor on, (vii) Crankease Heater ON/OFF, Entering/Leaving water Temp, (B) Refrigerant: (i) R-407c or any other non CFC / non HCFC gas (ii) Actual capacity as per Ambient condition, (iii) Scroll Chiller Unit shall be suitable for 400Volt +10%, 50C/S, 3Phase Ac Supply. (C) Chiller (i) Chilled water Inlet Temp. 12˚C, (ii) Chilled water outlet Temp. 7˚C, (iii) Fouling Factor: 0.000088 m2 K/W, (D) Condenser (i) water cooled shel and tube type with in built copper tubing (ii) Condenser water Inlet Temp. 32.5˚C, (iii) Condenser water outlet Temp. 37.5˚C
Supply, installation, testing and commissioning of AHU for operation of supply and return air application of suitable capacity, indoor type, draw through type of sectionalized construction, factory made, floor mounted double skin type made of 25mm thick modular AHU panels with GI casing of thickness 24 Gauge outside layers and 24 Gauge inside layer injected with CFC free polyurethane foam (PUF) of 38 kg/cum density insulation complete with blower section, chilled water cooling coil section, filter section with muffler and access door to attend the motor/fan with lighting provisions and all accessories capacity not less than 18000 CFM including necessary PCC foudation with vibration isolators complete all as specified and as directed including comprising of following:-
(i) Cooling coil of 6 row deep copper tube with aluminium fins and automatic controlled anti-freeze thermostat
(ii) Blower section complete with blower having forward curved centrifugal fan for weather maker suitable for desired static pressure as specified , with minimum 2 bends GSS eliminators with suitable capacity TEFC squirrel cage induction motor (IP 55 and class F insulation) for operation on 3 phase 415 volts, 50 HZ AC supply with belt driven pulley.
(iii) 50 mm thick washable type pre-filters with filter element made out of synthetic non-woven media supported by HDPE mesh on both side including stitching in diamond pattern complete including frame, suitable for efficiency 90% down to 10 micron EU-3 Type complete with mounting frame work.
(iv) Secondary dry type cleanable and easily maintainable air filter supported by GI wire and folder to form accordion plate having an efficiency of 99% down to 5 micron EU-5 TYPE complete with mounting frame works.
(v) Drain connection, stainless steel(SS304 Grade) drain pan and with necessary GI pipe for drain out the condensate to the open drain of the building.
(vi) Humidification system complete with mono-block pump set of suitable size, water tank, pipe line & sprinkler as required at site with fully automatic arrangement for operation with humidistate.
Supply, installation, testing and commissioning of AHU for operation of supply and return air application of suitable capacity, indoor type, draw through type of sectionalized construction, factory made, floor mounted double skin type made of 25mm thick modular AHU panels with GI casing of thickness 24 Gauge outside layers and 24 Gauge inside layer injected with CFC free polyurethane foam (PUF) of 38 kg/cum density insulation complete with blower section, chilled water cooling coil section, filter section with muffler and access door to attend the motor/fan with lighting provisions and all accessories capacity not less than 10400 CFM including necessary PCC foudation with vibration isolators complete all as specified and as directed including comprising of following:-
(i) Cooling coil of 6 row deep copper tube with aluminium fins and automatic controlled anti-freeze thermostat
(ii) Blower section complete with blower having forward curved centrifugal fan for weather maker suitable for desired static pressure as specified , with minimum 2 bends GSS eliminators with suitable capacity TEFC squirrel cage induction motor (IP 55 and class F insulation) for operation on 3 phase 415 volts, 50 HZ AC supply with belt driven pulley.
(iii) 50 mm thick washable type pre-filters with filter element made out of synthetic non-woven media supported by HDPE mesh on both side including stitching in diamond pattern complete including frame, suitable for efficiency 90% down to 10 micron EU-3 Type complete with mounting frame work.
(iv) Secondary dry type cleanable and easily maintainable air filter supported by GI wire and folder to form accordion plate having an efficiency of 99% down to 5 micron EU-5 TYPE complete with mounting frame works.
(v) Drain connection, stainless steel(SS304 Grade) drain pan and with necessary GI pipe for drain out the condensate to the open drain of the building.
(vi) Humidification system complete with mono-block pump set of suitable size, water tank, pipe line & sprinkler as required at site with fully automatic arrangement for operation with humidistate.
Supply & fixing of flexible canvass connection for AHU's/package units to duct including zib superior quality complete all as specified and directed.
Supply and fixing of GI volume control dampers with matching flanges complete all as specified and directed.
Supply and fixing of fresh air arrangement with VCD, louvers and bird screen complete all as specified and directed.
Supply and fixing of mechanical fire dampers fusible type approved for 90minutes fire rating as per UL 555-1995 in main supply air duct including control wiring. The dampers shall be made of heavy gauge galvanized steel having multi blade construction. The blades shall be fitted with chrome plated shaft and self lubricated phosphorus bronze bushes.The dampers shall also be provided with jam seal (compression type) on sides to prevent spread of smoke and fire. The blades of the dampers are held in the ‘open’ position by a high tensile spring and a fusible link. The fusible link should be UL stamped and operates at 74˚C, causing the damper to close immediately on break fire to prevent the spread of fire through the ducts complete all as specified and directed. Note : Operation fire dampers shall be interlocked with AHU & AC plant. In case of shutdown of fire dampers AHU & AC Plant should shut down automatically.
Supply and fixing of heater bank 9 Nos of 3 KW/Each for winter heating complete all as specified and directed
Supply and fixing of heater bank 6Nos of 3 KW/ Each for humidity control complete all as specified and directed
Supply and fixing of humidistate complete all as specified and directed.
Supply and fixing of digital temperature & humidy display system showing ambient temperature, humidity etc of AHU room unit and necessary temperature & humidity control wiring and sensor complete all as specified and as directed.
Supply and fixing thermostat compelte all as specified and directed.
Supply and fixing of PVC sheathed copper cable of size 35 Sqmm 3.5 core, superior quality, laying over GI slotted cable tray including necessary supports and frame work compelte all as specified and directed.
Supply and fixing of PVC sheathed copper cable of size 10Sqmm 4 core, superior quality, laying over GI slotted cable tray including necessary supports and frame work compelte all as specified and directed.
Supply and fixing of PVC sheathed copper cable of size 6 Sqmm 3 core, superior quality, laying over GI slotted cable tray including necessary supports and frame work compelte all as specified and directed.
Supply and fixing of PVC sheathed copper cable of size 1.5 Sqmm 2 core, superior quality, laying over GI slotted cable tray including necessary supports and frame work compelte all as specified and directed. Note for item Nos 14 to 17 :- GI slotted cable tray including necessary supports and frame work shall be measured and paid seperately. However necessary fixing arrangements required at site shall be deemed to be included in the unit quoted rate for the above items.
Supply and fixing of GI slotted cable tray 150mm width x50 mm depth made out of 2 mm thick galvanised MS Sheet thick complete all as specified and as directed.
Supply and fixing GI slotted cable tray 300mm width x 50mm depth made out 2mm thick galvanised sheet complete all as specified and directed. NOTE FOR ITEM No 18 & 19:-Necessary supports and frame work to cable tray shall be measured & paid for seperately.
M&L for necessary supports and mild steel frame work to GI Slotted cable tray including MS rod as fastner, MS angle iron nut bolts and washers including welding and grouting work etc fastner & MS angle iron cut to requires shape & size completed all as specified & directed.
M&L earthing complete with galvanised steet earth electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth electrode not less than 1.5 mtr below normal ground level, connected to galvanised iron strip 32 x 6 mm as earth lead by means of bolt, check nuts & washer of GI or steel connected to earth test point including earth strip from earth electrode to test point, Gl pipe 40 mm dia light grade as protection pipe and 20mm dia GI pipe light grade for watering pipe of required length including charcoal dust, common, salt, excavation and earth work, earth pit with PCC 1:3:6 type C 1 using 20mm graded stone aggregate, precast RCC cover 40mm thickness reinforced with 03 Nos TMT bars, 8 mm dia, both ways, funnel with wire mesh, testing and rest as shown in electrical plate No 3 of SSR Part -I including taking out old earthing material, complete all as specified and directed. Note: Earthing strip and protection pipe upto 7.5 metre length shall be deemed to be included in the quoted unit rate. Earthing strip beyond 7.5 metre shall be measured and paid for separately.
M&L earthing complete with Mild steel galvanized earth plate electrode 600 x 600 x 6 mm thick buried directly in ground (earth pit not less than 2.25 M deep below normal GL) with top edge of the plate not less than 1.5M below normal GL,connected to galvanized earth lead wire 4mm dia by means of bolts, nuts, check nuts & washers of GI or steel incl excavation and earth work, PCC (1:3:6) type C-1 chamber with RCC cover (1:2:4) type B0, 40 mm thick, reinforced with 8 mm dia TMT bar, 3 Nos. both way, 15 mm dia light grade GI protection pipe, funnel with wire mesh, watering GI pipe of 20 mm dia 'medium grade' and lugs including Charcoal dust, salt and testing etc. complete all as shown in electrical plate No. 3 of SSR Pt-I 2009 specification. Note : Earthing lead and protection pipe upto 7.5 metre length shall be deemed to be included in the quoted unit rate,earthing lead beyand 7.5 metre shall be measured and paid for separately.
S & F of GI strip 32 x6 mm for extension of earth and connected to equipment or panel complete all as specified and directed.
S & F of GI wire lead 4 mm dia for extension of earth and connected to equipment or panel complete all as specified and directed.
Supply, installation, testing & commissioning of centrifugal pump sets, factory assembled & tested for rated efficiency complete with motor & common base frame, coupling guard, cladded insulation etc. for re-circulation of condenser water from cooling tower to condenser for the air conditioning system. The pumps shall be suitable for operation on 415 ± 10% Volts, 50 Hz, 3 Phase AC power supply complete all as specified and directed . The pump characteristic of centrifugal pump set shall be as follows:- a) Water quantity : 200 US GPM b) Static Head : 20 M c) Impeller : Bronze
Supply, installation, testing & commissioning of centrifugal pump sets, factory assembled & tested for rated efficiency complete with motor & common base frame, coupling guard, cladded insulation etc. for re-circulation of chilled water for the air conditioning system. The pumps shall be suitable for operation on 415 ± 10% Volts, 50 Hz, 3 Phase AC power supply complete all as specified and directed. The pump characteristic shall be as follows: a) Water quantity : 160 US GPM b) Static Head : 24 M c) Impeller : Bronze
Supply, installation, testing & commissioning of centrifugal pump sets, factory assembled & tested for rated efficiency complete with motor & common base frame, coupling guard, cladded insulation etc. for re-circulation of chilled water for the air conditioning system. The pumps shall be suitable for operation on 415 ± 10% Volts, 50 Hz, 3 Phase AC power supply complete all as specified and directed. The pump characteristic shall be as follows: a) Water quantity : 100 US GPM b) Static Head : 20 M c) Impeller : Bronze
Supply, installation, testing & commissioning of centrifugal pump sets, factory assembled & tested for rated efficiency complete with motor & common base frame, coupling guard, cladded insulation etc. for re-circulation of chilled water for the air conditioning system. The pumps shall be suitable for operation on 415 ± 10% Volts, 50 Hz, 3 Phase AC power supply complete all as specified and directed. The pump characteristic shall be as follows: a) Water quantity : 85 US GPM b) Static Head : 20 M c) Impeller : Bronze
Supply,install,testing and commissioning of Induced draft type not less than 65 TR cooling tower of FRP complete with all accessories, basin, fittings, fan, fan motor etc with following technical data with necessary RCC foundation as per manufacturers standard specification including by-pass arrangement for non interruption in operation of AC plant while cleaning or replacing of strainer complete all as specified and directed.
Supply,install,testing and commissioning of Induced draft type not less than 35 TR cooling tower of FRP complete with all accessories, basin, fittings, fan, fan motor etc with following technical data with necessary RCC foundation as per manufacturers standard specification including by-pass arrangement for non interruption in operation of AC plant while cleaning or replacing of strainer complete all as specified and directed.
Supply, laying, testing and commissioning of galvanised iron 'heavy grade' condenser water pipes with complete fittings such as bends, tees, elbows, reducers, flanges, special fiittings, suspension hangers, etc. complete all as specified and directed of following sizes:- (a) 100 mm dia
(b) All as per Sl Item No. 31 above but of 80mm dia.
(c) All as per Sl Item No. 31 above but of 65mm dia
(d) All as per Sl Item No. 31 above but of 40mm dia
Supply and fixing of cast iron flannged balancing valves with pressure test cocks only in EN-3 Stem, EN-3 disc and EPDM sealing disc with PN -10 complete all as specified and directed of following sizes:- (a) 65 mm dia
(b) All as per Sl Item No.32 above but of 80mm dia
Supply and fixing of butterfly valves cast iron body, wafer type, integrally moulded close end body construction with hand lever operated and rating of PN-10 complete all as specified and directed of following sizes:- (a) 100 mm dia
(b) All as per Sl Item No.33 above but 80 mm dia
(c) All as per Sl Item No.33 above but 65 mm dia
Supply and fixing of dual plate check valves, cast iron body & rating of PN -10 complete all as specified and directed of following sizes:- (a) 65 mm dia
Supply and fixing of Y- Strainers cast iron body & rating of PN-10 of size 100 mm dia complete all as specified and directed.
All as per Sl Item No.35 above but 80 mm dia
Supply, laying, testing and commissioning, insulated Mild Steel 'C' class chilled water pipes of following size with complete fittings such as bends, tees, elbows, reducers, flanges, special fiittings, suspension hangers, thrust blocks of rubber material having density 1400 Kg/cum etc. as required including pipe insulation with two half round of PUF in density 36 + 2 Kg/cum confirming to IS 12436 section shall be banded to the surface of pipe with adhesive fevicol SR 998 and binded with metal binding wire apply fevicol AC duct tack coating AF:5590 on insulated surface uniformly and wrap the glass cloth tightly with over lapping so that no gaps are left and no air pockets are formed. Immediately apply additional coating as finish layer on the wrap cloth and finally finish with aluminium cladding 28 gauge with necessary hardware fitting :- (a) 50 mm dia,
(b) All as per Sl Item No.36 above but 65 mm dia
(c) All as per Sl Item No.36 above but 80 mm dia
Supply and Fixing of butterfly valve, cast iron body, Wafer type, integrally moulded close end body construction with hand lever operated and rating of PN-10 with insulation of following size complete all as specified and directed:- (a) 50 mm dia
Supply and fixing of cast iron flanged balancing valve of size 65 mm dia with pressure test cocks only in EN-3 Stem EN-3 disc and EPDM sealing Disc with PN -10 with insulation complete all as specified and directed.
Supply and fixing of dual plate check valve of size 65 mm dia Cast Iron body & Rating of PN -10 with insulation complete all as specified and directed.
Supply and fixing of ball valve/ purge valve of size 25 mm dia with insulation complete all as specified and directed.
Supply and fixing of water flow switches complete all as specified and directed.
Supply and fixing of pressure 4" Dia gauges of burden type, stainless steel or CP brass stem complete with Globe valve confirming to IS-3624 complete all as specified and directed.
Supply and fixing of bimetal dial type temperature Gauge of 100 mm dia. of suitable range with adjustable stem complete all as specified and directed.
Supply and laying of condensate drain water piping with PVC pipes and necessary fittings like elbows, tees, reducers etc and including insulation with 13 mm thick nitrile rubber, of 40 mm dia complete all as specified and directed.
Supply and fixing of 5000 Ltr PVC Make up Tank, three layer , white, including overflow valve, float valve and connection to cooling tower with 32mm dia GI ' medium grade' pipe of required length complete all as specified and directed. (NOTE: Quoted unit rate shall be included cost of make up tank, overflow valve, float valve and GI pipe complete.)
Supply and fixing of 500 Ltr PVC Chilled water Make up Tank, three layer , white, with and including required thermal insulation as per requirement of chilled water make up tank of AC plant and overflow valve, float valve & connection to chilled water pipe line with 32mm dia GI ' heavy grade' pipe of required length complete all as specified and directed. (NOTE: Quoted unit rate shall be included cost of make up tank, thermal insulations, overflow valve, float valve and GI pipe complete.)
Supply and erection of GI Sheet of 22 SWG GSS ducting metal work for ducting as per IS:655 complete with all fittings such as tee, bends,turning vanes, splitter dampers, inspection doors, transformation pieces etc including suspension and supporting arrangement for plenums, ducts complete all as specified and directed.
Supply and fixing of duct thermal insulation for ducts which are exposed to sunlight , insulation with 50 mm thick TF Quality thermocole having density of 16 Kg/cum+10% and including adhesive used for setting the insulation (Adhesive shall be non-flameable, vapour proof and cold setting compound), the insulation shall be covered with GI mesh, polythene sheet and cement sand motar rendering in ratio (1:3) complete all as specified and as directed.
Supply and laying of accoustic insulation of duct with 25 mm fibre glass rigid board covered with 28 Gauge aluminium perforated sheet and RP tissue complete all as specified and as directed.
Supply and laying of Thermal insulation of duct with 13 mm thick nitrile foam sheet insulation having density 50Kg/Cum and fixing with adhesive as per the recommendation of the manufacturer complete all as specified and as directed.
Supply , installation, testing and commissioning of 50/80 mm three way motorised modulating valves with modulating motor and thermostat etc. complete with fittings like elbows, tees, reducers, bends, MS flanges, supports, welding etc as per requirement complete all as specified and as directed.
Design, fabrication, supply, installation, testing and commissioning of the following Indoor type LT panel suitable to be mounted on the floor/cable duct/ wall as per site requirement using M.S channel frame work, with cable entry from bottom/top as per drawing coordination by EIC with removable gland plates with required knock-outs for incoming and outgoing cables. Panel shall be fabricated out of CRCA sheet 2 mm thick steel folded and braced as necessary to provide a rigid support for all components, totally enclosed and degree of protection shall not be less than IP-54, multi-tier cubicle type formation with front hinged lockable doors for the individual feeders/compartments, preparation of surface and treatment by seven tank process, powder coated with approved colour for not less than 50 microns and all doors and covers shall be fully gasket using good quality EPDM gasket and /or rubber strips, and to provide good quality locking arrangement, durable door opening & closing mechanism, aluminum bus bars for three phases and neutral, bus bar insulators, heat shrinable PVC sleeves etc, with necessary interconnections as spectified in Technical specifications for electrical & mechanical works including comprising of following switchgear and accessories complete in all respects:-
Incoming (a) MCCB Four ploe 250 Amps, 415Volts, 50KA breaking capacity with adjustable thermal setting based overload and short circuit release including door interlocking device, front operating handle, ON and OFF indication of LED module etc. Complete in all respects -1 No
(b) 400 Amp aluminium bus bars for phase and neutral with bus bar insulators, heat shrinkable PVC sleeves etc complete.
(f) 400/5A current transformers of class 0.5 and suitable VA burden for metering -1 Set.
(g) RYB indicating lamps of LED module with toggle switches - 1 Set.
(h) 2Amps, 230Volts, SP, MCB's for the protection of measuring instrument and control wiring -1 Set .
Outgoing (a) For 26 TR chiller units and spare 100 Amp. 36KA, 415V, TP+NL MCCB with adjustable thermal settings, overload and short circuit release including door interlocking device, front operating handle , ON and OFF indication of LED module, bus bar extension for connecting cables etc. complete in all respects - 03 Nos.
(b) For Chilled water pump 63 Amp. 36KA, 415V TP+NL MCCB with adjustable thermal with starter - 2 Nos .
(c) For Condenser water pump 63 Amp. 36KA, 415V, TP MCCB with adjustable thermal settings, with starter suitable for 3.7 KW condenser motors rating, AC 3 duty 415V, 50Hz, 3ph motor - 2Nos. (d) The starter shall be with single phase prevention and electronic timer, with sufficient auxiliary contacts for remote ON/OFF indication lamps, bi-metallic thermal overload relay of suitable size current rating, ON/OFF push buttons suitably wired and interconnected with 4.0 Sq.mm single stranded PVC copper wire, etc, complete in all respects. NOTE:- Starter shall be DOL type upto 5 HP motor & star delta type for above 5 HP motor
(e) For AHU 32 Amp. 36KA, 415V, TP+NL MCCB with adjustable thermal settings -2 Nos .
(f ) For Cooling Tower 16 Amp 36 KA, 415V, TP+NL MCCB with adjustable thermal settings, with starter suitable for 5 HP cooling Tower motors rating, AC 3 duty 415V, 50Hz, 3ph motor - 1 No. (g) The starter shall be with single phase prevention and electronic timer, with sufficient auxiliary contacts for remote ON/OFF indication lamps, bi-metallic thermal overload relay of suitable size current rating, ON/OFF push buttons suitably wired and interconnected with 4.0 Sq.mm single stranded PVC copper wire, etc, complete in all respects. NOTE:- Starter shall be DOL type upto 5 HP motor & star delta type for above 5 HP motor.
(h ) For Heater Bank
100 Amp. 36KA, 415V, TP+NL MCCB with adjustable thermal settings -1 No
Design, fabrication, supply, installation, testing and commissioning of the following Indoor type LT panel suitable to be mounted on the floor/cable duct/ wall as per site requirement using M.S channel frame work, with cable entry from bottom/top as per drawing coordination by EIC with removable gland plates with required knock-outs for incoming and outgoing cables. Panel shall be fabricated out of CRCA sheet 2 mm thick steel folded and braced as necessary to provide a rigid support for all components, totally enclosed and degree of protection shall not be less than IP-54, multi-tier cubicle type formation with front hinged lockable doors for the individual feeders/compartments, preparation of surface and treatment by seven tank process, powder coated with approved colour for not less than 50 microns and all doors and covers shall be fully gasket using good quality EPDM gasket and /or rubber strips, and to provide good quality locking arrangement, durable door opening & closing mechanism, Aluminium bus bars for three phases and neutral, bus bar insulators, heat shrinkable PVC sleeves etc, with necessary interconnections as specified in Technical specifications for electrical & mechanical works, including comprising of following switchgear and accessories complete in all respects:-
INCOMING (a) MCCB, four ploe, 100 Amp, 415V, 50KA breaking capacity with adjustable thermal setting based overload and short circuit release including door interlocking device, front operating handle, ON and OFF indication of LED module etc. Complete in all respects-1 No
(b) 200 Amp aluminium bus bars for phase and neutral with bus bar insulators, heat shrinkable PVC sleeves etc. complete.
(c) Multi function meter (MFM/MDM) suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1, RS 485 Port Digital MFM/MDM of power logic PM210 of Schneider or any approved equivalent make meeting technical specification of above MFM complete in all respect -01 No
(d) Digital temper proof energy meter (Kwh) -01 No
(f) 200/5A current transformers of class 0.5 and suitable VA burden for metering-01 Set.
(g) RYB indicating lamps of LED module with toggle switches-01 Set.
(h) 2A, 230V ,SP MCB's for the protection of measuring instrument and control wiring-1 Set.
OUTGOING (a) For 26 TR chiller units
63 Amp,36KA, 415V TP+NL MCCB with adjustable thermal settings, overload and short circuit release including door interlocking device, front operating handle , ON and OFF indication of LED module, bus bar extension for connecting cables etc. complete in all respects-02 Nos
(b) For Chilled water pump
16 Amp. 36KA, 415V TP MCCB with adjustable thermal with starter-02 Nos
(c) For Condenser water pump
16 Amp. 36KA, 415V TP MCCB with adjustable thermal settings, with starter suitable for condenser motors rating, AC 3 duty 415V, 50Hz, 3 Phase motor-2 Nos (d) The starter shall be with single phase prevention and electronic timer, with sufficient auxiliary contacts for remote ON/OFF indication lamps, bi-metallic thermal overload relay of suitable size current rating, ON/OFF push buttons suitably wired and interconnected with 4.0 Sq.mm single stranded PVC copper wire, etc., complete in all respects. (Note: Starter shall be DOL type upto 5 HP motor & star delta type for above 5 HP motor)
(e) For AHU Panel
16 Amp. 36KA, 415V TP+NL MCCB with adjustable thermal settings-01 Nos.
(f) For Cooling Tower
16 Amp. 36KA, 415V TP MCCB with adjustable thermal settings, with starter suitable for 5 HP cooling Tower motors rating, AC 3 duty 415V, 50Hz, 3Ph motor-1 No (g) The starter shall be with single phase prevention and electronic timer, with sufficient auxiliary contacts for remote ON/OFF indication lamps, bi-metallic thermal overload relay of suitable size current rating, ON/OFF push buttons suitably wired and interconnected with 4.0 Sq.mm single stranded PVC copper wire, etc., complete in all respects. (Note: Starter shall be DOL type upto 5 HP motor & star delta type for above 5 HP motor).
(h) For Heater Bank
40 Amp. 36KA, 415V TP+NL MCCB with adjustable thermal settings-01 Nos.
Supply & fixing cubical type vermin proof dust proof indoor type factory made by the manufacturer having type test report of CPRI approved wall mounted of size of 1.2 x 1.0 x 0.8 mtr LT electric panel board totally enclosed with separate chambers for bus bars cable entry exist and digital volt and Ampere Meter complete internal wiring with suitable size of copper conductor multi standard, indicator lamp etc. Suitable for 3 phase 415 Volt 50 Hz and having anodised copper bus bar (4 Nos of 100 Amp) fabricated from 2 mm thick CRCA sheet powder coated through 7 Tank process facility for pricking and degreasing duly interconnected for with all allied accessories for wall mounting type panel all as specified and directed by engineer in charge including comprising of the following (AHU Motor):-
(a) Main incoming MCCB 3 Pole 32 Amp 36 KA, 415 V 50 Hz- 01 Nos
(b) The starter shall be with single phase prevention and electronic timer, with sufficient auxiliary contacts for remote ON/OFF indication lamps, bi-metallic thermal overload relay of suitable size current rating, ON/OFF push buttons suitably wired and interconnected with 4.0 Sq.mm single stranded PVC copper wire, etc., complete in all respects. (Note: Starter shall be DOL type upto 5 HP motor & star delta type for above 5 HP motor).
Supply & fixing cubical type vermin proof dust proof indoor type factory made by the manufacturer having type test report of CPRI approved wall mounted of size of 0.9 x 0.9 x 0.6 mtr LT electric panel board totally enclosed with separate chambers for bus bars cable entry exist and digital volt and Ampere Meter complete internal wiring with suitable size of copper conductor multi standard, indicator lamp etc. Suitable for 3 phase 415 Volt 50 Hz and having anodised copper bus bar (4 Nos of 100 Amp) fabricated from 2 mm thick CRCA sheet powder coated through 7 Tank process facility for pricking and degreasing duly interconnected for with all allied accessories for wall mounting type panel all as specified and directed by engineer in charge including comprising of the following (for heater bank):-
(a) Main incoming MCCB TP+NL 100 Amp 36 KA, 415 V 50 Hz- 01 Nos
(b) Outgoing MCCB TP+NL 63 Amp, 25 KA, 415 V 50 Hz- 02 Nos
(c) S&F two set of heater starter system for winter heating and humidity control with thermostat and humidity stat and provision of necessary control wiring including interlocking arrangement and fully automatic ON/OFF control complete all as specified and directed-02 Nos
Supply and fixing aluminium extruded powder coated return/supply air grill with Volume control dampers with matching flanges horizontal fixed bar of 12 Nos, 1.2 mm thick and 11.5mm spacing with 0/15/30 degree deflection (ISI marked) complete all as specified and directedd by Engr-in-charge.
Supply and fixing aluminium extruded powder coated return/supply air grill with Volume control dampers with matching flanges horizontal fixed bar of 12 Nos, 1.2 mm thick and 11.5mm spacing with 0/15/30 degree deflection (ISI marked) complete all as specified and directedd by Engr-in-charge.
Supply, installation, Testing & commissioning water softening plant considering water softening flow rate of 2 cum/Hrs with inlet hardness given 105 PPM and hardness of outlet will be less than 5 PPM for condenser water circuit complete all as specified and directed by Engineer-in-charge.
S& F control cable PVC insulated PVC sheathed copper conductor 3 core 1.5 sqmm 1100 volt grade and testing complete all as specified and directed by Engineer-in-charge
Note for item No 01 to 59 above: The above sch is for replacement of 4x13 TR and 3 x25 TR centralized AC plant. The contractor shall submit the general layout plan before starting of work for approval of GE. The civil work like foundation of Eqpt as per manufacturers recommodation,pipe support, duct supports etc. given in the specification are deemed to be included in the quoted unit rate of Ser item No 1 to 59 above
Supply, installation, commissioning and testing of 2.0 TR hi wall split type AC indoor outdoor complete with cordless remote control unit with minimum 3 star rating and EER 3.2 of capacity as shown electric driven (single phase 6000 K cal/Hr, outer unit shall be fitted with discharged cooled type rotary/scrolled type compressor operating on non-CFC refrigerant R-410A/407C including copper piping as required between both the units with suction pipe, discharge pipe and electric cable from inner unit to outer unit, out door unit shall be fixed with PCC platform /powder coated stand fixed on wall including provision of drain pipe for taking out condensed water to appropriate place complete all as specified and directed.
Supply , installation, commissioning and testing of automatic voltage stabilizer for automatic operation single phase naturally air cooled indoor type and designed for input variation between 170 V to 260 V with output voltage at 230 V with accuracy of ± 2.5% and cap of 5 KVA complete.
S&F of sheet metal enclosure , 32 A single phase and neutral a two pin and earth plug and socket complete in metal clad board (Industrial type) with one SPN MCB 32 Amp fixed properly on in concealed position all as directed.
M&L sub main wiring with two single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 4 sqmm drawn in 20 mm dia steel enamelled conduit with 2.5 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete including MS steel conduit ISI marked medium grade of size not less than 20 mm dia in concealed position on wall and surface position of truss inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddles, pipe hooks etc. fixed properly & making good to disturbed surfaces so as to matching with the existing colour of wall/floor etc. complete. Note : Two single core cable of size 4 sqmmand one run of earth copper conductor of size 2.5 sqmm and one run of mild steel conduit shall be measured and paid as one unit length
(CIVIL WORK OTHER THAN INCLUDED UNDER SL ITEM NO 1 TO 63.) Demolition of cement concrete of any description over roof slab complete and removing debries outside MoD land at contractor's own arrangement complete all as specified and directed.
M & L wire brushing and cleaning top surface of tiles, lime terracing or cement concrete, including flashings and junction of parapets, etc., and surface painting, with a layer of blown bitumen of any penetration applied hot @ 1.7 kg per sqm blinded complete all as directed.
M& L 25mm thick cement concrete (1:2:4) type B-1, using 20mm graded stone aggregate mixed with liquid WPC @ 250 ml per 50 Kg bag of cement complete all as specified and as directed by the Engineer-in-Charge Note:- WPC shall be measured & paid separately
M & L brushing neat cement slurry @ 3.0 kg of cement per sqm area complete all as directed.
M&L applying water proofing treatment with one coat of cold applied polymeric primer @ 0.40 Ltr per Sqm and applying a layer of APP based polymeric membrane, not less than 3 mm thick, weighing not less than 3.00Kg/Sqm, reinforced with polyster non woven fabric (weighing not less than 150 gms/Sqm). Application of polymeric membrane shall be laid by torch application. Side overlaps shall be 75 mm and at the ends shall be 100 mm and all overlaps and joints shall also be sealed by torch applicatiion complete all as specified and directed.
M & L 20mm thick Screed bed or bedding layer in CM (1:6) for laying floor tiles, complete all as directed by the Engineer-in-Charge
M & L cement concrete tiles 25cm x 25cm x 22mm thick, machine pressed, set jointed and pointed in neat cement slurry with grey cement and no pigments, in floors, cut and polished complete all as specified and directed by the Engineer-in-Charge
M & L 20 mm thick Screed bed or bedding layer in CM (1:4) for laying floor tiles etc, complete all as specified and as directed
M&L 10 mm thick cement plaster in cement mortar 1:4 on fair faces of brick work or concrete surfaces for fixing of wall tiles on vertical surfaces complete all as specified & directed.
M&L coloured ceramic glazed tiles(Ist quality) of size 300x 450x 7-8mm thick as in vertical surface set & jointed in neat cement slurry and pointed in white or coloured cement to match the tiles all as specified and directed
M&L 18-20 mm thick machine cut kota stone slab mirror polished in floors ,set and jointed in neat cement slurry and pointed in coloured cement to match incl mirror polishing complete all as specified and directed
Taking down cement or cement lime plaster of any description on brick or stone walls or concrete surfaces etc including ranking out joints hacking for key scrubbing down with water etc complete all as specified and as directed
M&L rendering 10 mm thick in cement mortar 1:3 on ceiling of brick or concrete surface, finished even & smooth with out using extra cement complete all as specified and directed
Dismantling floor,hearth or wall tiling including cement mortar bedding, removing serviceable tiles to stores and rubbish off the premises complete all as specified and directed
Demolition of Brickwork masonry, built in cement mortar including removing of debries outside MoD land at contractor's own arrangment complete all as directed
M &L Brickwork with fly ash old size bricks, straright or corved on plan exc 6m mean radius built in Cement mortar 1:6 complete all as specified and directed
M & L rendering 15mm thick in cement plaster (1:6) on fair faces of brick work or concrete surfaces , finished even and smooth without using extra lime or cement all as directed
M&L three coats of white wash on newly plastered or unplastered surfaces of ceiling including preparation of surface complete all as specified and directed
Complete removal of existing treatment on wall, coloumn, beams etc by using wire brush and cleaning the surface for applying further treatment and all as specified and directed
M&L preparing of the plastered surfaces and applying three coats of white wash on walls complete all as specified and direcrted
M&L preparing the plastered surfaces of walls and applying two coats of cement base paint over a coat of cement primer complete all as specified and direcrted
Supply only liquid water proofing compound (best quality) complete.
Demolition of Cement concrete (Unreinforced) of any description in ground floors and pavings n exe 15 cm thickness (below or above ground level) complete all as directed
M &L 75mm thick P.C.C. 1:4:8 type D2 using 40mm graded stone aggregate as in sub-base under floor complete all as specified and as directed
M&L chequerred Cement concrete tiles 20 cm X20cm X 25 mm thick, set jointed and pointed in neat cement slurry with mixture of white and grey cement in equal proportion and no pigment complete all as specified
M&L 75 mm thick cement concrete 1:3:6 type C-2 (using 40mm graded stone agg) as in flooring/plinth protection/sub-base finishing concrete surface even and smooth without using extra cement including filling of joints with sealing compound grade 'B' complete all as specified and directed
M&L hardcore of broken stones of gauge n exc 63 mm , deposited spreaded , levelled in layers n exc 15 cm thick watered and rammed to true surface all as specified
Taking down chowkats or frames with shutters (without taking off shutters from the frames) exc. 1.5 sq. m but not exc 4 sq. m each complete all as directed
Supply and fix in repair steel windows with side hung shutters including box type hinges with steel handle and steel peg stay complete with glazing bars dovetailed or welded all as specified
Supply & fixing IInd class hardwood (Hollock) plain solid straight chowkhats and frames, wrought, framed, rebated on the solid, rounded or chamfered, put together with glue pinned at joints complete all as specified and as directed
S & F 35mm thick, 2nd class HW, plain framed, panelled shutter (two panel) with lock rail and panel of 9mm B.W.P. commercial ply or 12mm veneered particle board with commercial veneering on both faces. The size of rail and stile as per IS:1003 (Part I), kiln seasoned and chemically pressure treated complete all as specified and as directed
S&F Butt hinges of 100 mm size, Medium weight, cold rolled mild steel type and fixed complete all as specified and directed
S&F 250 mm long mild steel sliding door bolts, ISI marked clip type, stove enamelled black, with bright bolt not less than 12 mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate and fixed complete all as specified and directed
S & F 150mm long mild steel barrel tower bolts, stove enamelled black, with bright bolt and fixed complete all as specified and as directed
S&F 150mm long mild steel pressed handles, oval type stove enamelled black comple all as specified.
Supply & Fixing MS work as in hold fast etc conforming to Fe-410-0 or Fe-310-0 complete
M &L PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in hold fast, PCC Bed blocks incl finished all exposed surfaces of concrete incl necessary form work etc complete.
M&L preparation of new wooden surfaces of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of pink primer complete all as specified & directed.
M&L painting to new steel surfaces of any dedcription over 10 cm in with or girth,not otherwise describe and applying two coats of synthetic enamel paints over a coat of red oxide primer complete all as directed
Hacking out old broken glass (any tickness, size,quality or description) from metal frames including punching or drilling out old glazed pins / spring clip and providing and fixing new ones. complete all as specified and directed.
M & L sheet glass 3.0mm thick, ordinary quality and glazing with oil putty in square n exc 0.5 sq m in each pane complete all as specified and as directed
SCH 'A' PART-II (MANNING AND OPERATION OF AC PLANT): M&L for provisioning of resources for management of central AC plant different capacity of various locations having compressors with its connected items such as condensers/chillers, water circulating pumps, chilling pumps, blowers, blower motor, cooling tower with fan and motor including connected starters etc in all respect for smooth running of AC plants during the running period to maintain designed Air conditioning/chilled water temperature inside the building /block from 06:00 hrs to 22:00 hrs (Two shift of 08 hours) every day except holidays and sundays as observed by the air force authority including cleaning of all equipments and sweeping inside and outside of the installation and maintaining of log sheet on daily baisis and proper dress code followed by the operator complete and tightning of pump gland, filling of new gland and new gland nut bolts and electrical complaints of motor pump and panel and starter will be atteneded and rectified by the contractor without any extra cost for smooth function of plant complete all as specified and directed for the following capaciity of plant all working days:- (a) 3x25.5 TR AC Plant at AVOH lab at 1 BRD for the Ist year of defect liability period
(b) All as per Sl item No. 105 (a) above but for Second year of defect liability period.
M&L for provisioning of resources for management of central AC plant different capacity of various locations having compressors with its connected items such as condensers/chillers, water circulating pumps, chilling pumps, blowers, blower motor, cooling tower with fan and motor including connected starters etc in all respect for smooth running of AC plants during the running period to maintain designed Air conditioning/chilled water temperature inside the building /block from 06:00 hrs to 06:00 hrs (Three shift of 08 hours) every day including holidays & Sundays round 'o' clock & cleaning of all equipments and sweeping inside and outside of the installation and maintaining of log sheet on daily baisis and proper dress code followed by the operator complete and tightning of pump gland, filling of new gland and new gland nut bolts and electrical complaints of motor pump and panel and starter will be atteneded and rectified by the contractor without any extra cost for smooth function of plant all as specified and directed for the following capaciity of plant all day:- (a) 2x25.5 TR AC Plant at SITE-I (RSG) ARD-24 of 29 ED for the Ist year of defect liability period
(b) All as per Sl item No. 106 (a) above but for Second year of defect liability period. Note for item No 105, 105.01, 106 & 106.01 The record of manning & operation of all AC plants shall be maintained in each shift duly signed by Engr-in-charge & contractor. If AC plant not running in any shift during manning & operation period the payment of that shift shall be recovered from the contractor's dues against above items as under:- (a) Recovery rate per shift for Item No 105 & 105.01 = Quoted rate against the item per month 02 Shift x 26 days (b) Recovery rate per shift for item No 106 & 106.01 = Quoted rate against the item per month 03 Shift x 30 days
BRITE INDUSTRIES
SHRI RAMSONS PROJECTS CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .