Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance GARDEN AVENUE PLOT NO 242 243 244 RH 4 SECTOR 21 NERUL NAVI MUMBAI 400 706 | THANE | MAHARASHTRA | 400706 | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Admitted-Finance | Admitted-Finance |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
3 Feb 2020, 6:00 pmClosed
GE NW NOFRA
GE NW NOFRA DR HOMI BHABHA ROAD NAVY NAGAR COLABA MUMBAI
REPAIR REPLACEMENT OF UNDER GROUND CABLES AND MCCB LT PANEL BOARD EARTHING AND CERTAIN E M AND B R WORKS VARIOUS BLDGS AT NOFRA COLABA MUMBAI AND REPAIR REPLACEMENT OF UNDER GROUND CABLES AND MCCB LT PANEL BOARD EARTHING AND CERTAIN E M WORKS AT INS
2019_MES_309623_1
8676
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
MUMBAI
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE NW NOFRA
₹80,000
Yes
10 Feb 2020
26 Dec 2019
7 Feb 2020
26 Dec 2019
3 Feb 2020
9 Jan 2020
26 Dec 2019 - 7 Jan 2020
Amount
REPAIR/ REPLACEMENT OF UNDER GROUND CABLES AND MCCB/ LT PANEL BOARD, EARTHING AND CERTAIN E/M & B/R WORKS VARIOUS BLDGS AT NOFRA, COLABA, MUMBAI.
Taking up old U/S XLPE insulated screened , PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor including taking up old concrete cable cover from trenches/walls/ceiling/poles etc any size complete all as specified and directed
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of UG Electric cable / staying of steel tubular pole etc. and getting out in soft and loose soil, complete all as specified and as directed .
Cutting existing road surface or hard standing 0.45 mtr depth (22 cm thick comprising bituminous topping) for laying of pipes/ cables and making good distrubed surface to match with existing complete.
Removing the excavated material/ soil not exc 50m out of MD land complete all as specified and directed by EIC.
M&L of spreading levellings sand unwashed in trenches around the cable for cushioning complete all as specified and directed.
Returning & filling in, including spreading, levelling, watering & well ramming in layers not exc 25 cm as in soil complete all as specified & directed .
Supply and laying unreinforced precast cement concrete cable cover, class-LV, Type I, flat, size-250 x 150 x 40 mm ISI marked including material and labour all as specified and directed.
Laying only Old unreinforced precast cement concrete cable cover, class-LV, Type I, flat, size-250 x 150 x 40 mm for reuse ISI marked all as specified and directed.
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 35 Sqmm laid in trenches / through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 95 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 120 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all as specified & directed.
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 185 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 300 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
(b) (i) Capacitor bank, mixed di electric type 25 KVAR, 415 Volts 50Hz - 01 Nos (ii) -ditto- but rating 20 KVAR - 01 Nos (iii) -ditto- but rating 15 KVAR - 01 Nos (iv) -ditto- but rating 10 KVAR - 02 Nos (v) -ditto- but rating 5 KVAR - 04 Nos (vi) Suitable size of MCB, TP, 'D' Curve, 10 Amps - 01 Nos (vii) -ditto- but for 40 Amps - 01 Nos (viii) -ditto- but for 32 Amps - 01 Nos (ix) -ditto- but for 20 Amps - 02 Nos (x) -ditto- but for 16 Amps - 04 Nos (xi) Power contactors suitable for 25 KVAR capacitor bank -01 Nos (xii) -ditto- but for 20 KVAR - 01 Nos (xiii) -ditto- but for 15 KVAR - 01 Nos (xiv) -ditto- but for 10 KVAR - 02 Nos (xv) -ditto- but for 5 KVAR - 04 Nos (xvi) Switch fuse unit 315 TPN 415 V, with HRC fuses -01 Set
Supply and laying in repair 40 mm dia GI tubing light grade for cable protection at road crossing/ hard standing/ plinth protection/ on the pole etc complete all as specified and directed. Make- Jindal / TATA
Supply and lay in repair 80 mm dia GI tubing light grade for cable protection at road crossing/ hard standing/ plinth protection/ on the pole etc complete all as specified and directed. Make- Jindal / TATA
REPAIR/ REPLACEMENT OF UNDER GROUND CABLES AND MCCB/ LT PANEL BOARD, EARTHING AND CERTAIN E/M WORKS AT INS SHIKRA, NT POOL, BOAT POOL & MD ACCN AT OUTLAYING AREA OF NOFRA UNDER GE (NW) NOFRA, COLABA, MUMBAI
Excavation in trenches not exc 1.5 mtr wide and not exc 1.5 mtr in depth for foundation, laying of UG Electric cable / staying of steel tubular pole etc. and getting out in soft and loose soil, complete all as specified and as directed .
Removing the excavated material/ soil not exc 50m out of MD land complete all as specified and directed .
M&L Spreading levellings sand unwashed in trenches around the cable for cushioning all as specified and directed.
Returning & filling in, including spreading, levelling, watering & well ramming in layers not exc 25 cm as in soil complete all as specified & directed .
Taking up old U/S XLPE insulated screened, PVC bedded, galvanized steel strip or wire armored, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor including taking up Old concrete cable cover from trenches/walls/ceiling/poles etc any size all as specified and directed
Cutting existing road surface or hard standing 0.45 mtr depth (22 cm thick comprising bituminous topping) for laying of pipes/ cables and making good distrubed surface to match with existing complete.
Supply and laying unreinforced precast cement concrete cable cover, class-LV, Type I, flat, size-250 x 150 x 40 mm ISI marked including material and labour all as specified and directed.
Laying only Old unreinforced precast cement concrete cable cover, class-LV, Type I, flat, size-250 x 150 x 40 mm for reuse ISI marked all as specified and directed.
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 35 Sqmm laid in trenches / through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
(b) (i) Capacitor bank, mixed di electric type 25 KVAR, 415 Volts 50Hz - 01 Nos (ii) -ditto- but rating 20 KVAR - 01 Nos (iii) -ditto- but rating 15 KVAR - 01 Nos (iv) -ditto- but rating 10 KVAR - 02 Nos (v) -ditto- but rating 5 KVAR - 04 Nos (vi) Suitable size of MCB, TP, 'D' Curve, 10 Amps - 01 Nos (vii) -ditto- but for 40 Amps - 01 Nos (viii) -ditto- but for 32 Amps - 01 Nos (ix) -ditto- but for 20 Amps - 02 Nos (x) -ditto- but for 16 Amps - 04 Nos (xi) Power contactors suitable for 25 KVAR capacitor bank -01 Nos (xii) -ditto- but for 20 KVAR - 01 Nos (xiii) -ditto- but for 15 KVAR - 01 Nos (xiv) -ditto- but for 10 KVAR - 02 Nos (xv) -ditto- but for 5 KVAR - 04 Nos (xvi) Switch fuse unit 315 TPN 415 V, with HRC fuses -01 Set
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 95 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 120 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all as specified & directed.
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 185 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
Supply and laying in repair PVC insulated XLPE, armoured LT cable, 1100 Volts grade with aluminium conductor of size 3.5 core 300 Sqmm laid in trenches/through pipe /ducts or fixed on wall etc complete all connections to LT panel with proper size glands & lugs all as specified & directed. Make- Polycab / Finolex / Asian (RPG)/ CCI
Supply and laying in repair 40 mm dia GI tubing light grade for cable protection at road crossing/ hard standing/ plinth protection/ on the pole etc complete all as specified and directed. Make- Jindal / TATA
Supply and lay in repair 80 mm dia GI tubing light grade for cable protection at road crossing/ hard standing/ plinth protection/ on the pole etc complete all as specified and directed. Make- Jindal / TATA
ORIENT ELECTRIC CO
shubham construction
M/s S.D Construction Co
DHARMESH ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .